Test-case libraries and the MATPOWER parser

How GridSim gets its networks. Every standard test system - from the WSCC 9-bus toy up to ~78k-bus continental models - enters the solver through one of two doors: a small set of built-in factories (IeeeCases) or the MATPOWER .m parser reading files committed under data/matpower/. This document describes both, the committed archive, how cases are validated, how to add one, and the known non-convergence / parse-gap classes.

  • Parser: src/GridSim.Core/IO/Matpower/MatpowerParser.cs
  • Parse result record: src/GridSim.Core/IO/Matpower/MatpowerCase.cs
  • Built-in factories: src/GridSim.Core/IO/IeeeCases.cs
  • Embedding config: src/GridSim.Core/GridSim.Core.csproj
  • Committed archive: data/matpower/ (provenance in data/matpower/README.md)
  • Fetch script: tools/fetch-cases.sh
  • Tests: tests/GridSim.Tests/IeeeCasesTests.cs, tests/GridSim.Tests/MatpowerParserTests.cs
  • Server run findings: docs/developer/benchmarks/server-results/README-section.md

1. The MATPOWER .m parser

MatpowerParser (src/GridSim.Core/IO/Matpower/MatpowerParser.cs:24) is a static class and the single import path for the PEGASE, RTS, NESTA/PGLib and wider MATPOWER libraries, all of which ship natively in MATPOWER .m format (src/GridSim.Core/IO/Matpower/MatpowerParser.cs:8-13). It preserves the source operating point verbatim - mpc.gen Pg/Qg/Vg and the stored bus voltages are kept as-is, no dispatch reinterpretation - so the parsed model reproduces the file's snapshot.

Public API

Member Signature Behaviour
Parse Parse(string text, string? name = null, double frequencyHz = 50.0) : GridModel Parse case text; thin wrapper over ParseWithDiagnostics(...).Model. MatpowerParser.cs:28
ParseFile ParseFile(string path) : GridModel File.ReadAllText then Parse; case name defaults to the file stem (Path.GetFileNameWithoutExtension). MatpowerParser.cs:32
ParseWithDiagnostics ParseWithDiagnostics(string text, string? name = null, double frequencyHz = 50.0) : MatpowerParseResult The real workhorse; returns the model plus a list of informational notes. MatpowerParser.cs:36
MatpowerParseResult record (GridModel Model, IReadOnlyList<string> Notes) Model + diagnostics. Notes are informational only - a case that produced notes is still a valid, solvable model. MatpowerCase.cs:9
MatpowerUnitHandling optional last parameter of Parse, ParseFile and ParseWithDiagnostics (N165, October 2026) Default NormaliseRawFeeders: a raw ohm / kW distribution feeder (case22, case33bw, case69, case85) is converted to per-unit / MW by MatpowerUnitNormalizer.Normalize, with a parse note and MatpowerParseResult.RawUnitsConverted = true; every other file is unaffected. AsWritten keeps the numbers exactly as the file writes them (the behaviour before N165).

The case name resolves in priority order: the name argument, else the function mpc = <name> declaration, else the literal "matpower" (MatpowerParser.cs:26-27, :45, ExtractFunctionName at :209-213). baseMVA defaults to 100.0 when absent (MatpowerParser.cs:44). Default frequency is 50 Hz (GB). Empty/whitespace text throws InvalidDataException (MatpowerParser.cs:38-39).

Tokenizing

Parsing happens in two stages: Clean normalises the text, then regex-driven extractors pull out the scalar and each matrix.

  1. Comment strip + continuation join (Clean, MatpowerParser.cs:176-194). The text is split on \n; each line has its trailing % comment removed by StripComment (MatpowerParser.cs:197-207), which respects single-quoted strings so a % inside a bus name is not treated as a comment. A line whose trimmed content ends with ... is a MATLAB line continuation: its content (minus the ...) is buffered and joined onto the next line before emitting (MatpowerParser.cs:184-192).
  2. Scalar extraction (ExtractScalar, MatpowerParser.cs:215-219). mpc.baseMVA is matched with a regex accepting an optional sign, digits/decimal, and scientific e/E exponent.
  3. Matrix extraction (ExtractMatrix, MatpowerParser.cs:222-246). Finds the first mpc.<field> = [ (whole-word \b match so mpc.bus does not also match mpc.bus_name, MatpowerParser.cs:224-225), takes everything up to the next ], splits rows on ;, and splits each row on spaces/tabs/CR/LF/commas. Each token is parsed by ParseNum.
  4. Number parsing (ParseNum, MatpowerParser.cs:164-173) reads with InvariantCulture and maps MATLAB infinity/NaN spellings: Inf/inf/+Inf/Infinity -> +inf, -Inf/-inf/-Infinity -> -inf, NaN/nan -> NaN. These infinities are how MATPOWER encodes open generator limits.

At(row, i, dflt) (MatpowerParser.cs:159-160) reads column i safely, returning dflt when the row is shorter than expected - so cases that omit trailing optional columns still parse.

Column mappings

MATPOWER columns are 1-based in the file spec; the parser uses 0-based indices. The mappings below are exactly what the code reads.

mpc.bus (MatpowerParser.cs:58-84)

Col (1-based) Index Field Maps to
1 0 bus_i Bus.Id (id preserved verbatim; not required to be contiguous/sorted)
2 1 type Bus.Type (see rules below)
3 2 Pd Bus.Pd
4 3 Qd Bus.Qd
5 4 Gs Bus.Gs
6 5 Bs Bus.Bs
8 7 Vm Bus.Vm (default 1.0)
9 8 Va Bus.VaDeg
10 9 baseKV Bus.BaseKv

mpc.gen (MatpowerParser.cs:96-115)

Col (1-based) Index Field Maps to
1 0 bus Generator.Bus
2 1 Pg Generator.Pg
3 2 Qg Generator.Qg
4 3 Qmax Generator.Qmax (default +inf)
5 4 Qmin Generator.Qmin (default -inf)
6 5 Vg Generator.Vg (default 1.0)
7 6 mBase Generator.MBase if > 0, else the system baseMVA (MatpowerParser.cs:112)
8 7 status dropped if <= 0 (MatpowerParser.cs:99)
9 8 Pmax Generator.Pmax (default +inf)
10 9 Pmin Generator.Pmin

Inertia H is not present in MATPOWER data and is set to 0 (MatpowerParser.cs:113).

mpc.branch (MatpowerParser.cs:121-141)

Col (1-based) Index Field Maps to
1 0 fbus Branch.From
2 1 tbus Branch.To
3 2 r Branch.R
4 3 x Branch.X
5 4 b Branch.B
6 5 rateA Branch.RateAMva
9 8 ratio tap ratio - drives transformer detection (below)
10 9 angle Branch.PhaseShiftDeg
11 10 status dropped if <= 0 (MatpowerParser.cs:123)

Mapping rules

  • Bus type (MatpowerParser.cs:62-69): 3 -> Slack, 2 -> Pv, 1 -> Pq; anything else falls through the _ arm to Pq. Type 4 (isolated) buses are detected first and dropped (added to an isolated set, continued; MatpowerParser.cs:62).
  • Inf handling: open Q/P limits written as Inf/-Inf become double.PositiveInfinity / double.NegativeInfinity (ParseNum, MatpowerParser.cs:164-173); this is asserted by Maps_Inf_generator_limits_to_infinity (MatpowerParserTests.cs:48-55).
  • Transformer detection by tap ratio (MatpowerParser.cs:128-140): a branch is a transformer iff its ratio column is non-zero (ratio != 0.0). If so, IsTransformer = true and TapRatio = ratio; otherwise it is a line with TapRatio = 1.0. (MATPOWER's convention: 0 means "not a transformer / nominal ratio".) Verified by Line_vs_transformer_by_ratio (MatpowerParserTests.cs:57-75).
  • Dropping isolated / out-of-service / dangling elements:
  • Type-4 buses are removed and their ids never enter the liveIds set (MatpowerParser.cs:62, :83).
  • Generators with status <= 0 are skipped (genOff counter, MatpowerParser.cs:99); so are generators on a bus that isn't in liveIds, i.e. on a dropped/isolated bus (MatpowerParser.cs:100).
  • Branches with status <= 0 are skipped (brOff, MatpowerParser.cs:123); branches touching a dropped bus on either end are skipped (brDangling, MatpowerParser.cs:126). This guarantees no dangling reference can reach the solver (MatpowerParser.cs:20-22). Covered by Drops_isolated_buses_and_incident_elements (MatpowerParserTests.cs:77-90) and Skips_out_of_service_elements (MatpowerParserTests.cs:92-103).
  • Non-contiguous bus ids preserved (MatpowerParser.cs:18-22): buses need not be contiguous or sorted. The solvers key on the bus id, and result row i maps to model.Buses[i], so file order is preserved. Handles_noncontiguous_bus_ids parses ids {100, 205, 9999}, solves, and checks both m.Buses and r.BusIds come back in that exact order (MatpowerParserTests.cs:105-118).

Reference-bus check

After building the bus list the parser counts slack (type-3) buses (slackCount, MatpowerParser.cs:70) and enforces:

  • Zero slack -> throw. InvalidDataException("... has no reference (type 3) bus - the power flow would be singular.") (MatpowerParser.cs:86-87). Tested by Throws_when_no_reference_bus (MatpowerParserTests.cs:120-129).
  • Multiple slack -> note, not error. A diagnostic "N reference (slack) buses - treating as a multi-island system." is added (MatpowerParser.cs:88-89).

Other diagnostics appended to Notes: dropped isolated buses (:90-91), skipped out-of-service generators (:116), skipped out-of-service branches (:142), and skipped dangling branches (:143).

Known limitation: no arithmetic-expression evaluation

The parser reads each token as a single number via double.Parse (ParseNum, MatpowerParser.cs:171). It does not evaluate arithmetic expressions. Some ACTIVSg cases embed literals like 135/sqrt(3) in the data matrices; these fail to load. This is a current gap, not a corruption - on the server run the two case533mt files were the only load failures:

LOAD FAIL: The input string '135/sqrt(3)' was not in a correct format.
(docs/developer/benchmarks/server-results/README-section.md:93-94, docs/developer/benchmarks/server-results/20260701-101835/regime.log:110-111). Closing it would require a tiny expression evaluator in ParseNum.


2. Built-in cases (IeeeCases)

IeeeCases (src/GridSim.Core/IO/IeeeCases.cs:13) exposes standard systems as plain factory methods so callers use them identically regardless of origin - the solver neither knows nor cares where a GridModel came from (IeeeCases.cs:6-12).

Case9 - the MATPOWER file plus the WSCC machine data

Case9() is the WSCC 9-bus system (MATPOWER case9), 3 generators, 3 loads, 100 MVA base, 345 kV. Since N199 (October 2026) it reads the embedded case9.m itself, so its buses (with the file's 0.9-1.1 pu limits), branches (RATE_A, RATE_B, RATE_C), generators (Pmin 10 MW each) and cost curves are the file's, and lays over each unit only the published WSCC machine data from Anderson and Fouad: the machine rating as MBase (247.5 / 192 / 128 MVA) and the inertia constant H on that base (23.64 / 6.40 / 3.01 s), which no .m file carries. Before N199 it was typed out by hand without the limits, Pmin, RATE_B / RATE_C and costs. By project convention it is the physics ground truth.

Embedded .m factories

The remaining factories parse a .m file embedded in the assembly via the private helper Mpc (IeeeCases.cs:90-97), which loads the manifest resource GridSim.Core.cases.<res>.m and calls MatpowerParser.Parse.

Factory .m resource Display name Source
Case14() :60 case14 IEEE 14-bus MATPOWER 8.0
Case30() :63 case30 IEEE 30-bus MATPOWER 8.0
Case57() :66 case57 IEEE 57-bus MATPOWER 8.0
Case118() :69 case118 IEEE 118-bus MATPOWER 8.0
Case300() :72 case300 IEEE 300-bus MATPOWER 8.0
Case145() :75 case145 IEEE 145-bus (dynamic) MATPOWER 8.0
Case24Rts() :81 case24_ieee_rts IEEE RTS-79 24-bus MATPOWER 8.0
CigreMv() :87 cigre_mv CIGRE MV benchmark (TF C6.04.02) authored

How embedding works

GridSim.Core.csproj marks the nine .m files as <EmbeddedResource> with an explicit LogicalName, e.g.:

<EmbeddedResource Include="..\..\data\matpower\lib\case14.m"
                  LogicalName="GridSim.Core.cases.case14.m" />
(src/GridSim.Core/GridSim.Core.csproj, the <ItemGroup> of embedded cases). The LogicalName gives a stable resource id GridSim.Core.cases.<name>.m independent of the on-disk folder, which is exactly the string Mpc reconstructs (IeeeCases.cs:92). The single source of truth is the committed .m files under data/matpower; the classic IEEE cases + CIGRE MV are pulled from lib/ and benchmarks/ at build time. case9.m is embedded too: Case9() reads it (N199).

RTS-79 (24-bus) vs RTS-96 (73-bus)

These are distinct systems, easily confused:

  • RTS-79 is the single-area 24-bus IEEE Reliability Test System, exposed as Case24Rts() / case24_ieee_rts and embedded (IeeeCases.cs:77-81).
  • RTS-96 is the three-area 73-bus system, a separate and larger case shipped as data/matpower/rts/pglib_opf_case73_ieee_rts.m (RTS-96, 73-bus 3-area) and not embedded - it is loaded from disk (IeeeCases.cs:78-80, data/matpower/README.md:15).

CIGRE MV

CigreMv() / cigre_mv (IeeeCases.cs:83-87) is a ~15-node, 20 kV radial distribution feeder (not a transmission system), authored to the CIGRE Task Force C6.04.02 European MV distribution benchmark spec ("Benchmark Systems for Network Integration of Renewable and Distributed Energy Resources", 2014). The .m header documents the derivation: one 110 kV source (Bus 0) feeding two 20 kV feeders through two 25 MVA 110/20 kV transformers, base (no-DER) configuration with the three normally-open tie switches S1/S2/S3 open (so the network is a tree), line/transformer/load data reproducing pandapower's create_cigre_network_mv, converted to per-unit on a 100 MVA system base (data/matpower/benchmarks/cigre_mv.m:1-20). The test expects 15 buses / 14 branches and convergence (MatpowerParserTests.cs:181-189).


3. The committed archive (data/matpower/)

The repo commits a curated subset so a lean checkout can build, embed, and test without any network fetch. Layout (provenance table in data/matpower/README.md:11-17):

Folder Committed contents Source Version Licence
lib/ case9/14/30/57/118/145/300, case24_ieee_rts MATPOWER data/ 8.0 BSD-3-Clause (LICENSE-MATPOWER.txt)
pegase/ case1354pegase, case2869pegase, case9241pegase MATPOWER data/ 8.0 BSD-3-Clause + citation
rts/ pglib_opf_case73_ieee_rts (RTS-96, 73-bus 3-area) PGLib-OPF master CC BY 4.0
nesta/ pglib_opf_case{3_lmbd,5_pjm,30_as,162_ieee_dtc,240_pserc,588_sdet} PGLib-OPF master CC BY 4.0
benchmarks/ cigre_mv (authored, not upstream) CIGRE TF C6.04.02 / pandapower ref - see README

The lib/ files double as the embedded-resource source for IeeeCases. Provenance, required academic citations (PEGASE, PGLib-OPF/RTS-96/NESTA-lineage, CIGRE MV), the NESTA-retirement note, and the CIGRE MV derivation are all maintained in data/matpower/README.md - see there rather than duplicating. The BSD-3-Clause text for the MATPOWER case data is in data/matpower/LICENSE-MATPOWER.txt.

After the server fetch (tools/fetch-cases.sh)

tools/fetch-cases.sh (tools/fetch-cases.sh:1-35) expands the committed archive into the full standard-case universe on a build/benchmark host. It is idempotent (skips files already present, fetch-cases.sh:17, :28) and drops files into two new folders under data/matpower:

  • pglib/ (fetch-cases.sh:11-20): the entire PGLib-OPF archive. It hits the GitHub trees API for power-grid-lib/pglib-opf (master), greps out every pglib_opf_case*.m path, and downloads each from raw.githubusercontent.com/.../master/.
  • matpower-all/ (fetch-cases.sh:22-31): every data/case*.m from the MATPOWER repo, pinned to tag 8.0, via the same trees-API-then-raw pattern.

Nothing is embedded from these; they are disk-discovered only (see below). After the fetch the tree holds roughly ~161 .m cases spanning up to ~78k buses (e.g. the ACTIVSg25k / 70k networks), the union of PGLib-OPF and MATPOWER's data/. The server run confirmed clean scaling and reached 10,000 buses (case_ACTIVSg10k) in its partial snapshot (docs/developer/benchmarks/server-results/README-section.md:57-63).

Auto-discovery

Both the CLI and the WPF picker enumerate data/matpower recursively for *.m, so whatever fetch-cases.sh drops in is picked up automatically:

  • CLI registry BuildCases (src/GridSim.Cli/Program.cs:793-826): starts with the nine embedded classics, then Directory.EnumerateFiles(mp, "*.m", SearchOption.AllDirectories) (Program.cs:814), skipping any file whose stem duplicates an embedded classic so disk copies of case9/case14/... don't double-register (Program.cs:798-799, :817-818). A rough bus-count hint is parsed from digits in the filename for ordering (Program.cs:819-821).
  • WPF ModelCatalog.Discover (src/GridSim.Wpf/ModelCatalog.cs:38-44): adds one ModelSource per discovered .m labelled "MATPOWER <stem>", alongside the GB reduced/synthetic/GDA sources.

4. Validation

IeeeCasesTests (tests/GridSim.Tests/IeeeCasesTests.cs)

Validates the built-in systems on three axes:

  1. Dimensions (Has_expected_dimensions, IeeeCasesTests.cs:48-64): a [Theory] asserting the exact (buses, gens, branches) for each case (14/30/57/118/300/24/145), BaseMva == 100, and exactly one slack bus. The counts are post-parse (i.e. after dropped isolated/out-of-service elements): e.g. ("118", 118, 54, 186), ("300", 300, 69, 411), ("24", 24, 33, 38) (IeeeCasesTests.cs:49-55).
  2. Convergence + balance (Converges_and_balances, IeeeCasesTests.cs:66-86): solves with the default NewtonRaphsonPowerFlow (generator Q-limits on, like the case9 tests), asserts Converged, MaxMismatch < 1e-6, that net injections sum to total losses (r.TotalLossMw == r.PInjMw.Sum()), and that losses are non-negative.
  3. Published Vm/Va with slack re-anchoring (AssertPublished, IeeeCasesTests.cs:97-126). Each case has MATPOWER's stored solved Vm/Va arrays inlined (IeeeCasesTests.cs:16-33). The test solves, maps results by bus id, then compares. Because the source's angle reference need not be the slack bus, both sides are re-referenced to the slack before comparing angles: dva = (va[id] - solvedSlack) - (expVa[i] - offset) (IeeeCasesTests.cs:113-124). Per-case tolerances are ~2x the observed deviation:
Case Vm tol Va tol (deg) Ref
14 0.005 0.2 :91
57 0.02 1.5 :92
118 0.03 1.0 :93
300 0.02 12.0 :94
145 0.01 0.1 :95

The case300 angle bound is deliberately loose because its stored classic angles are only roughly converged; its voltages still match tightly (IeeeCasesTests.cs:88-90).

MatpowerParserTests (tests/GridSim.Tests/MatpowerParserTests.cs)

Two layers:

  • Tokenizer / mapping units over inline .m fragments (MatpowerParserTests.cs:17-129): scalar
  • matrix parse, Inf -> infinity, line-vs-transformer by ratio, isolated-bus dropping, out-of-service skipping, non-contiguous ids, and the no-reference-bus throw (all cited in section 1 above).
  • Round-trip + library integration. Case9_from_file_matches_handcoded_structure_and_solution (MatpowerParserTests.cs:133-158) parses lib/case9.m and asserts it matches IeeeCases.Case9() in structure and, after solving both, in Vm (6 dp) / Va (4 dp) - proving the parser reproduces the ground truth (since N199 N199AlignedCase9Tests proves the two bit-identical). Large_case_parses_and_converges (MatpowerParserTests.cs:162-179) is a [Theory] over the three PEGASE cases + RTS-96, guarded on file existence (if (!File.Exists(path)) return;, :170) so a lean checkout stays green; it solves with the sparse solver (Q-limits off, 100 iters) and requires MaxMismatch < 1e-4. CigreMv_parses_and_converges (:181-189) checks the 15-bus/14-branch radial feeder solves.

Dense-vs-sparse agreement

The trust signal for the large cases is that the dense (NewtonRaphsonPowerFlow) and sparse (SparseNewtonRaphsonPowerFlow, direct sparse LU with an ILU0/BiCGSTAB fallback) solvers agree case-for-case on iteration count and final mismatch. Since 1.95.001 they are bit-identical on the CPU (same Newton step; DenseSparseParityTests), so this cross-check now tests the two assemblies, not two numerical answers. The server regime runs both sweeps to cross-check. In the partial snapshot the dense reference sweep had not yet started, so its column is marked pending and the cross-check is explicitly not yet available (docs/developer/benchmarks/server-results/README-section.md:6-11, :32-35, :123-126). The sparse half alone landed every converged case at mismatch <= ~1e-9 (mostly 1e-11/1e-12).


5. How to add a case

Two paths, depending on whether the case should be built into GridSim.Core or just available to the tools.

A. Disk case (usual - no rebuild of Core needed)

  1. Drop a valid MATPOWER .m file anywhere under data/matpower/ (any subfolder; discovery is recursive).
  2. It is auto-discovered: the CLI bench/sweep/N-1/stress verbs and the WPF source picker enumerate data/matpower/**/*.m (src/GridSim.Cli/Program.cs:814, src/GridSim.Wpf/ModelCatalog.cs:41). No code change.
  3. Constraints: the file must have an mpc.bus matrix (MatpowerParser.cs:47-48) and at least one type-3 slack bus (MatpowerParser.cs:86-87). If the filename stem duplicates an embedded classic (case9, case14, ..., cigre_mv), the CLI skips the disk copy in favour of the embedded one (Program.cs:798-799, :817-818).
  4. If the case has real provenance/licence terms, add a row to data/matpower/README.md.

B. Embedded factory (built into GridSim.Core)

Use this only when the case must ship inside the Core assembly (as the classics do).

  1. Place the .m file under data/matpower/ (e.g. lib/ or benchmarks/).
  2. Add an <EmbeddedResource> line to src/GridSim.Core/GridSim.Core.csproj with a LogicalName="GridSim.Core.cases.<stem>.m" (match the existing pattern).
  3. Add a factory to IeeeCases returning Mpc("<stem>", "<display name>") (IeeeCases.cs:90-97).
  4. Add it to the embedded-classic skip set in the CLI (Program.cs:798-799) so the disk copy isn't also registered.
  5. Add a test: dimensions + convergence (and published Vm/Va if a solved snapshot exists), following IeeeCasesTests.

6. Known non-convergence classes (from the server run)

Findings below are from the partial server sweep, docs/developer/benchmarks/server-results/README-section.md:65-94 (mirrored in README.md:240-245). These are expected outcomes, not parser bugs or solver failures.

PGLib-OPF operating points (flat-start power flow)

PGLib-OPF cases ship an optimisation (OPF) benchmark operating point, not a solved power-flow snapshot. Run as a plain flat-start Newton-Raphson power flow they hit the 100-iteration cap with large residuals, while their non-OPF twins converge trivially (README-section.md:66-84):

PGLib OPF case Buses OPF result (conv / iters / mismatch) Non-OPF twin
..._case1888_rte 1888 NO / 100 / 2.35E+02 case1888rte yes / 2 / 118 ms
..._case1951_rte 1951 NO / 100 / 9.97E+01 case1951rte yes / 3 / 132 ms
..._case2848_rte 2848 NO / 100 / 2.12E+02 case2848rte yes / 2 / 440 ms
..._case2868_rte 2868 NO / 100 / 2.98E+01 case2868rte yes / 5 / 448 ms
..._case6470_rte 6470 NO / 100 / 1.15E+02 case6470rte yes / 3 / 2687 ms

Plus ..._case2000_goc, ..._case3022_goc, ..._case4917_goc, ..._case6495_rte, ..._case6515_rte, ..._case2853_sdet, ..._case240_pserc, ..._case300_ieee, ..._case179_goc, ..._case162_ieee_dtc, ..._case1803_snem, ..._case39_epri, ..._case3_lmbd (README-section.md:82-84). The NESTA note in data/matpower/README.md:19-25 flags the same: heavily-loaded OPF benchmarks may not converge under a plain NR power flow.

Radial distribution feeders

Small single-generator distribution feeders don't converge under the transmission-oriented polar Newton-Raphson solver: case12da, case15da, case16am, case18nbr, case22, case28da, case33bw, case33mg, case34sa, case38si, case51he/51ga, case69, case74ds, case85, case94pi, case118zh, case136ma, case141, case10ba (README-section.md:86-89). These motivate a dedicated backward/forward-sweep distribution solver (tracked). Note CIGRE MV is a radial feeder too, but small enough that the transmission NR still converges on it (data/matpower/benchmarks/cigre_mv.m:19-20).

Parse-gap load failures (not a convergence class)

case533mt_hi / case533mt_lo fail to load (not to converge) because of the unevaluated 135/sqrt(3) arithmetic literal - the section-1 parser gap (README-section.md:93-94).

Bottom line: on the 28-core EPYC 7763 the sparse solver converged the full IEEE/PEGASE line-up to machine-tight mismatches (<= ~1e-9) from 9 to 10,000 buses; the only non-convergences are the two expected classes above, and the only load failures are the two sqrt(3) cases (README-section.md:114-126).