29. OPF, CPF, taps, distribution factors and loss allocation

This chapter specifies the eight steady-state analyses that sit on top of the power flow: the DC power flow (DcPowerFlow), the DC optimal power flow (DcOptimalPowerFlow), the loss-aware optimal power flow (AcOptimalPowerFlow), the load-multiplier search for the voltage-collapse limit (ContinuationPowerFlow), the coordinated tap optimiser (TapOptimizer), the DC distribution factors (DistributionFactors: PTDF and LODF) and the loss decomposition (LossAllocation). All live in src/GridSim.Core/Analysis/. They reach the command line as dcpf, dcopf, acopf, cpf, taps, ptdf and lodf (the distribution factors) and losses. The chapter states each formulation as implemented, says plainly where a name promises more than the code does (acopf is a DC problem in a loss loop; cpf is a bisection, not a predictor-corrector continuation), and records the exact case-loading, result-file and exit behaviour of each verb. Usage is in ch. 6 of the user manual.

The AC solves inside acopf, cpf and taps use the Newton-Raphson engines of ch. 3, Power flow, chosen by SolverSelector.CreateNewton (sparse at the default threshold of 0, never the sweep). The two engines are bit-identical on the CPU, so the same model gives the same bits from either. The DC solves use the sparse LU of ch. 4, Sparse and GPU numerics. Per-unit conventions and the branch records are in ch. 2, Data model and per-unit conventions.

Model

The DC network model

DistributionFactors.Build (src/GridSim.Core/Analysis/DistributionFactors.cs) forms the DC model every other DC analysis uses. A branch takes part when it is in service, its series reactance X is not zero and both end buses exist in the model. Resistance, line charging, tap ratio and phase shift are ignored, and every voltage magnitude is 1 pu:

b_l       = 1 / X_l                                    (per-unit susceptance of branch l; X in pu on BaseMva)
B'[i,i]   = sum of b_l over participating branches at bus i
B'[i,j]   = - sum of b_l over participating branches joining i and j       (i != j)
every island reference bus: its row and column are removed from B'
theta     = B'^-1 * (P / BaseMva)                      (reference angles are 0; P is the net injection in MW)
f_l       = b_l * (theta_from(l) - theta_to(l)) * BaseMva                  (MW, positive from -> to)

Parallel branches add. B' is stamped in branch order into a CsrMatrix and factored once by SparseLu.Factor (reverse Cuthill-McKee ordering, partial pivoting; ch. 3). If the factorisation finds B' singular even with one reference per island, Build throws InvalidOperationException (DC susceptance is singular even with one reference bus per island ...). DcFlows is one solve of the equation above for any injection set; an injection at a reference bus or at an unknown bus id is dropped, which is the reference absorbing it.

Islands. FindIslands joins buses by union-find over exactly the participating branches. Each component is a DC island. If an in-service branch with X = 0 is the only link between two components, FindIslands throws InvalidOperationException, because the reactance-only model cannot represent an infinite susceptance and splitting there would invent an island. Islands are numbered by their first bus in model order. The reference of each island is chosen as follows:

Island Reference bus
Holds the overall slack: slackBusId if given and present, else the first Slack bus, else bus index 0 That slack
Any other island with a Slack bus The first Slack bus in model order
Any other island with generators The bus holding the largest single |Pg| (first in model order among ties)
An island with no generator (dead island) Its first bus, so that B' stays non-singular

The overall slack's reference is first in the reference list and becomes DistributionFactors.SlackBusId. With one island nothing changes from the single-slack formulation: the same reference, the same matrix, the same factorisation. The rule for the other islands is the AC island rule of IslandPartition (ch. 3), with one difference: the DC rule counts an island as having a generator when any generator sits on it, even one at Pg = 0, while the AC pre-pass blacks out an island whose generators all have Pg = 0. Such an island is a live island to the DC model and a dead one to the AC solve. DcIsland records the reference bus id, the bus ids, whether the island has any generator, and its total Pd.

DC power flow

DcPowerFlow.Solve (the dcpf verb) is the DC model above used as a power flow, not a second DC model. It forms the net injection of each bus as the sum of in-service Pg minus Pd (accumulated in model order), and calls DistributionFactors.DcSolve, which builds the same reduced right-hand side as DcFlows (mw / BaseMva, every island reference's entry dropped), solves B' theta = P with the one factorisation, and forms the flows b_l (theta_from - theta_to) BaseMva exactly as DcFlows does (the two share the right-hand-side and flow code, so they give the same bits). Angles are returned in degrees, every island reference at 0. Each island's reference injects -(sum of the other buses' net injections in the island): the DC model is lossless, so that is the whole imbalance. Loading is |flow| / RateAMva x 100, 0 for an unrated branch. The result (DcPowerFlowResult) holds the bus ids, angles and net injections, the branch flows and loadings, and one DcIslandBalance per island (reference bus, bus count, load, scheduled generation, reference injection, whether the island has a generator).

RunDcpf (src/GridSim.Cli/Program.cs) prints one line per island, the number of rated branches above ContingencyAnalysis.OverloadThresholdPercent (100) of RateA, and the --top branches (12 by default, 0 prints none) with the largest absolute flow, ties by branch index. It accepts --top, --out, --json and --csv. Exit 1 when the case does not load or DistributionFactors.Build throws InvalidOperationException. Exit 2 for a negative --top. Exit 3 when an island carries load and has no generator: the report is printed, then dcpf: N island(s) carry load but have no generator, so the DC solution has no physical meaning there. goes to standard error. An overload is reported, not an error. The result tables are branches (index, name, from, to, flow_mw, rate_mva, loading_pct), buses (bus_id, va_deg, p_inj_mw) and islands; --out <file>.csv writes the branch table to the file and the bus table to <stem>-buses.csv, as the verb did before the shared result writer.

PTDF

Column k of the PTDF matrix is the DC flow response to one per-unit injected at bus k and withdrawn at the reference of k's own island:

rhs       = e_k                                         (1.0 at the reduced index of bus k, 0 elsewhere)
theta     = B'^-1 * rhs
PTDF[l,k] = b_l * (theta_from(l) - theta_to(l))         (dimensionless: MW per MW)

PtdfColumn(busId) returns an all-zero column when the bus is a reference bus (the slack column is identically zero) or is not in the model. Every branch of another island has a zero entry. One column is one solve; Ptdf() builds the whole matrix and is memory-heavy beyond small cases. Flow under any injection is f = f0 + PTDF * P, where f0 is the flow of the fixed loads.

LODF

For an outage of branch k the code solves one transfer problem, a unit injected at the from bus of k and withdrawn at its to bus (a reference end contributes nothing to the right-hand side):

theta     = B'^-1 * (e_from(k) - e_to(k))
Phi[l,k]  = b_l * (theta_from(l) - theta_to(l))         (flow on l per unit transferred across k)
LODF[l,k] = Phi[l,k] / (1 - Phi[k,k])          LODF[k,k] = -1
f_l(after outage of k) = f_l + LODF[l,k] * f_k

Phi[k,k] is the share of the transfer that the branch carries itself; it is exactly 1 when the branch is a bridge (no other path). When |1 - Phi[k,k]| < DistributionFactors.IslandingSensitivityTolerance (1e-9, absolute) the outage islands its network: OutageIslands(k) returns true and LodfColumn(k) returns an all-NaN column. Both read the same expression, so they cannot disagree. For an out-of-service branch LodfColumn returns zeros and OutageIslands returns false.

The DC-OPF problem

DcOptimalPowerFlow.Solve(model, costPerGen, enforceLineLimits) (src/GridSim.Core/Analysis/DcOptimalPowerFlow.cs) minimises a linear generation cost; the overload Solve(model, DcOpfOptions) adds cost curves and prices (see Cost data). With g generators, L rated branches (RateAMva > 0, in branch order) and bus bus_i for generator i:

variables    Pg_i  (i = 1..g)           s_l  (l = 1..L)         dispatch in MW; one slack per rated line
minimise     sum_i cost_i * Pg_i
subject to   sum_i Pg_i = D                                      D = sum over buses of Pd
             sum_i PTDF[l, bus_i] * Pg_i + s_l = RateA_l - f0_l  one row per rated line l kept by the screen below
             Pmin_i <= Pg_i <= Pmax_i                            Pmax_i = 1e6 MW when infinite
             0 <= s_l <= 2 * RateA_l
f0_l   = DC flow on line l with every Pg = 0 and the loads at -Pd           (FlowsFrom)
flow_l = f0_l + sum_i PTDF[l, bus_i] * Pg_i = RateA_l - s_l      so -RateA_l <= flow_l <= +RateA_l on every kept line

Unrelievable lines. Before the LP is built, ScreenUnrelievable computes for each rated line the range of DC flows that any dispatch with every unit anywhere in [Pmin, Pmax] could give it (the balance row dropped, so the range covers every dispatch the LP could choose): flowMin = f0_l + sum_i min(a_i Pmin_i, a_i Pmax_i) and flowMax = f0_l + sum_i max(a_i Pmin_i, a_i Pmax_i) with a_i = PTDF[l, bus_i]. A line with flowMin > RateA_l + UnrelievableMarginMw or flowMax < -RateA_l - UnrelievableMarginMw (UnrelievableMarginMw = 1e-6 MW) cannot be brought within its rating by any dispatch. It is left out of the LP, which is then solved over the remaining lines, and it is reported in DcOpfResult.UnrelievableLines (branch index, name, rating, and the reachable minimum and maximum flow), in branch order. When no line is left out the LP is exactly the one described above. A line left out stays over its rating at the dispatch returned, so an Optimal LP gives Feasible = true (and dcopf exit 0, acopf Converged) while those lines are still overloaded. dcopf lists them under <n> rated line(s) cannot be brought within rating by any dispatch; left out of the security LP and still overloaded:, adds secure for every rated line except the <n> listed above (no dispatch can relieve them) to the summary, and writes an unrelievable_lines table and unrelievable_line_count to the result file; acopf lists the lines its final DC pass left out. Nothing in the exit code tells such a run from one with no unrelievable line: a script must read the listing or the result file.

The balance row has no loss term. Pmin is used as given, so a unit with a negative Pmin (storage charging, an exporting interconnector) can be dispatched below zero. A Pmin that is NaN or infinite, a Pmax that is NaN, or a Pmin above Pmax throws InvalidDataException. The generator Pg field is not read, except by the island reference election.

Merit order first. Before any LP the solver builds a merit-order dispatch: start every unit at Pmin, then fill units in ascending cost, ties in generator index order (OrderBy is stable), each to Pmax, until the unserved remainder is at most MeritOrderFillStopMw (1e-9). The dispatch is feasible when D - sum Pmin >= -BalanceToleranceMw (1e-6), sum (Pmax - Pmin) + BalanceToleranceMw >= D - sum Pmin, and the fill leaves a remainder of at most BalanceToleranceMw. This is the dispatch of --no-limits.

When the LP runs. Only when enforceLineLimits is true, the merit order is feasible and at least one branch has RateAMva > 0. Its answer replaces the merit order. A result is feasible only when the LP status is Optimal (over the lines the screen kept). For any other status (Infeasible, Unbounded, IterationLimit) the result carries the merit-order dispatch with Feasible = false, NetworkConstrained = true, the rated lines whose merit-order flow is within BindingToleranceMw (1e-3 MW) of the rating listed as binding, and the status in DcOpfResult.SecurityLpStatus. With no LP run the status is null.

Result. TotalCost = sum Pg_i * cost_i. BindingLines lists every rated line with |flow| >= RateA - BindingToleranceMw at the final dispatch, computed from the dispatch through DcFlows. NetworkConstrained is true when that list is not empty (or the LP failed). Because a dispatch of equal-cost units is a vertex of the LP, a case whose units all cost the same has many optimal dispatches. The DC-OPF LPs price with a near-tie rule (BoundedSimplex.DcOpfPricingTieMargin, relative 1e-10): among the improving columns whose reduced cost is within 1e-10 x S of the best score S, the lowest-index column enters. A degenerate dispatch is therefore the lowest-index optimal vertex, and a last-bit change in the factors cannot pick a different one. The contingency corrective redispatch and the storage LP scheduler pass the same margin (BoundedSimplex.NearTiePricingMargin).

Islands. When FindIslands returns more than one island, SolveIslands dispatches each energised island as its own model: its buses, the branches with both ends in it and its generators, all in model order, with its reference bus marked Slack if it is not already. Each is solved by the connected-case code above and the answers are merged back to the full model's generator and branch indices. No power crosses between islands. An island with no generator is reported and, if it carries load (more than BalanceToleranceMw), makes the result infeasible; it is never dropped. A branch joining two islands is out of service by construction. The result's Islands list holds, per island: reference bus, bus count, load, generation, whether it has generation, its own verdict and its own LP status. The overall SecurityLpStatus is null when no island ran an LP, Optimal when every island that did reached it, and otherwise the first non-optimal status in island order. A generator on a bus the model does not have, or a costPerGen array of the wrong length, throws in the island path.

Cost data

There are two cost paths. The default path prices each unit by its fuel type. The curve path (--costs) prices each unit by its own cost curve.

Fuel-type path. The cost of unit i is costPerGen[i] when the caller supplies an array aligned to model.Generators (no CLI verb does), and otherwise FuelCostPerMwh(Generator.Type). The unit's marginal cost is linear in output, with no fixed, quadratic or piecewise term. A MATPOWER case has an empty Type on every unit, so every unit costs 50 GBP/MWh (DefaultCostPerMwh). FuelCostPerMwh classifies the type with Core's one fuel taxonomy, GridSim.Core.Model.FuelTypes (the economics reader), and returns the cost of the kind:

Kind (FuelKind) GBP/MWh
empty type, or no keyword matches (Other) 50 (DefaultCostPerMwh)
WindOnshore, WindOffshore, Solar, Tidal 1
Hydro 5
Nuclear 10
Storage, PumpedStorage, Hydrogen 30
Coal 45
Biomass 55
Interconnector, GridInfeed 60
Ocgt 95
Recip 120
Ccgt, Chp, Gas 65

FuelTypes lower-cases the type and splits it into words at every character that is not a letter or digit. A keyword matches when each of its words is the start of consecutive words of the type, and the first matching keyword in list order decides, so hydro matches Hydroelectric but coal does not match Charcoal (kind Other, 50). The list, in order, with the kind each keyword selects (FuelTypes.Keywords):

Order Keywords Kind
1 nuclear Nuclear
2 pumped, pump storage PumpedStorage
3 ccgt, combined cycle Ccgt
4 ocgt, open cycle, gas turbine, peaker Ocgt
5 chp, cogen, combined heat Chp
6 coal, lignite Coal
7 biomass, biogas, anaerobic, landfill, waste Biomass
8 hydrogen, fuel cell, electrolys, electrolyz Hydrogen
9 hydro Hydro
10 tidal, wave, marine Tidal
11 offshore WindOffshore
12 wind, onshore WindOnshore
13 solar, pv, photovolt Solar
14 storage, battery, bess Storage
15 interconnector, hvdc, import Interconnector
16 grid, infeed GridInfeed
17 gas Gas
18 reciprocating, recip, diesel, engine, oil Recip

Each reader of the taxonomy skips the keywords it does not read (FuelKeyword.Readers); the economics reader reads every keyword except a bare combined. Because the order is fixed, hydrogen (30) is tested before hydro (5), pumped storage hydro is tested as pumped (30), gas turbine is Ocgt (95), Gas Reciprocating is Gas (65) and the bundled data/uk and data/gb-synthetic plant typed onshore and offshore costs 1. The tests FuelTypesTaxonomyTests.Every_bundled_type_reads_the_same_in_every_reader, A_gas_turbine_is_ocgt_to_every_reader, Hydrogen_and_pumped_storage_are_no_longer_priced_as_hydro, Keywords_match_whole_words_by_their_start and The_substring_false_positives_read_as_other_in_every_reader pin the costs and the rule.

Curve path. With DcOpfOptions.UseGeneratorCosts (the CLI's --costs), the cost of unit i is its Generator.Cost curve, and every in-service unit must carry one. --costs case uses the curves the MATPOWER parser read from mpc.gencost (MatpowerParser, carried in Generator.Cost; a case with a unit that has no row exits 1 with [dcopf] --costs case: K of N in-service generator(s) carry no cost curve (the case has no mpc.gencost for them); give a cost file instead.). --costs <file.json> overlays a gridsim-costs/1 file (GeneratorCostFile.Apply): each entry names a unit by 1-based index in file order or by exact name, and gives a polynomial (coefficients, highest order first) or piecewiseLinear (points, [MW, cost per hour]) model. An unknown key, a unit named twice, a missing file and an invalid curve exit 1 as [dcopf] --costs: <message>. A unit the file does not name keeps the case's own curve, if any. A MATPOWER case file without the flag reads its gencost and ignores it, with a note: on standard error.

GeneratorCostCurve.From accepts a convex quadratic a P^2 + b P + c (a >= 0) and a convex piecewise-linear curve through at least two points with strictly increasing MW and non-decreasing slopes (the first and last segments extend in a straight line outside the points). A polynomial with more than three coefficients is accepted only when every term above the quadratic is exactly 0. A cubic term, a negative quadratic coefficient, a non-convex piecewise curve and a non-finite number are refused with InvalidDataException, naming the unit.

The curve LP has the constraints of the security LP above (the balance row and one thermal row per rated line, DcOpfCosted). A polynomial unit is one column in [Pmin, Pmax] with its linear coefficient as cost; a piecewise unit is one column per segment, costed at the segment slope, which a convex curve fills in order. With no quadratic term the structured simplex solves it. With a quadratic term the simplex gives a feasible vertex and DcOpfQuadratic (a primal active-set method for convex quadratic programs, plain IEEE arithmetic in index order) takes it to the optimum. The total cost is the sum of the curves including their constants. With line limits off the problem has the balance row only.

Prices. With DcOpfOptions.ComputePrices (--prices), y0 is the dual of the balance row and y_r that of thermal row r (each the change in optimal cost per unit increase of the row's right-hand side). The price at bus k is

LMP_k = y0 + sum_r y_r PTDF[r, k]

y0 is the energy component (the price at the island's reference bus) and the sum is the congestion component. The DC model is lossless, so there is no loss component. A line's shadow price is the cost saved per MW of extra rating (-y_r when held at +RateA, +y_r at -RateA). At a degenerate optimum the duals need not be unique; the reported ones are those of the optimal basis or active set found. On a multi-island case each island is priced at its own marginal unit. prices works on the fuel-type path too (dcopf uk --prices).

DcOpfResult carries Prices (null when not asked for or when no optimum with duals was reached) and SolverFailure, the reason the curve solver stopped without an optimum, which the CLI prints as a solver: ... (status ...) line.

The CLI labels a curve run [cheapest secure dispatch on generator cost curves: case gencost|<file name>], prints money as cost units (a curve is in the case's own currency), shows each unit's marginal cost instead of the fuel price (marginal 24.0442 cost units/MWh), and labels the mode (network-constrained) or (no line limit binds). AcOptimalPowerFlow.Solve takes the same options (useGeneratorCosts, computePrices); a cost vector together with either is refused with ArgumentException.

The JSON loader sets Pmin = pMinMw (0 when the file does not give it) and Pmax = pMaxMw (capacityMva when not given) for each generator, and RateAMva = ratingMva x circuits for a line (with X and R divided, and B multiplied, by the circuit count). So in a JSON case a generator cannot be dispatched below zero unless the file allows it, and the uk line L2-3 B6 boundary is rated 2 x 2,200 = 4,400 MVA.

Preventive security-constrained DC-OPF

DcScopf.Solve(model, ScopfOptions) finds the cheapest dispatch that keeps every rated branch within RateA before any outage and within its post-outage rating after each listed single-branch outage, with no action after the outage (preventive). The CLI verb is scopf (manual chapter 19).

The LP is written on bus angles, so it stays sparse: columns are the dispatch P_g in [Pmin, Pmax] at a linear cost, an angle psi_i = base MVA x theta_i per bus (the reference bus fixed at 0) and a flow f_l per branch (within +/- RateA when rated, free otherwise). Rows are each bus's balance (its units' output, minus the flows leaving, plus the flows arriving, equals its demand) and each branch's flow, f_l - (psi_from - psi_to) / X_l = 0. After the outage of branch k, branch l carries f_l + LODF(l, k) f_k; a secured pair adds a column q within +/- the post-outage rating and the row q - f_l - LODF(l, k) f_k = 0. The LP is solved by SparseBoundedSimplex (two-phase, so an infeasible security set is proved infeasible and reported, never dispatched).

  • Outages. Contingencies null secures every in-service branch whose outage leaves the network connected; the outages that island it are listed in IslandingOutages and not secured. A listed islanding outage, an unknown or out-of-service branch and a duplicate are refused. One connected network only.
  • Post-outage rating. PostContingencyRating is RateA (default), RateB or RateC; RateB and RateC fall back to RateA on a branch where they are 0, as in the AC contingency analysis. The pre-outage state uses RateA.
  • Constraint generation (default). The LP starts with no post-outage row. After each solve every pair (outage, rated branch) is checked with the LODF; the pairs over their rating by more than ViolationToleranceMw (1e-6 MW) are added in outage then branch order and the LP is solved again. It stops when none is broken; the answer is then optimal for the LP holding every pair. MaxRounds (50) caps it; reaching the cap is status RoundLimit, with no dispatch. ConstraintGeneration = false puts every pair in the LP from the start.
  • Prices. A bus's price is the dual of its balance row: the change in optimal cost per extra MW of demand there, including the congestion of binding post-outage limits.
  • Result. Status, total cost, demand, dispatch, base flows, prices, the binding limits (pre-outage with contingency -1, and post-outage), the secured and islanding outages, the rounds, the post-outage rows in the last LP and the LP size. Every loop runs in a fixed order, so a repeat solve gives the same bits.

Validation (DcScopfTests). A three-bus case against hand calculation (dispatch 120 / 30 MW, cost 2100, prices 10 / 30 / 30, the binding limit of line 1-2 after the outage of line 1-3, and 1800 with RateC 135); the Wood and Wollenberg six-bus network and case30 against an independent formulation (one angle vector and flow set per outage state with the branch removed, no LODF or PTDF, solved by the interior point method) to 1e-8 relative; the plain DC-OPF when nothing is secured; every secured post-outage flow re-solved on the network with the branch removed; constraint generation against the full LP; repeat solves bit for bit; infeasibility and the round cap reported.

AC-OPF as implemented

AcOptimalPowerFlow.Solve is not an optimal power flow in the AC equations. It is the DC-OPF above, called repeatedly on loads scaled up by the losses of the previous pass, with an AC power flow in between that does nothing except measure those losses. Neither bus voltages, nor reactive power, nor AC branch loading, nor generator reactive limits appear as constraints or as results. The CLI header says so: ACOPF (DC dispatch + AC loss loop) - <case> (<n> buses) [not a full AC-OPF: no voltage, reactive-power or AC branch-flow limits]. A real AC-OPF with voltage and reactive limits is not implemented (see Limits).

D       = sum of Pd over buses
losses  = 0
for iter = 0 .. maxIterations - 1:
    scale = (D + losses) / D                      (1.0 when D <= 0)
    dc    = DcOptimalPowerFlow.Solve(ScaleLoads(model, scale), options)   (loads Pd and Qd scaled; fuel-type or cost-curve costs)
    if iter == 0 and StaysInfeasible(dc):  return Converged = false, Iterations = 0, Failure = DcDispatchInfeasible, StoppedAtInfeasibleFirstPass
    ac    = Newton(model with each generator's Pg := dc.Dispatch[i].Pg)                  (the UNscaled model)
    if not ac.Converged:  return Converged = false, Iterations = iter, Losses = NaN, Cost = NaN, Failure = AcPowerFlowNotConverged
    newLosses = sum over buses of ac.PInjMw                                              (net injections sum to the loss)
    settled   = | newLosses - losses | < lossToleranceMw
    losses    = newLosses
    if settled:  iter = iter + 1;  break
cost = sum Pg_i * cost_i of the last dc            (the dc total cost with cost curves)
Converged = settled AND dc.Feasible
Failure   = None | IterationCap (not settled) | DcDispatchInfeasible (settled, last dc infeasible)

options is the fuel-type default, or UseGeneratorCosts for --costs, with ComputePrices for --prices. The prices returned are those of the last DC pass: the lossless DC prices at the loss-inflated demand, with no marginal-loss component.

The pass-0 stop. An infeasible DC dispatch at pass 0 ends the run when no later pass can be feasible (StaysInfeasible). Every later pass scales demand by s >= 1, which holds because the loss estimate is non-negative when every branch has R >= 0 and every bus has Gs >= 0 (checked; otherwise the loop runs on). The proved cases are: (a) an island with demand and no unit; (b) island demand above its total Pmax plus BalanceToleranceMw; (c) the security LP proved Infeasible while every unit has Pmin <= 0 <= Pmax, because the feasible values of s then form an interval that contains 0, so s = 1 infeasible means every s >= 1 is infeasible. Demand below the units' total Pmin, an LP that stalled or was unbounded, and (c) with a unit whose Pmin is above 0 do not stop the run. A multi-island network stops when any one island is proved.

Islands. A network of several DC islands runs the same loop per island, because the DC-OPF dispatches each island on its own balance and no power crosses between islands: island k keeps its own losses_k (the sum of ac.PInjMw over its buses), its buses' Pd and Qd are scaled by (D_k + losses_k) / D_k (1.0 when D_k <= 0), the loop has settled when every island's estimate moved by less than lossToleranceMw, and the reported loss is the sum over all buses. No loss cover moves between islands, so each island's slack produces its dispatch to within the tolerance. A connected network runs the single-ratio loop above and its results are the same bits as before the per-island form existed (S4SolverConvergenceTests.N070_a_connected_network_keeps_its_loss_loop_to_the_bit); N070_each_island_pays_for_its_own_losses pins the per-island behaviour.

Details that follow from the code:

  • The AC power flow is a bare SolverSelector.CreateNewton(model) solve with default PowerFlowOptions (ch. 3): tolerance 1e-8 pu, generator reactive limits enforced, no OLTC loop. The slack bus ignores its generators' dispatched Pg, so the slack picks up whatever the other dispatches leave.
  • Each pass dispatches D + losses_previous. The new loss is sum Pg_dispatch - D + (P_slack_actual - Pg_slack_dispatch), so newLosses - losses = P_slack_actual - Pg_slack_dispatch, where Pg_slack_dispatch is the dispatch of the generators on the slack bus. The loop therefore stops when the slack bus's actual output equals the dispatch the LP gave its generators, to within lossToleranceMw. At that fixed point the generation covers the demand and the losses exactly.
  • The first pass always runs with losses = 0, so a case with any loss needs at least two passes to settle unless its first measured loss is below the tolerance (the lossless tri3 settles in one).
  • Iterations is the number of completed passes; on an AC failure it is the index of the failing pass, and it is 0 for a pass-0 stop. Converged is false for an unsettled loop, for an AC failure and for a final DC-OPF that is infeasible. AcOpfResult.Failure (AcOpfFailure: None, IterationCap, DcDispatchInfeasible, AcPowerFlowNotConverged) names the cause, AcFailure (AcOpfAcSolveFailure: pass, status, iterations, largest mismatch in pu, lowest voltage in pu) describes a failed AC solve, and StoppedAtInfeasibleFirstPass marks the pass-0 stop. No number of a run depends on them.
  • The CLI prints one of four messages after the header, all on standard error with exit 3:
  • acopf: the AC power flow at the DC-OPF dispatch of loss pass P (passes count from 0) did not converge: <status> after N iteration(s), largest mismatch M pu, lowest voltage V pu where it stopped. ... With every unit priced the same and no --costs, a second line says the dispatch is one arbitrary optimum of a degenerate LP and names --costs case.
  • acopf: the DC-OPF dispatch of loss pass 0 (passes count from 0) is infeasible ... so the loop stopped there; 'gridsim dcopf' on this case shows why.
  • acopf: the losses settled after N pass(es), but the DC-OPF dispatch of the final pass is infeasible ...
  • acopf: the losses did not settle within N pass(es) (--max-iter M, --loss-tol T MW).

N111_case118_acopf_fails_at_pass_0_on_the_ac_solve_and_says_so, N111_the_iteration_cap_is_reported_as_the_cap, N111_gb_synthetic_settles_on_an_infeasible_dc_dispatch and N111_cli_acopf_names_the_failed_ac_solve_and_the_flat_price in S4SolverDataFollowUpsTests pin the causes and the text, and N173AcopfEarlyStopTests pins the pass-0 stop. - TotalLossMw is the loss of the AC solve of the last pass. TotalCostPerHour prices the dispatch of the last DC solve, which covers D + losses_previous. - A DC-OPF that throws InvalidOperationException (for example a singular DC model) reaches the CLI as exit 1. A Newton solve cannot throw on a singular Jacobian: the step reports non-convergence.

Continuation power flow

ContinuationPowerFlow.MaxLoadability(model, step, minStep, maxSteps) searches for the largest uniform load multiplier at which the AC power flow converges. It is a bisection on the multiplier, not a predictor-corrector continuation. There is no tangent predictor, no arc-length or voltage parameterisation, and no tracking of the solution through the nose. The nose is located by the failure of Newton-Raphson to converge.

parameter    lambda scales every bus:  Pd := lambda * Pd,  Qd := lambda * Qd     (ScaleLoads; generators are unchanged)
corrector    r = Newton(ScaleLoads(model, lambda))      from the case's stored voltages

lambda = 1;  lastGood = 0;  solves = 0
while step >= minStep and solves < maxSteps:
    solves = solves + 1
    if Newton converges at lambda:   lastGood = lambda;  lambda = lambda + step
    else:                            lambda = lambda - step;  step = step / 2;  lambda = lambda + step
return lastGood                                           (0 when no solve converged)

The overload MaxLoadability(model, step, minStep, maxSteps) solves each point with the engine's default PowerFlowOptions and no OLTC loop. The overloads that take an IPowerFlowSolver and PowerFlowOptions (MaxLoadability, TracePvCurve, MaxLoadabilityWithEnd) solve each point with those. The cpf verb passes ContingencyAnalysis.WithOltcLoop(backend.NewtonSolver(m)) and ContingencyAnalysis.StudyOptions (100 iterations, generator reactive limits on, 1e-8 pu), so a cpf point is solved exactly as a stress load point is: the shared Newton engine on the selected backend, wrapped in the on-load tap changer loop (skipped when the model has no OLTC).

Step control: the step is fixed while solves succeed and halves on each failure, so the sequence of steps is step / 2^k. After a failure the next trial is lambda_failed - step_old/2, that is lastGood + step_new when the failed point was lastGood + step_old. The next success then advances by step_new and retries the point that has just failed, so each refinement costs one repeated solve. maxSteps counts every solve, failures included.

Nose detection: a solve whose status is not Converged (iteration cap, non-finite state, or a singular Jacobian, which the canonical Newton step reports as non-convergence) counts as past the nose. Each solve starts from the stored case voltages, not from the previous solution, so a failure can occur before the true nose. The slack bus supplies the whole increase, because generator Pg does not move; the power flow places no limit on the slack's active power, on any other generator's active power, or on a branch rating. Generator reactive limits are enforced by both option sets, and a bus that hits one becomes PQ.

Bracket. The loop ends when step < minStep and, if at least one failure occurred, it ended on a failure. The last failed point is lastGood + step_prev where step_prev = 2 * step_final, and minStep <= step_prev < 2 * minStep. So the first failing multiplier lies above the returned value by a width in [minStep, 2 minStep). The CLI prints nose bracketed to <minStep>, the lower end of that range. MaxLoadabilityWithEnd also returns how the walk ended (LoadabilityWalkEnd: whether the step fell below minStep, the solve count, the final step and the lowest failed multiplier, NaN when none failed). The CLI prints nose bracketed to <minStep> only when the walk ended on the step. When maxSteps ran out first it prints NOT bracketed: --max-steps <n> ran out with every solve converged, so lambda is only a lower bound (no solve failed) or NOT bracketed: --max-steps <n> ran out first; the nose lies between this lambda and <lowest failed lambda>, writes cpf: --max-steps <n> ran out before the nose was bracketed to --min-step <m>; ... Exit 3. to standard error, and exits 3. The result file carries nose_bracketed, solves and lowest_failed_lambda.

A failing base case. If the solve at lambda = 1 fails, the search steps down to 1 - step/2, then 1 - 3 step/4, and so on towards 1 - step; the first of those that converges becomes lastGood. The return value is then below 1 and positive. The CLI prints the lambda and the negative margin, writes cpf: the base case (lambda = 1) did not converge; only a lighter load did (largest converged lambda <lambda>, margin <m>%), so the case as given has no loadability margin. Exit 3. to standard error, and exits 3. When the return value is not positive (every solve failed) it prints no margin, writes cpf: the base case (lambda = 1) did not converge; no loadability margin. and exits 3.

PV curves. ContinuationPowerFlow.TracePvCurve runs the same loop (MaxLoadability and it share one private Run, the trace passing a recorder that only copies each converged result) and returns PvCurve(MaxLambda, BusIds, Points): MaxLambda is bit for bit MaxLoadability's answer, and Points holds each converged lambda with a copy of every bus voltage magnitude, in the order solved. The converged multipliers rise strictly (a failed step is backed off and halved, so the next point tried is still above the last converged one). DcPowerFlowAndPvCurveTests pins MaxLambda (The_pv_trace_max_lambda_is_bit_identical_to_MaxLoadability) and the first point (The_first_pv_point_is_the_base_case_solve_bit_for_bit).

cpf --pv-out <file.csv> writes one long CSV with the header case,lambda,bus_id,vm_pu and one row per converged point and bus, in the order solved, with numbers in round-trip form and invariant culture. A name that does not end in .csv exits 2. The file is written before the report, and [cpf] PV curves: N converged point(s) x M bus(es) -> <full path> goes to standard error. cpf case9 gives 12 points of 9 buses, 108 rows. stress --pv-out writes the same layout with a load_factor column in place of lambda for the voltages of its own grid of re-dispatched load points, up to its reported max loadability; the two curves answer different questions, as the two verbs do.

Tap optimiser

TapOptimizer.Flatten(model, targetVpu, options, optimizer) finds one set of tap ratios for all on-load tap changers that minimises the squared voltage deviation, by re-solving the nonlinear power flow for each candidate.

objective(taps) = sum over EVERY bus i of (Vm_i - target)^2           Vm from Newton(model with the taps), default options, fixed taps

The objective counts every bus of the solved state, the 400 kV generator buses as well as the transformer outlets, and uses no OLTC loop (the taps are the variables). A power flow that does not converge returns NonConvergedPenalty (1e9).

Mapping. Every Oltc record must name exactly one branch (ordinal comparison) and control a bus the model has (TapOptimizer.OltcProblems); otherwise Flatten throws ArgumentException naming every problem, before any solve. The record's ControlsBus, TargetVpu and DeadbandPu do not enter the objective; after the search each OLTC's controlled-bus voltage is checked against its own target and deadband (TapSchedule.Regulation, one OltcRegulationCheck per OLTC).

Search. With the base state solved and at least one matched OLTC:

seed     = TapRatio of each matched branch (1.0 when TapRatio <= 0)
Eval(t)  = penalty                      if any tap leaves [MinTap, MaxTap]; no solve is run
                                         penalty = sum over violating taps of (TapBoundPenalty + TapBoundPenaltyPerPu * excess_pu)
         = objective(t)                 otherwise
t*       = NelderMead.Minimize(Eval, seed, InitialStep = InitialTapStepPu)        continuous taps
snapped  = for each tap:  clamp(MinTap + Round((t* - MinTap) / step) * step, MinTap, MaxTap)     step = StepPu, or 0.0125 when StepPu <= 0
after    = objective(snapped)                                                       re-solved as it would be applied

Math.Round is round-half-to-even. The Nelder-Mead minimiser (src/GridSim.Core/Numerics/NelderMead.cs) is the classic one with reflection 1, expansion 2, contraction 0.5 and shrink 0.5. The initial simplex is the seed plus InitialStep * |seed| along each axis (0.02 for a seed of 1.0). It stops when the simplex spread is at most XTolerance (1e-8) and the objective spread at most FTolerance (1e-12), or after MaxIterations (2000). The minimiser's verdict is kept in TapSchedule.OptimizerConverged and OptimizerIterations.

Result. If the snapped schedule fails to solve, or after >= before, the schedule is the current taps on every row, with the objective unchanged. Otherwise the taps are snapped. TapSchedule.Improved is Solved && after < before - ImprovementEpsilon (1e-9). When no Oltc is matched, Taps is empty, before == after and Improved is false. If the base case does not converge, Solved is false and Taps is empty.

Loss allocation

LossAllocation.Allocate(model, result) decomposes a solved PowerFlowResult and runs no solver. For each entry of result.LineFlows, in branch order (the list holds a zero-flow placeholder for an out-of-service branch, so it is index-aligned with model.Branches):

PLoss_l = PFromMw + PToMw          QLoss_l = QFromMvar + QToMvar                (ch. 3, LineFlow)
IsTransformer_l = Branches[l].IsTransformer
TotalPLossMw = sum PLoss_l         TotalQLossMvar = sum QLoss_l
ShuntPMw = sum over buses of Gs_i * Vm_i^2                                      (MW; Gs is MW at 1 pu)
ReconciliationResidualMw = result.TotalLossMw - TotalPLossMw - ShuntPMw

result.TotalLossMw is the sum of the net bus injections, so it also holds the real power the bus shunt conductances draw, which flows in no branch. That power is ShuntPMw (the losses verb prints it as Bus shunt conductance when the case has any, and writes shunt_p_mw), so the residual is rounding: on case300, whose 17 conductive bus shunts total 1.30 MW at 1 pu, ShuntPMw is 1.21 MW. With no conductive shunt ShuntPMw is exactly 0 and the residual is the plain TotalLossMw - TotalPLossMw. S4SolverConvergenceTests.N053_case300_losses_reconcile_once_the_shunt_conductance_is_counted and N053_without_conductive_shunts_the_residual_is_unchanged_to_the_bit pin both.

Zones are the model's boundaries. Boundary.RequireResolvedBranchNames first throws unless every boundary branch name names exactly one branch of the model. A branch whose non-empty Name appears in a boundary's branch list belongs to that boundary, and when a name appears in several boundaries the first boundary wins (TryAdd). Every other branch, including every branch with no name, belongs to Other. Each zone's row is the sum of its branches' PLoss and QLoss and their count (out-of-service branches included). Zone rows are sorted by real loss, descending, then Other is appended when it holds any branch. The allocation is by branch and zone only; it does not apportion losses to generators or loads.

The losses verb loads its case through the shared loader (SingleCasePositional, then LoadCaseArgument) and solves the base case with a bare Newton engine chosen by the shared rule (backend.NewtonSolver: sparse at every size on the CPU, since SolverSelector.DefaultSparseThreshold = 0; the dense and sparse engines are bit-identical on the CPU), with default options. It does not use the radial test and runs no OLTC loop, so its total differs from the gridsim <case> --once report on a case with tap changers.

Algorithm

The bounded-variable simplex

BoundedSimplex.Solve(a, b, c, lo, hi, tol, maxIter) (src/GridSim.Core/Numerics/BoundedSimplex.cs) is the dense reference solver for

minimise c.x   subject to   A x = b,   lo <= x <= hi          (any hi may be +inf)

It is a two-phase primal simplex that handles bounds natively: a nonbasic variable rests at a finite bound (the lower in preference, else the upper, else 0 for a free variable), and the ratio test includes the entering variable's own opposite bound, so a step can be a bound flip with no basis change.

  1. Set-up. One artificial variable per row. Each structural variable starts at its resting bound; a row whose initial residual is negative is negated, so every artificial starts at a non-negative value and the artificials form an identity basis.
  2. Phase I minimises the sum of the artificials. If the sum is above PhaseOneFeasibilityTolerance (1e-7, absolute) the status is Infeasible.
  3. Phase II pins every artificial to 0 and minimises c.
  4. Pricing. Dantzig: the nonbasic variable with the most negative reduced cost for an increase from a lower bound (or the most positive for a decrease from an upper bound) beyond tol (1e-9), the first index winning a tie. A free nonbasic variable is priced in both directions.
  5. Ratio test. The step is the smallest of each basic variable's distance to its bound divided by its rate, and the entering variable's own bound gap. A candidate replaces the current leaving row only when its step is smaller by more than RatioTieMargin (1e-12), so among ties the first row wins. An unbounded step gives Unbounded.
  6. Basis inverse. Updated by eta (product-form) row operations. A chosen pivot below EtaPivotFloor (1e-12) is refused (the LP throws, naming the pivot) before the basis changes. The ratio test admits only rows with |alpha| above the tolerance (1e-9), so this cannot happen at the default tolerance, and a tolerance that is not positive and finite throws ArgumentOutOfRangeException (SimplexPivotFloorTests). A refactorisation (Gauss-Jordan with partial pivoting, first strict maximum) runs every RefactorInterval (64) iterations, bound flips included. A refactorisation pivot below RefactorPivotClamp (1e-14) is clamped to that magnitude with its sign.
  7. Limit. Each phase stops after DefaultMaxIterations (20000) iterations with status IterationLimit.

The statuses are LpStatus.Optimal, Infeasible, Unbounded and IterationLimit. The constants steer the pivot path, so changing any of them can move the reported optimum in its last digits or choose another optimal vertex of a degenerate LP.

The structured security simplex

DcOpfSecuritySimplex (src/GridSim.Core/Analysis/DcOpfSecuritySimplex.cs) runs the same algorithm as BoundedSimplex.Solve on the DC-OPF's LP without building its matrices, and returns the dense solver's answer bit for bit. It differs only in how the matrices are stored:

  • No constraint matrix. A dispatch column is a 1 in the balance row plus one PTDF entry per rated line. Generators on one bus share one column, so the PTDF block is held once per distinct generator bus, for the rated lines only, row-major (L x distinct buses). A slack or artificial column is a single +/-1 and is never stored. BuildSecurityLp builds this problem; it throws InvalidOperationException when the block would exceed Array.MaxLength cells.
  • Basis inverse in DcOpfHybridColumns. A column with one non-zero is stored as that value, and a column becomes dense only when a row operation gives it a second. The Gauss-Jordan working matrix of each refactorisation is held the same way.
  • Grouped pricing. One reduced cost is computed per (PTDF column, objective coefficient) group of generators, because generators with an identical column and cost have bit-identical reduced costs.

The only operations skipped are multiplications by an exact zero and the additions of their zero results, which can change at most the sign of a zero. No tolerance, floor or iteration cap is changed: every constant is read from BoundedSimplex. The dense path stays callable as DcOptimalPowerFlow.SolveDenseReference for the parity tests. The source comments record that the dense LP on gb-full (5,876 rated lines, 5,318 generators) needs 1.9 GB of arrays, against 73 MB for the structured PTDF block.

Parameters and defaults

Name Value Unit Meaning Source symbol
Unbounded Pmax 1e6 MW Stand-in for an infinite Pmax in the LP bounds. DcOptimalPowerFlow.UnboundedPmaxMw
Balance tolerance 1e-6 MW Feasibility margin of the merit order (demand versus the dispatchable range) and of a dead island's load. DcOptimalPowerFlow.BalanceToleranceMw
Merit-order stop 1e-9 MW The merit-order fill stops at or below this unserved remainder. DcOptimalPowerFlow.MeritOrderFillStopMw
Binding tolerance 1e-3 MW A rated line with abs(flow) >= RateA - this is reported binding. DcOptimalPowerFlow.BindingToleranceMw
Default cost 50 GBP/MWh Cost of an empty or unrecognised fuel type. DcOptimalPowerFlow.DefaultCostPerMwh
Islanding tolerance 1e-9 - A branch with abs(1 - Phi_kk) below this is a bridge. DistributionFactors.IslandingSensitivityTolerance
LP tolerance 1e-9 - Reduced-cost and ratio-test threshold. BoundedSimplex.DefaultTolerance
LP iteration cap 20000 iterations per phase Stops a stalled phase with IterationLimit. BoundedSimplex.DefaultMaxIterations
Phase I tolerance 1e-7 - Largest sum of artificials accepted as feasible (absolute). BoundedSimplex.PhaseOneFeasibilityTolerance
Refactor interval 64 iterations Simplex iterations (basis changes and bound flips) between refactorisations of the basis inverse. BoundedSimplex.RefactorInterval
Ratio tie margin 1e-12 - A leaving-row candidate must beat the current step by more than this. BoundedSimplex.RatioTieMargin
Eta pivot floor 1e-12 - A chosen pivot below this is refused (unreachable at the default tolerance). BoundedSimplex.EtaPivotFloor
Refactor pivot clamp 1e-14 - Smallest pivot magnitude kept in a refactorisation. BoundedSimplex.RefactorPivotClamp
AC-OPF loss tolerance 1e-3 MW Loss change that counts as settled. CLI --loss-tol, above 0. AcOptimalPowerFlow.Solve parameter lossToleranceMw
AC-OPF pass limit 20 passes Outer-loop cap. CLI --max-iter, at least 1. AcOptimalPowerFlow.Solve parameter maxIterations
CPF initial step 0.25 multiplier First increment of lambda. CLI --step, above 0. ContinuationPowerFlow.MaxLoadability parameter step
CPF minimum step 1e-3 multiplier The search ends when the step is below this. CLI --min-step, in (0, --step]. ContinuationPowerFlow.MaxLoadability parameter minStep
CPF solve limit 200 power flows Cap on solves, failures included. CLI --max-steps, at least 1. ContinuationPowerFlow.MaxLoadability parameter maxSteps
Tap target 1.0 pu Voltage the objective aims at. CLI --target, above 0. TapOptimizer.Flatten parameter targetVpu
Tap improvement threshold 1e-9 pu^2 The objective must fall by more than this to count as improved. TapOptimizer.ImprovementEpsilon
Tap initial step 0.02 relative to the seed Initial Nelder-Mead spread, 0.02 pu at a seed of 1.0. TapOptimizer.InitialTapStepPu
Non-converged penalty 1e9 pu^2 Objective of a tap vector whose power flow fails. TapOptimizer.NonConvergedPenalty
Tap bound penalty 1e6 plus 1e6 per pu pu^2 Added when a tap leaves its range; no solve is run. TapOptimizer.TapBoundPenalty, TapBoundPenaltyPerPu
Default tap step 0.0125 pu per position Snap step when an OLTC's StepPu is 0 or less. Oltc.DefaultStepPu
Nelder-Mead limits 2000, 1e-8, 1e-12 iterations, x spread, f spread Search stop. NelderMead.Options.MaxIterations, XTolerance, FTolerance
PTDF and LODF display floor 1e-4 MW/MW Factors at or below this absolute value are not printed by ptdf and lodf. CliDefaults.SensitivityDisplayFloor
Dispatch display floor 1e-3 MW A unit at or below this output is not printed by dcopf and acopf. CliDefaults.DcopfDispatchDisplayFloorMw
Rows listed 12 rows --top of dcopf, acopf, ptdf, lodf and dcpf. Program.cs (FlagInt(a, "--top", 12))
Sparse threshold 0 buses Above this acopf, cpf, taps and losses use the sparse Newton engine (so every CPU solve is sparse). SolverSelector.DefaultSparseThreshold
Overload threshold 100 % of RateA A branch above this loading is counted by dcpf. ContingencyAnalysis.OverloadThresholdPercent

All constants of DcOptimalPowerFlow, DistributionFactors and TapOptimizer listed above are pinned to the literals they replaced by Ws13CoreConstantsAntiDriftTests.

Case loading and exit behaviour of the verbs

The eight verbs load their case in three places, with the same rule for what a case argument may be.

Verb How the case is chosen A load failure No case given
dcopf, ptdf, lodf First free argument after the verb: a folder holding system.json (Gated.Dir), else a name ending .m (Gated.Matpower), else LoadNamed error loading case '<arg>': <reason>, exit 1 usage: ..., exit 2
acopf, cpf, taps, dcpf The same rule, through LoadAnalysisCase error loading case '<arg>': <reason>, exit 1 usage: ..., exit 2
losses SingleCasePositional (default case9), then LoadCaseArgument: the same three forms, and an existing folder without system.json is loaded so the loader says what is wrong with it An unknown name: error: losses: unknown case '<arg>' (built-in names: ...), exit 2. A missing .m file or an unloadable folder: error: <reason>, exit 1. A second case argument: exit 2 Solves case9

The free argument is the first token after the verb that is neither a --flag nor the value a flag consumes. A .m name is searched as given, then under data/matpower, then by file name through its subfolders (dcopf case33bw.m loads data/matpower/dist/case33bw.m). LoadNamed accepts case9/ieee9, case14, case30, case57, case118, case300, case145, case24/rts, cigre, uk/gb/gb-reduced, gb-full, gb-synthetic/synthetic, gb-reduced-29, gb-network-2224, pypsa-gb-reduced, a name ending .m, and a name ending .json (a JSON v2 case manifest, Gated.V2Case). pypsa-gb-zonal is refused (Gated.NotAcSolvable: a transport model with no power flow, exit 1). Any other name throws ArgumentException listing BuiltInCases.Names. A licence refusal (a user network above the tier's bus limit) exits 2 from inside Gated.

Flags. The result-writer flags --json, --csv and --out are taken off the argument list first (CliOutput.TakeFlags; all eight verbs are writer verbs). The process-wide gate then refuses a flag that no verb knows (exit 2). VerbFlags.Check then refuses a flag that the verb's own section of 0019 CLI reference.md does not name, with error: <verb> does not take <flag> (it is not one of <verb>'s flags, so it would be silently ignored). ... and exit 2, before the verb runs and with nothing on standard output. --dir is refused for every verb in this chapter this way, including losses. --costs and --prices are refused outside dcopf and acopf with error: --costs applies to dcopf and acopf only (got '<verb>').

Verb Exit 0 Exit 1 Exit 2 Exit 3
dcopf A feasible dispatch A load failure; an exception from the solve; a --costs problem No case; a bad flag value; an unknown flag or a flag of another verb An infeasible dispatch
acopf Converged A load failure; an exception from the solve; a --costs problem As dcopf One of the four failures (AC solve, pass-0 stop, infeasible final dispatch, pass limit)
cpf A bracketed nose A load failure As dcopf; --pv-out not ending in .csv The base case (lambda = 1) did not converge; --max-steps ran out before the nose was bracketed (NOT bracketed: ..., lambda a lower bound)
taps A schedule, improved or not No OLTC in the case; an OLTC that names no branch, several branches or a missing controlled bus; a load failure As dcopf The base case did not converge; the tap search stopped at its iteration cap
ptdf Factors printed (no rows when none exceeds the floor) A load failure; Build failed No case; --bus missing, negative or not a bus of the case; a bad flag value -
lodf Factors printed, or a bridge outage A load failure; Build failed No case; --branch missing or outside 0..N-1; a bad flag value -
dcpf The DC model solved A load failure; the DC model cannot be formed No case; a negative --top; a bad or foreign flag An island carries load and has no generator
losses The tables A missing .m file; an unloadable folder An unknown name; a second case argument; a foreign flag The base case did not converge (error: base case did not converge.)

DcOptimalPowerFlow throws InvalidDataException for Pmin above Pmax or a non-finite Pmin. On every path, with or without --costs and --prices, both verbs catch it (and InvalidOperationException) and exit 1 as [dcopf] <message> or [acopf] <message>. Output that reaches the console before a failure stays: acopf, cpf and taps print their header line to standard output and then the failure message to standard error. ptdf and lodf load the case and factor it before they test --bus or --branch, so a bad case exits 1 ahead of a missing flag.

dcopf infeasible messages. A case with several islands prints the island list and then INFEASIBLE: at least one island has no dispatch that meets its demand (within its line limits, when they are enforced); see the island list. A connected case prints one of three messages: INFEASIBLE: no dispatch within the units' output limits keeps every rated line within its rating (security LP Infeasible); '--no-limits' drops the line limits. when the security LP is Infeasible; INFEASIBLE: the security LP stopped without proving an optimum (status X); no secure dispatch is reported. for another LP status; and INFEASIBLE: generation capability cannot meet demand (N MW of in-service capability for M MW of demand). only when no LP ran. With --costs a failed solve adds solver: <reason> (status X). The --costs result keys carry no currency (a curve is in the case's own currency). A branch with no name is printed as from-to.

taps output. When the schedule leaves an OLTC's controlled bus outside that OLTC's own target +/- deadband, taps lists each such OLTC (its local regulator would retap). A search cut off at its iteration cap exits 3 with the iteration count.

Invariants

Invariant Pinned by
Without line limits the dispatch is a merit order: the cheapest unit is loaded to Pmax, the next takes the rest, and generation equals demand. DcOptimalPowerFlowTests.Unconstrained_dispatch_follows_merit_order
A binding line forces energy onto a dearer unit, the balance is preserved, the result is flagged NetworkConstrained, and the cheap unit backs off. DcOptimalPowerFlowTests.A_binding_line_forces_redispatch_onto_a_costlier_generator
Pmin is used as given: a unit with a negative Pmin dispatches below zero; Pmin above Pmax, and a non-finite Pmin, are rejected. AnalysisWs6Tests.Dc_opf_can_dispatch_storage_charging_below_zero, Dc_opf_rejects_pmin_above_pmax, Dc_opf_rejects_a_non_finite_pmin
No LP status is reported when no LP ran. ConvergenceContractTests.Dc_opf_reports_its_security_lp_outcome
The structured security simplex returns the dense solver's dispatch, binding set and status bit for bit on the bundled cases, reproduces results recorded from the original dense code, and matches BoundedSimplex on hundreds of randomised degenerate LPs through many refactorisations. DcOpfSecuritySimplexParityTests.Structured_security_dispatch_is_bit_identical_to_the_dense_reference, Structured_security_dispatch_reproduces_the_recorded_original_results, Structured_simplex_matches_the_dense_simplex_on_randomised_degenerate_lps, Structured_simplex_matches_the_dense_simplex_through_many_refactorisations, Hybrid_columns_track_a_dense_matrix_through_swaps_scalings_and_eliminations, Hybrid_columns_fail_loud_on_misuse, Structured_simplex_rejects_an_inconsistent_problem
BoundedSimplex reaches the textbook optimum, honours finite upper and non-zero lower bounds, and reports infeasible and unbounded programs, and prices a free variable in both directions. BoundedSimplexTests (five tests), Wave3NumericsTests.BoundedSimplex_optimises_over_a_free_variable
A pivot below the floor is refused by name before the basis changes, the default tolerance never chooses one, and both solvers check the pivot before the step. SimplexPivotFloorTests.A_tolerance_below_the_floor_that_chooses_a_tiny_pivot_is_refused_by_name, The_default_tolerance_never_chooses_a_pivot_below_the_floor, Both_solvers_check_the_pivot_before_the_step_and_no_longer_refactorise_around_it
A connected network has one island referenced at the slack; each island of a split network takes its own reference by the island rule; a PTDF column withdraws at its island's reference and leaves other islands untouched. DcIslandTests.A_connected_network_has_one_island_referenced_at_the_slack, Each_island_gets_its_own_reference_by_the_AC_island_rule, Ptdf_withdraws_at_the_bus_islands_reference_and_leaves_other_islands_untouched
A zero-reactance branch that alone joins two islands fails loud. DcIslandTests.A_zero_reactance_branch_that_alone_joins_two_islands_fails_loud
dcopf dispatches each island on its own balance, solves each as the island alone, reports a binding line with its full-model index, reports an island without generation (infeasible when it has load, harmless when it has none), and refuses a mismatched cost vector. DcIslandTests.Dcopf_dispatches_each_island_on_its_own_balance, Each_island_is_solved_exactly_as_the_island_alone, A_binding_line_in_a_second_island_is_reported_with_its_full_model_index, An_island_with_no_generation_is_reported_and_its_load_makes_the_dispatch_infeasible, An_island_with_no_generation_and_no_load_is_reported_but_harmless, A_cost_vector_that_does_not_match_the_generators_fails_loud_with_islands
gb-full has two DC islands, each with its own slack and generation. DcIslandTests.Gb_full_has_two_DC_islands_each_with_its_own_slack_and_generation
PTDF equals the analytic values on an equal-reactance triangle, and the slack column is zero. DistributionFactorsTests.PTDF_matches_the_analytic_triangle_and_the_slack_column_is_zero
The LODF diagonal is -1, and the post-outage flow equals the flow of the network with the branch removed. DistributionFactorsTests.LODF_diagonal_is_minus_one_and_satisfies_the_re_solve_identity
A bridge outage is flagged and its LODF column is NaN. DistributionFactorsTests.A_radial_bridge_outage_is_flagged_as_islanding
The DC power flow's branch flows are the bits DcFlows gives, every bus and island balances, the angles reproduce the flows, and each island of a multi-island case is reported. DcPowerFlowAndPvCurveTests.Dc_power_flow_branch_flows_are_bit_identical_to_DcFlows, Dc_power_flow_balances_every_bus_and_island, Dc_power_flow_angles_reproduce_the_flows, Dc_power_flow_reports_each_island_of_a_multi_island_case
The PV trace's MaxLambda is MaxLoadability's answer bit for bit, and its first point is the base-case solve. DcPowerFlowAndPvCurveTests.The_pv_trace_max_lambda_is_bit_identical_to_MaxLoadability, The_first_pv_point_is_the_base_case_solve_bit_for_bit
One taxonomy prices every fuel string: the cost of each bundled type, a gas turbine as Ocgt, hydrogen and pumped storage not as Hydro, whole-word matching with word-start keywords, splitting at every non-alphanumeric character. FuelTypesTaxonomyTests.Every_bundled_type_reads_the_same_in_every_reader, A_gas_turbine_is_ocgt_to_every_reader, Hydrogen_and_pumped_storage_are_no_longer_priced_as_hydro, Keywords_match_whole_words_by_their_start, The_substring_false_positives_read_as_other_in_every_reader, Words_split_at_every_non_alphanumeric_character
Cost curves: case9 quadratic costs reach the closed-form equal-marginal-cost dispatch, a convex piecewise curve fills its segments in order, prices match the published values, a binding line separates the prices, a unit with no curve is refused, demand beyond the fleet is infeasible with no prices, islands are priced each at its own marginal unit, and the cost file overlays by index and by name. GeneratorCostsAndPricesTests.Case9_quadratic_costs_reach_the_closed_form_equal_marginal_cost_dispatch, A_convex_piecewise_linear_cost_fills_its_segments_in_order_and_prices_at_the_marginal_slope, Pjm_5_bus_dispatch_matches_the_published_dc_opf_and_its_prices_match_highs, A_binding_line_separates_the_prices_on_a_hand_case, A_unit_with_no_curve_is_refused_when_curves_are_in_use, Demand_beyond_the_fleet_is_infeasible_with_curves_and_reports_no_prices, Two_islands_with_curves_are_priced_each_at_its_own_marginal_unit, The_cost_file_overlays_the_case_by_index_and_by_name_and_round_trips
acopf without cost curves is unchanged, with them reports the curve cost, and its final-pass prices are the loss-inflated DC prices; a cost vector with prices is refused. GeneratorCostsAndPricesTests.Acopf_without_cost_curves_is_unchanged_and_with_them_reports_the_curve_cost, AcOpfPricesTests.Pjm_5_bus_final_pass_prices_are_the_loss_inflated_dc_prices, Prices_and_a_cost_vector_are_refused_together
--costs and --prices are known flags, documented, and refused outside dcopf and acopf. GeneratorCostsAndPricesTests.Dcopf_costs_and_prices_flags_are_known_documented_and_refused_elsewhere
The AC-OPF converges on case14 to a dispatch whose total equals demand plus the reported losses to within 0.5 MW. AcOptimalPowerFlowTests.Converges_to_a_loss_aware_ac_feasible_dispatch
A loop that cannot settle is not reported converged. ConvergenceContractStudyTests.Ac_opf_that_cannot_settle_is_not_converged
Each island pays for its own losses, and a connected network keeps its loss loop to the bit. S4SolverConvergenceTests.N070_each_island_pays_for_its_own_losses, N070_a_connected_network_keeps_its_loss_loop_to_the_bit
The acopf failure causes are told apart (AC solve at pass 0, iteration cap, infeasible final dispatch), a converged run reports no failure, and the CLI names the cause. S4SolverDataFollowUpsTests.N111_case118_acopf_fails_at_pass_0_on_the_ac_solve_and_says_so, N111_the_iteration_cap_is_reported_as_the_cap, N111_gb_synthetic_settles_on_an_infeasible_dc_dispatch, N111_a_converged_run_reports_no_failure_and_keeps_its_numbers, N111_cli_acopf_names_the_failed_ac_solve_and_the_flat_price
dcopf tells a line-limit infeasibility from a shortfall of capability. S4SolverDataFollowUpsTests.N111_cli_dcopf_tells_line_limit_infeasibility_from_short_capability
An infeasible pass 0 that no later pass can cure stops the loop at pass 0, and a case where more demand could cure it keeps the full loop. N173AcopfEarlyStopTests.Demand_above_total_capability_stops_at_pass_0, Line_limits_proved_infeasible_stop_at_pass_0_when_every_unit_may_produce_nothing, Line_limits_with_a_unit_whose_pmin_is_above_zero_keep_the_full_loop, Demand_below_total_pmin_keeps_the_full_loop, Gb_synthetic_stops_at_pass_0_with_the_same_verdict, Cli_acopf_gb_synthetic_names_the_pass_0_stop_and_exits_3, Feasible_runs_are_untouched
The load search finds a multiplier above 1 on case9, and does not converge far past it. ContinuationPowerFlowTests.Finds_a_loadability_margin_beyond_the_base_case
The search reaches the nose without an exception. ConvergenceContractStudyTests.Continuation_reaches_the_nose_without_an_exception
The tap schedule improves the objective, stays inside the OLTC band, lands on the step grid, and lowers the worst voltage deviation when applied. TapOptimizerTests.Flattens_the_profile_across_both_transformers
A case with no OLTC returns an empty, unimproved schedule with equal objectives. TapOptimizerTests.No_oltcs_returns_the_unchanged_state
Branch losses sum to the solver's total (residual below 1e-6 MW), zone rows plus Other sum to the total, and no branch loss is negative beyond -1e-6 MW. LossAllocationTests.Branch_losses_sum_to_total, Zone_losses_plus_other_equal_total, Every_branch_loss_is_non_negative
The bus shunt draw closes the case300 residual, and without conductive shunts the residual is unchanged to the bit. S4SolverConvergenceTests.N053_case300_losses_reconcile_once_the_shunt_conductance_is_counted, N053_without_conductive_shunts_the_residual_is_unchanged_to_the_bit
losses loads its case through the shared loader (unknown name exit 2, missing .m exit 1, second case argument exit 2). CliContingencyVerdictTests.Losses_loads_its_case_through_the_shared_loader (a source-text test: no test runs losses on an unknown name)
The CLI result files carry the printed bits and every row, dcpf --out writes the same files byte for byte, a run with no result writes no file, and a failing verdict is still written. CliResultFilesProcessTests.Dcpf_out_csv_still_writes_the_f18_files_byte_for_byte, Json_numbers_are_the_exact_bits_the_console_prints_in_round_trip_form, Json_and_csv_carry_the_same_bits_and_every_row_not_just_the_printed_top, A_run_that_stops_before_its_result_writes_no_file_and_says_so, A_verdict_that_fails_is_still_written_with_its_exit_code
A flag of another verb exits 2 naming it with nothing on standard output, a documented flag is accepted, and every flag a verb's code reads is in its accepted set. CliS4CliAndLoaderProcessTests.N103_a_flag_of_another_verb_exits_2 (ptdf --branch), VerbFlagsTests.A_flag_of_another_verb_is_refused, A_documented_flag_is_accepted, Every_flag_a_verbs_code_reads_is_accepted_for_it
The built binary starts each verb on case9 and exits 0 with the verb's header: ptdf, lodf, dcopf, acopf, cpf and losses (PTDF -, LODF -, DC-OPF -, ACOPF (DC dispatch + AC loss loop) -, max loadability, Total losses:), and taps case9 exits 1 with no on-load tap changers. CliProcessSmokeTests.Verb_runs_on_case9_and_exits_0, Taps_on_a_case_without_tap_changers_is_an_input_error_exit_1

What is pinned about the CLI text and exit codes is what the rows above name: the header lines of six verbs and the taps failure (CliProcessSmokeTests), the acopf and dcopf failure messages and the pass-0 message, the cost per fuel kind (FuelTypesTaxonomyTests), and the exit 2 of a foreign flag. No test pins the console text of dcpf, the cpf and taps failure messages, the exit codes of losses on bad input, the tie-break of equal-cost dispatch, or the half-even rounding of the tap snap (the tap test checks only that every tap lies on the grid).

Worked example

Every number below is from a run in docs/_captures/opf/.

PTDF by hand: the three-bus case

docs/_captures/opf/tri3/ has buses 1 (slack, generator G1), 2 (generator G2) and 3 (load 100 MW), and three lines of X = 0.1 pu: L13 (branch 0), L23 (branch 1) and L12 (branch 2). Each b = 1 / 0.1 = 10. Removing the slack row and column (bus 1) leaves the buses 2 and 3:

B' = [ 20  -10 ]        B'^-1 = (1/300) * [ 20  10 ]
     [-10   20 ]                          [ 10  20 ]

An injection of 1 at bus 2 is rhs = [1, 0], so theta = [20/300, 10/300] = [0.066667, 0.033333] and theta_1 = 0:

L12 (1->2):  10 * (0 - 0.066667)         = -0.66667
L13 (1->3):  10 * (0 - 0.033333)         = -0.33333
L23 (2->3):  10 * (0.066667 - 0.033333)  = +0.33333

The run agrees to the printed four decimals:

$ gridsim ptdf docs/_captures/opf/tri3 --bus 2
PTDF - Three-bus worked example (3 buses): +1 MW injected at bus 2 (withdrawn at slack 1) flows on:
    branch 2    1->2           PTDF -0.6667  (-66.7%)
    branch 0    1->3           PTDF -0.3333  (-33.3%)
    branch 1    2->3           PTDF  0.3333  ( 33.3%)
[exit 0]

For bus 3, rhs = [0, 1] gives theta = [10/300, 20/300] and the factors L13 = -0.66667, L23 = -0.33333, L12 = -0.33333:

$ gridsim ptdf docs/_captures/opf/tri3 --bus 3
PTDF - Three-bus worked example (3 buses): +1 MW injected at bus 3 (withdrawn at slack 1) flows on:
    branch 0    1->3           PTDF -0.6667  (-66.7%)
    branch 1    2->3           PTDF -0.3333  (-33.3%)
    branch 2    1->2           PTDF -0.3333  (-33.3%)
[exit 0]

A ring check on case9: bus 5 reaches the slack through bus 4, either directly (4->5, X = 0.092) or round the ring 5-6-7-8-9-4. The ring reactance is 0.17 + 0.1008 + 0.072 + 0.161 + 0.085 = 0.5888, and a DC flow divides inversely with reactance, so the direct line carries 0.5888 / (0.5888 + 0.092) = 0.86486 and the ring the other 0.13514. Branches 3 (3->6) and 6 (8->2) are dead-end generator connections and carry nothing.

$ gridsim ptdf case9 --bus 5
PTDF - IEEE 9-bus (WSCC) (9 buses): +1 MW injected at bus 5 (withdrawn at slack 1) flows on:
    branch 0    1->4           PTDF -1.0000  (-100.0%)
    branch 1    4->5           PTDF -0.8649  (-86.5%)
    branch 7    8->9           PTDF  0.1351  ( 13.5%)
    branch 4    6->7           PTDF  0.1351  ( 13.5%)
    branch 8    9->4           PTDF  0.1351  ( 13.5%)
    branch 2    5->6           PTDF  0.1351  ( 13.5%)
    branch 5    7->8           PTDF  0.1351  ( 13.5%)
[exit 0]

LODF by hand

Outage of L13 (branch 0). The transfer problem is +1 at bus 1 (the slack, dropped) and -1 at bus 3: rhs = [0, -1], theta = [-10/300, -20/300]. Then Phi[L13,L13] = 10 * (0 + 0.066667) = 2/3, Phi[L23,L13] = 10 * (-0.033333 + 0.066667) = 1/3 and Phi[L12,L13] = 10 * (0 + 0.033333) = 1/3. With 1 - Phi_kk = 1/3, LODF[L23] = LODF[L12] = (1/3) / (1/3) = 1.0: the whole flow of L13 moves onto the path 1->2->3.

$ gridsim lodf docs/_captures/opf/tri3 --branch 0
LODF - Three-bus worked example (3 buses): outage of branch 0 (1->3) redistributes onto:
    branch 1    2->3           LODF  1.0000  (100.0% of the lost flow)
    branch 2    1->2           LODF  1.0000  (100.0% of the lost flow)
[exit 0]

DC power flow by hand

On tri3 the case is balanced when it loads: the ocgt unit on bus 2 schedules 10 MW and the slack unit 92 MW (the 100 MW demand plus a 2 % allowance, less the 10 MW). Bus 1 is the reference, so only buses 2 and 3 enter the right-hand side: P / BaseMva = [10, -100] / 100 = [0.1, -1.0]. With the B'^-1 above,

theta_2 = (20 x 0.1 + 10 x (-1.0)) / 300 = -0.026667 rad = -1.5279 deg
theta_3 = (10 x 0.1 + 20 x (-1.0)) / 300 = -0.063333 rad = -3.6287 deg
L13 (1->3):  10 x (0 + 0.063333)          x 100 = 63.333 MW      63.333 / 60  = 105.6 %
L23 (2->3):  10 x (-0.026667 + 0.063333)  x 100 = 36.667 MW      36.667 / 200 =  18.3 %
L12 (1->2):  10 x (0 + 0.026667)          x 100 = 26.667 MW      26.667 / 200 =  13.3 %

The reference injects -(10 - 100) = 90 MW, against the 92 MW the slack unit schedules, and the island's scheduled generation is 102 MW. The run agrees; angles and injections are in the result file (--csv), the console shows the flows:

$ gridsim dcpf docs/_captures/opf/tri3
DC power flow - Three-bus worked example (3 buses, 3 branches)  [linear: series reactance only; R, charging, shunts, taps and phase shifts ignored; |V| = 1 pu; lossless]
  island ref bus 1          3 buses  demand      100.0 MW  scheduled generation      102.0 MW  reference injects       90.0 MW
  1 of 3 rated branch(es) above 100% of RateA
  largest flows:
      branch 0     L13                   1 -> 3           63.33 MW    105.6% of 60 MVA
      branch 1     L23                   2 -> 3           36.67 MW     18.3% of 200 MVA
      branch 2     L12                   1 -> 2           26.67 MW     13.3% of 200 MVA
[exit 0]

DC-OPF by hand

The dispatch problem on tri3: G1 (nuclear, 10 GBP/MWh, 0 to 200 MW) at the slack bus, G2 (ocgt, 95 GBP/MWh, 0 to 200 MW) at bus 2, load 100 MW at bus 3, L13 rated 60 MVA and L23, L12 rated 200 MVA. G1 is on the reference bus, so its PTDF column is zero. The flows from the load alone, f0 = -100 x PTDF(bus 3), are L13 = +66.667, L23 = +33.333 and L12 = +33.333. The LP rows, in the order the code builds them (balance, then the rated lines in branch order), are:

balance   P1 + P2                     = 100
L13       -(1/3) P2 + s13             = 60 - 66.667  = -6.667
L23       +(1/3) P2 + s23             = 200 - 33.333 = 166.667
L12       -(2/3) P2 + s12             = 200 - 33.333 = 166.667
bounds    0 <= P1, P2 <= 200          0 <= s13, s23, s12 <= 120, 400, 400
minimise  10 P1 + 95 P2

The L13 row gives s13 = -6.667 + P2 / 3 >= 0, so P2 >= 20. G2 is dearer, so the optimum takes the smallest P2, which is 20, and P1 = 80. The slacks follow: s13 = 0 (the line is at its limit), s23 = 160 (flow 200 - 160 = 40) and s12 = 180 (flow 20). The cost is 80 x 10 + 20 x 95 = 2,700 GBP/h. Without the line row the same LP gives P1 = 100, cost 1,000 GBP/h, and a flow of 66.667 MW on a 60 MVA line. The run agrees on the dispatch, the cost and the binding line (60.0 MW / 60 MVA):

$ gridsim dcopf docs/_captures/opf/tri3
DC-OPF - Three-bus worked example (3 buses)  [cheapest secure dispatch]
  demand 100 MW  generation 100 MW  total cost 2,700 GBP/h  (network-constrained redispatch applied)
  dispatch (by output):
      gen bus 1          80.0 MW  @    10 GBP/MWh
      gen bus 2          20.0 MW  @    95 GBP/MWh
  binding line limits:
      branch 0    L13              60.0 MW / 60 MVA
[exit 0]
$ gridsim dcopf docs/_captures/opf/tri3 --no-limits
DC-OPF - Three-bus worked example (3 buses)  [cheapest secure dispatch]
  demand 100 MW  generation 100 MW  total cost 1,000 GBP/h  (unconstrained merit order)
  dispatch (by output):
      gen bus 1         100.0 MW  @    10 GBP/MWh
[exit 0]

Relaxing the L13 rating by 1 MW lets P2 fall by 3 MW, which saves 3 x (95 - 10) = 255 GBP/h.

With equal costs the optimum is not unique. case9 has three units at 50 GBP/MWh and demand 315 MW. The merit order (--no-limits) fills them in index order, 250 MW and then 65 MW, and the LP lands on a different vertex of the same cost, 270 MW and 45 MW. Both cost 315 x 50 = 15,750 GBP/h:

$ gridsim dcopf case9 --no-limits
DC-OPF - IEEE 9-bus (WSCC) (9 buses)  [cheapest secure dispatch]
  demand 315 MW  generation 315 MW  total cost 15,750 GBP/h  (unconstrained merit order)
  dispatch (by output):
      gen bus 1         250.0 MW  @    50 GBP/MWh
      gen bus 2          55.0 MW  @    50 GBP/MWh
      gen bus 3          10.0 MW  @    50 GBP/MWh
[exit 0]
$ gridsim dcopf case9
DC-OPF - IEEE 9-bus (WSCC) (9 buses)  [cheapest secure dispatch]
  demand 315 MW  generation 315 MW  total cost 15,750 GBP/h  (unconstrained merit order)
  dispatch (by output):
      gen bus 3         270.0 MW  @    50 GBP/MWh
      gen bus 2          35.0 MW  @    50 GBP/MWh
      gen bus 1          10.0 MW  @    50 GBP/MWh
[exit 0]

DC-OPF on cost curves and prices

docs/_captures/opf/tri3-costs.json gives G1 the curve 0.05 P^2 + 10 P and G2 the curve 95 P:

{
  "format": "gridsim-costs/1",
  "generators": [
    { "index": 1, "model": "polynomial", "coefficients": [0.05, 10, 0] },
    { "index": 2, "model": "polynomial", "coefficients": [0, 95, 0] }
  ]
}

The L13 row still forces P2 >= 20. G1's marginal cost at P1 = 80 is 10 + 0.1 x 80 = 18, below G2's 95, so the optimum is the same dispatch, 80 and 20 MW, and the cost is 10 x 80 + 0.05 x 80^2 + 95 x 20 = 1,120 + 1,900 = 3,020. The balance dual is G1's marginal cost, y0 = 18, and the energy component of every price. G2 sits strictly inside its bounds, so its reduced cost is 0: 95 = y0 + y x PTDF[L13, 2] = 18 + y x (-1/3), where y is the dual of the L13 row, so y = -231 (the line's shadow price is 231 per MW of extra rating). The prices follow from LMP_k = y0 + y x PTDF[L13, k]: bus 1 is 18, bus 2 is 18 + (-231) x (-1/3) = 95 and bus 3 is 18 + (-231) x (-2/3) = 172.

$ gridsim dcopf docs/_captures/opf/tri3 --costs docs/_captures/opf/tri3-costs.json --prices
DC-OPF - Three-bus worked example (3 buses)  [cheapest secure dispatch on generator cost curves: tri3-costs.json]
  demand 100 MW  generation 100 MW  total cost 3,020.00 cost units/h  (network-constrained)
  dispatch (by output):
      gen bus 1         80.00 MW  marginal   18.0000 cost units/MWh
      gen bus 2         20.00 MW  marginal   95.0000 cost units/MWh
  binding line limits:
      branch 0    L13              60.0 MW / 60 MVA
  nodal prices (LMP, cost units/MWh, lossless DC): 3 bus(es), highest 172.0000 at bus 3, lowest 18.0000 at bus 1
      bus 3      LMP   172.0000  (energy 18.0000, congestion 154.0000)
      bus 2      LMP    95.0000  (energy 18.0000, congestion 77.0000)
      bus 1      LMP    18.0000  (energy 18.0000, congestion 0.0000)
  line shadow prices (cost units/MWh per MW of extra rating):
      branch 0    L13              60.0 MW / 60 MVA  shadow price 231.0000
[exit 0]

AC-OPF fixed point

acopf case9 settles in 5 passes at 11.615 MW of losses with 270.0 MW on bus 3, 46.6 MW on bus 2 and 10.0 MW on bus 1. Generation is 270.0 + 46.6 + 10.0 = 326.6 MW, which equals demand plus losses (315 + 11.615 = 326.615 MW), and the cost is 326.615 x 50 = 16,331 GBP/h (the table prints 16,331). The case's own base dispatch (72.3, 163 and 85 MW) loses 4.64 MW (gridsim losses case9); this one loses 11.615 MW. The three units cost the same, so the LP is indifferent between the two dispatches, and the loss enters the choice only through the demand the loop inflates.

$ gridsim acopf case9
ACOPF (DC dispatch + AC loss loop) - IEEE 9-bus (WSCC) (9 buses)  [not a full AC-OPF: no voltage, reactive-power or AC branch-flow limits]
  converged in 5 iteration(s)  losses 11.615 MW  cost 16,331 GBP/h
      gen bus 3         270.0 MW  @    50 GBP/MWh
      gen bus 2          46.6 MW  @    50 GBP/MWh
      gen bus 1          10.0 MW  @    50 GBP/MWh
[exit 0]

The lossless tri3 settles in one pass, since the first measured loss is already below --loss-tol:

$ gridsim acopf docs/_captures/opf/tri3
ACOPF (DC dispatch + AC loss loop) - Three-bus worked example (3 buses)  [not a full AC-OPF: no voltage, reactive-power or AC branch-flow limits]
  converged in 1 iteration(s)  losses -0.000 MW  cost 2,700 GBP/h
      gen bus 1          80.0 MW  @    10 GBP/MWh
      gen bus 2          20.0 MW  @    95 GBP/MWh
[exit 0]

The CPF search, step by step

cpf case9 returns 2.373046875. Replaying the loop with Newton-Raphson converging at every multiplier up to a limit anywhere from 2.373046875 to just below 2.375 gives these 20 solves (the move of cpf to the study options and the OLTC loop left the printed lambda the same bits on every bundled case):

solve  lambda         step          converged
  1    1.0000000000   0.2500000000  yes
  2    1.2500000000   0.2500000000  yes
  3    1.5000000000   0.2500000000  yes
  4    1.7500000000   0.2500000000  yes
  5    2.0000000000   0.2500000000  yes
  6    2.2500000000   0.2500000000  yes
  7    2.5000000000   0.2500000000  no
  8    2.3750000000   0.1250000000  no
  9    2.3125000000   0.0625000000  yes
 10    2.3750000000   0.0625000000  no
 11    2.3437500000   0.0312500000  yes
 12    2.3750000000   0.0312500000  no
 13    2.3593750000   0.0156250000  yes
 14    2.3750000000   0.0156250000  no
 15    2.3671875000   0.0078125000  yes
 16    2.3750000000   0.0078125000  no
 17    2.3710937500   0.0039062500  yes
 18    2.3750000000   0.0039062500  no
 19    2.3730468750   0.0019531250  yes
 20    2.3750000000   0.0019531250  no

After solve 20 the step halves to 0.0009765625, which is below minStep (0.001), and the loop ends with lastGood = 2.373046875. The repeated trial at 2.375 on every other row is the retry of the point that failed one refinement earlier. The width of the bracket is 2.375 - 2.373046875 = 0.001953125, which is 2 x 0.0009765625, inside [0.001, 0.002). The replay reproduces the run's behaviour at every cap: --max-steps 5 returns 2.0 (solve 5), --max-steps 18 returns 2.37109375 (solve 17), and 19 or more returns 2.373046875. With --step 0.5 --min-step 0.01 the same loop ends after 13 solves at 2.359375:

$ gridsim cpf case9
CPF - IEEE 9-bus (WSCC) (9 buses)  [load scaled uniformly, slack absorbs the balance]
  max loadability lambda = 2.373046875  (base demand 315.0 MW -> 747.5 MW at the last converged point; nose bracketed to 0.001)
  margin 137.30% above base load
[exit 0]
$ gridsim cpf case9 --step 0.5 --min-step 0.01
CPF - IEEE 9-bus (WSCC) (9 buses)  [load scaled uniformly, slack absorbs the balance]
  max loadability lambda = 2.359375  (base demand 315.0 MW -> 743.2 MW at the last converged point; nose bracketed to 0.01)
  margin 135.94% above base load
[exit 0]
$ gridsim cpf case9 --max-steps 5
CPF - IEEE 9-bus (WSCC) (9 buses)  [load scaled uniformly, slack absorbs the balance]
  max loadability lambda = 2  (base demand 315.0 MW -> 630.0 MW at the last converged point; NOT bracketed: --max-steps 5 ran out with every solve converged, so lambda is only a lower bound)
  margin 100.00% above base load
cpf: --max-steps 5 ran out before the nose was bracketed to --min-step 0.001; the lambda above is a lower bound, not the loadability limit. Raise --max-steps (or --min-step). Exit 3.
[exit 3]

All five solves converge, so the bracket clause reads NOT bracketed: --max-steps 5 ran out with every solve converged, so lambda is only a lower bound, the --max-steps message goes to standard error and the run exits 3.

The tap objective

taps uk lowers the objective from 2.789433E-002 to 1.610133E-002:

$ gridsim taps uk
TAP SCHEDULE - GB reduced (10-zone) (10 OLTCs)  [minimise sum of squared deviation from 1.000 pu]
  objective 2.789433E-002 -> 1.610133E-002  (improved)
      T1 GSP N Scotland          1.0000 ->   1.0375
      T2 GSP S Scotland          1.0000 ->   1.0375
      T3 GSP N England           1.0000 ->   1.0375
      T4 GSP Yorkshire           1.0000 ->   1.0375
      T5 GSP N Wales & Mersey    1.0000 ->   1.0375
      T6 GSP Midlands            1.0000 ->   1.0250
      T7 GSP East Anglia         1.0000 ->   1.0375
      T8 GSP London & SE         1.0000 ->   1.0250
      T9 GSP South               1.0000 ->   1.0375
      T10 GSP SW & S Wales       1.0000 ->   1.0375
[exit 0]

The starting objective is the sum over the 20 bus voltages of a power flow with the taps at their case values and no OLTC loop, which gridsim pf uk --top 20 prints. The ten 400 kV buses are generator buses held at 1.040 pu, and the ten GSP buses sit between 1.0274 and 1.0392 pu. The sum of (V - 1)^2 over those 20 values is 2.789433E-002, the before value. The 400 kV buses alone contribute 10 x 0.04^2 = 0.016, and no tap moves them. The after value, 1.610133E-002, is 0.000101 above that floor, so the schedule has brought the ten GSP buses to an rms deviation of 0.0032 pu from 1.000 pu. A higher ratio on the 400 kV side lowers the GSP voltage. Eight taps sit at 1.0375 = 1.0 + 3 x 0.0125 and two at 1.0250 = 1.0 + 2 x 0.0125, all on the grid 0.9 + k x 0.0125.

Source map

File Type Responsibility
src/GridSim.Core/Analysis/DcOptimalPowerFlow.cs DcOptimalPowerFlow, DcOpfOptions Merit order, security LP build, island dispatch, fuel cost table, price assembly, result records.
src/GridSim.Core/Analysis/DcOpfCosted.cs DcOpfCosted The cost-curve LP on a connected network and its nodal and line prices.
src/GridSim.Core/Analysis/DcOpfQuadratic.cs DcOpfQuadratic The primal active-set solver for quadratic cost terms.
src/GridSim.Core/Analysis/GeneratorCostCurve.cs GeneratorCostCurve The optimisable curve form and the refusals.
src/GridSim.Core/Analysis/DcPowerFlow.cs DcPowerFlow, DcPowerFlowResult, DcIslandBalance The DC power flow over DistributionFactors.
src/GridSim.Core/Model/FuelTypes.cs FuelTypes, FuelKind, FuelKeyword The ordered keyword list and the matching rule behind FuelCostPerMwh.
src/GridSim.Core/IO/Matpower/MatpowerParser.cs MatpowerParser Reads mpc.gencost into Generator.Cost.
src/GridSim.Core/IO/Json/GeneratorCostFile.cs GeneratorCostFile The gridsim-costs/1 file and its overlay.
src/GridSim.Core/Analysis/DcScopf.cs DcScopf, ScopfOptions, ScopfResult The preventive security-constrained DC-OPF on the sparse simplex, with constraint generation.
src/GridSim.Core/Analysis/DcOpfSecuritySimplex.cs DcOpfSecuritySimplex The structured security LP solver, bit-identical to the dense reference.
src/GridSim.Core/Analysis/DcOpfHybridColumns.cs DcOpfHybridColumns Column storage (single or dense) for the basis inverse and the Gauss-Jordan matrix.
src/GridSim.Core/Numerics/BoundedSimplex.cs BoundedSimplex, LpStatus The dense two-phase bounded-variable simplex and its constants.
src/GridSim.Core/Analysis/DistributionFactors.cs DistributionFactors, DcIsland DC model, islands, PTDF, LODF, DC flows.
src/GridSim.Core/Analysis/AcOptimalPowerFlow.cs AcOptimalPowerFlow, AcOpfResult The loss loop around the DC-OPF.
src/GridSim.Core/Analysis/ContinuationPowerFlow.cs ContinuationPowerFlow, PvCurve Load scaling, the multiplier bisection and the PV trace.
src/GridSim.Core/Analysis/TapOptimizer.cs TapOptimizer, TapSchedule, TapSetting Tap objective, penalties, snap-to-grid, result.
src/GridSim.Core/Numerics/NelderMead.cs NelderMead Derivative-free simplex search used by TapOptimizer.
src/GridSim.Core/Analysis/LossAllocation.cs LossAllocation, BranchLoss, ZoneLoss Per-branch and per-zone loss decomposition.
src/GridSim.Core/IO/Json/JsonGridLoader.cs JsonGridLoader Pmin, Pmax, RateAMva and circuit handling of a JSON case.
src/GridSim.Core/PowerFlow/SolverSelector.cs SolverSelector CreateNewton, used by acopf, cpf and taps.
src/GridSim.Cli/Program.cs RunDcpf, RunDcOpf, RunAcOpf, RunCpf, RunTaps, RunDistributionFactors, RunLossAllocation, ApplyCostSource, WritePvCurveCsv, LoadAnalysisCase, LoadCaseArgument, SingleCasePositional, PositionalArg The verbs, their case loading, output and exit codes.
src/GridSim.Cli/VerbFlags.cs VerbFlags The per-verb accepted flags, read from chapter 19.
src/GridSim.Cli/CliResultWriter.cs CliOutput, CliResult --json, --csv and --out.
src/GridSim.Cli/CliDefaults.cs CliDefaults The display floors.
tests/GridSim.Tests/DcOptimalPowerFlowTests.cs, AnalysisWs6Tests.cs, ConvergenceContractTests.cs DC-OPF dispatch, Pmin, LP status.
tests/GridSim.Tests/DcPowerFlowAndPvCurveTests.cs, SimplexPivotFloorTests.cs The DC power flow, the PV trace, the pivot floor.
tests/GridSim.Tests/FuelTypesTaxonomyTests.cs, GeneratorCostsAndPricesTests.cs, AcOpfPricesTests.cs The cost per fuel kind, cost curves and prices.
tests/GridSim.Tests/N173AcopfEarlyStopTests.cs, S4SolverDataFollowUpsTests.cs, S4SolverConvergenceTests.cs The acopf and dcopf failure causes and text, the per-island loss loop, the shunt residual.
tests/GridSim.Tests/CliProcessSmokeTests.cs, CliS4CliAndLoaderProcessTests.cs, VerbFlagsTests.cs, CliResultFilesProcessTests.cs The built binary's headers and exit codes, flag refusal, result files.
tests/GridSim.Tests/DcOpfSecuritySimplexParityTests.cs, BoundedSimplexTests.cs Structured versus dense simplex; LP behaviour.
tests/GridSim.Tests/DistributionFactorsTests.cs, DcIslandTests.cs PTDF, LODF, islands, island dispatch.
tests/GridSim.Tests/DcScopfTests.cs The preventive SCOPF against hand calculation and an independent formulation.
tests/GridSim.Tests/AcOptimalPowerFlowTests.cs, ContinuationPowerFlowTests.cs, ConvergenceContractStudyTests.cs Loss loop and load search.
tests/GridSim.Tests/TapOptimizerTests.cs, LossAllocationTests.cs, Ws13CoreConstantsAntiDriftTests.cs Tap schedule, loss decomposition, constants.

Limits

  • acopf solves the DC problem and adds a loss loop; it does not solve the full AC equations. Voltage, reactive power and AC branch limits are not constraints, and the AC state is used only to measure the losses.
  • Without --costs the cost of a unit is linear and comes only from its fuel-type string. With --costs a curve is a polynomial up to quadratic with a non-negative quadratic term or a convex piecewise-linear curve; a cubic term, a concave curve, a non-convex piecewise curve and a unit without a curve are refused. Start-up and shut-down costs are carried and not optimised. The prices are lossless DC prices with no marginal-loss component, and at a degenerate optimum they are those of the basis found.
  • The DC-OPF leaves out of its LP a rated line that no dispatch can relieve and reports it, so a feasible result (dcopf exit 0, acopf Converged) can leave such a line over its rating; only the listing and the result file's unrelievable_lines say so.
  • dcpf is linear and lossless: the reference bus of each island absorbs the imbalance, and a rating is reported, not enforced.
  • cpf is a bisection on a uniform load multiplier with no predictor, no corrector and no parameterisation through the nose; each solve restarts from the stored voltages, so a failure can precede the true nose.
  • cpf scales loads only and takes the increase on the slack; it checks no generator active-power limit, no branch rating and no slack limit.
  • taps minimises the deviation of every bus from one target; each OLTC's own target and deadband are checked after the search, not optimised.
  • The preventive SCOPF (DcScopf) takes linear costs only (an explicit cost per unit or the fuel-type cost), secures single-branch outages only (no generator outage, no corrective action) and needs one connected network. A post-outage limit left out of the final LP holds to within 1e-6 MW.
  • ptdf, lodf, dcpf and the DC-OPF use series reactance only; resistance, charging, tap ratios and phase shifts are ignored.
  • The loss decomposition is by branch and zone only; it does not allocate losses to generators or loads.

See also