15. Protections

This chapter specifies the protection device layer on the asset-dynamics seam: free-standing protective devices (RoCoF and loss-of-mains, under- and over-frequency, df/dt, vector shift, under- and over-voltage, thermal overload, low-frequency demand disconnection and topology auto-reclosers) that run inside the same fleet as the inverter controllers. A device reads a locally sampled quantity, compares it with a threshold, and when the threshold has been crossed for a dwell time it acts on one of the channels the asset seam already carries: lost infeed, demand shed, or an opened branch. The code is in src/GridSim.Core/Assets/Protection/.

The layer models generic protective behaviour, not a site's relay scheme. Site relay settings are unpublished, so every authored setting is generic and carries the provenance rules described in ch. 8, Provenance and invariants; the grounding of the two shipped device classes is recorded in ch. 13, Asset dynamics data grounding. The passive relay overlay that grades a solved network state (protection-check) is ch. 17, Protection assessment. Short-circuit currents are chapter 25 (Short-circuit, IEC 60909) and inverse-time grading is chapter 26 (Overcurrent coordination); neither is repeated here. The frequency integrator that the layer plugs into is specified in ch. 5, Frequency dynamics. The authoring recipe for a new class is in ch. 29, Extending GridSim.

Model

Where a protection sits

A protection is an IActiveAssetDynamics (src/GridSim.Core/Assets/IAssetDynamics.cs): one stateful object per placed device, advanced once per fast sub-step by AssetDynamicsFleet. The fleet holds the inverter controllers and the protection controllers in one array. Each step the fleet sums the AssetActuation of every member:

AssetActuation(ActivePowerMw, TrippedNow, TrippedInfeedMw, TrippedInertiaMwS)

fleet net swing power   pAssetFleet   = sum of ActivePowerMw over the fleet
fleet trip deficit      tripDeficit   = running sum of TrippedInfeedMw over every step with TrippedNow
swing imbalance         pImbalance    = pBase + pAssetFleet - tripDeficit
RoCoF                   rocof         = f0 / (2 E) * pImbalance

pBase is the imbalance before the fleet (event, governor, fast response, damping, the standing imbalance pStanding and the system-response services), E is max(1, inertia + DeviceRotationalInertiaMwS) in MW.s and f0 the nominal frequency. In forming mode the predictor is f0 / (2 * eForming) * (pForcingBase - dampTotal * df), with the forming inertia and damping. A protection controller never reports inertia: TrippedInertiaMwS is always 0.

Stage

One definite-time stage is a ProtectionStage (ProtectionElement.cs):

Field Meaning
Quantity Frequency, Rocof, Voltage, LoadingFraction or PhaseShift.
Sense Above (operate when the value exceeds the threshold) or Below (operate when it falls under).
Threshold The pickup, in the unit of the quantity.
DwellSeconds The definite time the condition must hold.
Action TripInfeed, ShedDemand, InjectStep, OpenBranch or RestoreBranch.
ActionMw The MW the action moves. 0 means use the placed device's capacityMw.
LocalUpliftFactor Multiplies a RoCoF reading (sub-cycle local RoCoF is larger than the COI value).
AutoRestoreDelayS Reset delay after operating. +infinity (the default) latches.
ArmDelayS The stage cannot operate while the clock is below this.
TargetBranch The branch an OpenBranch action opens.

ArmDelayS is populated only by code that builds a stage directly. No class parameter sets it, and a class that carries an armDelayS key is refused at load as an unknown key, so an author cannot believe it took effect.

Quantities and units

The controller reads these from AssetStepContext (LocalHz, LocalRocofHzPerS, LocalPhaseDeg, LocalVoltagePu, LoadingFraction, DtSeconds, ClockSeconds). Per update:

push (ClockSeconds, LocalHz, LocalRocofHzPerS, LocalPhaseDeg) into the delay history
(fMeas, rocofMeas) = history sample read at  ClockSeconds - detectionLatencyS
phaseStep          = phase(newest sample) - phase(sample read at  ClockSeconds - max(DtSeconds, 0.02))

value(Frequency)       = fMeas                          Hz
value(Rocof)           = |rocofMeas| * LocalUpliftFactor   Hz/s
value(Voltage)         = LocalVoltagePu                 pu of nominal
value(LoadingFraction) = LoadingFraction                1.0 = 100 % of branch rating
value(PhaseShift)      = |phaseStep|                    degrees over the window

The delay history is MeasurementDelay (src/GridSim.Core/Assets/GridFollowingInverter.cs), the same buffer the inverter controllers use. It is a ring of 512 samples, 10.24 s at the 20 ms sub-step. Read(now, latency) returns the newest stored sample whose time stamp is at or before now - latency + 1e-12, and the oldest stored sample when none qualifies; an empty history reads nominal frequency, zero RoCoF and zero phase. A device therefore sees the start of the run, not the present, until latency seconds of history exist. Once the 512 samples are full, a latency longer than the span they hold is refused with an error (both the protection device and the inverter controller check it on every update), rather than being shortened to that span. Only frequency and RoCoF are delayed. Voltage and loading are taken from the step context as supplied, and the phase window is not delayed. PhaseStep reads zero until a stored sample at least one window old exists, so the first update of a run sees no phase step.

The RoCoF in the context is the integrator's predicted RoCoF: f0 / (2 E) * pBase (non-forming), computed before the fleet acts (AssetAwareFrequencyIntegrator.Step, AssetFrequencyDynamics.Simulate). It excludes the fleet's own contribution, which is what lets a device be evaluated without an algebraic loop. The phase is the accumulated angle against nominal, phaseDeg += 360 * (f - f0) * h in degrees, so a PhaseShift stage reads the angle moved in the last max(DtSeconds, 0.02) seconds.

Pickup and dwell: ProtectionEvaluator

ProtectionEvaluator (ProtectionEvaluator.cs) is the quantity-agnostic edge detector for one stage. It receives the already selected and scaled value. As coded:

Step(ctx, value):
    if operated:
        if ClockSeconds >= restoreAt:            # only reachable with a finite AutoRestoreDelayS
            operated = false;  dwell = 0;  restoreAt = +inf
            return Restored
        return None                              # latched, or waiting out the reclose delay
    if ClockSeconds < ArmDelayS:  return None
    over  = (Sense == Above) ? value > Threshold : value < Threshold      # strict comparison
    if over:  n = n + 1;  dwell = carry + n * DtSeconds                     # whole sub-steps counted
    else:     n = 0;  carry = 0;  dwell = 0                                   # any miss resets the dwell
    if over and DwellReached(dwell, DwellSeconds):
        operated  = true
        restoreAt = (AutoRestoreDelayS is +inf) ? +inf : ClockSeconds + AutoRestoreDelayS
        return Fired                             # exactly once per operation
    return None

Consequences that follow directly from the code:

  • The comparison is strict. A value equal to the threshold does not pick up.
  • The dwell counts whole over-threshold sub-steps and includes the step on which the stage fires: the elapsed time is the count times DtSeconds (a sub-step of a different length banks the steps counted so far into carry first), not a repeated sum. DwellReached(elapsed, dwell) is elapsed >= dwell, or, for a finite dwell, dwell - elapsed <= 2^-49 * dwell (DwellRelativeSlack), so a representation error in the step cannot add a step; an infinite dwell never times out. A stage with DwellSeconds = 0 fires on the first update whose value is over the threshold. A positive dwell is met on the first update at which the counted time reaches it, so the operating time is quantised to the sub-step (20 ms at the default DynamicsConfig.StepSeconds): a 0.2 s dwell at 20 ms is met on the tenth update. The inverter controllers' confirm times are counted the same way (ConfirmTimer).
  • A single update below the threshold clears the accumulated dwell. A spike shorter than the dwell never operates.
  • Fired is emitted once. While the stage is operated it returns None, whatever the value does.
  • After Restored the dwell restarts from zero, so a condition that persists through a reclose operates the stage again after its dwell.
  • ProtectionAction.RestoreBranch is refused: the ProtectionEvaluator constructor throws NotSupportedException for a stage with that action. Nothing acts on a restore request, so a stage built with it would operate and change nothing. Reclosing is expressed as an OpenBranch stage with a finite AutoRestoreDelayS. The controller's own RestoreBranch case also throws, so the action cannot become a silent no-op if the construction guard is removed.

Building the stages: ProtectionController

ProtectionController (ProtectionController.cs) builds one stage for each protection parameter the class sets and drives one evaluator per stage. A parameter the class omits builds no stage. The stages are built in this fixed order:

# Class key (stage built when set) Quantity Sense Threshold Dwell key Action
1 rocofTripHzPerS Rocof Above rocofTripHzPerS rocofTripConfirmS trip
2 dfDtTripHzPerS Rocof Above dfDtTripHzPerS dfDtTripDwellS trip
3 ufTripHz Frequency Below ufTripHz ufTripDwellS trip
4 ofTripHz Frequency Above ofTripHz ofTripDwellS trip
5 uvTripPu Voltage Below uvTripPu uvTripDwellS trip
6 lvrtVoltagePu, only when greater than 0 Voltage Below lvrtVoltagePu none (0 s) trip
7 ovTripPu Voltage Above ovTripPu ovTripDwellS trip
8 overloadTripFraction LoadingFraction Above overloadTripFraction overloadTripDwellS trip
9 vectorShiftTripDeg, only when finite PhaseShift Above vectorShiftTripDeg none (0 s) trip
10 lfddStageHz Frequency Below lfddStageHz lfddDwellS ShedDemand, ActionMw = lfddBlockMw

"Trip" in the table is TripInfeed for an ordinary class and OpenBranch for a recloser class (below). Stages 1 and 2 multiply the RoCoF by localRocofUpliftFactor (default 1.0); no other stage uses the uplift. A confirm or dwell key has no default: a class that sets a stage's threshold key without its confirm or dwell key is refused when the controller is built (InvalidDataException naming every missing key; write 0 for an instantaneous stage). Stages 6 and 9 have no dwell key and are instantaneous. Stage 10 is always a demand shed, whether or not the class is a recloser, and it never auto-restores.

The MW each stage moves is ActionMw when positive, else the placed device's capacityMw. For an infeed trip and an unset lfddBlockMw that is capacityMw.

What each action does when its stage fires (ProtectionController.Update):

Action Effect on the model
TripInfeed If the device has not already tripped: TrippedNow = true and TrippedInfeedMw = mw for this step, and Tripped latches. The fleet adds mw to tripDeficit, which enters the swing as lost infeed for the rest of the run. A device whose class builds several trip stages (RoCoF, df/dt, UF, ...) loses its infeed once: the second and later stages that fire find Tripped already set and add nothing.
ShedDemand shed += mw * demandScale (mw = lfddBlockMw; the block is a share of the demand now running, so it is exactly mw unless the live loop scaled the demand, N297; the stage remembers it so a reclose reconnects the same MW). The controller returns ActivePowerMw = shed, a positive swing-power term: demand removed reduces the deficit. Tripped is not set; a demand shed operates but is not a tripped unit.
InjectStep shed += ActionMw, a signed step on the same channel. No class parameter builds this action; it exists for code that builds stages directly.
OpenBranch Tripped latches and the target branch's hold count is incremented. The branch is reported through OpenBranches. Nothing is added to the swing at this point; the topology layer acts on the branch (below).
RestoreBranch Refused (see above).

When a finite-delay stage returns Restored, ShedDemand and InjectStep subtract what they added, and OpenBranch releases that stage's hold. The controller counts holds per branch: several stages (RoCoF, UF, ...) can open the same branch, each with its own reclose delay, and the branch stays open until the last holding stage has reclosed. Tripped then equals "at least one branch is still held open". The shipped LFDD stage latches, so Restored is not produced for it by the controller.

Reset() clears every evaluator, the delay history, the shed total, Tripped and the held branches.

Reduction gate

A controller whose stages never operate returns AssetActuation(0, false, 0, 0). The fleet then adds 0.0 to pAssetFleet and 0.0 to tripDeficit, and the swing computes pBase + 0.0 - 0.0, which equals pBase bit for bit. A case with no protections.json, or with devices that never operate, therefore reproduces the lumped trajectory exactly.

Placement and files

A protection has two parts. The class describes the device; the placement says where it is and what it acts on. Both files are optional, and both bundles are null-gated, so a case without them is untouched.

The class: asset-classes.json

A device class is an entry of kind: "protection" (the loader also accepts relay and protective) in the same asset-classes.json that holds the inverter classes. The entry is name, kind, mode, a flat params bag of class keys to numbers, and a provenance map from key to {tag, note}. The protections classes of the bundled data/gb-synthetic/asset-classes.json are these two:

Class params Provenance
prot-lom-legacy rocofTripHzPerS 0.125, rocofTripConfirmS 0.0, localRocofUpliftFactor 1.16 rocofTripHzPerS: Recorded (legacy GB loss-of-mains setting, GDA rocof_events relay_legacy grade). localRocofUpliftFactor: DerivedFromRecorded (sub-cycle local over COI RoCoF, 1.16).
prot-lfdd-stage1 lfddStageHz 48.8, lfddDwellS 0.0, lfddBlockMw 632.0 lfddStageHz: Recorded (GB Grid Code first LFDD stage, CC.A.5.5.1 Table CC.A.5.5.1a). lfddBlockMw: DerivedFromRecorded (GDA lfdd_risk 632 MW coincident block, 2019-08-09).

Class loading is strict (AssetClassSupport, src/GridSim.Core/Assets/AssetClassLibrary.cs). A protection class accepts exactly the keys in the parameter table below; any other key, a misspelling included, is refused at load with every problem listed. Class names are matched ignoring case. Every CuratedPlaceholder provenance note must carry the literal [VERIFY] token or the library is refused when a case is loaded (JsonGridLoader.BuildLibrary calls AssetClassLibrary.ValidateOrThrow; a library built in code is checked only if the caller invokes it). The meaning of each tag is defined once, in chapter 8.

The placement: protections.json

protections.json (schema schemas/v1/protections.schema.json, ProtectionInstanceDto) is an array of placed devices:

Member Required Meaning
name no Device name.
class yes A class of kind protection in asset-classes.json. In a v2 network the member is template.
monitorBus yes The bus whose solved voltage and loading the device reads. Must be a bus of the case.
capacityMw no, default 0, schema minimum 0; a negative or non-finite value is refused when the placement is validated (D-DOC-094) MW the device trips (infeed) or sheds (demand when lfddBlockMw is unset).
targetBranch recloser only The branch name the recloser opens.

The shipped placement for data/gb-synthetic:

embedded-dg-lom  class prot-lom-legacy   monitorBus 1  capacityMw 800
system-lfdd-1    class prot-lfdd-stage1  monitorBus 1  capacityMw 632

The loader (JsonGridLoader.BuildProtections) returns a ProtectionModel of the class library plus the placed ProtectionInstance records, or null when the file has no instances. It refuses a file with instances but no classes, an unknown class, and a class that is not of kind protection. After the model is built, ProtectionModel.ValidateAgainst checks the placement against the network and throws one InvalidDataException listing every problem:

  • a class missing from the library, or a class that is not of kind protection;
  • a monitorBus that is not a bus of the model (it would read 1.0 pu and zero loading, so its voltage and overload stages could never operate);
  • a recloser (a class that sets autoRecloseDelayS) with no targetBranch, or a targetBranch that names no branch;
  • a targetBranch on a device whose class is not a recloser.

The ProtectionController constructor repeats the recloser check: a recloser class built with no target throws InvalidDataException, so a device that cannot do what its class says never exists.

AssetDynamicsFleet.Build creates one ProtectionController per placed instance and adds it to the fleet after the inverter controllers. The loaded placement is also what GridModel.CopyWith and the island, inertia and cascade transforms carry through.

Recloser classes

A class that sets autoRecloseDelayS is a recloser. Every trip stage in it (rows 1 to 9 of the stage table) becomes an OpenBranch stage on the placement's targetBranch with AutoRestoreDelayS = autoRecloseDelayS. The class's LFDD stage, if it has one, stays a demand shed.

Integration with the frequency integrator and LiveSim

LiveSim runs the asset-aware integrator when its DynamicsConfig sets EnableAssetDynamics and the case carries an asset-dynamics bundle, a protections bundle, or both (LiveSim.HasAuthoredBundle). The desktop app, the web session and the scheduled-cycle runner build that configuration with one shared rule, LiveSim.AuthoredBundleConfig(model), so a case with only protections.json runs its protections there as it does under trip. (Before D-DOC-079 those three tested the asset-dynamics bundle only, and such a case ran with its protections idle. No bundled case changes: the one bundled protections bundle, gb-synthetic's, ships with an asset-dynamics bundle.)

Tier A: frequency and injection domain

RoCoF/loss-of-mains, under- and over-frequency, df/dt and LFDD plug into the fleet and need nothing from the network. The integrators call AssetDynamicsFleet.StepCoi(f, rocofPredict, phaseDeg, h, clock, ...) and fold pAssetFleet and tripDeficit into the imbalance as in the model section.

  • AssetFrequencyDynamics.Simulate (the scripted run of the trip verb) calls it once per outer step of DynamicsConfig.StepSeconds (default 0.02 s), with no further sub-division of the fleet step.
  • AssetAwareFrequencyIntegrator (the running clock of LiveSim), in non-forming mode, sub-steps each tick at h <= 20 ms (MaxInternalDt) and calls it once per sub-step, with at most 4000 sub-steps per tick.
  • In forming mode both call it once per step and sub-divide the swing by FormingKernel.SubStepCount.

LFDD is closed loop. The stage fires when the simulated frequency falls under lfddStageHz, and the shed +lfddBlockMw enters pAssetFleet on the update that fires, so it lowers the fall from that sample onward. It replaces a scripted LFDD step; it must not be run alongside one, or the demand is removed twice.

The fleet trip deficit and the LFDD shed persist until the fleet is reset (AssetDynamicsFleet.Reset, called by the integrator constructors and by AssetFrequencyDynamics.Simulate). In the scripted runs they stay applied for the run. In LiveSim the live deficit (manual trips through TripInfeed and the blackout term) decays with the 300 s secondary-restoration constant SecondaryTauS, and the integrator restores the fleet's standing deficit (its trips net of held protection injection, and its sheds) over the same constant (secondaryRestorationTauS): the redispatch R follows the deficit as a first-order lag, integrated exactly per sub-step. The tripped units stay tripped; what recovers is the balance.

Tier B: voltage and loading

Voltage and LoadingFraction stages read AssetStepContext.LocalVoltagePu and LoadingFraction. The pure lumped model solves no network, so the context holds NoNetworkVoltagePu and NoNetworkLoadingFraction, both NaN ("not known"). Every comparison with NaN is false, so no voltage or loading stage operates on a path that solves no network, whatever its setting; frequency, RoCoF and phase stages are unaffected. StepCoi builds the shared default context when both of its optional suppliers voltageOf and loadingOf are null, which keeps the lumped path bit-identical. trip with asset dynamics prints a note when assets carry such stages: they are not evaluated on that run.

LiveSim supplies the quantities after every power-flow solve through AssetAwareFrequencyIntegrator.SetNetworkState(voltageOf, loadingOf):

voltageOf(bus) = Vm of the bus in the solved result          (1.0 if the bus is absent)
loadingOf(bus) = max over the in-service branches incident to the bus of  LoadingPercent / 100
                                                              (0.0 when no branch is incident)

The values are held constant across the fast sub-steps of the tick, because the solve is much slower than the swing step. (The fleet's former per-domain Step(sampler, ...) entry, which had no production caller and built its context without voltage or loading, was removed in R074; StepCoi is the one fleet step.)

Topology: recloser, islanding and blackout

Each tick LiveSim does the following in order:

  1. aware.Fleet.OpenBranches() from the previous tick gives the set of branches held open.
  2. If the set is not empty, TopologyOps.Apply(model, openBranches) marks those branches InService = false and runs IslandPartition.Prepare. If it is empty, the model solves unchanged.
  3. The solve runs on the adjusted model. YBus.Build, the sparse SparseNewtonRaphsonPowerFlow.BuildY, BackwardForwardSweep and NewtonShell.ComputeLineFlows skip an out-of-service branch. With every branch in service the admittance accumulation order is unchanged, so the solve is bit-identical to a model with no topology feature.
  4. The island report's net blackout netBlackout = LostLoadMw - LostGenMw enters the swing as a one-off perturbation of the live deficit: _tripDeficitMw += netBlackout - lastBlackoutNetMw. Load lost is surplus, so frequency rises. When every branch has reclosed, the stored lastBlackoutNetMw is subtracted and cleared: the load coming back is a new step of -netBlackout, applied in full.

The live deficit is a superposition of step imbalances, each decaying with SecondaryTauS (300 s). The decay of the outage step stands for the rest of the system redispatching down to the smaller load, so at a reclose t seconds later the system is short by the redispatched amount, netBlackout * (1 - exp(-t / 300)): frequency dips (cold load pickup) and recovers as the reclose step decays in turn. A reclose within seconds leaves almost nothing; one after a long outage leaves nearly the whole block. This was reviewed under D-DOC-080 (a docs-session finding that read the reclose as an undo with a residual of the wrong sign) and kept as the intended behaviour; no number changed.

IslandPartition.Prepare is a union-find over in-service branches. It groups the buses into connected components and treats each island as follows:

Island has Action
a slack bus Kept as it is.
generation but no slack The bus carrying the largest single generator (by abs(Pg)) is promoted to slack.
no generation Blacked out: its buses, branches and generators are dropped, and its demand and generation are added to LostLoadMw and LostGenMw.

A model that is one component containing a slack bus is returned untouched. The reclose reverses the topology on the next tick, where the controller's hold count reaches zero and the branch leaves OpenBranches.

Parameters and defaults

Class keys of a protection (AssetParams, src/GridSim.Core/Assets/AssetClassLibrary.cs; the accepted set is AssetClassSupport.AcceptedKeys(AssetKind.Protection)). A key omitted from a class builds no stage or takes the default shown; a dwell key omitted while its threshold key is set is refused.

Key Unit When omitted Meaning
rocofTripHzPerS Hz/s no stage RoCoF/loss-of-mains pickup on abs(RoCoF) * uplift.
rocofTripConfirmS s refused when rocofTripHzPerS is set RoCoF dwell.
localRocofUpliftFactor ratio 1.0 Scales the RoCoF reading of stages 1 and 2.
dfDtTripHzPerS Hz/s no stage df/dt pickup.
dfDtTripDwellS s refused when dfDtTripHzPerS is set df/dt dwell.
ufTripHz Hz no stage Under-frequency pickup.
ufTripDwellS s refused when ufTripHz is set Under-frequency dwell.
ofTripHz Hz no stage Over-frequency pickup.
ofTripDwellS s refused when ofTripHz is set Over-frequency dwell.
uvTripPu pu no stage Under-voltage pickup.
uvTripDwellS s refused when uvTripPu is set Under-voltage dwell.
ovTripPu pu no stage Over-voltage pickup.
ovTripDwellS s refused when ovTripPu is set Over-voltage dwell.
lvrtVoltagePu pu no stage Low-voltage trip, instantaneous. A value of 0 or less builds no stage.
overloadTripFraction fraction of rating no stage Thermal-overload pickup on the incident-branch loading.
overloadTripDwellS s refused when overloadTripFraction is set Overload dwell.
vectorShiftTripDeg deg no stage Vector-shift pickup on the phase moved over the window. A non-finite value builds no stage.
detectionLatencyS s 0 Relay latency applied to the frequency and RoCoF readings.
lfddStageHz Hz no stage LFDD pickup (frequency below).
lfddDwellS s refused when lfddStageHz is set LFDD dwell.
lfddBlockMw MW placed capacityMw Demand shed by the stage.
autoRecloseDelayS s not a recloser Makes the class a recloser; the reset delay of its OpenBranch stages.
settingsNominalHz Hz 50 The nominal the frequency settings are written for; on a system at another nominal they move by the difference. Load refuses a ufTripHz or lfddStageHz that is not strictly below it, an ofTripHz that is not strictly above it, and any of them more than 10 Hz from it on its own side (AssetClassSupport.MaxFrequencySettingDistanceHz).

Fixed values in the code:

Value Setting Source
Phase window max(DtSeconds, 0.02) s ProtectionController.Update
Delay history 512 samples MeasurementDelay.Capacity
Read tolerance 1e-12 s on the latency cut-off MeasurementDelay.Read
Sub-step at most 0.02 s AssetAwareFrequencyIntegrator.MaxInternalDt
Sub-steps per tick at most 4000 AssetAwareFrequencyIntegrator.MaxSubSteps
Live trip-deficit decay 300 s LiveSim.SecondaryTauS

This layer ships no pickup defaults of its own: a stage exists only for a key the class sets, and the two bundled classes above are the whole shipped set. The ENA G99 Issue 2 Table 10.1 interface-protection settings (27 at 0.80 pu, 59 at 1.10 pu, 81U at 47.5 Hz, 81O at 52.0 Hz, 81R at 1.0 Hz/s with 0.5 s) are the pickups of the passive relay overlay, ProtectionSettings in src/GridSim.Core/Protection/ProtectionTypes.cs, and are specified in chapter 17. A class in this layer reproduces them by setting the keys above to the same numbers.

Invariants

Invariant Pinned by
No protections.json gives a trajectory byte-identical to the lumped baseline. ProtectionTests.Reduction_gate_no_protections_is_byte_identical
A device whose threshold is never reached gives a byte-identical trajectory. ProtectionTests.A_protection_that_never_operates_is_byte_identical
A RoCoF stage trips at least the placed capacityMw (the test asserts a lower bound) and deepens the nadir. ProtectionTests.Rocof_lom_protection_trips_and_deepens_the_nadir
An under-frequency stage operates when the frequency falls through its pickup. ProtectionTests.Under_frequency_protection_trips_when_frequency_falls_through_its_stage
Dynamic LFDD sheds demand, raises the nadir, and is not counted as a trip. ProtectionTests.Dynamic_lfdd_sheds_demand_and_arrests_the_fall
A stage fires only after its dwell, and a spike shorter than the dwell does not fire. ProtectionEvaluatorTests.Fires_only_after_the_dwell_is_satisfied, A_sub_dwell_spike_does_not_fire
A finite reclose delay resets the stage. ProtectionEvaluatorTests.Auto_reclose_restores_after_the_delay
A stage is blocked until its arm delay has passed. ProtectionEvaluatorTests.Arm_delay_blocks_operation_until_armed
An under-voltage stage trips on a fed low voltage and stays quiet at nominal; over-voltage and overload trip on their fed quantities. ProtectionVoltageTests.Under_voltage_protection_trips_when_fed_a_low_voltage_and_is_inert_at_nominal, Over_voltage_and_thermal_overload_trip_on_their_fed_quantities
An under-voltage stage is inert in the pure lumped model (the test covers under-voltage only; over-voltage and overload rest on the strict comparison above). ProtectionVoltageTests.Voltage_protection_is_inert_in_the_pure_lumped_model
A recloser opens its branch on its condition without an infeed trip, holds it through the delay, and recloses. ProtectionRecloserTests.Recloser_opens_its_branch_on_under_frequency_and_recloses_after_the_delay
Opening a branch partitions the model and books the lost load. ProtectionRecloserTests.TopologyOps_applies_an_open_branch_and_partitions
No open branch is a no-op. ProtectionRecloserTests.No_open_branches_is_a_no_op, IslandPartitionTests.All_in_service_is_a_no_op
An island with generation gets a slack; a dead island is blacked out with its load booked; the adjusted model solves. IslandPartitionTests.Islanding_a_generating_region_elects_a_slack, Islanding_a_dead_region_blacks_it_out_and_books_the_lost_load, The_adjusted_islanded_model_solves
A recloser with no target branch fails loud; an invalid placement names its problem (each test row has one problem); a valid one passes. ProtectionWs6Tests.A_recloser_with_no_target_branch_fails_loud, An_invalid_placement_fails_loud, A_valid_placement_passes
The shipped placement validates, and the loader calls ValidateAgainst. FollowUpWiringTests
A RestoreBranch stage is refused. AssetClassSupportTests.A_restore_branch_protection_stage_is_refused_rather_than_silently_doing_nothing
An armDelayS key, or any key no protection reads, is refused. AssetClassSupportTests.A_key_no_consumer_of_the_kind_reads_is_refused
The accepted keys equal the v2 kind specs less the refused keys; the bundled classes load. AssetClassSupportTests.The_accepted_keys_match_the_v2_kind_specs_less_the_refused_keys, The_bundled_classes_load_and_no_longer_carry_the_unread_ramp_key
A CuratedPlaceholder note without [VERIFY] is refused. ProtectionTests.Protection_provenance_verify_rule_is_enforced

Worked example

The run is the trip verb on the bundled data/gb-synthetic case with --asset-dynamics. trip removes the largest non-slack synchronous unit at t = 1.0 s: Hinkley Point Nuclear, 2880 MW. The case places two devices on bus 1: embedded-dg-lom (RoCoF 0.125 Hz/s, uplift 1.16, 800 MW) and system-lfdd-1 (48.8 Hz, 632 MW block). The runs are deterministic and the captured output carries no timing stamps.

To isolate the two devices, the runs below use copies of the case under results/protections/: prot-only is data/gb-synthetic with asset-bindings.json removed, so only the protections act and no inverter responds; lom-only and lfdd-only are that copy with one placement line deleted from protections.json.

$ gridsim trip results/protections/prot-only --asset-dynamics
Asset dynamics: on  (8 class(es), 2 protection(s), 1 unit(s) tripped, 800 MW lost to LoM)
GridSim  -  contingency on GB synthetic
================================================================
Tripped:        Hinkley Point Nuclear  (2880 MW lost, nuclear)
System inertia: 171.7 -> 158.9 GVAs after the trip
Peak RoCoF:     -0.579 Hz/s  (largest |df/dt| over the run)
Nadir:          48.186 Hz  (t+6.3 s)
Settling:       49.076 Hz

50.05 Hz |***+=-:,,..           ...,,,::::-----============-----------::::| 48.19 Hz (nadir)

...at HALF the inertia (79.5 GVAs): RoCoF -0.906 Hz/s, nadir 47.872 Hz
[exit 0]

The header line reports the library's 8 classes (the file defines six inverter classes besides the two protections), 2 placed protections, and 1 unit tripped: the LoM device. The LFDD device sheds demand, so it is not a tripped unit. The last line is a baseline without the fleet and does not change between runs. Its nadir equals the LoM-only nadir (47.872 Hz) to three decimals by coincidence; the two runs have different inertia and deficit.

What each device did, from the four captures in docs/_captures/protections/:

Case Capture Peak RoCoF (Hz/s) Nadir (Hz) Nadir time Settling (Hz)
No asset dynamics trip-no-assets.txt -0.453 48.334 t+6.9 s 49.142
LoM only trip-lom-only.txt -0.579 47.872 t+6.9 s 48.903
LFDD only trip-lfdd-only.txt -0.453 48.592 t+5.8 s 49.307
LoM and LFDD trip-prot-only.txt -0.579 48.186 t+6.3 s 49.076
Full case: protections plus inverter fleet trip-asset-dynamics.txt -0.576 49.052 t+5.5 s 49.525

The numbers follow from the equations:

  • Without the fleet the first post-event RoCoF is 50 * 2880 / (2 * 158900) = 0.453 Hz/s (E is the 158.9 GVA.s after the trip, 158900 MW.s).
  • The LoM stage reads 0.453 * 1.16 = 0.526 Hz/s, above its 0.125 Hz/s pickup, with a 0 s dwell. It fires on the first fleet update after the event, at t = 1.0 s, and adds 800 MW to the deficit. The new imbalance is 3680 MW and 50 * 3680 / (2 * 158900) = 0.579 Hz/s, which is the captured peak.
  • With LoM and LFDD both placed, the exported trajectory (--export) first reads under 48.8 Hz at the sub-step at t = 3.36 s (48.79468 Hz; the step before reads 48.80311 Hz). The LFDD stage fires on that sub-step. The following step falls 0.00641 Hz where the LoM-only run falls 0.00840 Hz, a difference of 0.00199 Hz per 20 ms step, against the predicted 50 * 632 / (2 * 158900) * 0.02 = 0.0019887 Hz: the 632 MW block, entering as a positive swing term. The exported CSV is rounded to 5 decimals.
  • LFDD alone (first RoCoF 0.453 Hz/s) crosses 48.8 Hz later, at t = 4.24 s, and holds the nadir at 48.592 Hz.
  • With the LoM trip alone the nadir is 47.872 Hz; adding the LFDD block lifts it to 48.186 Hz.
  • The full case adds the inverter fleet bound by asset-bindings.json. Its nadir is 49.052 Hz, above the 48.8 Hz LFDD stage, so LFDD does not operate in that run; the LoM device still trips (1 unit, 800 MW in the header).

To reproduce the full-case row, run gridsim trip data/gb-synthetic --asset-dynamics.

Source map

File Type or member Responsibility
src/GridSim.Core/Assets/Protection/ProtectionElement.cs MonitoredQuantity, ThresholdSense, ProtectionAction, ProtectionStage The vocabulary: what a stage watches, how it compares, what it does.
src/GridSim.Core/Assets/Protection/ProtectionEvaluator.cs ProtectionEvaluator, ProtectionEdge The dwell, arm and reclose state machine of one stage; refuses RestoreBranch.
src/GridSim.Core/Assets/Protection/ProtectionController.cs ProtectionController Builds stages from a class, reads the delayed measurements, applies actions, tracks held branches.
src/GridSim.Core/Assets/Protection/ProtectionModel.cs ProtectionInstance, ProtectionModel.ValidateAgainst Placement record and the placement-against-network check.
src/GridSim.Core/Assets/AssetDynamicsFleet.cs AssetDynamicsFleet.Build, StepCoi, OpenBranches Creates controllers per placement, steps the fleet, aggregates swing power, deficit and open branches.
src/GridSim.Core/Assets/GridFollowingInverter.cs MeasurementDelay The 512-sample delay history shared with the inverter controllers.
src/GridSim.Core/Assets/IAssetDynamics.cs AssetStepContext, AssetActuation, IActiveAssetDynamics The seam.
src/GridSim.Core/Assets/AssetClassLibrary.cs AssetClass, AssetClassLibrary, AssetClassSupport, AssetParams Class parsing, accepted keys, [VERIFY] rule.
src/GridSim.Core/IO/Json/ProtectionDto.cs, JsonGridLoader.cs, V2CaseLoader.cs ProtectionInstanceDto, BuildProtections, MapProtection Reading protections.json (v1) and the protections member (v2).
src/GridSim.Core/Dynamics/AssetFrequencyDynamics.cs AssetFrequencyDynamics.Simulate Scripted lumped run with the fleet (the trip verb).
src/GridSim.Core/Dynamics/AssetAwareFrequencyIntegrator.cs AssetAwareFrequencyIntegrator, SetNetworkState Running-clock integrator with the fleet and the network feed.
src/GridSim.Core/Simulation/LiveSim.cs LiveSim.Step, BuildVoltageOf, BuildLoadingOf Network feed, topology application, blackout perturbation, trip-deficit decay.
src/GridSim.Core/PowerFlow/TopologyOps.cs TopologyOps.Apply Marks opened branches out of service and partitions.
src/GridSim.Core/PowerFlow/IslandPartition.cs IslandPartition.Prepare, IslandReport Islands, slack election, blackout.
src/GridSim.Core/Model/Model.cs Branch.InService, GridModel.Protections The model fields.
src/GridSim.Core/PowerFlow/YBus.cs, SparseNewtonRaphsonPowerFlow.cs, BackwardForwardSweep.cs, NewtonShell.cs admittance and flow assembly Skip out-of-service branches.
src/GridSim.Cli/Program.cs trip --asset-dynamics The verb that runs a protection event on a case.
tests/GridSim.Tests/ ProtectionTests, ProtectionEvaluatorTests, ProtectionVoltageTests, ProtectionRecloserTests, ProtectionWs6Tests, IslandPartitionTests, AssetClassSupportTests, FollowUpWiringTests The pins listed under Invariants.

Limits

  • Every stage is definite-time; inverse-time characteristics are not part of this layer.
  • Frequency and RoCoF stages read the single lumped centre-of-inertia signal, so an island created by a recloser has no frequency of its own and monitorBus selects only the bus for the voltage and loading readings.
  • Voltage and thermal stages operate only under LiveSim with a solved network; the scripted AssetFrequencyDynamics run (trip, h0-study, asset sweeps) and the fleet's sampler path feed NaN voltage and loading, so those stages are not evaluated there.
  • In the scripted runs a tripped infeed stays in the fleet deficit and an LFDD shed stays in pAssetFleet until the fleet is reset; only LiveSim restores them by secondary response.
  • A class holds one LFDD stage (lfddStageHz), so a multi-stage scheme needs one class and one placed device per stage.
  • Reconnection is a single step of the whole blacked-out block: there is no staged restoration, no cold-load inrush above the pre-outage demand, and no resynchronising delay for generation in the dead island.
  • ProtectionStage.ArmDelayS and ProtectionAction.InjectStep cannot be set from a class file.
  • The recloser, auto-reclose, measured-voltage, thermal-loading and fault-level settings have no recorded source; they are CuratedPlaceholder with the [VERIFY] token.
  • The case writer does not write protections.json; a written case needs the file copied across by hand.