14. Frequency studies

A frequency study answers four questions about a loss of generation or infeed. How fast does frequency fall straight after the loss (the RoCoF, in Hz/s)? How low does it go before the response arrests it (the nadir)? Where does it settle? Which services (governor droop, Dynamic Containment, Dynamic Moderation, Dynamic Regulation) did the arresting? GridSim answers them with five verbs and one live view. freq and replay read a recorded frequency trace. transient runs a case through a time-domain simulation with an optional infeed trip. domains reports how the generator fleet divides into speed domains for the distributed inertia model. h0-study sweeps a recorded event toward zero synchronous inertia with a growing grid-forming converter fleet. The desktop app plays the same physics live. This chapter shows each verb on real output, explains every line it prints, and states what each verb does with the inertia model and the response services.

Which verb answers which question

Question Use Chapter
Did a recorded NESO trace breach the GB limits, and how steep was its worst RoCoF? freq this chapter
Play a recorded trace back at 20 ms, slice by slice. replay this chapter
What RoCoF and nadir does a case give when an infeed of N MW is lost at time T, with a full time series and solve exports? transient this chapter
One generator trips: RoCoF, nadir and settling frequency, plus the same trip at half the inertia. trip contingency analysis
How does the fleet divide into speed domains, and does one domain dominate? domains this chapter
Does the model reproduce a recorded event? replay-event replaying recorded events
What happens to a recorded event with a device, or with less inertia? scenario, fleet, evidence counterfactuals
What if the synchronous inertia goes to zero and converters form the grid? h0-study this chapter, then counterfactuals
Trip a generator by hand and watch frequency live. the desktop app the desktop app
Rotor-angle stability, machine by machine. stability ch. 19, CLI reference
Sub-cycle waveforms, not frequency. emt electromagnetic transients

The frequency verbs model the electromechanical timescale: seconds to minutes, one frequency for the system (or one per speed domain), with the network held at its steady-state solution. Waveform behaviour inside a cycle is outside them and belongs to the EMT chapter. The equations are in the frequency dynamics technical chapter.

Before you start

  • freq and replay read a NESO frequency CSV with one timestamp,hertz row per line and a dtm,f header. Blank lines are skipped, and so is the first non-blank line when it is not a data row and its first field holds no digit (the header). Every other line must be a timestamp, a comma and a finite frequency above 0 Hz; any other line stops the read with exit 1 and a message naming the file, the line number and the line. Timestamps are read as UTC. The bundled files are data/neso/frequency-sample.csv (300 s of ambient frequency on 2024-08-01, the default), data/neso/gb-2019-08-09-frequency.csv and data/neso/gb-2023-12-22-frequency.csv.
  • Every timestamp is checked against the forward-inference guard: GridSim reads history only, so a row newer than 169 hours before now is refused (see Pitfalls).
  • The relative file name data/neso/... resolves against the directory that holds the executable for the default input, and against the current directory for a path you type.
  • transient, h0-study and replay-event write into results/ under the current directory unless --out names a directory (see Run directories).
  • Timings, stamps and run-directory names in the captured output differ by machine and by run.
  • The CLI prints a run directory as an absolute path. The captures in this chapter are written by tools/docs/capture.ps1, which removes the repository root from every path, so a run directory appears relative to the repository (results\transient-uk-..., results\h0-study-...).
  • A capture is the standard output of the run followed by its standard error. On a terminal the two streams interleave in the order written, so a transient run shows its progress line (standard error) before its done in line (standard output); the captured blocks list the done in line first.

Worked example

Score a recorded excursion

On 22 December 2023 an interconnector trip and a power-station trip pulled GB frequency down to 49.275 Hz. NESO's one-second trace for that window is bundled. freq scores it against the GB limits:

gridsim freq data/neso/gb-2023-12-22-frequency.csv
$ gridsim freq data/neso/gb-2023-12-22-frequency.csv
NESO frequency  -  gb-2023-12-22-frequency.csv
================================================================
Samples      601  (1 s cadence)
Frequency    min 49.275 Hz  mean 49.778 Hz  max 49.930 Hz
Max |RoCoF|  0.1020 Hz/s  at 2023-12-22 13:09:53

vs GB limits:
  RoCoF 0.125 Hz/s: within  (worst 0.1020 Hz/s)
  operational 49.8 Hz: 299 s below    statutory 49.5 Hz: 60 s below    LFDD 48.8 Hz: clear

Upsample demo  -  1 s frames expanded to 20 ms by RoCoF interpolation:
  time            Hz         RoCoF (Hz/s)
  13:07:00.000   49.93000    -0.0080
  13:07:00.020   49.92984    -0.0080
  13:07:00.040   49.92968    -0.0080
  13:07:00.060   49.92952    -0.0080
  13:07:00.080   49.92936    -0.0080
  13:07:00.100   49.92920    -0.0080
  13:07:00.120   49.92904    -0.0080
  13:07:00.140   49.92888    -0.0080
[exit 0]

The trace spent 299 samples below the 49.8 Hz operational floor and 60 below the 49.5 Hz statutory floor, never reached the 48.8 Hz demand-disconnection stage, and its steepest one-second fall was 0.1020 Hz/s, inside the 0.125 Hz/s limit. The minimum, 49.275 Hz, and the 0.1020 Hz/s are the two numbers the event record holds as the outcome that replay-event and the counterfactual verbs try to reproduce.

Simulate a loss of infeed

transient runs a case forward in time at a fixed slice, tripping an infeed part-way through. This run takes the reduced GB model (uk, 171.7 GVA.s of inertia), runs it for one simulated minute in 100 ms slices, and trips 1,000 MW at 10 s:

gridsim transient uk --minutes 1 --dt-ms 100 --trip 1000 --trip-at 10
$ gridsim transient uk --minutes 1 --dt-ms 100 --trip 1000 --trip-at 10
[transient] uk: done in 1.4s  nadir 49.448Hz  maxRoCoF -0.147Hz/s  exports 42  -> results\transient-uk-20261019-183826
[transient] uk: 600 slices @ 100ms (1 min) on Newton-Raphson (dense)...
[exit 0]

The run lost 1,000 MW of a 39,500 MW system carrying 171.7 GVA.s. The frequency fell at 0.147 Hz/s, reached 49.448 Hz at t=17 s and was recovering at the end of the minute (49.769 Hz at t=60 s). The first line of the block is written to standard output when the run ends; the second is the progress line on standard error, which the run writes first, so a terminal shows the progress line before the done line (see Before you start). All 600 slices converged, so the exit code is 0.

Reading the output

freq

  • Title line. NESO frequency - <file name> names the file read, without its directory.
  • Samples. The number of parsed rows. The text (1 s cadence) is fixed; freq does not measure the cadence.
  • Frequency. The minimum, mean and maximum over every sample, to three decimals.
  • Max |RoCoF|. The largest absolute value of (f2 - f1) / dt over consecutive sample pairs, and the timestamp of the later sample of that pair. A trace with one-second rows gives the one-second average slope, not an instantaneous one.
  • RoCoF 0.125 Hz/s. within or EXCEEDED, with the worst figure repeated. 0.125 Hz/s is the legacy GB loss-of-mains relay setting (FrequencyLimits.RocofLimitLegacyHzPerS). The modern 1.0 Hz/s setting is not printed by this verb.
  • operational 49.8 Hz, statutory 49.5 Hz. held when no sample is below the floor, otherwise N s below, where N is the count of samples strictly below it. N equals seconds only at a one-second cadence. The upper limits are on the over-frequency line below.
  • LFDD 48.8 Hz. clear, or REACHED when any sample is at or below the first low-frequency demand-disconnection stage.
  • over-frequency. Printed only when some sample is above 50.2 Hz: operational 50.2 Hz: N s above and statutory 50.5 Hz: held or N s above, counted as for the low side. A trace that stays at or below 50.2 Hz has no such line.
  • Upsample demo. The first three samples expanded to 20 ms: 50 sub-samples per second. Each interval's RoCoF is (f2 - f1) / dt and the sub-samples follow f(t) = f1 + RoCoF * t, so the RoCoF column holds one value for each 1 s interval. In the capture the first interval falls at -0.0080 Hz/s, and 49.93000 - 0.0080 * 0.02 gives the 49.92984 of the second row. replay plays these frames.

replay

replay prints no statistics headlessly; it plays frames. A five-frame headless run:

gridsim replay --frames 5
$ gridsim replay --frames 5
Loading frequency-sample.csv (600 s) and upsampling to 20 ms...
[     0/14951] 00:00:00.000  50.1050 Hz  RoCoF  0.0010  @50 sps
[     1/14951] 00:00:00.020  50.1050 Hz  RoCoF  0.0010  @50 sps
[     2/14951] 00:00:00.040  50.1050 Hz  RoCoF  0.0010  @50 sps
[     3/14951] 00:00:00.060  50.1051 Hz  RoCoF  0.0010  @50 sps
[     4/14951] 00:00:00.080  50.1051 Hz  RoCoF  0.0010  @50 sps
[exit 0]
  • Loading line. The file name and the --seconds value (default 600). It reads --seconds + 1 samples, or all of them when the file is shorter, so the (600 s) is the limit and not the file length. The sample file holds 300 samples, which is 299 intervals of 50 frames plus one closing frame: 14,951 frames.
  • [index/count]. The zero-based frame index and the total frame count.
  • Time, Hz, RoCoF. The frame's timestamp, its frequency to four decimals, and the RoCoF of its source interval in Hz/s.
  • @50 sps. The playback rate in slices per second, after clamping to the range 0.25 to 2,000. Headless mode does not pace itself, so the rate is a label there.

Headless mode stops after the requested number of frames or at the end of the data, whichever is first, and exits 0. The interactive form (no --frames) is a console display: a title line, the timestamp and slice counter, a gauge from 49.5 Hz to 50.5 Hz with | at 50 Hz and # at the current frequency, the frequency with its deviation from 50 Hz and the RoCoF, and a progress bar. The gauge is green inside 0.10 Hz of nominal, dark yellow inside 0.20 Hz, yellow inside 0.50 Hz and red beyond. Keys: space plays or pauses, up and down (or + and -) double or halve the speed, left and right step one frame and pause, Home restarts, and Q or Esc quits. At the end of the data the display pauses.

transient

Console summary. done in 1.4s is wall-clock time. nadir 49.448Hz is the lowest frequency over the run. maxRoCoF -0.147Hz/s is the RoCoF of largest magnitude, with its sign (negative is falling). exports 42 is the number of full solve exports written, and the path is the run directory. The progress line on standard error names the case, slice count, step, duration and engine, and repeats every 100,000 slices on long runs.

What each slice does. The case is solved by power flow, warm-started from the last converged state, and the frequency integrator then advances one step against the net imbalance. Loads are held constant (no daily demand curve). Three things move the frequency:

  • The trip. At --trip-at the lost MW enters the integrator as a deficit. The deficit decays with a 300 s time constant of simulated time, the stand-in for reserve and redispatch picking up the loss (SecondaryTauS in src/GridSim.Core/Simulation/LiveSim.cs). The inertia of the tripped unit stays in the system energy, and the power flow does not see the trip: gen_mw and demand_mw do not change.
  • Ambient jitter. A small random load imbalance of up to 0.08 % of base demand (AmbientNoiseFraction) is added each slice so the dial moves in steady state. The generator is seeded with a fixed value (LiveSimSeed), so a rerun gives the same sequence. A run with no trip therefore shows a nadir at the case's nominal frequency (50.000 Hz on a 50 Hz case; case9 is a 60 Hz system and runs at 60 Hz). The largest RoCoF is the amplitude AmbientNoiseFraction * demand * f0 / (2E); the captured runs print -0.001 Hz/s (case9, 10 ms slices) and -0.005 Hz/s (uk, 100 ms slices).
  • Response. The integrator carries governor droop (5 % droop on 20 % of demand with an 8 s lag) and load damping (1 % of demand per Hz). It carries no Dynamic Containment, Moderation or Regulation. See Response services and How far to trust a nadir.
  • Grid-forming and asset dynamics. --forming (with --forming-inertia and --forming-damping) runs the integrator's grid-forming kernel, and --asset-dynamics runs the asset-aware integrator on the case's asset bundle: inverter and protection trips are taken from the running dispatch, and the balance they remove is restored over the same 300 s secondary time constant as the trip. --asset-dynamics on a case with no asset bundle exits 1. The run description in run-metadata.json and the file headers records both switches.
  • Machine data. --dyn-data <file> gives the machines the file binds the file's inertia H; its reactances, exciters and governors are not part of this model, and a [transient] line on standard error says so. A batch run (--cases) refuses it with exit 2.

Inertia. The system energy is the sum of H x MBase over the rotating machines (a converter-type unit adds nothing, whatever H its data carries). A case that carries no inertia data (every MATPOWER case) has less than 100 MW.s, and transient then substitutes 4 s on the generators' MVA base (LiveSolveSettings.FallbackInertiaH, MinInertiaMwS); read the frequency of such a case as a demonstration. The reduced GB model carries its own data. A step longer than 20 ms is integrated in sub-steps of at most 20 ms (capped at 4,000 sub-steps per slice), so a 100 ms slice is five sub-steps. The RoCoF logged for a slice is the one at its last sub-step.

timeseries.csv has a # header block (commit, machine, run description) and then one row per logged slice:

Column Meaning
tick Slice number, from 1.
t_seconds tick x dt, in seconds.
freq_hz Frequency after the slice.
rocof_hz_s RoCoF at the slice, Hz/s; negative is falling.
gen_mw Sum of the positive bus net injections of the solved state.
demand_mw Total real demand of the solved state.
iters Newton iterations the slice needed. 0 means the warm start already met the tolerance.
max_mismatch Largest power mismatch at the end of the slice, per-unit on the system base.
vmin_pu, vmax_pu Lowest and highest bus voltage magnitude.
solve_ms Wall-clock time of the power-flow solve, in milliseconds. Differs on every run.
converged True or False. A slice that does not converge is never used as the next warm start.

Values from this run's file show the shape of the event. Before the trip the frequency sits at 50.000 Hz plus jitter (50.00015 Hz and 0.00146 Hz/s at slice 1). At slice 100 (t=10.0 s, the trip) the RoCoF is -0.14693 Hz/s, which is the swing-equation figure plus jitter. The deficit decays by exp(-0.1 / 300) before the step, so it is 999.667 MW and the figure is f0 x 999.667 / (2 x 171,700) = 0.14555 Hz/s; the jitter is the remaining -0.00138 Hz/s. By t=11.0 s frequency is 49.846 Hz and RoCoF -0.130 Hz/s as governor and damping act. At t=15.0 s frequency is 49.490 Hz with the RoCoF down to -0.038 Hz/s, and the nadir of 49.4475 Hz falls at t=17.0 s, where RoCoF crosses zero. After that the frequency recovers as the deficit decays and the governor holds the response.

summary.md repeats the headline: slices, wall time, engine, nadir and maximum |RoCoF| to four decimals, each with its time to three decimals, the count of non-converged slices (and the first one), and the export count.

exports/ holds slice-NNNNNNNNN.json solve exports: slice 1, every slice within --trip-window seconds (default 2.0) of the trip, and every --export-everyth slice. This run wrote 42: slice 1 and the 41 slices from 8.0 s to 12.0 s. The format is in exports and formats.

A quiet run, with no trip, shows the ambient floor:

$ gridsim transient case9 --minutes 0.1 --dt-ms 10
[transient] case9: done in 0.2s  nadir 60.000Hz  maxRoCoF -0.001Hz/s  exports 1  -> results\transient-case9-20261019-183822
[transient] case9: 600 slices @ 10ms (0.1 min) on Newton-Raphson (dense)...
[exit 0]

domains

domains groups the case's generators into speed domains and ranks them by stiffness. It loads the positional case or the folder named by --dir, and otherwise data/uk, the reduced GB model.

gridsim domains
$ gridsim domains
GridSim  -  SPEED DOMAINS on GB reduced (10-zone)
==================================================================
3 speed domains  *  deltaGVa 56 %  *  dominant = Domain 1

Domain   Speed         Kind               Mach      GVA.s   GVad GVA
Domain 1 2p/3000rpm    Synchronous          12     167.80      24.34  *
Domain 0 inverter      Pll                  16       0.00      15.61
Domain 2 8p/750rpm     Synchronous           1       3.90       0.65

GVad = apparent-power stiffness sum(S*C); GVA.s = real spinning inertia. A domain is dominant
when deltaGVa >= 10% (LOS sec. 5.5). Distributed model: spatial spread & propagation are unvalidated at scale.
[exit 0]
  • Header. The model name, then the count of speed domains, deltaGVa and the dominant domain.
  • Grouping. Each generator is mapped from its type to a machine speed: nuclear, coal, biomass, CCGT, OCGT, CHP and gas are 2-pole turbo-alternators at 3,000 rpm; reciprocating engines are 4-pole at 1,500 rpm; hydro and pumped storage are 8-pole at 750 rpm. Storage, battery and BESS units form a synthetic-inertia domain. Every other inverter-based type (wind, solar, converter, interconnector, tidal, unknown) falls into a PLL domain. A machine of unknown type that carries inertia (H above zero) is placed in the 2-pole synchronous domain. Domains are numbered by pole count and kind, so inverter domains take the lowest numbers.
  • Domain, Speed, Kind. The domain id, its speed (2p/3000rpm, or inverter), and Synchronous, SyntheticInertia or Pll.
  • Mach. The count of generators in the domain.
  • GVA.s. Real stored kinetic energy, the sum of H x MBase over the members, in GVA.s. Inverter domains show 0.00.
  • GVad GVA. The apparent-power stiffness: the sum of MBase x C over the members, where the availability coefficient C is |Pg| / MBase clamped to 0 to 1. Rows are ordered by this column, largest first, and * marks the dominant domain.
  • deltaGVa. The gap between the largest and second-largest GVad as a fraction of the second: (top - second) / second. The top domain is dominant when this is at least 10 %. When the runner-up carries no dispatch, the verb prints sole domain and the top domain dominates. When no domain dominates it prints no dominant domain (inertia too evenly spread - the LOS fragmentation mode).

The 56 % in the capture means the 2-pole synchronous domain is 56 % stiffer than the next (the PLL converters at 15.61 GVA). --dir selects a JSON case directory; the synthetic GB model gives a different split:

$ gridsim domains --dir data/gb-synthetic
GridSim  -  SPEED DOMAINS on GB synthetic
==================================================================
4 speed domains  *  deltaGVa 52 %  *  dominant = Domain 2

Domain   Speed         Kind               Mach      GVA.s   GVad GVA
Domain 2 2p/3000rpm    Synchronous          23     167.80      23.92  *
...

The full output of that run is in docs/_captures/frequency/domains-synthetic.txt; its second row is Domain 1 inverter Pll, with 35 machines, 0.00 GVA.s and 15.76 GVad GVA, and its fourth is Domain 0 inverter SyntheticInertia with 15 machines and 0.05 GVad GVA.

h0-study

The H=0 study asks how a recorded loss would have played out if the real synchronous inertia were scaled toward zero while an increasing share of the converter fleet were grid-forming. It first re-simulates the recorded event with no device and refuses to continue unless that baseline reproduces the record (the gate described in replaying recorded events). It needs a case directory that ships an asset-dynamics bundle (asset-classes.json and asset-bindings.json); the default is data/gb-synthetic.

gridsim h0-study --event gb-largest-loss-1320
$ gridsim h0-study --event gb-largest-loss-1320

=== H=0 counterfactual: GB normal infeed loss risk screening (SQSS): single 1320 MW infeed trip [VERIFY] ===
  input provenance: [CuratedPlaceholder]  (event 'gb-largest-loss-1320' is effectively CuratedPlaceholder, the weakest of its parts): a design-basis study, not a reproduction of history; every figure below inherits it and none is Recorded.
  baseline gate: Reproduced   dP=1320 MW (first 5 s; 1320 MW over the whole event)   LFDD stage: 48.8 Hz
  GFM class: gfm-vsm-study-2024   GFL class: gfl-wind-2024   (Ev is virtual control inertia, NEVER in real E)
  GFM fraction realised by whole units: 0.25 -> 0.392, 0.50 -> 0.588, 0.75 -> 0.833

  corner Best: cell = nadir Hz / verdict  (HELD=formed & clear of LFDD, LFDD=below stage, CASC=Loss-of-Mains cascade, NaN=un-formable)
   scale\gfm |       0.00       0.25       0.50       0.75       1.00
  -------------------------------------------------------------------
        1.00 | 49.76 HELD 49.67 HELD 49.56 HELD 49.41 HELD 49.51 HELD
        0.50 | 49.58 HELD 49.48 HELD 49.40 HELD 49.25 HELD 49.47 HELD
        0.25 | 49.31 HELD 49.21 HELD 49.16 HELD 49.06 HELD 49.44 HELD
        0.00 |   -    NaN 41.09 CASC 44.66 CASC 48.70 CASC 49.40 HELD

  corner Worst: cell = nadir Hz / verdict  (HELD=formed & clear of LFDD, LFDD=below stage, CASC=Loss-of-Mains cascade, NaN=un-formable)
   scale\gfm |       0.00       0.25       0.50       0.75       1.00
  -------------------------------------------------------------------
        1.00 | 49.74 HELD 49.40 HELD 49.09 HELD 48.80 CASC 49.21 HELD
        0.50 | 49.51 HELD 49.19 HELD 48.84 HELD 48.79 CASC 49.17 HELD
        0.25 | 49.13 HELD 48.85 HELD 48.80 CASC 48.70 CASC 49.14 HELD
        0.00 |   -    NaN 28.42 CASC 37.11 CASC 44.52 CASC 49.10 HELD

  28/40 cells HELD (formed, clear of LFDD); 2 forming-dependent (H=0, no grid-forming source).
  Note: forming-dependent cells are expected DATA, not an error - the run still exits 0.

  -> results\h0-study-gb-largest-loss-1320
[exit 0]
  • Title and gate line. The event title and baseline gate: Reproduced, the size of the exogenous loss in MW (dP) and the LFDD stage (48.8 Hz). The study runs only when the gate says Reproduced.
  • Class line. The asset classes used for the grid-forming (--gfm-class) and grid-following (--gfl-class) converters. The virtual inertia Ev of the grid-forming units enters only the forming denominator; it is never added to the real inertia.
  • One table per corner. Best and Worst are the two bracketing sets of the unfitted constants (see How far to trust a nadir). Rows are the synchronous-inertia scale, from 1.00 (the case as it is) to 0.00 (no real inertia). Columns are the fraction of the converter fleet made grid-forming, from 0.00 to 1.00.
  • A cell is nadir Hz then a verdict.
  • HELD: the frequency was formed and its nadir stayed above the 48.8 Hz LFDD stage. It does not mean the nadir stayed above the 49.5 Hz statutory floor: 49.25 Hz reads HELD.
  • CASC: grid-following converters tripped on Loss-of-Mains protection and the nadir reached 48.8 Hz or lower. The cascade removes infeed as the frequency falls; a nadir far below 48.8 Hz (the 28.42 Hz cell) ranks severity and is not a forecast, because the model sheds no load and trips no further plant to arrest it.
  • LFDD: the nadir reached the LFDD stage with no converter trips.
  • NaN, with - in place of a nadir: zero real inertia and no grid-forming source, so nothing forms the frequency. RoCoF, nadir and settling are undefined, and these cells count as a collapse of every grid-following unit. In the capture they are the scale 0.00, fraction 0.00 cells of both corners.
  • Summary line. The number of cells that were HELD, out of all cells (here 2 corners x 4 scales x 5 fractions = 40), and the count of forming-dependent cells. Those cells are data, so the run exits 0.
  • Path line. The run directory.

The run directory holds h0-study.json (every cell with its separate real and virtual inertia, RoCoF, nadir, settling frequency, trip counts and assessment), matrix.csv (one row per cell), summary.md and run-metadata.json.

Variations

Replay a trace interactively

gridsim replay data/neso/gb-2023-12-22-frequency.csv --sps 100 --seconds 120

This loads the first 121 samples of the 2023 trace and plays them at twice real time. Press Q to quit. Never start the interactive form from a script: it waits for keys. Use --frames N there.

Batch and sweep runs

transient runs several cases in one command. --cases suite (or all) runs case9, case14, case30, case57, case118, case300 and pegase/case1354pegase.m; --cases a,b,c takes a list. Each case gets a subdirectory of results/transient-<stamp>/, named after the case with path separators replaced by _.

gridsim transient --cases case14,case118 --minutes 1 --dt-ms 20 --trip 200 --trip-at 5

--log-every N thins the time series (the first slice, the last, and every slice within the trip window are always logged). --export-every N adds full solve exports. --solver dense|sparse|bfs forces a power-flow engine. A run directory written by transient loads in the desktop app through LOAD RUN and plays back frame by frame.

Try different sweeps in h0-study

gridsim h0-study --event gb-largest-loss-1320 --sync-inertia-scale 1,0.5,0 --gfm-fraction 0,1 --corners best

--sync-inertia-scale and --gfm-fraction take comma lists and --corners takes best, nominal, worst. The verbs scenario, fleet and evidence use the same gate and the same event file; see counterfactuals.

Fit the unfitted constants to a measured trace

fit-frequency fits load damping, the responsive fraction and the governor time constant of the lumped swing model to one measured loss-of-infeed trace, by least squares on the trajectory for the given loss, inertia and demand. The form is gridsim fit-frequency <trace.csv> --inertia <GVA.s> --demand <MW> --loss <MW> [--loss-at <s>] [--fit damping,...]. No trace in this form ships with GridSim, so bring your own measured window. The trace is a two-column seconds,Hz CSV on the model's clock. The report gives each constant's seed (the shipped default), its fitted value, the RMS error and the nadir error. It is a calibration check: the shipped defaults do not change. The nominal frequency comes from the trace (50 or 60 Hz) or --nominal-hz. Damping alone is well identified from one trace; fitting all three is weakly identified and a Note: line says so. Every flag and exit code is in ch. 19, fit-frequency.

Bracket a trip's nadir

trip --band adds the nadir band over the same three unfitted constants, each moved by +/- 20 % one at a time and over every corner of the joint box; trip --gb-services adds the GB Dynamic Containment, Moderation and Regulation layer at the typical volumes; and trip --asset-dynamics --envelope <class>:<param>=<low>..<high> sweeps asset-class control parameters around the trip:

gridsim trip --band
gridsim trip --dir data/gb-synthetic --asset-dynamics --envelope dg-alomcp:rocofTripHzPerS=0.5..2

See ch. 19, trip and contingency analysis.

The live frequency view in the desktop app

The desktop app integrates frequency on every tick of the live sim. To run an event by hand, load a case, pick a fine step in the transport bar (1 ms to 20 min), and right-click a bus on the network map, or press T to trip the largest online generator. The lost MW enters the same integrator that transient uses, with the same 300 s decay and the same ambient jitter, at the case's own nominal frequency. The OPERATOR tab shows the frequency and RoCoF, the NESO RP1 tab shows the RoCoF (on a 50 Hz case only), the MECHANICAL tab shows the RoCoF margin against the 0.125 and 1.0 Hz/s relay settings, and SCADA raises its P2 frequency alarm when the excursion leaves the band 0.1 Hz either side of nominal (49.9 Hz to 50.1 Hz on a 50 Hz case). The event log records TRIP <unit> (<MW> MW) RoCoF <x> Hz/s nadir <y> Hz; those two figures are an analytical estimate, not the live reading: a batch FrequencyDynamics.Simulate of the same loss at t = 1 s, on the inertia with the tripped unit removed and a default DynamicsConfig, so they differ from the live trace. The GENERATION & INERTIA tab runs an analytical comparison of the same trip with the configured TSGB device; that analysis removes the tripped unit's inertia from the system, where the live integrator leaves it in. In replay mode and on a bridge stream there is no live integrator, and a right-click logs TRIP is not available on this feed (replay or bridge stream). When the case ships an asset-dynamics bundle, the live integrator runs the asset-aware variant: asset protection trips are taken from the running dispatch, and the imbalance they leave is restored over the same 300 s secondary time constant as a manual trip; the tripped units stay tripped. Details are in the desktop app.

Inertia models

Frequency studies run on one of two inertia models, chosen with the global switch --inertia-model lumped|distributed (see ch. 19, CLI reference).

Lumped (the default). The whole system is one mass with energy E = sum(H x MBase), one frequency, and RoCoF = f0 x deltaP / (2E) at the instant of the loss. Every verb in this chapter that integrates frequency does this unless told otherwise.

Distributed (experimental). Generators are grouped into speed domains (the grouping domains prints). Each synchronous domain is a coherent mass with its own frequency and rotor angle, coupled to the others by synchronising power derived from the network. The system-level forcing (the loss, governor, damping) is computed from the inertia-weighted centre-of-inertia frequency exactly as in the lumped model, so the centre-of-inertia frequency equals the lumped trajectory to rounding. What the distributed model adds is per-domain traces and a per-bus RoCoF map. With one synchronous domain it delegates to the lumped model, so the reduction is exact.

What each verb does with the switch:

Verb With --inertia-model distributed
trip Integrates the multi-domain model on the post-trip network and prints the centre-of-inertia result, preceded by an Inertia model: line. The half-inertia comparison line runs lumped.
transient Prints the speed-domain split on standard error and integrates lumped.
domains Unaffected: it always reports the domain split.
replay-event, scenario, fleet, evidence, h0-study Print a warning on standard error and run lumped.
freq, replay Not applicable; they read recorded data.
the desktop app Lumped.

The same trip on the reduced GB model under each model gives the same centre-of-inertia numbers. Under the distributed model the verb adds an Inertia model: line naming the swing masses at the trip and a Loss placed: line stating where the loss lands: on the speed domain whose machines remain at the tripped unit's bus, or, when the unit was the only machine there, shared among the domains by their synchronising coupling to that bus. When the coupling cannot be derived from the network a Coupling: line says so and why:

$ gridsim trip --inertia-model distributed
Inertia model:  distributed  (2 speed domain(s), dGVa 0.37)
Loss placed:    bus 10 hosts the machines of speed domain 1, which takes the whole step
GridSim  -  contingency on GB reduced (10-zone)
================================================================
Tripped:        Hinkley Point Nuclear  (2880 MW lost, nuclear)
System inertia: 171.7 -> 158.9 GVAs after the trip
Peak RoCoF:     -0.453 Hz/s  (largest |df/dt| over the run)
Nadir:          48.340 Hz  (t+6.9 s)
Settling:       49.144 Hz
...

The full output for both models is in docs/_captures/frequency/trip-lumped.txt and trip-distributed.txt; the lines from Peak RoCoF to the half-inertia line are the same in both. dGVa 0.37 is the dominance ratio of the post-trip network (37 %); the 56 % that domains prints is for the network before the trip, which still has Hinkley Point in its dominant domain. On trip, Settling is the frequency at the end of the 30 s window, not a separately detected steady state.

The 2 in that line is the number of swing masses (synchronous domains that carry inertia) at the trip. domains counts every speed domain, including the Pll domain, so it prints 3, and so does the transient line below.

transient under the distributed switch reports the split and does not use it:

$ gridsim transient uk --minutes 0.1 --dt-ms 100 --inertia-model distributed
[transient] uk: done in 0.3s  nadir 50.000Hz  maxRoCoF -0.005Hz/s  exports 1  -> results\transient-uk-20261019-183828
[transient] uk: 60 slices @ 100ms (0.1 min) on Newton-Raphson (dense)...
[transient] distributed inertia: 3 speed domains, deltaGVa 56 % (per-tick integration remains the lumped live model; a distributed live integrator is a follow-up)
[exit 0]

The other verbs print this warning, taken from an h0-study run:

warning: --inertia-model distributed is not honored by 'h0-study' - it runs the lumped scalar model. Only 'trip' integrates the distributed multi-domain model (and 'transient' reports the speed-domain split but still integrates lumped).

Spatial spread between domains and propagation delay are unvalidated at scale. Propagation is off by default (DistributedConfig.EnablePropagation).

Response services

After a loss, three layers arrest the fall.

  1. Stored energy sets the initial slope (the RoCoF) and does nothing to arrest it.
  2. Load damping (demand falls as frequency falls, 1 % of demand per Hz) and governor droop (5 % droop on a responsive share of demand, 20 %, with an 8 s lag) are the generic model of the conventional system's response.
  3. Procured frequency response: Dynamic Containment (DC), Dynamic Moderation (DM) and Dynamic Regulation (DR). Each is a block of MW with a published delivery curve and a response lag.

A service delivers nothing inside its deadband around 50 Hz. Past the deadband the delivery rises along the published curve until the full-delivery deviation, then stays at its MW cap. A knee is a point where the slope changes: below it the service delivers only a small fraction of its volume, past it the slope steepens. The delivered power then follows its target through a first-order lag, with the service's time constant. Low frequency makes a service inject; high frequency makes it absorb.

Service Deadband Knee Full delivery Shape
DC 0.015 Hz 0.2 Hz, at 5 % of volume 0.5 Hz Low-gain segment to the knee, steep segment to full.
DM 0.1 Hz at the deadband, 0 % 0.2 Hz Ramp from the deadband to full.
DR 0.015 Hz at the deadband, 0 % 0.2 Hz Ramp from the deadband to full.

For the 22 December 2023 event the event record holds the volumes the system had cleared in the EAC auction for that delivery block: DC 873 MW (lag 0.3 s), DM 150 MW (0.3 s) and DR 203 MW (4 s), 1,226 MW in all. At a deviation of 0.3 Hz, DC's target is 873 x (0.05 + 0.95 x (0.3 - 0.2) / (0.5 - 0.2)) = 320.1 MW. An event that lists its services as complete (responseServicesComplete, true for events from the start of EAC on 2 November 2023) switches the generic governor off, so the response is not counted twice; load damping always stays. The event also records the frequency the trip landed on (49.879 Hz for 22 December 2023), and the simulation starts in equilibrium there, with services partly deployed.

Where the services apply:

  • Applied: replay-event, scenario, fleet, evidence and h0-study, from the event record, in the baseline and in every counterfactual (a device is additional to what the system held).
  • Not applied: transient and the live view in the apps use the generic governor and damping only, and so does trip without --gb-services.
  • The library also holds a typical GB fleet at DC 950 MW, DM 520 MW and DR 490 MW (GbResponseServices.Typical), with lags of 0.5 s, 2 s and 10 s. trip --gb-services[=<scale>] adds it, times the scale, on top of the generic governor.

Services are changed through the event file: gridsim replay-event <id> --dump-catalog <file> writes the built-in events as JSON, the responseServices array holds mw, deadbandHz, fullDeliveryDeviationHz, timeConstantS, kneeDeviationHz and kneeFraction for each, and --catalog <file> loads an edited copy (see replaying recorded events).

How far to trust a nadir

The RoCoF is set by the inertia and the size of the loss. For a step loss from nominal the swing equation fixes it exactly. The ambient NESO sample is a consistency check on the scale only: its 0.0080 Hz/s implies a 64 MW imbalance at 200 GVA.s, and the calibration test round-trips that figure through the same equation. The nadir and the recovery also depend on three constants that no measured loss-of-infeed trace has yet fitted: load damping (1 % of demand per Hz), the responsive fraction (0.20 of demand) and the governor time constant (8 s). They are literature-typical GB values, and the code documents their uncertainty as a factor of two. The governor droop (5 %) is the GB Grid Code figure and is firm. The delivery curves of DC, DM and DR are the published service shapes; their time constants are literature-typical. fit-frequency fits the three constants to a measured trace and trip --band shows how far each moves a nadir (see Variations); neither changes the shipped values.

Read a nadir as an indicative figure bracketed by the Best and Worst corners, never as a validated prediction. The corners scale the three constants (Best: damping x1.5, responsive fraction x1.5, governor lag x0.7; Worst: damping x0.6, responsive fraction x0.6, governor lag x1.4). On the 22 December 2023 event the corners give a nadir envelope of 48.65 Hz to 49.20 Hz against a recorded 49.275 Hz, and replay-event reports the record as outside the envelope.

The tag [VERIFY] on an event figure means a curated placeholder awaiting a source. The event gb-largest-loss-1320, the SQSS normal infeed loss risk of 1,320 MW, is such a screening case. Its recorded outcome is a placeholder, so Reproduced on its gate says only that the model agrees with the placeholder. replay-event refuses it, because a replay presents its output as a reproduction of history; h0-study, scenario, fleet and evidence study it, print an input provenance: [CuratedPlaceholder] line and tag every figure they write with it.

Run directories

Verb Default location Contents
transient results/transient-<case>-<stamp>/ in the current directory; a batch uses results/transient-<stamp>/<case>/ timeseries.csv, summary.md, run-metadata.json, exports/slice-*.json
h0-study results/h0-study-<event>/ in the current directory h0-study.json, matrix.csv, summary.md, run-metadata.json
replay-event results/replay-<event>/ in the current directory baseline-frequency.json, summary.md, run-metadata.json
freq, replay, domains none They print only.

--out <dir> names the directory for transient and h0-study. run-metadata.json holds the commit, backend, machine, runtime and the run description, so a result traces to the build that produced it. Run directories under a results/ folder are discovered by the desktop app and can be stepped frame by frame (exports and formats).

Exit codes

The general table is in ch. 19, CLI reference. For this chapter's verbs:

Verb Code Meaning
freq 0 Printed.
1 The CSV does not exist.
replay 0 Played, or printed --frames frames.
1 The CSV does not exist, or it holds no data.
transient 0 Every slice converged.
1 No case loaded, or some cases of a batch failed to load (the rest still ran).
2 --dt-ms or --minutes is zero or negative, the run is shorter than one slice, --trip-at falls past the end of the run, --solver is not one of auto, dense, sparse, bfs, sweep, or a numeric flag is malformed.
3 One or more slices did not converge. The run completes and summary.md records the count.
domains 0 Printed.
2 --dir has no value.
h0-study 0 The study ran, including cells that read NaN.
1 The event id is not a built-in event or in the --catalog file, the case fails to load, the case ships no asset-dynamics bundle, or the engine fails.
2 No --event (usage is printed), a malformed list or --corners value, or an event whose timestamp is newer than 169 hours before now.
3 The no-device baseline did not reproduce the record.

Why h0-study exits 3 on gb-2023-12-22

gridsim h0-study --event gb-2023-12-22 --sync-inertia-scale 1,0 --gfm-fraction 0,1
$ gridsim h0-study --event gb-2023-12-22 --sync-inertia-scale 1,0 --gfm-fraction 0,1
GATE FAILED: Refusing to run counterfactuals: the no-device baseline is 'Marginal', not 'Reproduced'. Reproduce reality first. Marginal: RoCoF sim -0.123 vs rec -0.102 Hz/s (20 % err); nadir sim 48.98 vs rec 49.27 Hz (0.30 Hz err); RMSE n/a (no trace)
Fix the event's [VERIFY] figures (or tolerances) until 'replay-event' reports Reproduced, then re-run.
[exit 3]

h0-study first calls the replay validator (ReplayValidator.Validate) with its default tolerances. The validator re-simulates the recorded event with no device and scores two figures. The RoCoF must agree within 15 % of the recorded value, and the nadir within 0.15 Hz. The verdict is Reproduced when both are inside those bounds, Marginal when both are inside twice those bounds (30 % and 0.30 Hz) but not both inside the first, and Failed otherwise. A per-sample RMSE against a trace above 0.05 Hz also demotes a Reproduced result to Marginal; h0-study attaches no trace, which the message states as RMSE n/a (no trace).

Here the simulated RoCoF is -0.123 Hz/s against a recorded -0.102 Hz/s, an error of 20 %: outside 15 %, inside 30 %. The simulated nadir is 48.98 Hz against 49.275 Hz recorded, an error of 0.295 Hz: outside 0.15 Hz, inside 0.30 Hz. Neither figure is inside the first bound, both are inside the second, so the verdict is Marginal. Only Reproduced unlocks a counterfactual, so the engine throws BaselineNotReproducedException, the CLI prints a GATE FAILED line and a one-line hint, and the exit code is 3. This is the only condition that gives h0-study exit 3. replay-event on the same event, with the real 1 s trace attached, reports the same verdict and a trace RMSE of 0.281 Hz. Its full output is in docs/_captures/frequency/replay-event-gb-2023-12-22.txt. The gate message points at the cause: this event is blocked by the model's own figures and tolerances, not by anything in the study.

The h0-study with no arguments prints its usage and exits 2:

$ gridsim h0-study
usage: gridsim h0-study --event <id> [--catalog f] [--dir case]
                        [--sync-inertia-scale 1,0.5,0.25,0] [--gfm-fraction 0,0.25,0.5,0.75,1]
                        [--gfm-class gfm-vsm-study-2024] [--gfl-class gfl-wind-2024] [--corners best,worst]
                        [--trace <neso.csv>] [--out <dir>]
Built-in events: gb-2019-08-09, gb-2023-12-22, gb-largest-loss-1320
Scales REAL synchronous inertia toward 0 x makes the converter fleet grid-forming. REQUIRES a reproduced baseline.
[exit 2]

Pitfalls

  • domains takes a case or --dir, not both. gridsim domains case9 reports SPEED DOMAINS on IEEE 9-bus (WSCC); with no case it loads data/uk. A positional case and a --dir folder that name different networks exit 2, and a --dir folder that does not exist exits 1 (ch. 19, Case arguments).
  • transient with no flags is a long run. The defaults are 60 minutes at 1 ms, which is 3.6 million power-flow solves. The uk run in this chapter solved 600 slices in 1.4 s, about 429 slices per second, so 3.6 million slices take 3,600,000 x 1.4 / 600 = 8,400 s (2.3 hours) at that rate. Set --minutes and --dt-ms for the question you are asking.
  • --trip-at needs --trip. Without --trip MW above zero no trip is scheduled, so --trip-at or --trip-window without it is refused (exit 2) rather than ignored. A --trip-at of 0 trips on the first slice. A --trip-at past the end of the run is refused:
$ gridsim transient case9 --minutes 0.1 --dt-ms 100 --trip 100 --trip-at 30
[transient] case9: --trip-at 30s is past the run end (0.1 min = 60 slices @ 100ms) - the contingency never fires. Aborting.
[exit 2]
  • A trip changes the frequency and nothing else. In transient and the live view the trip enters the swing integrator only. The power flow keeps the unit, so gen_mw, voltages and flows do not respond. Use trip for the contingency that removes the unit and its inertia.
  • A CASC nadir is not a Hz forecast. A cell far below 48.8 Hz tells you a Loss-of-Mains cascade ran away in the model. Compare the verdict, not the figure.
  • HELD is relative to LFDD. It means the nadir stayed above 48.8 Hz.
  • A recent CSV is refused. A row dated within 169 hours of now stops freq and replay with REJECTED (forward inference): ... and exit 2, as on every event verb. Use data that is at least a week old.
  • A damaged or empty CSV is refused. A line after the header that is not a data row exits 1 naming the line. freq on a file with no data rows exits 1 with error: frequency file '<file>' holds no data rows ...; replay prints No data. and exits 1.
  • The interactive replay never ends by itself. It waits for Q or Esc. Always pass --frames N from a script.
  • Run-directory names and timings change on every run. The stamp in a transient directory name, done in ... and solve_ms differ by machine and by run. The frequencies, RoCoF and nadir repeat on the same machine and build with the same case and flags, because the ambient jitter is seeded. No test compares machines.

Limits

  • transient integrates the lumped model under --inertia-model distributed; it prints the speed-domain split only.
  • The live view and transient carry no response services (DC, DM, DR); the event-driven verbs apply the event's recorded services, and only trip --gb-services applies the typical GB fleet.
  • The shipped damping, responsive-fraction and governor-lag constants are not fitted to a measured loss-of-infeed trace (fit-frequency fits them to one trace but does not change them), so a nadir is indicative within the Best and Worst corners.
  • Spatial spread and propagation between speed domains are unvalidated at scale, and the distributed model has no grid-forming path (a forming run falls back to the lumped forming integrator).
  • A transient trip is a deficit in the swing integrator; the power-flow state does not respond to it.
  • h0-study runs only on events whose no-device baseline is Reproduced; gb-2023-12-22 is Marginal and cannot be studied.