16. Physics conformance and the constrained estimator

This chapter specifies the physical-law audit: the function PhysicsLaws.Audit that scores a solved or estimated grid state against ten named laws, the residual each law reports, the tolerance it is held to, the five laws that gate acceptance, and the case-by-law conformance matrix that gridsim conformance writes. The audit (src/GridSim.Core/Physics/PhysicsLaws.cs) is a positive-sequence phasor check. It recomputes every branch flow and bus injection from the solved voltages and the branch data by its own per-branch path and never calls a power-flow solver, so a pass is corroboration that the voltages satisfy the network equations.

The Feasible estimator (EstimationMethod.Feasible) uses the audit as its acceptance gate. This chapter specifies the gate: which laws it scores, against which injections, at which tolerance, and when it demotes a state. The estimator's solve (the interior guard, the active-set KKT, the observability and bad-data machinery) is specified in ch. 6, State estimation. It is not repeated here. The power flow whose states are audited is ch. 3, Power flow; the per-unit conventions and the branch stamp are in ch. 2, Data model and per-unit conventions. Running the verbs is ch. 27, Validation tools.

Model

The ten laws

GridSim is a positive-sequence phasor model with an electromechanical frequency layer. The circuit laws and AC synchronism are checkable against it. The field laws are not, and the audit reports them as Constitutive or NotModeled with no fabricated residual. PhysicsCheckRegistry.Names (src/GridSim.Core/Physics/PhysicsCheckRegistry.cs) holds the ten labels; the audit reads them from there, so a label is written once.

# Law Class Residual Unit Status rule
1 Conservation of energy hard abs(sum_i P_net_i - TotalLossMw) MW Holds when the residual is at most tol
2 Ohm's law hard largest per-branch-end difference between the recomputed flow and the solver's LineFlow MVA Holds when at most tol
3 Joule heating hard abs((sum_k L_k + shuntLoss) - TotalLossMw) MW Holds when at most tol
4 Faraday induction constitutive none (NaN) - always Constitutive
5 Ampere's law (passivity) reported max(0, -min_k L_k) MW Constitutive when min_k L_k >= -tol, else Violated
6 Kirchhoff's current law hard largest real injection mismatch over the constrained buses MW Holds when at most tol; NotApplicable in an AuditAgainst with no real injection named
7 Kirchhoff's voltage law structural 0 V always Holds
8 Complex power S = V I* hard max(r6, rq), the larger of the real and reactive injection mismatches MVA Holds when both are at most tol; NotApplicable as law 6, with no reactive injection named either
9 AC phase and frequency synchronism dynamics larger of the normalised angle and frequency margins margin Holds when at most 1.0; NotApplicable without a SynchronismSample, with a detail starting NOT SCORED:
10 Gauss's law / Coulomb not modelled none (NaN) - always NotModeled

tol is tolMva, compared with the MW or MVA number directly, not in per-unit. When a caller passes none it is PhysicsLaws.DefaultTolMva(model) = BaseMva * 1e-8 (see "Where tolerances come from"). The unit of law 9 is Hz on a steady-state snapshot (where it is NotApplicable and has no residual) and margin when a dynamics sample is scored.

Independent recomputation

For every in-service branch whose two ends are in the solved result, the audit forms the branch end currents and complex powers from the solved voltages with the branch pi-model stamp:

v_i              = Vm_i * (cos(Va_i) + j sin(Va_i))               Va in radians
(Yff,Yft,Ytf,Ytt)= AdmittanceStamp.Branch(R, X, B, TapRatio, PhaseShiftDeg)
I_from           = Yff*v_f + Yft*v_t           I_to = Ytf*v_f + Ytt*v_t
S_from           = v_f * conj(I_from)          S_to = v_t * conj(I_to)          (pu)
Sbus[f]         += S_from                      Sbus[t] += S_to
L_k              = Re(S_from + S_to) * BaseMva                                    (MW, branch k)

A bus shunt (Gs + jBs)/BaseMva contributes S = v_i * conj(ySh * v_i) to Sbus[i], and its real part, times BaseMva, to shuntLoss. Sbus[i] is the complex power the network draws at bus i, so it equals the specified injection (generation minus load) at a bus the solver balanced. Then:

P_net_i   = Re(Sbus[i]) * BaseMva              Q_net_i = Im(Sbus[i]) * BaseMva
r1        = abs(sum_i P_net_i - TotalLossMw)
r3        = abs((sum_k L_k + shuntLoss) - TotalLossMw)
r2        = max over aligned branches, over the four terms
            |Re(S_from)*B - PFromMw|, |Im(S_from)*B - QFromMvar|,
            |Re(S_to)*B   - PToMw|,   |Im(S_to)*B   - QToMvar|            (B = BaseMva)
r6        = max over i with constrainP[i]:  |P_net_i - specP_i|
rq        = max over i with constrainQ[i]:  |Q_net_i - specQ_i|
r8        = max(r6, rq)
r5        = max(0, -min_k L_k)                              minimum over audited branches

A branch is aligned when its ordinal is inside LineFlows and the flow's From and To equal the branch's. An out-of-service branch is electrically absent: it is skipped, and so is a branch with an endpoint missing from the result, but the ordinal advances for both so that every later branch is compared with its own flow. Laws 1 and 3 read one quantity, the total dissipation, two ways (the sum of net injections and the sum of branch plus shunt losses), and agree to rounding. Law 2 is the only law that compares against what the solver reported per branch.

The audit takes the branch stamp from AdmittanceStamp.Branch, the same function the Y-bus uses. It is independent of the solver's nodal Y V product and of its iteration, and shares the stamp arithmetic, which AdmittanceStampPinTests pins separately. tools/crossval/physics_audit.py rebuilds the admittance matrix in NumPy and is the cross-language backstop.

Specified injections for laws 6 and 8

specP_i = sum(Pg at bus i) - pLoad_i          specQ_i = sum(Qg at bus i) - qLoad_i
(pLoad_i, qLoad_i) = LoadAtVoltage.Mw(bus i, Vm_i)

LoadAtVoltage returns the nominal Pd, Qd untouched for a constant-power bus and Pd * PMultiplier(Vm), Qd * QMultiplier(Vm) for a voltage-dependent ZIP load, the rule the Newton mismatch uses. The constrained components depend on which entry point is called.

Entry point constrainP[i] constrainQ[i] specP, specQ
Audit bus is not Slack the bus ENDED the solve as Pq (PowerFlowResult.SolvedBusTypes; the declared type when the solver does not report one) the model's Pg - load, as above; at a declared-PV bus pinned at a reactive limit, the nearer of sum(Qmax) - qLoad and sum(Qmin) - qLoad
AuditAgainst the bus appears in SpecifiedInjections.PMw the bus appears in SpecifiedInjections.QMvar the caller's value, replacing the model's, for exactly the named components

Audit is the right test of a power-flow solution of the case-file dispatch. It is the wrong test of a state estimate, because the real injections differ from the case file by megawatts. AuditAgainst(model, result, specified, tolMva, synchronism) therefore scores laws 6 and 8 against the injections the state is bound to. Buses the specification does not name are unconstrained, since the state alone is the authority on what flows there. A specification that names a bus absent from the state, or a non-finite value, throws ArgumentException: silently skipping either would make the verdict claim a check that never ran. When a specification names no real injection, law 6 is NotApplicable with a NaN residual, and law 8 is NotApplicable when it names no real and no reactive injection; there is never a vacuous Holds. AuditAgainst with the case-file injections reproduces Audit bit for bit (FeasibleKclGateTests.AuditAgainst_with_the_static_dispatch_reproduces_the_plain_audit_bit_for_bit).

Law 9: synchronism

A steady-state power flow is a snapshot at the model frequency, so law 9 is NotApplicable. A dynamics caller supplies a SynchronismSample and the law is scored on a real residual:

angleMargin = MaxAngleSpreadDeg / PoleSlipLimitDeg        (infinite when the limit is not positive)
freqMargin  = MaxFreqExcursionHz / FreqBandHz             (infinite when the band is not positive)
residual    = max(angleMargin, freqMargin)
if FormingBoundHz > 0:  residual = max(residual, MaxFreqExcursionHz / FormingBoundHz)
status      = Holds when residual <= 1.0, else Violated

SynchronismSample defaults are PoleSlipLimitDeg 180, FreqBandHz 0.8 and FormingBoundHz 0 (inactive). A residual below 1 means synchronism held with headroom. Law 9 is never in the hard-gate set.

No verb or export supplies a sample (D-DOC-188, October 2026), so outside the tests law 9 always reads NotApplicable and its detail starts NOT SCORED:. The one verb with machine trajectories, stability --clear, gives its own synchronism verdict from the integrator's pole-slip test (ClassicalMultiMachine.StayedInSynchronism: any machine more than 2 pi from the centre of inertia), on a different angle limit and with no frequency band, so a second verdict from law 9 there could contradict it; it is not wired.

The hard-gate set and the gate

PhysicsCheckRegistry.HardGateLaws = { 1, 2, 3, 6, 8 }
Gate(hardLaws) = every law whose number is in hardLaws has Status != Violated

The hard laws are those whose violation is physically impossible: a state that breaks one is not a network state. The gate passes a hard law that is NotApplicable, so a gate verdict reads "no hard law is violated", not "every hard law was checked". PhysicsLawReport.AllHold is the stricter test that no law at all is Violated. The other five laws are reported and never gate: 4 and 5 are constitutive, 7 is structural, 9 is a dynamics property and 10 is outside the model. Laws 6 and 8 share one residual (law 8 is the larger of the real and reactive parts); law 1 does not use a specified injection and checks the total dissipation against the reported loss.

Joule and Ampere: the passivity split

Joule heating gates the consistency of the reported total loss. Passivity, that every branch dissipates I^2 R >= 0, is Ampere's law (law 5) and is reported when violated but never gated. Some case data carries a branch with negative resistance, a network-reduction artefact. A negative I^2 R is a property of the model, not of the state, and neither the solver nor the estimator can repair a model. case145 is the bundled example. Its audit holds laws 1 to 3, 6 and 8, reports law 5 Violated with the most negative branch loss, and the gate passes (see the worked example).

Where tolerances come from

One documented rule (D-DOC-125, October 2026): the default tolerance is the power-flow convergence tolerance on the case's own base, DefaultTolMva(model) = BaseMva * DefaultTolerancePu with DefaultTolerancePu = 1e-8 (equal to the PowerFlowOptions.Tolerance default; a test pins them together). Newton stops when the largest bus mismatch is below 1e-8 pu, so a converged solve promises exactly BaseMva * 1e-8 MVA: laws 6 and 8 re-derive that mismatch by another path, and laws 1, 2 and 3 are identities that hold to rounding. On a 100 MVA base the rule is exactly the double 1e-6, the old absolute default, so every 100 MVA verdict is unchanged; on the 10,000 MVA uk base it is 1e-4, where the old 1e-6 failed a converged solve (law 6 1.06e-6 MW, law 8 2.48e-6 MVA); on the 1 and 10 MVA distribution bases it is tighter than before. The rule scores the physics block of the solve export, the default of physics-check and conformance (whose --tol sets one absolute line instead; the default was an absolute 1e-4), the scheduler job physics (also enabled by the job name conformance; the gridsim conformance verb is separate), the web conformance panel (FrameProjector.BuildConformance), the WPF experimental view, and the sidecars physics_audit.py and residual_check.py (whose defaults were an absolute 1e-4 and 1e-6). The Feasible estimator's gate passes FeasibilityConstraints.AuditTolMva, default 1e-4, its own documented envelope setting. The false-data-injection screen uses its own 0.1 * BaseMva (see ch. 6).

The estimate exports (estimate-export.json and the --export-solve estimated-solve-export.json) are scored against the estimate's own state, not the case-file dispatch (D-DOC-040, EstimateExport.PhysicsReport): when the Feasible gate ran, its own report is written (KCL against the hard zero-injection rows at AuditTolMva); otherwise AuditAgainst with no specified injection at DefaultTolMva, so laws 1, 2 and 3 are scored and laws 6 and 8 read NotApplicable. The physics block names which in an additive basis field: case-dispatch, zero-injection-constraints or estimate-state.

The conformance sweep

gridsim conformance is the audit over a fixed corpus. The corpus is nine embedded cases (case9, case14, case30, case57, case118, case145, case300, case24_ieee_rts and cigre_mv) plus every .m file under data/matpower/ whose stem is not one of those nine (those nine stems are the embedded copies), 27 cases in all. BuildCases assembles the list and RunConformance sorts it by a size key and then by label: the key is the bus count for an embedded case and, for a file, the first six digits of all the digits in the stem joined together (0 when there are none). For each case, with PowerFlowOptions { MaxIterations = 100, EnforceQLimits = true } and the selected engine:

load fails or the solve throws        -> skipped    (message on the error stream)
not Converged, on the allowance list
  with the status the list expects    -> allowed (row printed with "allowed", reason listed, no audit, no CSV rows)
not Converged, otherwise              -> unconverged (row printed, no audit, no CSV rows)
otherwise  report = Audit(model, result, tol or DefaultTolMva);  gate = report.Gate(HardGateLaws)
           worst  = the hard law with the largest residual (NaN counts as 0; a tie keeps the lower number)

The matrix has one row per case. conformance.md (the table printed to the console) has the columns case, buses, conv, gate, worst hard law and residual. conformance.csv has one row per converged case per law, after #-prefixed run-stamp lines, with the columns case,buses,converged,gate_pass,law_number,law_name,status,residual, unit,tolerance,commit; residual is written with six decimals of mantissa (E6) and is empty for a NaN. run-metadata.json is the run stamp. The exit code is:

exit 0   every converged case passed, none was skipped, and every unconverged case is allowed
exit 1   a converged case failed the gate
exit 3   any case skipped, or unconverged without an allowance   (overrides 1)

Exit 3 exists so a case that stops converging cannot disappear from the gate. On the shipped corpus three cases are unconverged on every run: pglib_opf_case3_lmbd, pglib_opf_case162_ieee_dtc and pglib_opf_case240_pserc. Each is a PGLib optimal-power-flow operating point, an optimisation solution that plain Newton-Raphson from its stored voltages does not converge on within 100 iterations (status MaxIterations). They are on the explicit allowance list (ConformanceAllowances.KnownUnconverged, D-DOC-039), each with its reason, matched by file stem and by the expected status, so the shipped corpus exits 0 and any new failure still fails. An allowed case that converges is audited like any other (a stderr note says the allowance was not needed); --no-allowances switches the list off.

A separate lake-scale sweep audits stored, demand-scaled states: tools/crossval/lake_conformance.py compares S = V conj(Y V) with the stored injection of each period rather than the case file's Pg - Pd (see ch. 11).

How the Feasible estimator uses the audit

After the Feasible loop converges, the estimator evaluates the state as a power-flow result (EstimationResult.ToPowerFlowResult, pure evaluation, no solver call) and runs two checks (src/GridSim.Core/Estimation/WlsStateEstimator.cs):

report = AuditAgainst(model, projected, ZeroInjectionSpecification(mm), AuditTolMva)
limits = PhysicsFeasibility.Check(model, projected, Feasibility)

lawBreach   = not report.Gate(HardGateLaws)
limitBreach = RejectOnLimitViolation and limits.Count > 0
if lawBreach or limitBreach:  Status = Infeasible,  Converged = false

ZeroInjectionSpecification names exactly the buses whose real or reactive injection a hard zero-injection constraint row binds, at the constraint's value. The converged state must meet those to AuditTolMva. A telemetered injection is a noisy observation of a device, so the estimate's departure from it is a statistical residual, judged by the chi-square test and the bad-data loop, not a breach of Kirchhoff's law. Two constraint rows for one bus and component that disagree throw ArgumentException. Laws 1, 2 and 3 are identities of the projected state and gate as before. With no zero-injection rows, laws 6 and 8 read NotApplicable, the gate passes them, and the estimate is bound to no nodal injection. AuditGate (default true) switches the gate off; Feasibility.Validate() rejects an empty or inverted envelope before the solve starts.

The solve's convergence test accounts for step scaling: the loop stops when the largest component of the applied step is below Tolerance (default 1e-8) and either the step was left unscaled (neither a trust cap nor, for the Feasible method, the interior guard reduced it) or the largest component of the unscaled Gauss-Newton correction is also below Tolerance, so a step that a cap or the guard shrank, even to zero, cannot end the solve as converged. The rule is the one in ch. 6 (WlsStateEstimator, stepScale >= 1.0 || rawUpdate < Tolerance). The envelope fields and the rings are in ch. 6.

The operational envelope

PhysicsFeasibility.Check (src/GridSim.Core/Physics/PhysicsFeasibility.cs) is separate from the laws. The laws ask whether the state is a network state at all; the envelope asks whether the equipment can hold it. It reports a LimitViolation(Kind, A, B, Value, Limit, Detail) for each breach and never gates by itself.

Kind Breach Slack
VmBand Vm < lo or Vm > hi, per-bus band else VmMin..VmMax VmBandTolPu = 1e-9 pu
GenQ Qg outside the summed [Qmin, Qmax] of the generators on the bus; the slack bus is exempt GenQTolMvar = 1e-3 MVAr
Rating LoadingPercent > 100 on a branch with a positive rating RatingTolPercent = 1e-6 percentage points

Qg is QInjMvar + qLoad with the load taken at the solved voltage. GenQTolMvar is NewtonShell.QLimitTolMva itself, so the audit and the solver cannot disagree on whether a bus is at its limit. An infinite limit is not checked. A breach demotes a state only under RejectOnLimitViolation; otherwise it is reported on EstimationResult.LimitViolations.

Experimental laws 11 to 16

Law numbers above 10 are allocated in one place, PhysicsCheckRegistry, so two audits cannot claim one number. None is in the hard-gate set, none is part of Audit, and each is reached through gridsim experimental and src/GridSim.Core/Physics/Experimental/. Each is off by default and collapses to a trivial pass in its degenerate limit.

# Law Residual Unit Default tol Verb
11 Reciprocity max abs(Y_ij - Y_ji) over branch pairs with no phase shift; phase shifters are excluded as non-reciprocal by design pu 1e-9 experimental reciprocity <case>
12 Harmonic KCL max abs(Y(h) V(h) - I(h)) over analysed orders (h = 1 and orders with no injection skipped) and buses pu 1e-8 experimental harmonic-kcl <case>
13 Synchronising-Laplacian row sum max abs(row sum of K_ext) MW/rad 1e-6 * max(1, max abs(K_ext)) experimental modal-consistency <case>
14 Grid passivity max(0, -min Re(Z_grid(jw))) over 5 to 2500 Hz in 5 Hz steps pu 1e-9 experimental passivity <case> [--bus ID]
15 Converter non-passive band max(0, -min Re(Y_conv(jw))) pu 0 none
16 COI null mode smallest abs(eigenvalue) of the swing-only A matrix rad/s 1e-6 experimental modal-consistency <case>

A residual in laws 11, 12, 13 or 16 is a model or solve defect, not an impossible state. Law 14 reports Constitutive when the driving-point impedance is positive-real and Violated with the worst frequency otherwise. It skips frequencies where the network is singular and counts them in the detail line; when every frequency is singular it throws rather than report "passive". Law 15 is always Constitutive: a grid-following converter is expected to show a negative-real band near its PLL bandwidth, which the Nyquist test then adjudicates. The default bus for law 14 is the bus of the generator with the largest Pg.

experimental wave <case> (ContinuumWaveModel) is not a law. It treats the linearised swing as a damped wave equation M d2(delta)/dt2 + D d(delta)/dt + K_L delta = P (inertia M = 2H/ws, synchronising graph-Laplacian K_L), whose modes K_L phi = w^2 M phi are the inter-area electromechanical modes, solved by the Jacobi eigensolver SymmetricEigen. It is a linearisation of ClassicalMultiMachine and reduces to the single-machine analytic frequency in its degenerate limit. The other experimental verbs (trace, carbon, boundaries) are listed in the CLI reference.

Parameters and defaults

Name Value Unit Meaning Source symbol
Audit tolerance BaseMva * 1e-8 MVA default pass line of Audit (and the exports, verbs and sidecars); 1e-6 on a 100 MVA case PhysicsLaws.DefaultTolMva, DefaultTolerancePu
physics-check tolerance BaseMva * 1e-8 MVA --tol default (an explicit value is one absolute line) RunPhysicsCheck in src/GridSim.Cli/Program.cs
conformance tolerance BaseMva * 1e-8 per case MVA --tol default (an explicit value is one absolute line) RunConformance in src/GridSim.Cli/Program.cs
Conformance allowances 3 PGLib cases, status MaxIterations - unconverged cases that do not fail the run ConformanceAllowances.KnownUnconverged in src/GridSim.Cli/ConformanceAllowances.cs
Gate audit tolerance 1e-4 MVA the Feasible gate's pass line FeasibilityConstraints.AuditTolMva
Hard-gate laws {1, 2, 3, 6, 8} - laws whose violation fails the gate PhysicsCheckRegistry.HardGateLaws
Verb power-flow options 100 iterations, Q limits on, case-file start - solve used by physics-check and conformance PowerFlowOptions as built in Program.cs
Law 9 pass line 1.0 margin synchronism holds at or below PhysicsLaws.SynchronismLaw
Pole-slip limit 180 deg angle denominator of law 9 SynchronismSample.PoleSlipLimitDeg
Frequency band 0.8 Hz frequency denominator of law 9 SynchronismSample.FreqBandHz
Forming bound 0 (inactive) Hz extra grid-forming margin when positive SynchronismSample.FormingBoundHz
Voltage floor 1e-6 pu positivity floor of the Feasible interior guard FeasibilityConstraints.VmFloor
Voltage band 0.9 to 1.1 pu audited after convergence, per-bus override allowed FeasibilityConstraints.VmMin, VmMax, PerBusVm
Angle-difference limit pi/2 rad across-branch ceiling the active set holds FeasibilityConstraints.AngleDiffMaxRad
Enforce generator Q true - hold each generator inside [Qmin, Qmax] at solve time FeasibilityConstraints.EnforceGeneratorQ
Enforce branch ratings false - hold branch flow at its rating at solve time FeasibilityConstraints.EnforceBranchRatings
Fraction to boundary 0.995 - interior-guard step fraction FeasibilityConstraints.FractionToBoundary
Audit gate true - run the acceptance gate FeasibilityConstraints.AuditGate
Reject on limit violation false - a limit breach also demotes FeasibilityConstraints.RejectOnLimitViolation
Band slack 1e-9 pu voltage-band edge tolerance PhysicsFeasibility.VmBandTolPu
Generator Q slack 1e-3 MVAr reactive-capability tolerance PhysicsFeasibility.GenQTolMvar
Rating slack 1e-6 percentage points thermal-loading tolerance PhysicsFeasibility.RatingTolPercent

Invariants

Invariant Pinned by
A true power-flow solution holds every hard law at 1e-4 MVA on case9, 14, 30, 57, 118 and 300, and no law is Violated PhysicsAuditTests.A_true_solution_holds_every_hard_law
The audit reports ten laws in order, with Faraday and Ampere Constitutive, Gauss NotModeled and synchronism NotApplicable without a sample PhysicsAuditTests.All_ten_laws_are_reported_in_order
A physically impossible state (a negative voltage magnitude) fails the gate PhysicsAuditTests.A_negative_bus_voltage_is_caught_by_the_gate
Law 9 scores a real margin: held at 40 deg spread, violated at 200 deg PhysicsAuditTests.Synchronism_scores_a_real_residual_from_a_sample
Law labels come from the registry, with the audit's wording, and the audit source carries no hand-written headline label PhysicsRegistryNamesTests
An exactly solved ZIP case holds laws 6 and 8 PowerFlowPhysicsConsistencyTests.Physics_audit_of_an_exactly_solved_zip_case_holds
A branch the audit cannot check does not misalign later branches with their line flows PowerFlowPhysicsConsistencyTests.Physics_audit_keeps_line_flow_alignment_after_a_branch_it_cannot_audit
AuditAgainst with the case-file injections equals Audit bit for bit; bad specifications and contradictory constraints fail loud FeasibleKclGateTests
A noisy Feasible estimate is not demoted by the case-file dispatch, KCL is checked at the zero-injection bus, and the gate still demotes a state that breaks a constraint FeasibleKclGateTests.Noisy_feasible_estimate_is_not_demoted_by_the_static_dispatch, Gate_still_demotes_a_state_that_breaks_a_zero_injection_constraint
The acceptance gate demotes a state that fails a hard law; limit breaches are reported and do not demote by default FeasibleEstimationTests.The_acceptance_gate_demotes_to_Infeasible_when_a_hard_law_fails, Operational_limits_are_reported_but_do_not_demote_by_default
Feasible keeps every voltage positive and equals Constrained on clean data FeasibleEstimationTests.Feasible_keeps_every_voltage_strictly_positive, Feasible_matches_Constrained_on_clean_data
An empty or inverted envelope fails loud before the solve FeasibilityEnvelopeValidationTests
The export physics block carries the gate verdict, the hard-law list and all ten laws with the full field set PhysicsExportContractTests
Experimental law numbers are unique, named, above 10 and never hard-gate laws ExperimentalLawNumberTests.Experimental_law_numbers_are_unique_named_and_never_hard_gates
The hard-gate set is the definition of "physically possible": no operational preference (band, rating) joins it PhysicsCheckRegistry.HardGateLaws, read by every gate caller

Worked example

gridsim physics-check case14 solves the IEEE 14-bus case in 2 Newton iterations and audits it:

$ gridsim physics-check case14
...
| 1 | Conservation of energy | Holds | 2.38E-013 | MW | independent dissipation 13.393272 MW (branch 13.3933 + shunt 0.0000) vs reported loss 13.393272 MW |
...
| 6 | Kirchhoff's current law | Holds | 2.01E-009 | MW | network real injection vs specified, at constrained buses |
...
| 8 | Complex power S = V I* | Holds | 1.32E-008 | MVA | same residual as law 6, reactive component included at 9 PQ bus(es), by the bus types the solve ended with |
...
GATE: PASS  -  state is physically admissible (all hard laws hold).
[exit 0]

Law 1 compares the sum of the per-branch dissipation (13.3933 MW, shunt 0.0000 MW) with the reported total loss 13.393272 MW and finds 2.38e-13 MW. Law 6 is the real-power mismatch at the 13 non-slack buses, 2.01e-9 MW, and law 8 is the larger of that and the reactive mismatch at the PQ buses, so the reactive mismatch is 1.32e-8 MVAr. The independent NumPy audit of the same export agrees on the two balance residuals to the digits printed:

$ python tools/crossval/physics_audit.py src/GridSim.Cli/bin/Release/net10.0/results/crossval-case14/solve-export.json
physics audit: ? (14 buses), tol 0.0001 MVA
  energy 4.01e-13 MW  KCL 2.01e-09 MW  S=VI 1.32e-08 MVAr  min branch loss -2.84e-14 MW
  independent gate: PASS   exported gate: PASS   agree: True
VERDICT: PASS
[exit 0]

The model-passivity case. gridsim physics-check case145 carries a negative-resistance branch, and the audit holds the hard laws while reporting law 5 (case145 total loss 74802.589870 MW: branch -1829.8883 MW plus shunt 76632.4782 MW):

$ gridsim physics-check case145
...
| 5 | Ampere's law (passivity) | Violated | 2.80E+002 | MW | NON-PASSIVE branch in the model: most-negative branch loss -2.80E+002 MW (R < 0 in the data) |
| 6 | Kirchhoff's current law | Holds | 1.35E-007 | MW | network real injection vs specified, at constrained buses |
...
GATE: PASS  -  state is physically admissible (all hard laws hold).
[exit 0]

The same holds at scale. gridsim physics-check data/gb-full (3,539 buses) reports law 1 at 3.39e-09 MW on a loss of 523.821145 MW, law 6 at 1.81e-09 MW and law 8 at 5.00e-09 MVA, and passes the gate.

A noisy estimate is not a dispatch. gridsim estimate case14 --synth --export-solve --out results/est-case14s writes estimated-solve-export.json. Its physics block is scored by Audit against the case-file dispatch, and so is the NumPy audit; both fail on the same 1.90 MW real mismatch, and agree that they fail:

$ python tools/crossval/physics_audit.py results/est-case14s/estimated-solve-export.json
physics audit: ? (14 buses), tol 0.0001 MVA
  energy 2.49e-14 MW  KCL 1.90e+00 MW  S=VI 1.35e+00 MVAr  min branch loss -3.55e-15 MW
  independent gate: FAIL   exported gate: FAIL   agree: True
VERDICT: FAIL
[exit 1]

Energy conservation holds to 2.5e-14 MW, since the projected state is exact network physics, and the injections differ from the case file by the telemetry noise. This is why the Feasible gate uses AuditAgainst against the zero-injection rows and not Audit (FeasibleKclGateTests.Noisy_feasible_estimate_is_not_demoted_by_the_static_dispatch proves the case-file audit would reject that state).

The sweep, gridsim conformance, over the shipped corpus gives 24 audited cases, all PASS, with worst hard-law residuals from 1.69e-12 (case9) to 2.20e-07 (case1354pegase), and 3 unconverged PGLib operating points (exit 3). The complete matrix is in ch. 27.

Source map

File Type Responsibility
src/GridSim.Core/Physics/PhysicsLaws.cs PhysicsLaws, SpecifiedInjections Audit, AuditAgainst, the independent recomputation, laws 1 to 10
src/GridSim.Core/Physics/PhysicsLawReport.cs LawStatus, LawResult, PhysicsLawReport, SynchronismSample status, per-law result, Gate, AllHold, the dynamics input
src/GridSim.Core/Physics/PhysicsCheckRegistry.cs PhysicsCheckRegistry law names, HardGateLaws, experimental law numbers
src/GridSim.Core/Physics/PhysicsFeasibility.cs PhysicsFeasibility the operational envelope check
src/GridSim.Core/Estimation/FeasibilityConstraints.cs FeasibilityConstraints the Feasible envelope, Validate, AuditTolMva
src/GridSim.Core/Estimation/WlsStateEstimator.cs WlsStateEstimator the acceptance gate, ZeroInjectionSpecification, the convergence test
src/GridSim.Core/Estimation/FeasibleWlsStep.cs FeasibleWlsStep the active-set KKT (ch. 6)
src/GridSim.Core/IO/SolveExport.cs, EstimateExport.cs SolveExport.PhysicsBlock the additive physics block
src/GridSim.Cli/Program.cs RunPhysicsCheck, RunConformance, BuildCases the two verbs and the corpus
src/GridSim.Core/Physics/Experimental/ ReciprocityCheck, HarmonicKclCheck, SmallSignalConsistency, ImpedancePassivityCheck, ContinuumWaveModel laws 11 to 16 and the wave model
src/GridSim.Core/Scheduling/AnalysisJobLibrary.cs PhysicsAudit the scheduler job
src/GridSim.Web/Projection/FrameProjector.cs BuildConformance the web conformance panel
tools/crossval/physics_audit.py script independent NumPy recomputation of laws 1, 6 and 8 and the exported-gate cross-check
tools/crossval/residual_check.py script independent admittance matrix and power-balance residual
tools/crossval/lake_conformance.py script the audit over the stored GDA lake

Limits

  • No verb or export supplies a SynchronismSample, so law 9 reads NotApplicable (NOT SCORED) outside the tests.
  • A solver that does not report the bus types it ended with (the backward/forward sweep, a presolved state read from disk) leaves SolvedBusTypes null, and laws 6 and 8 then use the declared types, as before October 2026.
  • The physics block's gatePass is the hard-law gate only; whether the solve converged is the separate converged field of the export (physics-check itself fails a non-converged solve, exit 3).
  • experimental wave builds a non-symmetric synchronising Laplacian on a solved case and feeds it to a solver that reads one triangle, so the centre-of-inertia eigenvalue lifts off zero and the dominant inter-area mode it reports can be that lifted mode (R035).

See also