27. Battery energy storage

This chapter specifies the battery model in src/GridSim.Core/Storage/ and the way studies use it: the cell equivalent circuit, the six chemistry presets, pack assembly and its limits, the thermal and auxiliary-load model, the ageing model, efficiency and round trip, the dispatch policies and the linear-programme scheduler, the price series, and the fleet that carries storage sites through a time series of AC power flows. A battery's grid behaviour is the output of its chemistry. How much power it delivers, for how long and at what temperature is set by the cell's open-circuit-voltage curve, its impedance and how that rises in the cold, its rate limits, its thermal mass and its ageing. The converter is the output stage, bounded by what the DC side can deliver.

The model has four consumers:

  • gridsim chain --bess and gridsim gda-replay --bess run sites through StorageFleet (src/GridSim.Core/Storage/StorageFleet.cs) and report them. The user chapter is ch. 13, Battery storage studies.
  • LiveSim carries a StorageFleet tick to tick (the storage constructor argument); each SimFrame carries the site records. No CLI verb attaches one.
  • The grid-following and grid-forming inverter assets draw through an IDcSource, and BatteryDcSource is the pack behind the inverter.
  • RmsConverterUnit.Store puts an IDcSource behind an RMS converter.

Cell and pack state are SI throughout: volts, amperes, ohms, seconds, joules, kelvin. Dispatch and reporting are in MW and MWh, discharge positive. Every chemistry preset is ProvenanceTag.CuratedPlaceholder with a [VERIFY] note: a representative cell for its class, fit for comparing chemistries and exercising the model, to be replaced by a specific cell's datasheet or fitted test data before a result is quoted for a real asset. The tag is defined in ch. 8, Provenance and invariants.

Model

Cell: equivalent circuit (CellModel)

One representative cell carries the state of a pack: state of charge SoC (fraction of the present, faded capacity), the two polarisation voltages V1 and V2, temperature T (K) and capacity fade fade (fraction of rated capacity lost). Current I is per cell and positive on discharge. Tables (LookupTable) are piecewise linear on strictly ascending x, clamped at both ends, and need at least two points.

Rg   = 8.314462618 J/mol/K          Tref = 298.15 K
OCV(SoC, T)  = OCV25(SoC) + dUdT(SoC) * (T - Tref)
f_res(T)     = exp(Ea / Rg * (1/T - 1/Tref))                    Arrhenius, 1 at 25 C
R0           = R0_25(SoC) * f_res(T) * (1 + g * fade)
R1           = R1_25      * f_res(T) * (1 + g * fade)
R2           = R2_25      * f_res(T) * (1 + g * fade)
Q(fade)      = Q_rated * (1 - fade)
E            = OCV - V1 - V2                                    Thevenin source behind R0
V_t(I)       = E - I * R0

Step(I, dt) advances the electrochemical state by dt seconds at constant I and returns the heat of the step. R0, R1, R2, the OCV and the entropic coefficient are evaluated once, at the start-of-step state.

a_k   = exp(-dt / tau_k)                                        k = 1, 2
V_k+  = V_k * a_k + I * R_k * (1 - a_k)                         exact zero-order hold
Qirr  = I^2 R0 dt + 0.5 (V1^2 + V1+^2) / R1 dt + 0.5 (V2^2 + V2+^2) / R2 dt
Qrev  = I * T * dUdT(SoC) * dt
heat  = Qirr + Qrev                                             J per cell

Qirr integrates the dissipation in each RC resistor with a trapezoid on the squared voltage. Qrev is the reversible entropic term. Where dU/dT is negative, as for LFP and NMC, it cools the cell on discharge and heats it on charge. The charge and rate effects are:

cRate  = I / Q_rated
I_eff  = I * (cRate / Cref)^(kP - 1)       I > 0, kP > 1 and cRate > Cref     Peukert
I_eff  = I                                 I > 0 otherwise
I_eff  = I * CE                            I < 0                              coulombic efficiency on charge
sd     = SelfDischargePerMonth / (30 * 86400)                                 per second
SoC+   = clamp(SoC - I_eff * dt / (3600 * Q(fade)) - sd * dt, 0, 1)

Q_rated in the Peukert test is the unfaded rated capacity. Self-discharge acts on every step, charging, discharging or idle, and acts below the SoC floor and above the ceiling too: the window is enforced on current, not on state. Step never changes T; the pack's thermal model does.

Rate capability is not a parameter. At higher current the terminal voltage sags further through R0, V1 and V2, so the cut-off voltage is reached with less charge delivered; the resistance rises in the cold through f_res; lead-acid adds kP for the rate effect resistance alone does not capture. NominalVoltage is OCV25(0.5). NominalEnergyWh is the cell energy Q_rated * (SocMax - SocMin) * mean(OCV25), with the mean taken over 100 mid-point samples of the SoC window.

Pack: assembly and sizing (PackModel)

A pack is Ns x Np identical cells (series count by parallel strings), lumped so that one representative cell carries the state. PackModel.Sized builds a pack for a target nominal energy and DC voltage:

Ns = max(1, round(Vdc / Vnom_cell))
Np = max(1, round(E_target / (Ns * Ecell_nominal)))
NominalEnergyWh = Ecell_nominal * Ns * Np

round is Math.Round, which rounds halves to even. The pack nominal energy is close to, not equal to, the target. The rated power RatedPowerW defaults to NominalEnergyWh * MaxDischargeCRate; the CLI and DcSources pass the site's AC rating instead. It scales the auxiliary load and bounds the state-of-power search. Sizing for 10 MWh at 1000 V, from docs/_captures/bess/api-probe-sizing.txt:

$ API probe (GridSim.Core, Release build): sizing
chemistry   Vnom_V  cell_Wh   Ns   Np  pack_MWh
LFP         3.2900   824.40  304   40   10.0247
NMC         3.7800   219.10  265  172    9.9868
LTO         2.3000    64.87  435  354    9.9891
Na-ion      3.1000   466.73  323   66    9.9497
VRFB        1.4000   980.00  714   14    9.7961
Lead-acid   2.0400  1603.84  490   13   10.2164
[exit 0]

The BMS current limits MaxDischargeCRate * Q(fade) and MaxChargeCRate * Q(fade) are per cell in amperes, so they are multiples of the Ah capacity, not of the windowed nominal energy. For the LFP pack above, 280 A and 140 A per cell over 40 strings at 304 * 3.29 = 1000.2 V are 11.2 MW and 5.6 MW before sag.

Pack quantities:

AvailableEnergyWh = max(0, SoC - SocMin) * Q(fade) * Np * Ns * Vnom_cell
OpenCircuitVoltage = Ocv(SoC, T) * Ns                      (no V1, V2)

Pack: one step (PackModel.Step)

Step(P, dt) delivers a DC power request P (W, discharge positive) for dt seconds. It solves the cell current at the start-of-step state, applies the battery-management limits, advances the cell, ageing and temperature, and reports what was delivered and which limit bound.

  1. Per-cell power and unconstrained current. p = P / (Ns Np), with E and R0 at the start of the step. The cell current solves E I - R0 I^2 = p, taking the smaller root:
disc = E^2 - 4 R0 p
I    = (E - sqrt(disc)) / (2 R0)          disc >= 0
I    = E / (2 R0)                         disc < 0: beyond maximum power transfer; reason = "maximum power transfer"
  1. Limits. The current limits (A, per cell, both positive) are:
derate = clamp((TMax - Tc) / max(1e-9, TMax - TDerate), 0, 1)           Tc = cell temperature, C
iDis   = min(MaxDischargeCRate * Q(fade) * derate, max(0, (E - VMin) / R0))
iChg   = min(MaxChargeCRate    * Q(fade) * derate, max(0, (VMax - E) / R0))
iDis   = 0   when SoC <= SocMin
iChg   = 0   when SoC >= SocMax or Tc < TMinCharge

The step never carries the SoC across its window. The current that would land exactly on the edge caps the step, so the battery-management system tapers into the limit:

chargeRoom    = (SocMax - SoC) * 3600 * Q(fade) / dt / max(CE, 1e-9)
dischargeRoom = (SoC - SocMin) * 3600 * Q(fade) / dt
dischargeRoom = (dischargeRoom * Iref^(kP-1))^(1/kP)       kP > 1 and dischargeRoom > Cref * Q(fade);  Iref = Cref * Q_rated
iChg = min(iChg, max(0, chargeRoom))        iDis = min(iDis, max(0, dischargeRoom))

The last Peukert line inverts I_eff = I (I / Iref)^(kP-1), so the discharge room is a current that depletes the charge to the floor and no further. Self-discharge is not in the room, so a pack at the floor drifts a little below it.

  1. Clip. If I > iDis then I = iDis; if I < -iChg then I = -iChg. The limit is named in this order, and a reason already set by step 1 is kept:
Direction Reason, first match wins
Discharge SoC floor when SoC - SocMin < 1e-3 or iDis equals the discharge room to 1e-9 A
temperature derate when derate < 1 and iDis equals MaxDischargeCRate * Q * derate to 1e-9 A
cut-off voltage when iDis equals (E - VMin) / R0 to 1e-9 A
current limit otherwise
Charge SoC ceiling when SocMax - SoC < 1e-3 or (iChg > 0 and iChg equals the charge room to 1e-9 A)
too cold to charge when Tc < TMinCharge
charge voltage when iChg equals (VMax - E) / R0 to 1e-9 A
current limit otherwise
  1. Advance. vCell = E - I R0 at the start-of-step state. heatJ = CellModel.Step(I, dt) * Ns * Np. If ageing is tracked, AgeingModel.Advance(cell, I, dt) runs next, on the post-step SoC and the pre-thermal temperature. The thermal model then sets the new temperature (next section).

  2. Report.

DcPowerW        = vCell * I * Ns * Np
CurrentA        = I * Np               TerminalVoltageV = vCell * Ns       HeatW = heatJ / dt
Limited         = reason is set  and  |DcPowerW - P| > 1e-6 * max(1 W, |P|)

vCell is the start-of-step terminal voltage, so an unconstrained step delivers the requested power exactly (the quadratic in step 1 solves for it). A limit that binds but costs less than 1e-6 of the request is not reported.

InstantaneousLimitsW() is the power at the battery-management limits now, with no look-ahead, cheap enough to query every control step. With iDis and iChg from the limits above (the discharge current also capped at E / (2 R0), the maximum-power-transfer current):

DischargeW = (E * iDis - R0 * iDis^2) * Ns * Np
ChargeW    = (E * iChg + R0 * iChg^2) * Ns * Np

StateOfPower(horizon, substeps = 40) is the largest constant DC power the pack sustains for the horizon with no limit binding, for discharge and charge (both positive). Sustains(P) clones the pack without ageing, steps it substeps times of horizon / substeps and fails if any step is Limited. The search brackets [0, max(RatedPowerW, 20 * NominalEnergyWh)]. It first requires 1 W to be sustainable, else the state of power is 0, then bisects for at most 50 iterations and stops when the bracket is narrower than 1e-4 * max(1, hi). Because it simulates the horizon, it includes the sag building up over it, the SoC window and heating. A 10 s pulse and a 30 minute delivery give different answers, and chemistries differ exactly there. For packs sized to 1 MWh at 1000 V, from 90 % SoC, from docs/_captures/bess/api-probe-sop.txt:

$ API probe (GridSim.Core, Release build): sop
chemistry  10 s pulse  30 min   2 h   10 s at -10 C   (MW, discharge)
LFP         1.104    1.071    0.465    0.955
NMC         2.258    1.758    0.458    1.725
LTO         6.210    1.771    0.452    4.851
Na-ion      2.352    1.716    0.472    1.998
[exit 0]

Thermal model and auxiliary load

The pack temperature is one lumped mass per pack, advanced by an explicit Euler step inside PackModel.Step. The cells are at the pack temperature. Heat enters from the cells, leaves passively to ambient, and leaves actively through the HVAC while the temperature is above its setpoint:

mcp       = MassKg * SpecificHeat * Ns * Np                           J/K
passiveW  = PassiveCoolingWPerK * Ns * Np * (T - (Tambient + 273.15))
T_noHvac  = T + (heatJ - passiveW * dt) / mcp
hvacW     = min((T_noHvac - Tset) * mcp / dt, HvacCapacityFraction * RatedPowerW)    HvacCop > 0 and T_noHvac > Tset
hvacW     = 0                                                                         otherwise
T+        = T_noHvac - hvacW * dt / mcp

hvacW is heat removed, capped by the HVAC capacity as a fraction of the rated power. Tset = HvacSetpointC + 273.15. Chemistries with HvacCop = 0 (VRFB, lead-acid) have no HVAC and cool only passively. The pack ambient AmbientC defaults to 25 C. The pack heat limits power through the temperature derate in the current limits.

The auxiliary (balance-of-plant) electrical load of the step, in W, is:

aux = StandbyFraction * RatedPowerW
    + (HvacCop > 0 ? hvacW / HvacCop : 0)
    + PumpFraction * |DcPowerW|

Standby covers controls, the battery-management system and idle fans. The HVAC term is the electrical power that removes hvacW of heat. The pump term is the electrolyte pumps of a flow battery as a fraction of the power moved. StorageFleet adds the mean auxiliary power to the site's bus as demand (see Time series). It is not in the round-trip figure.

Ageing (AgeingModel, Rainflow)

AgeingModel.Advance(cell, I, dt) accumulates calendar fade and cycle fade and writes cell.CapacityFade = min(0.8, calendar + cycle). The cap MaxCapacityFade is 0.8: beyond it the cell would have almost no capacity left and its resistance growth stops being meaningful. The reported CalendarFade and CycleFade are not clamped. Capacity and resistance both feel the fade on the next step (Q(fade) and 1 + g * fade).

Arr(E, T)  = exp(-E / Rg * (1/T - 1/Tref))                        T = temperature before this step's thermal update
stress     = k_cal * Arr(E_cal, T) * max(0.05, 1 + a_soc * (SoC - 0.5))     SoC after this step's cell update
tEq        = (calendar / stress)^2 days          if calendar > 0, else 0
calendar+  = stress * sqrt(tEq + dt / 86400)

The calendar law is k_cal * sqrt(days), so one day is sqrt(1/365), 5.2 %, of a year's fade at constant stress. For LFP at 25 C and 50 % SoC that is 0.001 * sqrt(365) = 1.91 % for a year; the captured LFP day reads 0.1369 %. The equivalent-time form maps the fade so far to the age at which the present stress would have produced it, so the result does not depend on the step size and follows time-varying stress. At 25 C and 50 % SoC, calendar = k_cal * sqrt(days) exactly, for any step size. The floor 0.05 on the SoC stress factor keeps a negative a_soc from driving stress to zero.

if I != 0:
  cRate   = |I| / Q_rated
  cFactor = 1 + CRateSensitivity * max(0, cRate - 1)
  EFC     = |I| * dt / 3600 / (2 * Q_rated)                         equivalent full cycles of this step
  cycle+  = cycle + (0.2 / N80) * EFC * Arr(E_cyc, T) * cFactor

0.2 is EndOfLifeFade, the 20 % fade that defines N80, the equivalent full cycles to 80 % capacity. One equivalent full cycle is a charge plus a discharge of the full capacity (ThroughputPerFullCycle = 2). Cycle fade is linear in throughput and independent of depth of discharge; the depth effect comes from rainflow counting below.

Resistance growth is 1 + g * fade on R0, R1 and R2, with g = ResistanceGrowthPerFade. At the 20 % end-of-life fade the resistance has grown by g * 0.2, 50 % for the default g = 2.5.

Rainflow (Rainflow.Count, ASTM E1049-85 three-point method) counts cycles in a SoC history as (range, count) pairs. The history is reduced to turning points first: a value equal to the last is dropped, and a value continuing the direction of the last segment replaces the last point. Each point is then pushed on a stack. While the stack holds at least three points, with X the latest range and Y the one before it:

  • if X < Y, stop;
  • if the stack holds exactly three points, Y contains the start point: count (Y, 0.5) and drop the first point;
  • otherwise count (Y, 1.0) and drop the two points of Y.

What remains on the stack at the end is the residue, and each of its consecutive ranges counts (range, 0.5). AgeingModel.CycleFadeFromRainflow turns the counts into a depth-aware cycle fade:

fade_rainflow = sum over (d, n) of  n * (0.2 / N80) * |d|^beta           beta = DodExponent

A full-window cycle, d = 1, costs the reference amount. Many shallow cycles cost less than one deep one for beta > 1. The fleet counts the SoC trace of the whole run, the starting SoC followed by the SoC after every substep. The rainflow fade is a report, shown beside the throughput fade; the fade fed back into the cell is calendar plus throughput cycle fade.

Converter (BatteryDcSource)

BatteryDcSource (src/GridSim.Core/Assets/DcSource.cs) puts a pack behind a converter of one-way efficiency eta, which must lie in [0.5, 1] (anything else, or a value that is not finite, is refused), default 0.98. Its power is AC side, discharge positive:

Draw(acMw, dt):   dcW = acMw >= 0 ? acMw * 1e6 / eta : acMw * 1e6 * eta
                  r = pack.Step(dcW, dt)
                  delivered = r.DcPowerW >= 0 ? r.DcPowerW * eta / 1e6 : r.DcPowerW / eta / 1e6
Headroom():       (Up, Down) = (DischargeW * eta / 1e6, ChargeW / eta / 1e6)       from InstantaneousLimitsW()

A discharge draws 1/eta more from the pack than it delivers; a charge stores eta less than it absorbs. Reset() restores the pack from a clone made at construction, which has no ageing tracking.

Efficiency and round trip

Energy is lost in four places: the converter in each direction (0.98), the cell's series resistance and the two polarisation resistors (heat), the coulombic efficiency on charge, and the balance-of-plant load. The first three set the round trip. For a lithium preset the product of the converter and the coulombic efficiency bounds it: for LFP, 0.98^2 * 0.995 = 0.9556, before any cell resistance.

The scheduler's envelope uses a linearised pack efficiency (next section). The study report measures the actual run (StorageFleet.Summaries), with out and in the AC energy delivered and absorbed, summed over steps as max(delivered, 0) * h and max(-delivered, 0) * h:

storedChange = AvailableEnergyWh(end) / 1e6 - AvailableEnergyWh(start) / 1e6            MWh
roundTrip    = (out + max(0, storedChange)) / (in + max(0, -storedChange))              NaN when in <= 1e-9 MWh
EFC          = (out + in) / (2 * NominalEnergyWh / 1e6)

The stored-change credit means a run that ends empty or full is neither flattered nor penalised. The round trip is NaN, printed -, when the run absorbed nothing. Auxiliary energy is not in it and is reported separately. EFC is measured against the nominal pack energy as sized, not the energy requested.

Dispatch policies (StorageDispatch.cs)

A policy gives the AC power to request each step (MW, discharge positive). The chemistry then decides what is delivered. A policy sees a DispatchContext: the step index, the hour of day at the start of the step, the step length in hours, the system demand in MW, the price in GBP/MWh (NaN when there is no price series), the unit's SoC at the start of the step and the unit's rated MW. StorageFleet.Advance clamps the request to [-RatedMw, RatedMw].

Policy Request Parameters and defaults
idle (IdlePolicy) 0 none
peak-shave (PeakShavePolicy) demand > High: min(Rated, demand - High); demand < Low: -min(Rated, Low - demand); else 0 High 0.9 and Low 0.7 of the peak demand of the run; --shave-high, --shave-low in absolute MW
price-threshold (PriceThresholdPolicy), CLI price NaN price: 0; price >= SellAbove: Rated; price <= BuyBelow: -Rated; else 0 BuyBelow 40, SellAbove 90 GBP/MWh; --buy-below, --sell-above
response-holding (ResponseHoldingPolicy), CLI hold SoC > Target + Band: Restore * Rated; SoC < Target - Band: -Restore * Rated; else 0 Target 0.5, Band 0.05, Restore 0.2; no CLI flag
schedule (SchedulePolicy), label lp on the CLI Mw[step], 0 beyond the array the net MW array of a plan

The comparisons in peak-shave and price-threshold against the thresholds are strict where written: a demand exactly on a threshold requests nothing. The peak demand the CLI derives the peak-shave thresholds from is the case's total load times the largest load factor of the run (chain) or of the series (gda-replay). hold reads the SoC at the start of the step, so a step long enough to move the SoC across the whole band swings it either side of the band; it keeps the SoC where a response service could be delivered and does not deliver the service.

Which policy is reachable from which verb. --prices is accepted on dcopf, acopf and chain with --bess; any other verb refuses it (error: --prices applies to dcopf, acopf and chain (with --bess) only (got '<verb>')., exit 2). On chain it takes a value: synthetic (the SyntheticPrices.GbDay day, one value per step) or a price file; a bare --prices is refused. With prices and no --policy, the policy is lp.

Policy gridsim chain gridsim gda-replay
idle --policy idle --policy idle
peak-shave the default without prices; --shave-high, --shave-low the default; the same flags
hold --policy hold --policy hold
price with --prices; without it refused (--policy price needs --prices ..., exit 2) refused: gda-replay takes no price series (exit 2)
lp the default with --prices; without it refused (--policy lp needs --prices, exit 2) refused, as price

A storage flag (--prices, --policy, --shave-high, --shave-low, --buy-below, --sell-above, --degradation-gbp-per-mwh, --step-hours) on chain without --bess exits 2. Each --bess chemistry:bus:MW:MWh[:soc] spec is checked field by field (StorageCli.ParseBessSpec): four or five fields, a known chemistry, an integer bus, MW and MWh finite and above 0, the starting state of charge (when given) from 0 to 1; each refusal names the spec and the field (exit 2). A price file that is missing, unreadable or malformed exits 1.

Optimal schedule: linear programme (StorageLpScheduler)

StorageLpScheduler.Solve(env, prices, stepHours, w = 0, endEnergyMwh = null) plans a net MW schedule over a price series. With T steps, dt = stepHours and unknowns discharge d_t and charge c_t (AC MW) and stored energy e_t (MWh), laid out as [d_0..d_T-1, c_0..c_T-1, e_0..e_T-1]:

minimise    sum_t [ (-price_t + w) d_t + (price_t + w) c_t ] dt            w = degradation GBP/MWh of throughput
subject to  e_t - e_{t-1} + d_t dt / eta_d - c_t dt eta_c = 0              e_{-1} = EnergyNow (moved to the right-hand side)
            0 <= d_t <= Dmax        0 <= c_t <= Cmax
            Emin <= e_t <= Emax
            e_{T-1} >= e_end        e_end = clamp(endEnergyMwh ?? EnergyNow, Emin, Emax)

That is T equality rows over 3T bounded variables. BoundedSimplex.Solve(a, b, cost, lo, hi) (src/GridSim.Core/Numerics/BoundedSimplex.cs) is a dense two-phase bounded-variable primal simplex that returns an LpStatus (Optimal, Infeasible, Unbounded, IterationLimit), the vector and the objective. The plan is NetMw[t] = d_t - c_t, EnergyMwh[t] = e_t and ObjectiveGbp = -objective, the price revenue less the degradation cost. With no steps the plan is empty and Optimal. The default end energy is the starting energy, so the schedule returns the battery to where it started.

Envelope linearisation. The LP is linear, the pack is not. StorageEnvelope.FromPack(pack, ratedMw, eta, stepHours) reduces the pack to constants:

mid       = a pack of the same chemistry and size at SoC 0.5, no ageing tracking
sop       = mid.StateOfPower(min(stepHours * 3600, 1800) s, substeps = 20)           W, discharge and charge
Dmax      = min(ratedMw, sopDis * eta / 1e6)          Cmax = min(ratedMw, sopChg / eta / 1e6)
wh        = Q(fade) * Np * Ns * Vnom_cell                                            Wh per unit SoC
Emin, Emax, EnergyNow = SocMin * wh / 1e6, SocMax * wh / 1e6, SoC * wh / 1e6         MWh
iRated    = max(1e-9, Dmax * 1e6 / eta / (Ns * Np) / max(E_mid, 1e-6))               rated per-cell current, A
cellEta   = clamp(1 - iRated * R0_mid / E_mid, 0.5, 1)
eta_d     = eta * cellEta                              eta_c = eta * cellEta * CE

E_mid and R0_mid are the internal emf and series resistance of the mid-SoC pack. The power limits are therefore the sustained state of power at mid SoC, so a pack that starts empty or full does not shrink the whole plan's limits. The efficiencies are the converter times the chemistry's own resistive loss at the planned rate. Envelope for 5 MW / 10 MWh at SoC 0.5, converter 0.98, step 0.5 h, from docs/_captures/bess/api-probe-envelope.txt:

$ API probe (GridSim.Core, Release build): envelope
chemistry   MaxDis_MW MaxChg_MW  Emin_MWh  Emax_MWh  Enow_MWh  eta_d    eta_c
LFP           5.0000    5.0000    0.5601   10.6417    5.6009  0.97050  0.96565
NMC           5.0000    5.0000    0.5513   10.4754    5.5134  0.97271  0.97076
LTO           5.0000    5.0000    0.3188   10.3066    5.3127  0.97509  0.97411
Na-ion        5.0000    5.0000    0.3172   10.2565    5.2869  0.96658  0.95691
VRFB          1.8169    2.3581    2.0992   11.8952    6.9972  0.86872  0.84266
Lead-acid     3.3572    2.7380    2.5990   12.7349    6.4974  0.93805  0.84425
[exit 0]

The flow battery and lead-acid are limited by their state of power below the 5 MW rating, which a 0.25C and 0.3C battery-management limit and the rate effect produce. The plan is linear and execution is through the chemistry: SchedulePolicy hands the plan's net MW to the pack step by step, so the tracking error and clipped steps show where the envelope and the battery differ. Round trip and rainflow are measured on the execution, not the plan.

Status. The CLI wraps the plan in OptimalLpPlan: any status other than Optimal raises InvalidOperationException("--policy lp: the storage schedule LP did not solve (status ...); no schedule to run."). A meaningless vector is never run as if it were the schedule.

No complementarity. The LP has no constraint that stops charging and discharging in the same step. When a later charge repays the degradation cost of throughput that only dissipates energy, the plan can charge and discharge together, and its energy trajectory then describes a path the net schedule does not follow. A full battery at a negative price shows it (docs/_captures/bess/api-probe-lp.txt): with w = 0 the net MW is zero for three steps while the stored energy falls from 10.0816 MWh to 9.5960 MWh, then charges 2.3438 MW in step 3. With w = 5 the plan charges once and holds.

$ API probe (GridSim.Core, Release build): lp
LFP 5 MW/10 MWh, SoC 0.9, price -10 x4, w=0: status=Optimal
  net_MW  = 0.0000 0.0000 0.0000 -2.3438
  e_MWh   = 9.9198 9.7579 9.5960 10.6417   (Emax 10.6417, now 10.0816)
LFP 5 MW/10 MWh, SoC 0.9, price -10 x4, w=5: status=Optimal
  net_MW  = -1.1600 0.0000 0.0000 0.0000
  e_MWh   = 10.6417 10.6417 10.6417 10.6417   (Emax 10.6417, now 10.0816)
...
[exit 0]

On the synthetic GB day (48 steps of 0.5 h, NMC 5 MW / 10 MWh at SoC 0.5, w = 0) the same probe gives status Optimal, an objective of GBP 1193.44, 11 charge steps and 8 discharge steps, and an end energy equal to the start energy 5.5134 MWh.

Time series: fleet and network (StorageFleet, StorageTimeSeries)

StorageFleet carries the sites of a sequential study. Each site is a StorageSite: name <chem> <MW>MW/<MWh>MWh @<bus> (MW and MWh with no decimals), bus, rated MW, pack, policy and converter efficiency (default 0.98). The fleet runs, per step:

  1. Request. The site's policy gets the DispatchContext and the request is clamped to [-RatedMw, RatedMw].
  2. Substeps. The step is split into 30 substeps (DefaultSubstepsPerStep) of subDt = stepHours * 3600 / 30 s. Each calls BatteryDcSource.Draw(request, subDt). The fleet sums the delivered MW and the auxiliary MW over the substeps, divides by 30 for the step means, and records the SoC after every substep for rainflow. The first substep that is Limited names the step's limit reason.
  3. Books. out += max(delivered, 0) * h, in += max(-delivered, 0) * h, aux += aux * h, and, only when the price is not NaN, revenue += price * (delivered - aux) * h. The SiteStepRecord carries the request, the mean delivered MW, the mean auxiliary MW, and the SoC, temperature and capacity fade at the end of the step.
  4. Inject. Apply(model) adds, for each site, a generator at the site's bus with Pg = delivered, Qg = 0, Qmin = Qmax = 0, Pmin = -RatedMw, Pmax = RatedMw, MBase = RatedMw, type storage, converter interfaced. It adds the auxiliary MW to the bus demand Pd. The storage generator is appended after the case's generators and its Vg is the setpoint the bus already has: the existing generators' Vg by the shared VoltageSetpoint rule, else the bus's stored Vm. A site never moves a regulated bus's voltage. A storage site delivers real power only.

StorageTimeSeries.Run(baseModel, sites, spec, solver, options) drives the fleet:

hour    = (StartHour + step * StepHours) mod 24
m       = GridScenario.AtLoad(baseModel, LoadFactor(step))              scales Pd, Qd and non-slack Pg; rebalances
demand  = sum of m.Buses.Pd                                             before the battery's auxiliary load
records = fleet.Advance(step, hour, StepHours, demand, price)           price NaN without a series
model   = fleet.Apply(m), warm-started from the last converged step     GridScenario.WithSolvedVoltages
pf      = solver.Solve(model, options)
slackMw = pf.PInjMw[slack] + Pd[slack]                                  NaN when no slack bus

Only a converged solve becomes the next warm start. A step that does not converge is recorded with Converged = false and Vmin, Vmax NaN; the CLI prints - in its slack and voltage columns and exits 3. Without options the run solves with 100 iterations and reactive limits enforced. The chain verb passes ContingencyAnalysis.StudyOptions and wraps its solver in the on-load tap-changer loop, so each step solves exactly as plain chain does. Without tap-changer records in the case the loop returns the engine's answer to the bit (S4SolverConvergenceTests).

Validation is StorageFleet.Validate(model): every site's bus must be in the model, else ArgumentException("storage site '<name>' is at unknown bus N."). StorageTimeSeries.Run and LiveSim call it at construction; GdaReplayLoop.Replay calls it at its start. Apply throws InvalidOperationException for a site whose bus is missing from the model it is given. Nothing else range-checks a site. CellModel clamps the starting SoC to [0, 1]; BatteryDcSource refuses an eta outside [0.5, 1]; PackModel needs positive cell counts, which Sized guarantees; LookupTable rejects fewer than two points and non-ascending x; BatteryChemistryLibrary.ByName rejects an unknown name. A zero or negative energy sizes one string (the report of a zero-energy pack shows maximum power transfer, docs/_captures/bess/chain-zero-mwh.txt), a zero rating delivers nothing, and a negative rating fails in the request clamp (docs/_captures/bess/chain-negative-mw.txt).

Entry points and step length.

Entry point Step length Hour seen by the policy Price Policy flags
chain (StorageCli.Run) --step-hours, else 24 / steps in daily mode, else 0.5 (step * StepHours) mod 24 none (see reachability) idle, peak-shave, price, hold, lp parsed; see the reachability table
gda-replay (GdaReplayLoop.Replay) the gap to the next timestamp; the last step reuses the previous gap; a one-step series uses 0.5; floored at 1e-6 h the UTC clock time of the timestamp NaN idle, peak-shave, hold
LiveSim the tick length in minutes over 60 the tick's hour of day NaN set by the caller

gda-replay takes no --step-hours flag; its step length is read from the series. The replay result is tagged ProvenanceTag.Counterfactual, a plain reconstruction stays DerivedFromRecorded, and the CLI prints and writes it as a counterfactual (storage-counterfactual.csv). The counterfactual CSV is not a time-series file that --series reads, so it cannot feed another replay (ch. 22, ch. 9).

Outputs. chain writes results/chain-storage-<case>.md and .csv; gda-replay writes storage-counterfactual.csv beside state-estimate.csv. The columns are documented in ch. 13.

Price data

SyntheticPrices.GbDay(hour) is a synthetic GB-shaped price day in GBP/MWh, synthetic in the sense of ProvenanceTag.Synthetic, and labelled Synthetic GB-shaped price day (not a market record). It is a shape for exercising dispatch logic, never a market record. With h = ((hour mod 24) + 24) mod 24:

bump(c, w, a) = a * exp(-0.5 * ((h - c) / w)^2)
GbDay(h) = 45 + bump(8, 1.5, 35) - bump(13, 2, 20) + bump(18, 1.5, 85)

The overnight base is 45, the morning ramp adds 35 at 08:00, the solar dip removes 20 at 13:00 and the evening peak adds 85 at 18:00. GbDay(0) = 45.00, GbDay(8) = 79.12, GbDay(13) = 25.46, GbDay(18) = 129.12.

A price file in StorageCli.Run is read line by line. Blank lines and lines whose first non-blank character is # are skipped. Each other line contributes the last comma-separated field, which must be a finite number in invariant culture (negative prices are allowed); anything else is refused naming the line (PriceFileException, exit 1), a header line included. The file needs at least one value per step, else --prices <file> has N values; S steps need one each. (exit 1); extra values are ignored with a note: on stderr. The report says prices: file <name>, or prices: Synthetic GB-shaped price day (not a market record). for the synthetic day.

Behind the inverter and behind the RMS converter

The grid-following and grid-forming inverter assets draw through an IDcSource:

  • SocBucket is the linear store: SoC -= P dt / 3600 / capacity, no losses, no rate limit, headroom closed only at the SoC bounds. Every run without a chemistry is arithmetically the bucket.
  • BatteryDcSource is a pack behind a converter (above). Its headroom is the pack's instantaneous battery-management limit, and a draw steps the pack. Reset restores the pack from a clone made without ageing tracking, and the asset-frequency integrators (AssetFrequencyDynamics, AssetAwareFrequencyIntegrator) reset the fleet at the start of every run, so a pack behind an inverter asset does not accumulate capacity fade or resistance growth. The StorageFleet sites do.

An asset class selects the model with the parameters batteryChemistry (1 LFP, 2 NMC, 3 LTO, 4 Na-ion, 5 VRFB, 6 lead-acid), capacityMwh (the nominal energy the pack is sized to) and optionally dcVoltageV (default 1000), converterEfficiency (default 0.98) and ambientC (default 25). With capacityMwh set and no chemistry the class gets a SocBucket between socMin and socMax; with capacityMwh unset or zero it has no store, whatever batteryChemistry says. The rated power of the pack is the inverter's rating. A 2 MW / 1 MWh frequency-response service at full droop is held by NMC between 1.85 and 2.0 MW, held by LFP at the 1C limit (0.9 to 1.15 MW), and stops at the SoC floor after 20 to 30 minutes having delivered 0.70 to 0.90 MWh (BatteryAssetTests). The grid-side control law is in ch. 13, Asset dynamics and ch. 24, Standard dynamic model library.

RmsConverterUnit.Store puts an IDcSource (MW, with BaseMva) behind an RMS converter. The store's instantaneous headroom caps the active current of a grid-following unit (ipRef clamped to -Down / BaseMva / V and Up / BaseMva / V) and the power reference of a grid-forming unit. Each step then draws the active power the converter injects. For a grid-following unit that is |V| * Ip * Lvacm(|V|) * BaseMva at the start-of-step terminal voltage, and a shortfall scales Ip so the injection equals what the store delivered; a grid-forming unit draws Pe * BaseMva. A depleted, cold or hot pack cannot sustain its output. Reactive current (ride-through support) is not drawn from the store. A 50 MW converter on a 30 MWh NMC pack at 7 % SoC holds 0.5 pu for 10 s, falls below 0.01 pu by 120 s with the store at its SoC floor, and still gives more than 0.5 pu of reactive current in a later dip (RmsConverterTests). Store is an API option: SubtransientInit does not attach one, so gridsim stability --rms runs without it.

Parameters and defaults

The six presets are in src/GridSim.Core/Storage/BatteryChemistryLibrary.cs. ByName matches case-insensitively and accepts the aliases sodium-ion, naion, sib (Na-ion), flow, vanadium (VRFB) and lead, vrla (lead-acid). All values are per cell. The source symbol is the ChemistryParameters property.

Scalar constants per chemistry

Parameter (source symbol) Unit LFP NMC LTO Na-ion VRFB Lead-acid
Rated capacity (CapacityAh) Ah 280 64 30 160 1000 1000
Nominal voltage (NominalVoltage, OCV at 50 %) V 3.29 3.78 2.30 3.10 1.40 2.04
Nominal cell energy (NominalEnergyWh) Wh 824.40 219.10 64.87 466.73 980.00 1603.84
Fast pair (R1, Tau1) mOhm, s 0.12, 10 0.55, 8 0.25, 5 0.30, 8 0.30, 2 0.20, 30
Slow pair (R2, Tau2) mOhm, s 0.18, 400 0.75, 300 0.30, 150 0.40, 300 0.20, 60 0.30, 1200
Resistance activation energy (ResistanceActivationEnergy) J/mol 32000 35000 25000 20000 15000 25000
Entropic coefficient (EntropicCoefficient, constant) mV/K -0.05 -0.10 0 0 0 0
Coulombic efficiency (CoulombicEfficiency) fraction 0.995 0.998 0.999 0.99 0.97 0.90
Self-discharge (SelfDischargePerMonth) fraction per 30 d 0.03 0.02 0.01 0.03 0.02 0.03
Peukert exponent, reference (PeukertExponent, PeukertReferenceCRate) -, C 1, 0.1 1, 0.1 1, 0.1 1, 0.1 1, 0.1 1.15, 0.1
Cut-off, charge voltage (VMin, VMax) V 2.5, 3.65 3.0, 4.2 1.5, 2.8 2.0, 3.95 1.10, 1.65 1.75, 2.40
Max discharge, charge rate (MaxDischargeCRate, MaxChargeCRate) C 1.0, 0.5 2.0, 1.0 6.0, 6.0 2.0, 1.0 0.25, 0.25 0.3, 0.2
SoC window (SocMin, SocMax) fraction 0.05, 0.95 0.05, 0.95 0.03, 0.97 0.03, 0.97 0.15, 0.85 0.20, 0.98
Derate start, limit (TDerateC, TMaxC) C 45, 55 40, 50 50, 60 45, 55 38, 45 40, 50
Minimum charge temperature (TMinChargeC) C 0 5 -20 -10 5 -10
Cell mass (MassKg) kg 5.4 0.9 1.0 3.0 45 60
Specific heat (SpecificHeat) J/kg/K 1100 1000 1000 1050 3000 800
Passive cooling (PassiveCoolingWPerK) W/K per cell 0.08 0.02 0.03 0.06 0.4 0.5

ChemistryParameters defaults for any field a preset leaves out: ResistanceActivationEnergy 30000, CoulombicEfficiency 0.998, SelfDischargePerMonth 0.02, PeukertExponent 1, PeukertReferenceCRate 0.1, SocMin 0.05, SocMax 0.95, TDerateC 45, TMaxC 55, TMinChargeC 0, SpecificHeat 1000, PassiveCoolingWPerK 0.05, entropic coefficient 0.

Ageing constants per chemistry (AgeingParameters)

Parameter (source symbol) Unit LFP NMC LTO Na-ion VRFB Lead-acid
Calendar fade (CalendarFadePerSqrtDay, k_cal) per sqrt day 0.0010 0.0016 0.0005 0.0014 0.0002 0.0025
Calendar activation energy (CalendarActivationEnergy, E_cal) J/mol 50000 55000 50000 50000 50000 50000
Calendar SoC sensitivity (CalendarSocSensitivity, a_soc) - 0.6 0.6 0.6 0.6 0.6 0.6
Cycles to 80 % (CyclesTo80Percent, N80) cycles 6000 3500 20000 4000 20000 1200
Cycle activation energy (CycleActivationEnergy, E_cyc) J/mol 30000 30000 30000 30000 30000 30000
C-rate sensitivity (CRateSensitivity) - 0.25 0.35 0.05 0.3 0 0.3
Depth exponent (DodExponent, beta) - 1.3 1.3 1.3 1.3 1.3 1.6
Resistance growth (ResistanceGrowthPerFade, g) per unit fade 2.5 2.5 2.5 2.5 2.5 2.5

AgeingParameters defaults: CalendarFadePerSqrtDay 0.0012, CalendarActivationEnergy 50000, CalendarSocSensitivity 0.6, CyclesTo80Percent 6000, CycleActivationEnergy 30000, CRateSensitivity 0.3, DodExponent 1.3, ResistanceGrowthPerFade 2.5.

Auxiliary constants per chemistry (AuxiliaryModel)

Parameter (source symbol) Unit LFP NMC LTO Na-ion VRFB Lead-acid
Standby (StandbyFraction) of rated power 0.002 0.002 0.002 0.002 0.003 0.001
HVAC coefficient of performance (HvacCop) - 3.0 3.0 3.0 3.0 0 0
HVAC setpoint (HvacSetpointC) C 30 28 35 30 not used not used
HVAC capacity (HvacCapacityFraction) of rated power 0.05 0.06 0.08 0.05 not used not used
Pump (PumpFraction) of power moved 0 0 0 0 0.04 0

AuxiliaryModel defaults: StandbyFraction 0.002, HvacCop 3.0, HvacSetpointC 30, HvacCapacityFraction 0.05, PumpFraction 0.

Open-circuit-voltage and resistance tables

OCV in V on the SoC grid 0, 0.05, 0.10, 0.20, 0.30, 0.40, 0.50, 0.60, 0.70, 0.80, 0.90, 0.95, 1.0 (BatteryChemistryLibrary.Ocv):

Chemistry OCV at the 13 grid points
LFP 2.50, 3.00, 3.17, 3.22, 3.25, 3.27, 3.29, 3.30, 3.31, 3.33, 3.34, 3.36, 3.45
NMC 3.00, 3.45, 3.55, 3.62, 3.66, 3.72, 3.78, 3.86, 3.94, 4.02, 4.10, 4.14, 4.20
LTO 1.50, 2.00, 2.15, 2.22, 2.25, 2.28, 2.30, 2.33, 2.36, 2.40, 2.46, 2.52, 2.80
Na-ion 2.00, 2.50, 2.70, 2.85, 2.95, 3.03, 3.10, 3.18, 3.27, 3.38, 3.52, 3.62, 3.90
Lead-acid linear from 1.95 at SoC 0 to 2.13 at SoC 1 (two points)

The VRFB curve is the Nernst equation E = 1.40 + (2 Rg Tref / F) * ln(s / (1 - s)) with F = 96485.332 and s clamped to [0.01, 0.99], tabulated at SoC 0, 0.02, 0.05, 0.10, 0.15, 0.25, 0.35, 0.50, 0.65, 0.75, 0.85, 0.90, 0.95, 0.98, 1.0 (from docs/_captures/bess/api-probe-vrfb.txt):

$ API probe (GridSim.Core, Release build): vrfb
VRFB OCV (SoC:V): 0.00:1.1639 0.02:1.2000 0.05:1.2487 0.10:1.2871 0.15:1.3109 0.25:1.3435 0.35:1.3682 0.50:1.4000 0.65:1.4318 0.75:1.4565 0.85:1.4891 0.90:1.5129 0.95:1.5513 0.98:1.6000 1.00:1.6361
[exit 0]

R0 at 25 C in mOhm:

Chemistry SoC grid R0
LFP 0, 0.1, 0.5, 0.9, 1.0 0.45, 0.30, 0.25, 0.27, 0.35
NMC 0, 0.1, 0.5, 0.9, 1.0 1.6, 1.1, 0.95, 1.0, 1.2
Na-ion 0, 0.1, 0.5, 0.9, 1.0 0.9, 0.65, 0.55, 0.6, 0.75
Lead-acid 0, 0.2, 1.0 0.6, 0.35, 0.3
LTO constant 0.8
VRFB constant 1.2

Preset character

Preset Character
LFP (280 Ah) flat OCV plateau, 1C energy-storage rating, 6000 cycles, thermally robust
NMC (64 Ah) sloped OCV, 2C, higher energy density, 3500 cycles, more temperature-sensitive
LTO (30 Ah) low voltage, 6C for fast frequency-response duty, 20000 cycles, charges down to -20 C
Na-ion (160 Ah) sloped OCV, 2C, lower activation energy so it keeps power in the cold, cycle life still maturing
VRFB (1000 Ah tank share per cell) Nernst OCV, 0.25C, 15 to 85 % window, pumps 4 % of the power moved, lowest cycle fade of the six in the daily comparison (0.0006 %), CRateSensitivity 0
Lead-acid (1000 Ah, 2 V) near-linear OCV, Peukert 1.15, 90 % coulombic efficiency, 1200 cycles, deeper-cycle exponent 1.6

Model and CLI constants

Name Value Unit Meaning Source symbol
Gas constant 8.314462618 J/mol/K Arrhenius laws ChemistryParameters.GasConstant
Reference temperature 298.15 K 25 C reference of every Arrhenius law ChemistryParameters.TRefK
Celsius offset 273.15 K C to K ChemistryParameters.Kelvin0
Self-discharge month 30 days the "month" the self-discharge rate is quoted per CellModel.SelfDischargeMonthDays
End-of-life fade 0.2 fraction fade that defines N80 AgeingModel.EndOfLifeFade
Fade cap 0.8 fraction cap on the fade written to the cell AgeingModel.MaxCapacityFade
Minimum SoC stress 0.05 - floor on the calendar SoC factor AgeingModel.MinSocStressFactor
SoC stress reference 0.5 - SoC where the factor is 1 AgeingModel.SocStressReference
Seconds per day 86400 s calendar law is in sqrt days AgeingModel.SecondsPerDay
Throughput per full cycle 2 capacities charge plus discharge AgeingModel.ThroughputPerFullCycle
Divisor guard 1e-9 - floors on the derate span and coulombic efficiency PackModel.DivisorGuard
SoC edge proximity 1e-3 SoC within this counts as at the edge when naming a limit PackModel.SocEdgeProximity
Limit match tolerance 1e-9 A two currents this close are the same limit PackModel.LimitMatchToleranceA
Limited tolerance 1e-6 of max(1 W, request) a shortfall below this is not reported PackModel.LimitedRelativeTolerance
State-of-power search ceiling 20 C upper bound of the bisection, times nominal energy PackModel.MaxSearchCRate
State-of-power probe 1 W a pack that cannot sustain this has zero state of power PackModel.ProbePowerW
Bisection iterations 50 - cap PackModel.MaxBisectionIterations
Bisection tolerance 1e-4 of max(1 W, hi) bracket width that stops it PackModel.BisectionRelativeTolerance
Planning SoC 0.5 SoC the envelope's operating point StorageEnvelope.PlanningSoc
Planning horizon cap 1800 s cap on the envelope's state-of-power horizon StorageEnvelope.MaxSopHorizonSeconds
Envelope substeps 20 - substeps of that simulation StorageEnvelope.SopSubsteps
Rated cell current floor 1e-9 A floor in the cell-efficiency estimate StorageEnvelope.MinRatedCellCurrentA
Cell emf floor 1e-6 V floor where the emf divides StorageEnvelope.MinCellEmfV
Cell efficiency floor 0.5 - lower clamp on cellEta StorageEnvelope.MinCellEfficiency
Substeps per step 30 - pack substeps per network step StorageFleet.DefaultSubstepsPerStep
Power-flow iterations 100 - default Newton cap of a storage step StorageTimeSeries.DefaultMaxIterations
Converter efficiency 0.98 - one way; default of StorageSite and BatteryDcSource BatteryDcSource.DefaultConverterEfficiency, StorageCli.DefaultConverterEfficiency
Converter efficiency floor 0.5 - lowest accepted value BatteryDcSource.MinConverterEfficiency
Step length 0.5 h non-daily chain modes and gda-replay single-step series StorageCli.DefaultStepHours, LiveSolveSettings.GdaSingleStepHours
Replay step floor 1e-6 h no zero-length replay step LiveSolveSettings.GdaMinStepHours
Initial SoC 0.5 SoC when the --bess spec gives none StorageCli.DefaultInitialSoc
Pack DC voltage 1000 V sizes the series count StorageCli.DefaultPackDcVoltage
Peak-shave thresholds 0.9, 0.7 of peak demand high and low StorageCli.PeakShaveHighFraction, StorageCli.PeakShaveLowFraction
Price thresholds 40, 90 GBP/MWh buy below, sell above StorageCli.DefaultBuyBelowGbpPerMwh, StorageCli.DefaultSellAboveGbpPerMwh
Simplex tolerance, iteration cap 1e-9, 20000 - BoundedSimplex defaults BoundedSimplex.DefaultTolerance, BoundedSimplex.DefaultMaxIterations

Invariants

Every invariant below is pinned by the named test, in tests/GridSim.Tests/.

Invariant Test
Delivered charge to cut-off falls with discharge rate for every chemistry, and a C/20 discharge delivers more than 85 % of Q * SocMax StorageChemistryTests.Delivered_charge_falls_with_discharge_rate (theory over all six presets)
The two RC voltages relax on their time constants, V1 * exp(-1) and V2 * exp(-tau1/tau2) after one tau1 at rest, to 12 decimals StorageChemistryTests.Rc_pairs_relax_on_their_time_constants
Energy balances over a discharge with the entropic coefficient set to zero and the temperature held at 25 C: integral(OCV I) = integral(P) + heat + stored RC energy, residual below 1e-3 of the OCV energy StorageChemistryTests.Energy_balance_closes_over_a_discharge
Cell heating scales with I^2: the temperature rise at 2C over 1C lies in 3.6 to 4.2 StorageChemistryTests.Cell_heat_scales_with_current_squared
A 10 s pulse exceeds a 30 minute delivery for LFP and NMC, NMC's pulse exceeds 1.5 times LFP's, NMC's 30 minute power exceeds LFP's, and NMC's 30 minute delivery at 0.8 SoC never exceeds the energy above the SoC floor (within 2 %) StorageChemistryTests.Pulse_power_exceeds_sustained_power_and_nmc_out_powers_lfp_on_both
Na-ion keeps a larger fraction of its 10 s power at -10 C than NMC StorageChemistryTests.Sodium_ion_keeps_more_power_in_the_cold_than_nmc
Lead-acid at 0.3C delivers a smaller fraction of its C/20 charge than LFP at 1C, by more than 0.05 StorageChemistryTests.Lead_acid_loses_capacity_at_rate_far_more_than_lfp
NMC charging at -5 C is blocked: Limited, reason too cold to charge, zero DC power StorageChemistryTests.Charging_is_blocked_below_the_minimum_charge_temperature
A flow battery's pumps draw PumpFraction of the power moved (4 % of 200 kW) on top of the standby load, and the step is not limited StorageChemistryTests.Flow_battery_pumps_draw_a_share_of_the_power_moved
Rainflow reproduces the ASTM E1049-85 worked example: ranges 3 (0.5), 4 (1.5), 6 (0.5), 8 (1.0), 9 (0.5) StorageChemistryTests.Rainflow_matches_the_astm_e1049_example
Calendar fade is step-size independent (1 step against 365 steps agree to 10 decimals), equals k_cal * sqrt(365) at 25 C and 50 % SoC to 12 decimals, and 40 C ages more than twice as fast as 25 C StorageChemistryTests.Calendar_fade_integrates_consistently_and_accelerates_with_heat
Every preset is CuratedPlaceholder and its note contains [VERIFY] StorageChemistryTests.Presets_are_curated_placeholders_with_verify_notes
A peak-shaving day converges at every step, keeps SoC within [SocMin - self-discharge per day, SocMax], discharges only above the high threshold and charges only below the low one (checked for deliveries above 1 MW), and the slack relief equals the delivered power less auxiliary within 5 % StorageTimeSeriesTests.Peak_shaving_day_relieves_the_slack_and_keeps_soc_in_its_window (IEEE 118, 100 MW / 200 MWh LFP, 48 steps)
The LP plan is Optimal, discharges only in the dear half, charges only in the cheap half, and executes within 10 % of the planned revenue and 5 MW of tracking error StorageTimeSeriesTests.Lp_arbitrage_plan_buys_low_sells_high_and_survives_execution_through_the_chemistry
Energy books close: round trip in 0.85 to 0.97, out <= in + max(0, -storedChange), the deepest rainflow cycle in 0.2 to 0.95, and calendar and rainflow fade are positive StorageTimeSeriesTests.Energy_books_close_with_a_plausible_round_trip_and_rainflow_counts_the_daily_cycle
The live loop carries storage state across 24 hours, converges every tick, moves SoC by at most one tick's worth, and the solved model contains the storage generator at its delivered output StorageLoopTests.Live_loop_carries_storage_state_across_a_day
LiveSim without storage is unchanged: Storage is null and the voltages are equal StorageLoopTests.Live_loop_without_storage_is_unchanged
A replay with storage is tagged Counterfactual, a plain replay stays DerivedFromRecorded, and the counterfactual carries 48 step records StorageLoopTests.Replay_with_hypothetical_storage_is_counterfactual
A storage site on a regulated bus keeps the bus's existing Vg (1.04), and on a bus without a generator takes the bus Vm PowerFlowPhysicsConsistencyTests.Storage_on_a_regulated_bus_keeps_the_existing_setpoint, Storage_on_a_bus_without_a_generator_takes_the_bus_voltage
An NMC pack behind a 2 MW inverter holds the service, LFP is limited at 1C, delivery stops at the SoC floor, Reset restores the pack, and the bucket path is unchanged BatteryAssetTests (four tests)
An RMS converter's store sustains active power until empty and not the reactive support RmsConverterTests.Energy_store_sustains_the_active_power_until_it_is_empty_but_not_the_reactive_support
chain --bess passes the study option set and the tap-changer loop (a source-text check of Program.cs and StorageCli.cs), and without tap-changers is bit-identical to the raw engine on IEEE 118 (a behavioural check of Vmin, Vmax, slack and loss) S4SolverConvergenceTests.N084_chain_bess_passes_the_study_set_and_the_oltc_loop_to_the_storage_time_series, N084_without_oltcs_the_storage_chain_is_unchanged_to_the_bit
The named constants equal the literals they replaced (ageing, cell, pack, envelope, fleet, time series) Ws13CoreConstantsAntiDriftTests.Simulation_and_storage_constants_equal_the_literals_they_replaced
The CLI storage defaults are named and gda-replay reuses the step length CliLiteralsAndFlagsContractTests.Storage_defaults_are_named_and_reused_by_gda_replay

The tests build IdlePolicy, PeakShavePolicy and SchedulePolicy (with an lp plan from an explicit price array) and nothing else. Stated in this chapter with no dedicated test: the exact limit-reason order and matching tolerances, the asymmetric converter formulas, the price-threshold and response-holding policies, the peak-shave thresholds as formulas (the peak-shave behaviour is covered by the time-series test), the round-trip and EFC formulas as exact expressions, the OptimalLpPlan status check, SyntheticPrices.GbDay, the price-file reader and the StorageFleet.Validate message. They are read from the source named in the source map.

Determinism

A storage run is sequential and has no random input and no clock input. Sites are processed in --bess order, every loop has a fixed bound or a fixed iteration cap (30 substeps, 50 bisection iterations, the simplex iteration cap), the simplex breaks ratio-test ties by the first row, and the CLI sets the invariant culture for the whole process (Program.cs, CultureInfo.CurrentCulture), which is how numbers are formatted. The same inputs give the same outputs run to run, and the CLI report carries no timings, so the same command prints the same text. The network solves underneath are the validated Newton engines of ch. 3, Power flow with their bit-identity contract. S4SolverConvergenceTests compares two storage configurations bit for bit; no test repeats a storage run and compares the bits across CPUs.

Worked example

The run is a 5 MW / 10 MWh LFP battery at bus 5 of case9 over the 24 h demand day in six 4 h steps, shaving the peak. The case has 315 MW of load, so the thresholds are 283.5 MW and 220.5 MW. The timings and stamps of any output differ by machine and run; this report holds none.

$ gridsim chain case9 --mode daily --steps 6 --bess lfp:5:5:10 --policy peak-shave
GridSim - storage time series  *  case9  *  6 x 4 h  *  mode=daily  *  policy=peak-shave
prices: none.  Chemistry presets are CuratedPlaceholder [VERIFY] (representative cells).

...
|---:|---:|---:|---:|---:|---|---:|---:|:-:|
| 0 | 0.0 | 0.700 | 220 | - |     0.0 / 0.500 / 25.0 | 49 | 1.024 | y |
| 1 | 4.0 | 0.600 | 189 | - |    -1.3 / 0.950 / 29.4 (SoC ceiling) | 43 | 1.025 | y |
| 2 | 8.0 | 0.700 | 220 | - |     0.0 / 0.950 / 28.6 | 49 | 1.024 | y |
| 3 | 12.0 | 0.900 | 283 | - |     0.0 / 0.950 / 28.0 | 64 | 1.005 | y |
| 4 | 16.0 | 1.000 | 315 | - |     2.4 / 0.050 / 29.6 (SoC floor) | 69 | 0.996 | y |
| 5 | 20.0 | 0.900 | 284 | - |     0.0 / 0.050 / 28.8 | 64 | 1.005 | y |

LFP 5MW/10MWh @5: out 9.7 MWh, in 5.3 MWh, aux 0.27 MWh, stored change -5.0 MWh, round trip 93.5 %, 0.75 equivalent full cycles
    ageing over the run: calendar 0.1372 %, cycle 0.0026 % (rainflow, depth-aware: 0.0020 %), deepest cycle 90 % SoC
[chain] done -> results\chain-storage-case9.md
[exit 0]

The same run's CSV, docs/_captures/bess/chain-csv-head.txt, holds the numbers to six significant figures (StorageCli.cs, F(v) is ToString("G6"); NaN is an empty field):

$ head -4 results/bess-demo.csv
step,hour,load_factor,demand_mw,price,s0_request_mw,s0_delivered_mw,s0_aux_mw,s0_soc,s0_temp_c,s0_fade,s0_limited,slack_mw,vmin,vmax,loss_mw,converged
0,0,0.7,220.5,,0,0,0.01,0.499833,25,0.000408227,0,49.0992,1.02356,1.04076,2.18915,1
1,4,0.6,189,,-5,-1.32387,0.0109119,0.949994,29.3712,0.000796927,1,43.1443,1.025,1.04385,1.60956,1
2,8,0.7,220.5,,0,0,0.01,0.949828,28.5984,0.0010474,0,49.0992,1.02356,1.04076,2.18915,1
[exit 0]

Step 0: idle at the threshold, closed form

Step 0 has a demand of 220.5 MW, exactly the low threshold, and the comparison is strict, so the request is 0. Over 4 h the SoC falls only by self-discharge: 0.03 / 30 * (4 / 24) = 0.000166667, so 0.5 - 0.000166667 = 0.499833, the CSV's s0_soc. The auxiliary power is the standby load, 0.002 * 5 MW = 0.01 MW, the CSV's s0_aux_mw. The calendar fade at 25 C and SoC 0.5 is 0.001 * sqrt(4 / 24) = 0.000408248 as a single step; the 30 substeps give 0.000408227 (the CSV's s0_fade) because the SoC factor 1 + 0.6 * (SoC - 0.5) is below 1 as the SoC drifts down by 1.7e-4.

Step 1: the charge step by hand

The re-computation below is an independent implementation of the equations in this chapter, in docs/_captures/bess/hand-recompute-chain-lfp-step1.txt (the first of 30 substeps), against the CSV's step 1. The pack is Ns = 304, Np = 40, 12160 cells, 10.02466 MWh nominal.

$ python hand.py   (independent re-computation of step 1 of: gridsim chain case9 --mode daily --steps 6 --bess lfp:5:5:10 --policy peak-shave, first of 30 substeps)
start of step 1: SoC=0.4998333 T=25.00 C V1=0 V2=0 fade=0.000408227
pack: Ns=304 Np=40 cells=12160  nominal 10.02466 MWh
OCV = 3.27 + 0.998333*(3.29-3.27) = 3.2899667 V (entropic term 0 at 298.15 K)
R0(25C) = 2.5002083e-04 ohm; ageing factor 1+2.5*fade = 1.0010206; R0 = 2.5027600e-04 ohm
DC request = -5 MW * 0.98 = -4900000 W; per cell p = -402.9605 W
disc = E^2 - 4 R0 p = 11.227286; I = (E - sqrt(disc))/(2 R0) = -121.3612 A
limits: C-rate 139.94 A, SoC-ceiling room 949.7 A -> neither binds (|I|=121.36 A)
terminal V = E - I R0 = 3.320340 V; DC power = V*I*cells = -4900000.0 W; AC = DC/0.98 = -5.000000 MW
V1 = -0.014578 V, V2 = -0.015281 V
heat per cell: I2R0 1769.4 + RC1 424.6 + RC2 311.0 + entropic 868.4 = 3373.4 J; pack 4.1021e+07 J
m cp = 5.4*1100*12160 = 72230400.0 J/K; T no HVAC = 298.15 + 4.1021e+07/72230400.0 = 298.7179 K = 25.568 C
I_eff = I*0.995 = -120.7544 A; dSoC charge = 0.057526; self-discharge = 5.556e-06; SoC = 0.557353
calendar: stress 1.034412e-03, tEq 0.155746 d, fade 0.000415444; cycle: EFC 0.028896, fade 9.6318e-07
[exit 0]

Reading it against the equations: the request is -5 MW AC, so the converter takes 5 * 0.98 = 4.9 MW from the grid side to the DC side (charge multiplies by eta). The OCV is interpolated between the grid points 0.4 and 0.5. R0 is interpolated between 0.1 and 0.5 and scaled by 1 + 2.5 * fade; the Arrhenius factor is 1 at 25 C. The smaller root of E I - R0 I^2 = p is I = -121.36 A per cell, which neither the 0.5C limit (139.94 A) nor the SoC-ceiling room (949.7 A) binds, so the step delivers the request exactly, -5.000000 MW. The heat is the sum of the four terms, 41.02 MJ for the pack, and raises the 72.23 MJ/K pack mass by 0.568 K to 25.568 C. Charging stores I * CE and the SoC rises 0.057526, to 0.557353.

The remaining substeps, docs/_captures/bess/hand-recompute-chain-lfp-step1-substeps.txt (AC MW delivered, SoC, T in C):

$ python run2.py   (all 30 substeps of step 1, same run: AC MW delivered, SoC, T in C)
after step0 0.4998333333333339 298.15 0.00040822719780544584 0.00040822719780544584
0 -5.0 0.557353 25.568
1 -5.0 0.614276 26.278
2 -5.0 0.671053 27.017
3 -5.0 0.727742 27.75
4 -5.0 0.784312 28.466
5 -5.0 0.840721 29.161
6 -5.0 0.897038 29.836
7 -4.70531 0.949994 30.0
8 -0.00049 0.949994 30.0
9 -0.00049 0.949994 29.976
...
29 -0.00049 0.949994 29.371
[exit 0]

Seven substeps run at the full -5 MW. In substep 7 the charge room (0.95 - 0.897038) * 3600 * Q / 480 / 0.995 is below the requested current, so the current is capped and the step lands on 0.949994 (the ceiling less one substep of self-discharge), delivering -4.70531 MW. The temperature reaches the 30 C HVAC setpoint in substep 7, where the HVAC engages and holds the pack at 30.0 C; from substep 9 the pack, with almost no current, cools passively. From substep 8 only a -0.00049 MW trickle flows: the room above the ceiling is the self-discharge of one substep. The step's mean is (7 * 5 + 4.70531 + 22 * 0.00049) / 30 = 1.32387, the CSV's s0_delivered_mw of -1.32387, and the limit reason is SoC ceiling. The end state is SoC 0.949994 and 29.3712 C, the CSV's s0_soc and s0_temp_c.

The whole run

docs/_captures/bess/hand-recompute-chain-lfp-run.txt re-computes all six steps and the summary.

$ python run1b.py   (independent re-computation of all six steps of: gridsim chain case9 --mode daily --steps 6 --bess lfp:5:5:10 --policy peak-shave)
step request_MW delivered_MW aux_MW SoC T_C total_fade
0   0.00   0.00000  0.010000 0.499833  25.000 0.000408227
1  -5.00  -1.32387  0.010912 0.949994  29.371 0.000796927
2   0.00   0.00000  0.010000 0.949828  28.598 0.001047403
3   0.00   0.00000  0.010000 0.949661  27.962 0.001231714
4   5.00   2.41494  0.017145 0.049911  29.570 0.001340755
5   0.00   0.00000  0.010000 0.049744  28.762 0.001398409
out 9.65975 MWh, in 5.29548 MWh, aux 0.27223 MWh
calendar fade 0.0013721 (0.1372 %), cycle fade 2.6283e-05 (0.0026 %)
stored change = 0 - 5.0408 = -5.0408 MWh (SoC 0.04974 is below the 0.05 floor)
round trip = 9.65975 / (5.29548 + 5.0408) = 0.93455
EFC = (9.65975 + 5.29548) / (2 * 10.02466) = 0.74592
[exit 0]

It reproduces the report: out 9.7, in 5.3, aux 0.27, calendar 0.1372 %, cycle 0.0026 %. The stored change is the energy above the SoC floor at the end less at the start: at the start 0.45 * 280 * 40 * 304 * 3.29 = 5.0408 MWh, at the end 0 because the SoC 0.04974 is below the floor. The round trip is 9.65975 / (5.29548 + 5.0408) = 0.93455, printed 93.5 %, and EFC = (9.65975 + 5.29548) / (2 * 10.02466) = 0.74592, printed 0.75. Step 4 delivers a mean 2.41 MW instead of the 5 MW asked for, because the discharge room to the 0.05 floor is exhausted partway through the step; the reason is SoC floor.

Two losses are visible in the report. The converter costs 2 % each way: a 5 MW charge takes 4.9 MW into the pack and a 5 MW discharge draws 5.102 MW from it. The cell's resistance and polarisation heat the pack from 25.0 C to 29.4 C in step 1 alone, and the HVAC load shows in the step-4 auxiliary power, 0.017 MW against the 0.010 MW standby.

Source map

File Type Responsibility
src/GridSim.Core/Storage/CellModel.cs CellModel equivalent circuit, RC relaxation, Peukert, coulombic efficiency, self-discharge, heat
src/GridSim.Core/Storage/ChemistryParameters.cs ChemistryParameters, AgeingParameters, AuxiliaryModel, LookupTable the per-chemistry constants, defaults, Arrhenius factor, nominal voltage and energy
src/GridSim.Core/Storage/BatteryChemistryLibrary.cs BatteryChemistryLibrary the six presets, ByName, the Nernst table
src/GridSim.Core/Storage/PackModel.cs PackModel, PackStepResult sizing, the pack step, limits and limit reasons, thermal model, auxiliary load, state of power
src/GridSim.Core/Storage/AgeingModel.cs AgeingModel, Rainflow calendar and cycle fade, resistance growth feed-back, the fade cap, rainflow counting
src/GridSim.Core/Storage/StorageDispatch.cs IStorageDispatchPolicy and the five policies, StorageEnvelope, StorageLpScheduler dispatch rules, envelope linearisation, the LP
src/GridSim.Core/Numerics/BoundedSimplex.cs BoundedSimplex, LpStatus the bounded-variable simplex behind the LP
src/GridSim.Core/Storage/StorageFleet.cs StorageFleet substeps, books, injection into the model, validation, per-site summaries
src/GridSim.Core/Storage/StorageTimeSeries.cs StorageTimeSeries, StorageSite, StorageTimeSeriesSpec and the record types the step loop, warm start, slack bookkeeping
src/GridSim.Core/Storage/SyntheticPrices.cs SyntheticPrices the synthetic GB price day
src/GridSim.Core/Assets/DcSource.cs IDcSource, SocBucket, BatteryDcSource, DcSources the pack behind a converter, the asset-class factory
src/GridSim.Core/Dynamics/Models/RmsConverter.cs RmsConverterUnit.Store the store behind an RMS converter
src/GridSim.Core/Simulation/GdaReplayLoop.cs GdaReplayLoop.Replay storage on recorded history, step length from the series
src/GridSim.Core/Simulation/LiveSim.cs LiveSim storage carried tick to tick
src/GridSim.Cli/StorageCli.cs StorageCli --bess parsing, defaults, price reading, policies, reports
src/GridSim.Cli/Program.cs chain and gda-replay branches, the --prices guard verb wiring, option set and tap-changer loop, refusals

Limits

  • gda-replay takes no price series, so its sites run idle, peak-shave or hold only.
  • gridsim gda-replay checks every --bess site's bus against the replay case (StorageFleet.Validate) inside the verb's error handling, so a site on a bus the case does not have is refused with exit 2 before the replay starts.
  • The LP has no charge and discharge complementarity, so at a negative price it can charge and discharge in one step and its energy trajectory then differs from the net schedule.
  • The LP envelope is linear: power limits come from the state of power at mid SoC and efficiencies from the rated current, so sag, fade and temperature during the day are not in the plan.
  • Each site is planned independently of the network and of the other sites.
  • A site injects real power only: its reactive range is zero and it holds the voltage set-point its bus already had.
  • The pack is one lumped cell: no cell-to-cell imbalance, no module thermal gradient, one temperature per pack.
  • The Peukert test and the cycle C-rate use the unfaded rated capacity.
  • The limit-reason comparisons use an absolute 1e-9 A tolerance, where a relative test would be more robust for large currents (R198).
  • The chain and replay verbs fix the converter efficiency (0.98 one way), the pack DC voltage (1000 V) and the ambient temperature (25 C); no flag changes them.
  • All sites in a run share one policy and one set of thresholds, and chain scales every load in the case uniformly.
  • The rainflow fade is a report beside the throughput fade and is not fed back into the cell.
  • A site's SoC, rating and energy are not range-checked beyond the case's bus list; a negative rating fails in the request clamp with a message that does not name the flag.
  • The chemistry presets are CuratedPlaceholder representative cells, not products.
  • No test repeats a storage run to compare its bits across runs or CPUs.
  • stability --rms runs without an energy store behind its converters.

See also