24. Standard dynamic-model library

This chapter specifies the dynamic-model library under src/GridSim.Core/Dynamics/Models/ and the study built on it: the block primitives, the synchronous-machine models (classical, one-axis, two-axis and the six-state subtransient machine with magnetic saturation), the exciters (SEXS, IEEET1), the stabiliser (PSS1A), the turbine-governors (TGOV1, IEEEG1 and a hydro governor), the converter-plant models the RMS engine carries beside the machines, the initialisation of a fleet from a solved power flow (SubtransientInit), and the RMS transient-stability integrator (MultiMachineSubtransient, RmsTransientStability) with its critical-clearing-time search. It gives the equations as coded, every parameter with its default, unit and source symbol, the invariants and the tests that pin them, and one machine initialised by hand against a captured run.

The library follows one design rule. Every dynamic element is a wiring of five blocks (FirstOrderLag, LeadLag, Washout, Integrator, PiController) that advance by the exact zero-order-hold solution of their own pole. A standard model adds routing and limits, never numerics of its own, so the block tests validate the arithmetic once and the model tests validate the wiring. Machines add one more rule: over a step the flux inputs (Id, Iq, Efd) are evaluated at the start-of-step state and held, the flux states advance on the block exact solution, and the rotor swing advances by RK4 with the EMFs frozen, re-solving Pe at each RK4 stage (operator splitting).

The classical machine's swing, its Kron reduction and the small-signal linearisation of it are specified in ch. 30, Small-signal and impedance stability; this chapter repeats only the classical equations the library reuses. The task view of the same verbs is ch. 15, RMS, modal and impedance stability.

Quantities are per-unit. Machine reactances and inertia are converted to the system base GridModel.BaseMva (ch. 2); a quantity "on the machine base" is converted by BaseMva / MBase. In the subtransient fleet (SubtransientInit) MBase <= 0 means BaseMva. The classical path (ClassicalInit) uses the same rule (MachineBase.EffectiveMva: a non-positive MBase means the system base, and a NaN or infinite one is refused). Angles are radians, speed deviation omega is per-unit of synchronous speed, ws = 2 pi f0.

Model

Block library

src/GridSim.Core/Dynamics/Models/ControlBlocks.cs. The three linear dynamic blocks advance by the closed-form solution of T dx/dt = K u - x for an input held across the step:

a = exp(-dt / T)
x <- a*x + (1 - a)*K*u

This is exact for a held input and A-stable at every step size. Every block is a pure function of (state, input, dt): no static state, no threads, no clock, so a run is bit-identical to the next run.

Block Transfer function Realisation as coded
FirstOrderLag(K, T, min, max) K / (1 + sT) x <- clamp(a*x + (1-a)*K*u, min, max); T <= 1e-12 (ControlBlocks.InstantThresholdSeconds) gives x <- clamp(K*u); max < min throws
LeadLag(Ta, Tb) (1 + sTa)/(1 + sTb) c = Ta/Tb; y = c*u + xL; xL <- a*xL + (1-a)*(1-c)*u with a = exp(-dt/Tb); Ta < 0 or Tb <= 0 throws
Washout(T) sT/(1 + sT) xL <- a*xL + (1-a)*u; y = u - xL; T <= 0 throws
Integrator(K, min, max) K/s x <- clamp(x + K*u*dt, min, max) (exact for a held input)
PiController(Kp, Ki, min, max) Kp + Ki/s y = clamp(Kp*u + I(u), min, max); I is an Integrator with the same limits

Initialisation puts a block at its equilibrium: FirstOrderLag.Initialize(y) sets x = clamp(y); LeadLag.Initialize(u) sets xL = (1 - c)*u, so the output is u exactly; Washout.Initialize(u) sets xL = u, so the output is zero; PiController.Initialize(u, y) sets the integral to y - Kp*u.

Limits clamp the state itself, not only the reported output. A lag or integrator at its limit therefore holds no wound-up state and leaves the limit on the first step in which its input reverses (non-windup).

Two reductions are exact by construction. A LeadLag with Ta == Tb has c = 1 and internal gain 1 - c = 0, so y = u bit for bit. A FirstOrderLag with T = 0 is the gain y = K*u bit for bit.

Rotor equations shared by every machine

ddelta/dt = ws * omega                                   (rotor angle)
domega/dt = (Pm - Pe - D*omega) / (2*H)                  (swing; H and Pe on one base, D in pu power per pu speed)

H is the inertia constant in seconds on the machine base; the multi-machine engine converts it to the system base as H_sys = H * MBase / BaseMva (SubtransientInit.FromSolvedCase). D is used as given, in system-base pu, and is not rescaled.

Classical machine

ClassicalMultiMachine (src/GridSim.Core/Dynamics/Distributed/ClassicalMultiMachine.cs) is a constant internal EMF E' angle delta behind X'd, with the machines coupled through the Kron-reduced admittance Y = G + jB of the augmented network (internal nodes behind X'd, loads as constant admittance conj(S)/|V|^2):

Pe_i = E_i^2*G_ii + E_i * sum_{j != i} E_j * (G_ij*cos(d_i - d_j) + B_ij*sin(d_i - d_j))

The swing advances by RK4. Two optional hooks make it the host of the control models: mechanicalPower(i, omega_i) replaces Pm once per step and is held across the RK4 stages, and internalVoltage(i, E_i, Id_i) replaces E_i for the next step. With neither hook the integration is the constant-Pm, constant-E' swing byte for byte. ClassicalInit.FromSolvedCase seeds it: E' = Vt + j*X'd*It with It = conj(S_gen/Vt) from the solved power flow, delta0 = arg(E'), and Pm set to the computed Pe at delta0, so an undisturbed run is a fixed point. X'd comes on the machine base and is converted to the system base by BaseMva / MBase; it defaults to 0.30 pu when the caller supplies none.

One-axis machine (flux decay), SMIB

OneAxisMachine is a machine whose transient EMF E'q is a state, on a single-machine infinite-bus network (Vinf through the external reactance Xe). Three states:

ddelta/dt    = ws * omega
domega/dt    = (Pm - Pe - D*omega) / (2*H)
T'do dE'q/dt = Efd - E'q - (Xd - X'd)*Id

The stator is algebraic with Rs = 0: Vd = Xq*Iq, Vq = E'q - X'd*Id. Against the infinite bus the currents have a closed form, so there is no network iteration:

Id = (E'q - Vinf*cos(delta)) / (X'd + Xe)
Iq =        Vinf*sin(delta)  / (Xq  + Xe)
Pe = E'q*Iq + (Xq - X'd)*Id*Iq                      (the second term is reluctance power)
Vt = sqrt(Vd^2 + Vq^2)

Over a step Id and Efd are held, so the flux equation is a first-order lag with input u = Efd - (Xd - X'd)*Id; E'q advances on FirstOrderLag(1, T'do). Rotor: RK4 with E'q frozen. An optional Sexs closes the AVR on Vt: Efd = Sexs.Step(Vref - Vt) at the start of each step. Equilibrium(p, delta0, E'q0) returns Efd = E'q0 + (Xd - X'd)*Id and Pm = Pe.

Two-axis machine, SMIB

TwoAxisMachine adds the q-axis transient EMF E'd as a fourth state and puts X'q in the stator:

T'qo dE'd/dt = -E'd + (Xq - X'q)*Iq
Vd = E'd + X'q*Iq          Vq = E'q - X'd*Id
Id = (E'q - Vinf*cos(delta)) / (X'd + Xe)
Iq = (Vinf*sin(delta) - E'd) / (X'q + Xe)
Pe = E'd*Id + E'q*Iq + (X'q - X'd)*Id*Iq

The d-axis equation is the one-axis equation. The q-axis fixed point is E'd = (Xq - X'q)*Vinf*sin(delta)/(Xq + Xe) (TwoAxisMachine.EquilibriumEdp).

Subtransient machine (GENROU-style), SMIB

SubtransientMachine is the six-state machine: rotor delta, omega, and four flux EMFs, the two subtransient ones cascaded off the transient ones:

T'do  dE'q/dt  = Efd - E'q - (Xd - X'd)*Id - E''q*Se(|E''|)
T''do dE''q/dt = E'q - E''q - (X'd - X''d)*Id
T'qo  dE'd/dt  = -E'd + (Xq - X'q)*Iq - E''d*Se(|E''|)*(Xq - Xl)/(Xd - Xl)
T''qo dE''d/dt = E'd - E''d + (X'q - X''q)*Iq
|E''| = sqrt(E''q^2 + E''d^2);  Xl = stator leakage reactance (0 when not given)

The stator sees the subtransient EMFs behind the subtransient reactances (Rs = 0):

Vd = E''d + X''q*Iq            Vq = E''q - X''d*Id
Id = (E''q - Vinf*cos(delta)) / (X''d + Xe)
Iq = (Vinf*sin(delta) - E''d) / (X''q + Xe)
Pe = E''d*Id + E''q*Iq + (X''q - X''d)*Id*Iq

Each flux state advances on FirstOrderLag(1, T) with the input frozen at the start-of-step state (currents, Efd, and the transient EMF that drives the subtransient one). The rotor advances by RK4 with E''q, E''d frozen.

Saturation. SaturationCurve(S1, S12) is the scaled-quadratic open-circuit form fitted in closed form to the two tabulated points Se(1.0) = S1 and Se(1.2) = S12 (LowerFitPointPu = 1.0, UpperFitPointPu = 1.2):

k  = sqrt(1.2 * S12 / S1)
A  = (k - 1.2) / (k - 1)
B  = S1 / (1 - A)^2
Se(x) = B * (x - A)^2 / x        for x > A, else 0
FieldIncrement(x) = x * Se(x) = B * (x - A)^2

Se is the dimensionless PSS/E saturation factor (Ifd = x*(1 + Se(x)) in air-gap-line per-unit). The machine applies it in the PSS/E GENROU form (SaturationCurve.GenrouIncrements): Se is evaluated on the subtransient flux magnitude |E''|, the d-axis increment is E''q * Se(|E''|) and the q-axis increment is E''d * Se(|E''|) * (Xq - Xl)/(Xd - Xl), both frozen at the start-of-step subtransient EMFs. Xl must be finite, at least 0 and below X''d. S1 = 0 is the unsaturated machine (A = B = 0, Se = 0), and any S12 given with it is ignored. A negative S1 or S12 throws, and S1 > 0 requires S12 > S1. For S1 = 0.10, S12 = 0.30 the increment x * Se(x) is 0.10 pu at 1.0 pu flux and 0.36 pu at 1.2 pu. At equilibrium a saturated machine needs exactly the d-axis increment more Efd than the unsaturated one: Efd = E'q + (Xd - X'd)*Id + E''q*Se(|E''|).

The closed-form SMIB fixed point (SubtransientMachine.Equilibrium) is Iq_sync = Vinf*sin(delta0)/(Xq + Xe), E'd = (Xq - X'q)*Iq_sync, E''d = (Xq - X''q)*Iq_sync, and E''q solved from E''q = E'q - (X'd - X''d)*Id with Id = (E''q - Vinf*cos(delta0))/(X''d + Xe). When the machine is saturated at that point (Se(|E''|) > 0) the q-axis fixed point moves: with s = Se(|E''|) * (Xq - Xl)/(Xd - Xl), E''d = (Xq - X''q)*Vinf*sin(delta0) / ((1 + s)(X''q + Xe) + Xq - X''q), solved by fixed-point iteration from the unsaturated value (at most SaturatedEquilibriumMaxIterations = 200 iterations, settled at a relative move of 1e-15; otherwise InvalidOperationException), then E'd = E''d - (X'q - X''q)*Iq. Below the knee the closed form above is kept, bit for bit.

SubtransientMachine.Simulate takes an optional Sexs exciter with an explicit Vref.

Multi-machine network interface

SubtransientNetworkInterface carries the dq machine into a coupled network. Each machine's subtransient EMF is rotated from its rotor frame into the network frame by the load angle:

Er_i = E''q_i*cos(d_i) + E''d_i*sin(d_i)
Ei_i = E''q_i*sin(d_i) - E''d_i*cos(d_i)
I    = Y_red * E                                       (one complex matrix-vector product)
Pe_i = Er_i*Ir_i + Ei_i*Ii_i                           (Re(E conj(I)))
Iq_i = Ir_i*cos(d_i) + Ii_i*sin(d_i)                   (inverse rotation to the machine frame)
Id_i = Ir_i*sin(d_i) - Ii_i*cos(d_i)
Vt_i = E_i - j*X''_i*I_i                               (terminal voltage, for the AVR)

The reduced admittance holds the round subtransient reactance X'' of each machine (X''d = X''q), so each machine is a voltage behind one reactance at the interface while its flux dynamics stay fully salient. With E''d = 0 the interface is exactly the round-rotor injection of MultiMachineFluxDecay.NetworkInjection (Pe_i = E_i * sum_j E_j*(G_ij*cos(d_ij) + B_ij*sin(d_ij)), Id_i = Qe_i/E_i).

MultiMachineFluxDecay is the round-rotor multi-machine model that uses this closed form: every machine carries E'q with Xq = X'd, the flux advances on the same exact lag with input Efd_i - (Xd_i - X'd_i)*Id_i, and the swing is ClassicalMultiMachine with the internalVoltage hook.

Exciters

SEXS (Sexs): the simplified excitation system.

Verr = Vref - Vt + Vs
v1   = LeadLag_{Ta/Tb}(Verr)
Efd  = FirstOrderLag_{K, Te, [Emin, Emax]}(v1)

The steady field is clamp(K*Verr, Emin, Emax). Initialize(Efd0) sets Verr = Efd0/K. K <= 0 throws.

IEEET1 (Ieeet1): the IEEE Type 1 DC exciter, with a regulator lag, a self-excited exciter with exponential saturation, and rate feedback.

Vf  = (Kf/Tf) * Washout_Tf(Efd)                       sKf/(1 + sTf) of the field voltage
Vr  = FirstOrderLag_{Ka, Ta, [Vrmin, Vrmax]}(Verr - Vf)
Se  = Aex * exp(Bex * Efd)
Te dEfd/dt = Vr - (Ke + Se)*Efd                        Se frozen at the start-of-step Efd

The exciter ODE advances by the exact hold of its linearised pole: with s = Ke + Se, a = exp(-dt*s/Te) and Efd <- a*Efd + (1 - a)*Vr/s; when |s| <= 1e-12 (Ieeet1.ExciterPoleAtOriginTolerance) the pole is at the origin and Efd <- Efd + Vr/Te*dt. The feedback washout then advances on the new Efd. Initialize(Efd0) sets Vr = (Ke + Se(Efd0))*Efd0 and the washout output to zero, so the steady error is Verr = (Ke + Se)*Efd/Ka. Ka <= 0, Te <= 0, Tf <= 0 or Aex < 0 throws. With Se = 0, Ke = 1, Kf = 0 it is a two-lag AVR whose steady field is Ka*Verr.

EXAC1 and ESAC1A (AcExciter): the alternator-rectifier exciters of the IEEE AC1 family (EXAC1 the 1981 type AC1, ESAC1A the 421.5-2005 type AC1A). They read the machine's field current IFD (non-reciprocal Xad base).

VFE = VE*(KE + SE(VE)) + KD*IFD           VE*SE(VE) = B*(VE - A)^2 above A (quadratic through (E1, SE1), (E2, SE2))
VF  = (KF/TF) * Washout_TF(VFE)
x   = LeadLag_{TC/TB}(Verr - VF)          (TB = TC = 0 bypasses it)
EXAC1:  VR = FirstOrderLag_{KA, TA, [VRMIN, VRMAX]}(x)
ESAC1A: VA = FirstOrderLag_{KA, TA, [VAMIN, VAMAX]}(x),  VR = clamp(VA, VRMIN, VRMAX)
TE dVE/dt = VR - VFE                      SE frozen at the start-of-step VE; ESAC1A: VE >= 0
Efd = VE * FEX(KC*IFD/VE)                 FEX the IEEE 421.5 rectifier regulation function

Initialize(Efd0) takes IFD = Efd0 (true at every machine equilibrium), inverts Efd0 = VE*FEX(KC*Efd0/VE) branch by branch for VE, and sets VR = VFE and the washout output to zero; VR (and VA) outside its limits throws. The steady error is VFE/KA. The RMS kernel supplies IFD = E'q + (Xd - X'd)*Id + the d-axis saturation increment at the start of each step to a controller that implements IRmsFieldCurrentController with NeedsFieldCurrent true; every other controller takes the old path unchanged. ESST4B (Esst4b): the IEEE 421.5-2005 type ST4B static exciter, fed from a potential and/or compound source, with an outer voltage PI regulator and an inner field-voltage PI regulator.

VE   = | KP e^(j THETAP) VT + j (KI + KP e^(j THETAP) XL) IT |     (machine base)
VB   = min(VE * FEX(KC*IFD/VE), VBMAX)
VR'  = PI_{KPR, KIR, [VRMIN, VRMAX]}(Verr)      VR = lag_{TA}(VR')
VM   = PI_{KPM, KIM, [VMMIN, VMMAX]}(VR - KG*Efd)     (the loop through Efd = VM*VB solved exactly each step)
Efd  = VM * VB

It needs the terminal phasors, so it implements IRmsTerminalFieldController: the kernel passes V_t = E'' - jX'' I and the machine current on the system base, which RmsExciter converts to the machine base bound by the study (BindMachineBase, MBase / system base). A unit with a unit transformer folded into its reactances is refused, because its terminal voltage is then not available. Initialize(Efd0) records the field and the first step sets every state from that step's measurements (VM0 = Efd0/VB0, VR0 = KG*Efd0 with KIM above 0); states outside their limits throw. KIR above 0 gives a steady error of 0; KIR = 0 needs KIM above 0 (error KG*Efd0/KPR); KIR = KIM = 0 is refused. The PSS/E data carry no VGMAX, so none is applied. RmsExciter (src/GridSim.Core/Dynamics/Models/RmsTransientStability.cs) is the IRmsFieldController the RMS engine drives. It wraps one Sexs, one Ieeet1, one AcExciter or one Esst4b, built by RmsExciter.FromSexs, RmsExciter.FromIeeet1, RmsExciter.FromAc or RmsExciter.FromEsst4b, and an optional Pss1a:

Vs   = Pss1a.Step(omega)           (omega = this machine's speed deviation; 0 without a PSS)
Efd  = AVR.Step(Vref - Vt + Vs)

Initialize(Efd0) refuses an Efd0 the limits cannot hold: SEXS needs Efd0 in [Emin, Emax], IEEET1 needs Vr = (Ke + Se)*Efd0 in [Vrmin, Vrmax]; either throws InvalidOperationException rather than clamping silently. A non-finite Efd0 throws ArgumentOutOfRangeException. FromSexs throws when Emax < Emin, FromIeeet1 when Vrmax < Vrmin; the Sexs and Ieeet1 constructors throw ArgumentException for the same inverted limits. EquilibriumErrorPu(Efd0) returns the steady regulator error Efd0/K (SEXS) or (Ke + Se)*Efd0/Ka (IEEET1).

Power-system stabiliser PSS1A

Pss1a is a subset of the IEEE 421.5 PSS1A:

g  = Ks * u                                  u = speed deviation (pu)
w  = Washout_Tw(g)
v1 = LeadLag_{T1/T2}(w)
v2 = LeadLag_{T3/T4}(v1)
Vs = clamp(v2, Vsmin, Vsmax)

A stage with T1 = T2 = 0 (or T3 = T4 = 0) is bypassed and is exactly unity. A stage with a zero lag and a non-zero lead is an improper pure derivative and throws, naming the parameter. Vsmax < Vsmin throws. A PSS adds nothing in steady state, because the washout blocks any sustained input: Initialize sets Vs = 0.

Turbine-governors

All four map speed deviation dw (pu) to mechanical power Pmech (pu on the machine base). Initialize(Pm0) sets the reference and every state so that dw = 0 holds Pm0 exactly.

TGOV1 (Tgov1):

valveCmd = Pref - dw/R
Pgv      = FirstOrderLag_{T1, [Vmin, Vmax]}(valveCmd)
Pt       = LeadLag_{T2/T3}(Pgv)
Pmech    = Pt - Dt*dw

With Pref = Pm0 the steady droop in the unlimited region is dPmech/dw = -1/R - Dt. R <= 0 throws.

IEEEG1 (Ieeeg1), the tandem-compound steam governor:

s1   = LeadLag_{T2/T1}(-dw/R)
Pgv  = FirstOrderLag_{T3, [Pmin, Pmax]}(Pref + s1)
y4   = lag_{T4}(Pgv)     y5 = lag_{T5}(y4)     y6 = lag_{T6}(y5)     y7 = lag_{T7}(y6)
Pmech = K1*y4 + K3*y5 + K5*y6 + K7*y7

The steady droop is -1/R when the fractions sum to 1. With K1 = 1 and T2 = T1 it is a single-stage governor.

HydroGovernor, the transient-droop hydro governor with the ideal water column:

err   = Pref - dw
c     = (err - Rt*Washout_Tr(g)) / Rp
g     = FirstOrderLag_{Tg, [gmin, gmax]}(c)
Pmech = (1 - s*Tw)/(1 + 0.5*s*Tw) * g  =  3*lag_{0.5*Tw}(g) - 2*g

Initialize(Pm0) sets Pref = Rp*Pm0, the gate to Pm0 and the water lag to 3*Pm0. The partial-fraction form is 3*lag - 2*g, so a gate opening dg drives the power first to -2*dg and then settles at +dg (the water-hammer inverse response). Rp <= 0 or Tw <= 0 throws.

GAST (Gast), the simple gas turbine with its exhaust temperature load limit (PSS/E GAST, CGMES GovGAST; data R, T1, T2, T3, AT, KT, VMAX, VMIN, DTURB):

pd     = Pref - dw/R
limit  = AT + KT*(AT - x3)          (x3 at the start of the step)
x1     = FirstOrderLag_{T1, [VMIN, VMAX]}(min(pd, limit))
x2     = lag_{T2}(x1)               x3 = lag_{T3}(x2)
Pmech  = x2 - DTURB*dw

On the temperature limit the steady state solves x = AT + KT*(AT - x), so the turbine settles at AT whatever KT. Initialize(Pm0) needs Pm0 inside [VMIN, VMAX] and at most AT (above it the limit binds and the start is not an equilibrium); R <= 0 or KT < 0 throws. GovernedMultiMachine hosts Tgov1 on the classical swing through the mechanicalPower hook, one optional governor per machine. It initialises each governor at the machine's initial Pm and then applies a supplied mechanicalReference with SetReference (R246), so a set-point step travels through the valve and reheat lags; it passes no hook at all when no governor is present, so a governed run with no governor is the classical run bit for bit. An islanded pair with a sustained reference step dP settles to omega_ss = dP / sum_i(1/R_i + Dt_i + D_i), where Dt_i is the governor's turbine damping and D_i the swing damping (the test uses Dt = 0). TGOV1 data is on the machine's own base: pass machineToSystemBase (MBase / system base, one per machine, GR-560) and each governor is initialised at Pm / k, referenced at reference / k and its output scaled back by k, so a machine-base droop R acts as k / R on the system base; without it the governor reads the system-base powers directly (exact only for a machine rated at the system base).

Converter plant in the RMS engine

A generator with IsConverterInterfaced (battery, PV, wind, VSC HVDC) has no rotor. SubtransientInit removes it from the machine fleet and retains its terminal bus as a network node after the machine internal nodes; converters on one bus and of one class are aggregated into one RmsConverterUnit. The unit is a phase-locked current source. Parameters are RmsConverterParameters; its state is RmsConverterState (after the WECC REGC_A interface with REEC-style control):

Vf   = FirstOrderLag_{Tr}(|Vt|)
normal:     Ip* = P0/max(Vf, 0.01)        Iq* = Q0/max(Vf, 0.01)    (MinControlVoltagePu)
dip (Vf < Vdip):  Iq* = Iq0 + Kqv*(V0 - Vf)*Rating     Ip* = Ip frozen at dip entry
limit:      |Iq*| <= Imax*Rating (reactive priority);   |Ip*| <= sqrt((Imax*Rating)^2 - Iq*^2)
REGC_A:     Ip, Iq follow Ip*, Iq* on lag Tg; any rise in |Ip| is capped at rrpwr*Rating*dt per step
LVACM:      injected Ip scaled by 0 at |V| <= LvPnt0, 1 at |V| >= LvPnt1, linear between
injection:  I = (Ip*Lvacm - j*Iq) * exp(j*angle),   angle = terminal-voltage angle while |V| > 1e-3

A unit with fault-current limit k = 0 (line-commutated HVDC) has BlockInDip: it feeds no current while in the dip and ramps back after it, and it is never aggregated with current-limited units.

A unit with Generator.GridForming is a virtual synchronous machine: an EMF E angle delta behind the virtual reactance Xv, stamped into the network as the Norton admittance y = Rating/(j*Xv):

2*Hv*domega/dt = Pref - Pe - Dv*omega          ddelta/dt = ws*omega        (H = 2 s, D = 20 pu on the rating)
dE/dt = Kv*(Vref - |V|)    clamped to [0.5, 1.5] pu, frozen while current-limited
current limit: when |(E - V)*y| > k*Rating the terminal current is held at the limit in the same direction

The speed is advanced by semi-implicit Euler, omega <- (omega + dt*(Pref - Pe)/(2H)) / (1 + dt*D/(2H)).

WECC second-generation renewable models

A converter unit can instead be driven by the WECC second-generation generic renewable models, bound from a PSS/E DYR file (Dynamics/Models/Wecc/). The block diagrams are those of EPRI 3002006525, Model User Guide for Generic Renewable Energy System Models (2015, public): REGC_A Fig. D-4, REEC_A Fig. D-1, REEC_B Fig. D-2, REEC_C Fig. D-3 and Fig. 3-4, REPC_A Fig. 3-5, the current limit logic App. B. The data path is SubtransientInit.MachineData.Renewable (a WeccPlant): a unit that carries a chain is converter plant whatever its case type (a PSS/E RAW renewable is typed as a synchronous unit), is never aggregated with other converters on its bus, is a current source (no Norton admittance) unless its generator model is the voltage-source REGC_B or REGFM_A1 (below), and is driven by WeccConverterState through the kernel's IRmsConverterModel interface. A unit without a chain keeps the converter model above, through an adapter that makes exactly the calls the kernel made before, so its numbers are unchanged bit for bit. Every quantity of the WECC models is per unit on the unit's MBASE; the network sees it scaled by MBASE / system base. Reactive current is held exporting positive (the diagrams' -1/(1+sTg) gives the network-convention Iq = -Iq_export).

REGC_A   Ip  = lag(Ipcmd, Tg), rise <= Rrpwr, upper limit LVPL(Vf)       Vf = lag(|Vt|, Tfltr)
         Iqx = lag(Iqcmd, Tg), export fall <= Iqrmax when Q0 > 0, export rise <= -Iqrmin when Q0 < 0
         LVPL(Vf) = 0 at or below Zerox, Lvpl1 (Vf - Zerox)/(Brkpt - Zerox) between, none at or above Brkpt
         network:  Ip_out = Ip * LVACM(|Vt|)  (0 at Lvpnt0, 1 at Lvpnt1, linear between)
                   Iqx_out = max(Iqx - Khv max(|Vt| - Volim, 0), Iolim)                   (HVRCM)
         injection I = (Ip_out - j Iqx_out) exp(j angle(Vt)) * MBASE / system base
REEC_A   Vt_filt = lag(Vt, Trv);  Voltage_dip = Vt < Vdip or Vt > Vup (raw Vt)
         Qref = PfFlag ? tan(pf0) lag(Pe, Tp) : Qext,  Qlim = clamp(Qref, Qmin, Qmax)
         VFlag=1: Vsel = PI(Kqp, Kqi) on (Qlim - Qgen) in [Vmin, Vmax];   VFlag=0: Vsel = Vref1 + Qlim
         QFlag=1: Iq = PI(Kvp, Kvi) on (Vsel - Vt_filt) in [-Iqmax, Iqmax];  QFlag=0: Iq = lag(Qlim / Vt_filt, Tiq)
         Iqinj = Kqv db(Vref0 - Vt_filt, dbd1, dbd2) in [Iql1, Iqh1] in a dip; after it Iqfrz for Thld (Thld > 0),
                 Iqv for -Thld (Thld < 0), else 0;  Iqcmd = clamp(Iq + Iqinj, -Iqmax, Iqmax)
         Pord = lag(rate-limited Pref [x speed when PFlag = 1], Tpord) in [Pmin, Pmax]
         Ipcmd = clamp(Pord / Vt_filt, Ipmin, Ipmax)
         Q priority: Iqmax = min(VDL1, Imax), Ipmax = min(VDL2, sqrt(Imax^2 - Iqcmd^2))
         P priority: Ipmax = min(VDL2, Imax), Iqmax = min(VDL1, sqrt(Imax^2 - Ipcmd^2));  Ipmin = 0
         Thld2: Ipmax held at its dip value for Thld2 after the dip
         the PI integrals, the Tiq lag and Pord freeze while Voltage_dip = 1
REEC_B   REEC_A without the VDL tables, the Iqfrz/Thld/Thld2 state machine, PFlag and Vref1 (VFlag=0: Vsel = Qlim)
REEC_C   REEC_B with the VDL tables and the store: SOC = SOCini - (1/T) integral(Pe dt), Ipmin = -Ipmax,
         SOC <= SOCmin -> Ipmax = 0, SOC >= SOCmax -> Ipmin = 0
REPC_A   Vmeas = VCFlag ? |Vreg - (Rc + jXc) I| : Vreg + Kc Qbranch;  s0 = lag(Vmeas, Tfltr), s1 = lag(Qbranch, Tfltr)
         e = clamp(db(RefFlag ? Vref - s0 : Qref - s1, dbd1, dbd2), emin, emax)
         Qext = leadlag(Tft, Tfv) of PI(Kp, Ki) on e in [Qmin, Qmax], integral frozen while Vreg < Vfrz
         df = db(1 - f, fdbd1, fdbd2);  droop = Ddn min(df, 0) + Dup max(df, 0)
         Pref (Fflag = 1) = lag(PI(Kpg, Kig) on clamp(Plant_pref - lag(Pbranch, Tp) + droop, femin, femax) in [Pmin, Pmax], Tg)

Plant controller measurements. REPC_A's regulated bus (BUSR) and the buses of its flow branch (BUS1, BUS2) are retained as converter nodes with no injection, after every unit's bus (RmsConverterUnit.NodeBuses, the one order the network builder and the kernel share), so the controller reads the voltages the network solves each step. The branch current at BUS1 is I = Y11 V(BUS1) + Y12 V(BUS2) from the branch's own pi-model stamp (AdmittanceStamp, tap and phase shift included); its P and Q are converted to the unit's MBASE, and so are I and (Rc + jXc) (all REPC_A quantities are on the unit's MBASE). With no branch the plant output is the unit's own P, Q and current. Frequency is the backward difference of the regulated voltage angle over the step, 1 + wrap(theta_k - theta_k-1)/(2 pi f0 dt), through a first-order lag of RepcaParameters.FrequencyFilterSeconds (default 0.02 s, 0 for none; a GridSim parameter, not WECC data, so no DYR record carries it; at a steady state the estimate is constant and the lag moves nothing); a network event steps the angle, which this measurement sees as a short frequency spike, as a PSS/E bus frequency estimate also does. At the start Vref is the initial Vmeas, Qref the initial Qbranch, Plant_pref the initial Pbranch and the reference frequency 1 pu, so the controller starts with zero error; its integrals carry the REEC model's initial Qext and Pref. The converter trace carries the regulated bus voltage (RmsConverterTrace.RegulatedBusVoltagePu).

Network interface and integration. LVACM and HVRCM are algebraic in the terminal voltage and are evaluated inside the converter / network fixed point each step (to 1e-10 pu), as PSS/E evaluates them in its network interface. Every dynamic state advances once per step from the start-of-step terminal voltage and the power measured at the committed current: lags by the exact zero-order hold, integrators by forward Euler with non-windup limits, rate limits as a bound on the change over the step, all states from the same start-of-step inputs. REGC_A's Accel (a PSS/E network-solution acceleration factor) has no counterpart: the fixed point is solved to 1e-10 pu whatever its value.

Initialisation and its checks. From the unit's share of the solved injection (P0, Q0, V0), each model works backwards: REGC_A Ip = (P0/V0)/LVACM(V0), Iqx = Q0/V0; REEC_A the Pref and the Qext that hold that point (Q0 for Q control, V0 - Vref1 for local voltage control), the PI integrals, Pord = P0, Vref0 = V0 when the record gives 0 (the PSS/E convention). A start the model cannot hold is refused, naming the quantity: inside the dip band, a reference outside its limit, a current command above the current limit, LVACM below 1 with power flowing, the voltage above Volim with HVRCM active. The composed unit then evaluates every state's residual (lag input minus state, integrator input) at t = 0 and refuses the start if any exceeds 1e-9 pu (WeccEquilibrium.Tolerance), listing them. The REEC_C state of charge is not checked: a store delivering power is genuinely not at rest. Where the sources differ (the HVRCM sign, which signal the Iq rate limits bound, the LVPL above Brkpt) the choice and the alternatives are recorded in the code comments.

Wind turbine mechanics (EPRI 3002006525 App. C). A type 4 turbine may add the WTGT_A drive train alone (its mechanical power held; with REEC_A PFlag = 1 the drive train's torsional mode then shows in the electrical power, the type 4A behaviour); a type 3 turbine has WTGT_A, WTGAR_A, WTGPT_A and WTGTRQ_A together with REEC_A PFlag = 1 (the torque controller gives a torque, which REEC_A multiplies by the generator speed, the PSS/E convention).

WTGT_A    2 Ht dwt/dt = Pm/omega_t - K theta - Dshaft (wt - wg)      Ht = Htfrac H, Hg = H - Ht
          2 Hg dwg/dt = -Pe/omega_g + K theta + Dshaft (wt - wg) - DAMP wg
          dtheta/dt = wt - wg,   K = 2 Ht Hg (2 pi Freq1)^2 / H   (the undamped torsional mode is exactly Freq1 Hz)
          Htfrac = 0: one mass, 2 H dw/dt = (Pm - Pe)/omega - DAMP w
WTGAR_A   Pm = Pm0 - Ka theta (theta - theta0)                       (pitch in degrees)
WTGPT_A   ew = omega_t - omega_ref + Kcc (Pord - Psel);  theta = lag(PI(Kpw, Kiw) on ew + PI(Kpc, Kic) on (Pord - Psel), Tp)
          every PI and theta within [TetaMin, TetaMax], theta's rate within [RTetaMin, RTetaMax]
WTGTRQ_A  omega_ref = lag(f(lag(Pe, Tp)), Twref)  (f: the four-point power-speed table)
          Tref = PI(Kpp, Kip) on (Tflag ? (Pref0 - Pe_filt)/omega_g : omega_g - omega_ref) within [Temin, Temax],
          integral frozen in a voltage dip; Pref0 is the plant controller's Pref, or P0

The drive train's torques are held over a step and its linear part is advanced by its exact zero-order hold, from the matrix exponential of the augmented [[A, B], [0, 0]] (scaling and squaring of the Taylor series in plain arithmetic), so the discrete torsional mode is exact: forward Euler would grow an undamped mode by |1 + j w dt| every step (about 36 times over 10 s at 2 Hz and 5 ms). A type 3 unit starts at the speed its power-speed table gives for P0, with the pitch at WTGAR_A's theta0 (inside the pitch limits), the shaft twist carrying the steady torque, and the pitch's initial angle in its speed integral. The pitch controller compares the REEC power order with the REEC power reference after the speed multiplication. WTGTRQ_A's TRATE must equal the unit's MBASE (or be 0): the scaling between the turbine and machine bases is not publicly specified, so a different value is refused rather than guessed.

DER_A (aggregated distributed energy resources; P. Pourbeik, Proposal for DER_A model, WECC REMTF memo, revised 6/19/19, public: Fig. 2, Fig. 3, the Appendix pseudo code and Table 1). It stands alone (no REGC/REEC/REPC) and is driven by DerAState.

DER_A   Vt_filt = lag(Vt, Trv);  Iqv = clamp(Kqv db(Vref0 - Vt_filt, dbd1, dbd2), Iql1, Iqh1)   (always active)
        s1 = lag(Pord, Tp)  (the power feedback is the power order);  s2 = lag((Pflag ? tan(pf0) s1 : Qref) / Vt_filt, Tiq)
        Iqcmd = clamp(s2 + Iqv, -Iqmax, Iqmax);  Frq_filt = lag(f, Trf);  droop = Ddn min(df, 0) + Dup max(df, 0)
        Pord = lag(rate-limited [Freq_flag ? PI(Kpg, Kig) on clamp(Pref - s1 + droop, femin, femax) : Pref], Tpord)
        Ipcmd = clamp(Pord / Vt_filt, Ipmin, Ipmax)    (Q or P priority; Ipmin = -Ipmax for storage, typeflag = 0)
        m = lag(Vrfrac multiplier of Vt_filt, Tv) when Vtripflag = 1;  m = 0 once the frequency trip has acted
        Iq = lag(m Iqcmd, Tg);  Ip = lag(m Ipcmd, Tg) with the rrpwr rise limit (and its charging mirror)

The partial voltage trip is the memo's Appendix pseudo code on Vt_filt: between vl0 and vl1 the multiplier is (V - vl0)/(vl1 - vl0); after the voltage stays below vl1 for more than tvl1 the trip latches, Vmin is taken at that instant, and on recovery the multiplier is Vrfrac (vl1 - Vmin)/(vl1 - vl0) + (Vmin - vl0)/(vl1 - vl0) (the tripped part recovers Vrfrac of itself); below vl0 for more than tvl0 the unit trips for good. The high side mirrors it (vh1, vh0, tvh1, tvh0, Vmax); the two multipliers multiply. The frequency trip (Ftripflag) acts after the filtered frequency stays below fl for tfl or above fh for tfh, and reads nominal while Vt_filt <= Vpr. The memo's voltage source behind Xe is a numerical interface device: GridSim solves the current-source interface to its fixed point, so Xe has no effect (it is range-checked and named in a note). A start must have vl1 < V0 < vh1 (memo note 9); with Kqv not zero, V0 - Vref0 must be inside the deadband: the memo has the software move Vref0 with a warning, GridSim refuses instead (Vref0 = 0 means the initial voltage). PSS/E's DERA1 / DERAU1 record order is not in any public source, so those records are refused by name; a DYR file gives DER_A as a 'DER_A' record with the 48 values of the memo's Table 1, in that order.

REGC_B, REEC_D and the voltage-source interface (P. Pourbeik, Proposal for new features for the renewable energy system generic models, WECC REMWG memo Rev. 27b, 2/16/23, public: REGC_B Fig. 1 and Table 1, REEC_D Fig. 3; the full REEC_D parameter list is Table 5 of the EPRI REGC_B/REEC_D test protocol, memo to the WECC REMTF, 8/17/2020). REGC_B replaces REGC_A's current source by a voltage source behind re + jXe; REEC_D extends REEC_A. Either REEC_D or REEC_A/B/C may drive either generator model.

REGC_B   Iqx = lag(Iqcmd, Tg) with REGC_A's Iqrmax / Iqrmin rate limits;  Vf = lag(|Vt|, Tfltr), vp = max(Vf, 0.01)
         s1 = lag(RateFlag ? Ipcmd vp : Ipcmd, Tg), a rising magnitude limited to rrpwr (either sign: a store charging
              recovers at -rrpwr);  Ip = RateFlag ? s1 / vp : s1
         E target (terminal-voltage frame: d along Vt, Vtq = 0, id = Ip):  |Vt| + (re + jXe)(Ip - j Iqx)
         Ed, Eq = lag(target, Te)
         network: source (Ed + j Eq) e^{j theta} behind Z = re + jXe, theta the angle of Vt in the SAME network solution;
                  terminal current I = (E e^{j theta} - V)/Z, above Imax limited on the frame axis with priority pqflag
                  (Q: Iqx clamped to +-Imax, then Ip to +-sqrt(Imax^2 - Iqx^2); P: the other way round);
                  a converter blocked by REEC_D passes no current
REEC_D   Vt_filt = lag(Vt, Trv); Voltage_dip from Vt_filt (Vdip, Vup);  Vcomp = lag(Vcmpflag ? |Vt - (rc + jXc) It| : Vt + Kc Qgen, Tr1)
         Q path as REEC_A on Vcomp; Iqinj = clamp(Kqv db(Vref0 - Vt_filt, dbd1, dbd2), Iql1, Iqh1), always active
         Iqcmd held after a dip for |Thld| (Thld > 0: its last dip value; Thld < 0: Iqfrz); Ipcmd and Ipmax held for Thld2
         VDLq, VDLp: ten-point tables (a negative VDLq gives Iqmin = Iqmax < 0); Ipmin = -Ke Ipmax
         blocking: Vt_filt <= vblkl or >= vblkh sets every current limit to 0 until Tblk_delay after it returns; REGC_B then
                  passes no current at once (the memo's link from REEC_D to the generator)

The Norton admittance MBASE/SBASE / (re + jXe) is stamped on the unit's bus and the unit injects I + y V. Each step the unit's interface is solved EXACTLY with the network (Regcb.SolveWithNetwork, through the kernel's opt-in IRmsNetworkSolvedConverterModel path): from the second pass of the converter iteration on, the kernel gives the unit the Thevenin view of its node, V c1 = a + c2 I with a the node voltage without the unit's own injection, c1 = 1 - Zdd y, c2 = Zdd MBASE/SBASE and Zdd the driving-point impedance of the stamped network (one network solve per such node, once per network stage). Writing V = x e^{j phi} turns the frame condition into one scalar equation, |x c1 - c2 L((E - x)/Z)| = |a|, phi = arg a - arg(x c1 - c2 L), with L the limit. Between the break points of the limit it is a quadratic (unlimited or saturated: closed form) or smooth (partly limited: a 24-point scan and bisection to the last bit). Of its roots the one whose angle is nearest the last committed angle is taken. Where no root exists (a bolted fault near the terminal while the source still has its quadrature part Xe Ip, so no terminal angle is consistent) the frame is held at the last angle, as a phase-locked loop freezes, and the limited current is solved in closed form in that frame. With several REGC_B units each pass takes one Newton step on their injections, using each unit's 2 x 2 sensitivity to a (two extra local solves) and the network columns between their nodes; one unit needs no Newton step. The kernel's 1e-10 pu convergence test is unchanged, and a run with no REGC_B unit takes the historical iteration line for line. REGC_A units keep plain substitution, but when a step's iteration hits the 50-pass cap the kernel restarts that step from its starting voltages with every REGC_A unit solved exactly too (CurrentSourceNetworkSolver: the injected frame current Ip LVACM(x) - j HVRCM(x) is affine in the terminal magnitude between Lvpnt0, Lvpnt1, Volim and the Iolim point, so the frame equation is a quadratic per piece), and counts the step in Result.ConverterRescuedSteps; a step that converges keeps its historical numbers. On IEEE 118 with four large REGC_A units and a bolted fault at bus 30, substitution alone left 95 steps at the cap; with the rescue none. Plain substitution, which the other converter models use, does not converge for REGC_B on a weak node: with the limit or blocking acting, the y V part is fed back with gain |Zth/(Zth + Ze)| and the limited current's free component with gain about |Zth/Ze|.

Because the source sits in the terminal frame of each solution, a terminal turning at an off-nominal frequency leaves no error: on a Thevenin source turning at +1 % for 2000 steps P and Q stay within 1e-12 pu (holding the source at the start-of-step angle instead leaves |E||V| 2 pi f0 df dt / |Z|, 0.094 pu at 1 %, 5 ms and Xe = 0.2). The states advance once per step from the start-of-step terminal voltage with the commands held, so a change of terminal voltage magnitude moves the current at once, the voltage-source behaviour REGC_B exists for.

REGFM_A1 (droop grid-forming inverter; W. Du et al., PNNL-35110, Model Specification of Droop-Controlled, Grid-Forming Inverters (REGFM_A1), September 2023, public: Fig. 1-5, Table 1), driven by RegfmA1State:

REGFM_A1  Pinv = lag(P, TPf), Qinv = lag(Q, TQf), Vinv = lag(|V|, TVf)            (P, Q at the terminal, MBASE)
          d omega = omega0 (mp (Pref - Pinv) + dPmax + dPmin),  delta' = d omega
          dPmax = min(0, kppmax (Pmax - Pinv) + xPmax), xPmax' = kipmax (Pmax - Pinv) <= 0;  dPmin mirrors it
          Vcmd = Vref + mq (Qref - Qinv) + dQmax + dQmin                           (dQ limits as dP, on Qinv)
          VFlag 1: Edroop = PI(kpv, kiv) on (Vcmd - Vinv) in [Emin, Emax];  VFlag 0: Edroop = clamp(Vcmd, Emin, Emax)
          network: I = (Edroop e^{j delta} - V)/(j XL); |I| > ImaxF -> I = ImaxF I/|I| (the angle kept, Fig. 4)

Without a plant controller Pref, Qref and Vref keep the values that hold the solved point; omega0 is data and must agree with 2 pi f0 of the case to 0.1 %; nothing is frozen while the current limit acts (the specification is silent).

Record names. No public source gives the PSS/E record orders of REGCB1, REECDU1, REGFMA1 or DERA1, so GridSim refuses those names with the reason and reads WECC-named records in the order of the public specification tables: 'REGC_B' (Table 1 of the Rev. 27b memo, 11 values), 'REEC_D' (six flags, then the 78 values of Table 5 of the EPRI protocol), 'REGFM_A1' (the 22 data values of PNNL-35110 Table 1, without the three set points the power flow gives) and 'DER_A' (the 48 values of the DER_A memo's Table 1). REGFM_B1, REPC_B and REPC_C are not modelled: REGFM_B1's public text leaves its steady-state current limiter and several units unspecified, REPC_B has no public block diagram, and REPC_C's shunt switching needs controller-to-shunt data no case format carries.

From a DYR file. PsseDyrRenewables maps REGCA1, REECA1, REECB1, REECCU1, REPCA1, WTDTA1, WTARA1, WTPTA1, WTTQA1, DER_A, REGC_B, REEC_D and REGFM_A1 (and the V33 user-model names, the WECC names and USRMDL records) value for value, range-checks every parameter (REPCA1's regulated bus must be a bus of the RAW case and its flow branch a two-terminal branch of it, found by its buses and circuit identifier), and returns the chains in PsseDyrResult.Renewables; the CLI carries them to stability --rms (see manual ch. 2 and ch. 15).

Machines and converters share one network. With the retained admittance partitioned machines-then-converters, [Ymm Ymc; Ycm Ycc] (ConverterNetwork):

Vc  = Ycc^-1 * (Ic - Ycm*E)
Im  = Yeff*E + Ymc*Ycc^-1*Ic,         Yeff = Ymm - Ymc*Ycc^-1*Ycm

A singular Ycc (a retained converter bus connected to nothing) throws ArgumentException rather than simulating on a fabricated inverse. Each network stage is partitioned once.

Algorithm

Initialisation from a solved case

SubtransientInit.FromSolvedCase(model, result, data, faultBusId, convertersAsCurrentSources) builds the Prepared fleet. It calls result.RequireConverged("Subtransient initialisation") first and throws NonConvergedStateException on a power flow that did not converge. Then:

  1. Classify generators. A generator is held when it is PowerFlowOnly, or is not a converter and has H <= 0; a converter when IsConverterInterfaced or its data carries a WECC chain (SubtransientInit.IsConverterUnit; unless convertersAsCurrentSources is false); otherwise a machine. With no machine the call throws InvalidOperationException. data must have one entry per generator.
  2. Island references. An island with no integrable machine gets a synthetic stiff source at its slack bus (else a PV bus): H = 1e4 s, all reactances 1e-3 pu, T'do = 8, T''do = 0.03, T'qo = 0.4, T''qo = 0.05 s (SubtransientInit.IslandReference*). References are excluded from the synchronism test.
  3. Saliency gate. X''d and X''q must agree to 1e-9 relative (SubtransientSaliencyRelativeTolerance), because only X''d is folded into the network; otherwise it throws ArgumentException.
  4. Per-unit. For a machine of rating MBase with unit-transformer reactance xt (Generator.UnitTransformerXPu, floored at 0): X_sys = (X + xt) * BaseMva/MBase for every reactance, H_sys = H * MBase/BaseMva.
  5. Terminal condition. Co-located units split the solved bus generation: active power by scheduled Pg (equally when |sum Pg| <= 1e-9, MinScheduledPowerMw), reactive power by capability Qmax - Qmin (else MBase); a lone unit takes all of it. With Vt the solved bus voltage and S the unit's share: It = conj(S/Vt).
  6. Rotor angle. delta0 = arg(Vt + j*Xq*It). Placing the rotor on the q-axis phasor makes Vd = Xq*Iq, the condition that zeroes the q-axis flux derivative.
  7. dq quantities.
Vq = Re(Vt)*cos(d) + Im(Vt)*sin(d)        Vd = Re(Vt)*sin(d) - Im(Vt)*cos(d)
Iq = Re(It)*cos(d) + Im(It)*sin(d)        Id = Re(It)*sin(d) - Im(It)*cos(d)
E'q  = Vq + X'd*Id      E'd  = Vd - X'q*Iq
E''q = Vq + X''d*Id     E''d = Vd - X''q*Iq
Efd  = E'q + (Xd - X'd)*Id + E''q*Se(|E''|)
Pm   = Vd*Id + Vq*Iq

Every one of the four flux derivatives and the swing derivative is zero by construction. 8. Network. Loads become constant shunts conj(S)/|V|^2 with |V|^2 floored at 1e-9. Each machine enters as 1/(j*X''d) between its terminal and an internal node; held units enter as a negative load -conj(S)/|V|^2 at their bus; each grid-forming converter adds its Norton admittance. At every size the full network is kept as a SparseRmsNetwork (Prepared.Network, Prepared.NetworkFaulted) and no dense matrix is formed, so a 9-bus case and gb-full run the same arithmetic. The dense Kron reduction into YReduced (KronReduction.Reduce, machines first, then retained converter buses) survives only as a test oracle (SubtransientInit.DenseKronReferenceScope, internal); no production path can select it. For a fault at faultBusId the faulted network is the same with BoltedFaultShuntPu = 1e7 pu added at that bus.

SubtransientInit.Prepared carries H, Damping, Pm, Efd, Delta0, Eqp0, Edp0, Eqpp0, Edpp0, the networks, the converter units, the held-unit names and the island references.

The RMS integrator

MultiMachineSubtransient.Simulate integrates the fleet with a fixed step dt for round(duration/dt) steps. Step k, at t = k*dt:

  1. Network stage. The network in force is the last RmsNetworkStage in the list (which must be in time order; it is not sorted) whose AtSeconds satisfies t + 1e-6*dt >= AtSeconds (StageTimeToleranceSteps = 1e-6); before the first stage it is the base network. An event therefore takes effect on the first step at or after it, and an event time one rounding unit above its grid point (0.1 + 0.14 against 48*0.005) still lands on that grid point.
  2. EMFs and currents. E from (E''q, E''d, delta); Im = network.Solve(E, Ic). With converters, the phase-locked currents and their terminal voltages are iterated to the algebraic fixed point (at most 50 iterations, converged when the largest change of a converter voltage is below 1e-10 pu, MaxConverterIterations, ConverterVoltageTolerancePu); a step that does not settle is counted in Result.ConverterIterationFailures, never hidden. The machine currents are then re-solved against the committed converter currents.
  3. Record and judge. The state is appended to the traces and synchronism is tested (below).
  4. Field. For machine i with a controller, Vt = E - j*X''*Im and Efd_i = controller.Step(Vref_i - |Vt|, omega_i, dt); without one the field is the seeded Efd_i. With no Vref supplied, each controlled machine's reference is set once, on the first step, to |Vt| + controller.EquilibriumErrorPu(Efd), so the fleet starts at equilibrium; this needs the base network in force at t = 0 and throws InvalidOperationException if any network stage other than the base network is in force at t = 0.
  5. Fluxes. With the start-of-step Id, Iq and EMFs:
E'q  <- lag_{T'do }( Efd - (Xd - X'd)*Id - E''q*Se(|E''|) )
E''q <- lag_{T''do}( E'q - (X'd - X''d)*Id )
E'd  <- lag_{T'qo }( (Xq - X'q)*Iq - E''d*Se(|E''|)*(Xq - Xl)/(Xd - Xl) )
E''d <- lag_{T''qo}( E'd + (X'q - X''q)*Iq )
|E''| = sqrt(E''q^2 + E''d^2)

The saturation is the PSS/E GENROU form: Se is evaluated on the subtransient flux magnitude |E''| at the start of the step, and applied on both axes, the q-axis increment scaled by (Xq - Xl) / (Xd - Xl), where Xl is the stator leakage reactance (0 when the data gives none, the leakage-free limit Xq / Xd). An unsaturated machine has both increments exactly 0. SubtransientInit seeds the field and the rotor angle with the same terms, so a saturated fleet starts at equilibrium.

  1. Mechanical power. Pm_i = mechanicalPower(i, omega_i) when a governor hook is supplied, else the seeded Pm_i; held across the RK4 stages.
  2. Converter controls advance from the start-of-step terminal voltage.
  3. Swing. Coupled RK4 on (delta, omega) of all machines, with E''q, E''d and the converter currents frozen and Pe_i = Re(E_i conj(Im_i)) re-solved from the network at each of the four stages.

The step is fixed (no error control). The frozen-input splitting of steps 5 and 8 is designed to be first order in the step (no test measures the order), and this is the reason the step is a stated parameter of every result (StudyDefaultStepSeconds = 0.005 s for a study, CctDefaultStepSeconds = 0.002 s for the clearing-time search).

Network solve. IRmsNetwork takes machine EMFs and converter currents and returns machine currents and converter voltages. SparseRmsNetwork, the production network, stamps each machine as a Norton source E/(jX'') behind 1/(jX'') at its terminal and solves the full network by FaultNetworkSystem (sparse LU, factored once per network stage): Im = (E - V_terminal)/(jX''). The test oracle's DenseMachineNetwork multiplies Im = Yred*E with MachineAdmittanceColumns: the product is vectorised across rows and keeps each row's own ascending summation order with no fused multiply-add, so it is bit-identical to the scalar product on every vector width. ConverterNetwork is the oracle's dense form with converter buses retained.

Loss of synchronism. After each step record, with syncCount the machines in the test (all, less the island references) and COI = sum(H_i*delta_i)/sum(H_i) over them, the run is lost when any delta_i is not finite, any omega_i is not finite, or |delta_i - COI| > slipLimitRad (default 2 pi, DefaultSlipLimitRad). The test is written !(|d - COI| <= limit) so a NaN fails it. Once lost the verdict stays lost.

RmsTransientStability.Study(model, result, data, faultBusId, onsetSeconds, clearingSeconds, ...) prepares the fleet with SubtransientInit, schedules a bolted three-phase fault at faultBusId from onsetSeconds and the base network again from onsetSeconds + max(0, clearingSeconds), and integrates durationSeconds (default StudyDefaultDurationSeconds = 10 s) at stepSeconds (default 0.005 s). It requires a converged power flow. An optional exciters list, one RmsExciter? per entry of model.Generators (null holds that field), installs the AVRs. The list must align to the generators, entries for converter or held units must be null, an exciter or a PSS instance may serve one machine only, and each violation throws ArgumentException. With exciters null the study passes no controllers and is bit for bit the held-field study; an all-null list takes the controller path with every field held and is bit for bit the same. No governor enters the study: mechanical power is held at Pm.

CriticalClearingBracket returns a CctBracket (CriticalClearingTimeSeconds is its StableSeconds). The fault is applied at onsetSeconds (default CctDefaultOnsetSeconds = 0.1 s) and cleared m whole steps later, so the trial for m steps clears at m*stepSeconds and runs onset + m*stepSeconds + PostClearWindowSeconds (5 s). The step defaults to 0.002 s, the window to CctDefaultMaxSeconds = 1.0 s, giving M = floor(1.0/0.002 + 1e-6) = 500 whole steps. Because the integrator switches the fault only on whole steps, every clearing time inside one step is the same run; the search is therefore over integers. CctSearch.Run does:

  1. Bisection over 0 .. M for at most iterations halvings (CctDefaultBisectionIterations = 18, which is a cap: 9 halvings reach step resolution at M = 500). No floating-point midpoint is formed. If step 0 loses synchronism the bracket is UnstableAtZero; if step M survives the bracket has no unstable end.
  2. Downward verification of the scanSteps (default CctSearch.DefaultScanSteps = 16) step counts below the stable end. A loss found there means the bisection landed on a stable pocket; the stable end becomes a recorded pocket and the bisection restarts below the loss. After CctSearch.MaxRefinementRounds = 4 such rounds it walks up from step 1 instead, which is exact.
  3. Upward probe of as many step counts above the unstable end; a step that holds again is recorded as the pocket.

Every trial is memoised. The result is the first loss from below: StableSteps is the last step below the first loss and UnstableSteps is the next step. A pocket above it may still hold: on classical case9 bus 2 the search reports 312 ms, and 320 ms holds. CctBracket.NonMonotone is true when a pocket was found (PocketStableSteps), Trials is the number of simulations, and scanSteps = 0 is the plain bisection. The guarantee holds provided no stable pocket is wider than scanSteps steps. The arguments are gated: a non-positive or non-finite step or window, a window shorter than one step, iterations < 1 and scanSteps < 0 throw ArgumentOutOfRangeException. The classical search (ClassicalInit.CriticalClearingBracket) runs the same CctSearch with the classical integrator.

How the CLI exposes the library

gridsim stability <case> --rms runs RunRmsStability (src/GridSim.Cli/Program.cs); the verb's flags are in the CLI reference. Without --dyn-data (a gridsim-dynamics/2 machine data file bound to the case's generators) the CLI builds the machine data from X'd: Anderson-Fouad X'd for case9 (0.0608, 0.1198, 0.1813 pu on the machine base), the fixed 0.30 pu (CliDefaults.SyntheticXdpPu) for every other case, with the ratios of CliDefaults:

Xd = 3.0*X'd    X'q = 1.5*X'd    Xq = 2.5*X'd    X''d = X''q = 0.8*X'd
T'do = 8.0 s    T''do = 0.03 s   T'qo = 0.4 s    T''qo = 0.05 s      D = 0      no saturation

H is the case's own H. The flags that select library models:

Flag Effect
--rms Selects the six-state engine; without it the classical swing runs.
--avr none (default) Field held; the study is the held-field study.
--avr sexs One SEXS per synchronous machine: Ta = 0.1, Tb = 1.0, K = 100, Te = 0.05, [Emin, Emax] = [0, 8].
--avr ieeet1 One IEEET1 per synchronous machine: Ka = 50, Ta = 0.02, Ke = 1.0, Te = 0.2, Kf = 0.05, Tf = 1.0, [Vrmin, Vrmax] = [-10, 10], no saturation.
--pss Adds one PSS1A to each exciter: Ks = 20, Tw = 10, T1 = T3 = 0.15, T2 = T4 = 0.05, [Vsmin, Vsmax] = [-0.1, 0.1].

A machine receives an exciter when it is not power-flow-only, not converter-interfaced and has H > 0; all other entries are null. --avr accepts none, sexs or ieeet1 (case-insensitive) and exits 2 with a message for any other value; --avr or --pss without --rms exits 2; --pss without an AVR exits 2. A non-converged base power flow exits 3. A study error (no machines, an exciter the initial field cannot satisfy, a singular converter block) is printed as stability: <message> and exits 2.

The single-study form (--clear <ms>) uses a fault onset of 0.1 s, step 0.005 s and a duration of 3.0 s (CliDefaults.FaultOnsetS, RmsStepS, RmsDurationS); the clearing-time forms use the CctSearch defaults above. The default fault bus is 7 for case9, else the first non-generator bus. Every case runs on the sparse network. The RMS study integrates at the case's own nominal frequency (GridModel.FrequencyHz: 60 Hz for case9, 50 Hz for the GB cases); the library's f0 argument overrides it.

RMS event studies

RmsTransientStability.StudyEvents(model, result, data, events, f0, stepSeconds, durationSeconds, slipLimitRad, exciters) drives the same machines, control library and sparse network with a list of scheduled events (src/GridSim.Core/Dynamics/Models/RmsEvents.cs):

Event Spec form (RmsEventSpec.Parse) Effect
RmsBusFault fault:BUS@t bolted three-phase fault (BoltedFaultShuntPu) at the bus until cleared
RmsFaultClear clear:BUS@t removes that bus's fault shunt
RmsBranchTrip trip:BRANCH@t takes the branch (0-based index) out of service
RmsBranchReclose reclose:BRANCH@t returns a tripped branch to service
RmsLoadStep load:BUS:PMW:QMVAR@t adds a constant-admittance load step; steps on one bus add
RmsGeneratorTrip gentrip:GEN@t disconnects the machine (0-based generator index), zeroes its mechanical power and leaves it out of the synchronism verdict

Every event takes effect at the first integration step whose time has reached its AtSeconds and stays in effect unless a later event undoes it. The events are taken in time order, input order for equal times. At each distinct event time a network stage is built from the base network's own stamps (SubtransientInit.Prepared.Basis): the Y-bus of the branches still in service (rebuilt by YBus.BuildSparse once any branch is out), the load, held-unit and converter stamps, the Norton stamp of every machine still connected, the accumulated load steps and a fault shunt on every bus faulted at that time. Every stage is built and factored before the run starts, so a stage that cannot be solved (a branch trip that leaves a bus with no path to earth) fails before any integration. The study refuses, naming the event: an empty list or a null entry; a time that is not finite, not after t = 0 or after the run's end; an unknown bus; a branch index out of range, already out of service or tripped twice; a second fault on a faulted bus or a clearance with no fault in place; a load step that is not finite or zero in both parts; a generator index out of range, a unit that is not an integrated synchronous machine, a machine tripped twice, or a trip of every machine. A fault and its clearance reproduce the single-fault Study bit for bit.

RmsTransientStability.CriticalClearingBracketEvents(model, result, data, faultBusId, clearingActions, background, ...) runs the shared CctSearch on event studies: each trial places the fault at the onset, its clearance m steps later, re-times every clearing action (a branch trip, typically) to that instant, keeps the background events as given, and runs over onset + clearing + PostClearWindowSeconds. A clearing action that is itself a fault or a clearance is refused.

The CLI exposes both (stability <case> --rms):

  • --events <list> runs one StudyEvents with the comma-separated spec list. It takes no --fault-bus, --clear or --clear-by-trip, and no --screen. The run lasts CliDefaults.RmsDurationS (3.0 s) or 3.0 s past the last event, whichever is later, at the 0.005 s step; it prints the events in time order and the verdict.
  • --clear-by-trip <i,j,...> clears the fault at --fault-bus by tripping the listed branches: with --clear <ms> it is one event study at that clearing time; without it, the CriticalClearingBracketEvents search.
  • --events-out <dir> (with --rms --events only; exit 2 otherwise) writes the event study's export (RmsEventsExport, src/GridSim.Core/IO/RmsEventsExport.cs): rms-events-machines.csv (t_s,trace,bus,delta_rad,speed_pu,eqp_pu,edp_pu,eqpp_pu,eddp_pu, every machine trace including island references, each double in round-trip form), rms-events-converters.csv when the fleet has converters (t_s,converter,name,bus,v_pu,p_pu,q_pu,ip_pu,iq_pu,in_dip_mode), rms-events.json (schema gridsim-rms-events-export/1: case, nominal frequency, step, duration, samples, everySteps, samplesWritten, the events in time order, the verdict, the converter-iteration failures, the machine and converter lists, the file names, provenance and the indicative flag with its note) and run-metadata.json. Both CSVs open with the run header lines and a # provenance: line; the export is tagged Synthetic (a model trajectory, not a record), and its note says whether the machine data was synthesised (INDICATIVE) or came from a --dyn-data file tagged Recorded or DerivedFromRecorded throughout. An output error exits 1; the verdict is unchanged.
  • --events-every <N> (with --events-out only) writes every N-th integration step (k = 0, N, 2N, ...) to the CSVs; N is a whole number from 1 to RmsEventsExport.MaxEverySteps (1,000,000), default 1 (every step). The summary records everySteps and samplesWritten. A full-resolution export holds one row per machine per step (a 3 s run at 0.005 s is 601 samples per machine).

The captured critical-clearing-time screens for case9 (fault at each generator bus, worst first) show the effect of the library models on the same synthesised machines:

Capture Field Bus 3 (ms) Bus 2 (ms) Bus 1 (ms)
docs/_captures/stability/stability-case9-rms-screen.txt held 320 358 530
docs/_captures/stability/stability-case9-rms-sexs-screen.txt SEXS 340 410 694
docs/_captures/dynlib/stability-case9-rms-avr-ieeet1-screen.txt IEEET1 336 398 636
docs/_captures/dynlib/stability-case9-rms-avr-sexs-pss-screen.txt SEXS + PSS1A 342 410 788

The exciters raise every clearing time and the PSS raises bus 1 further. The values are indicative because the machine data is synthesised.

A complete captured error pair:

$ gridsim stability case9 --rms --avr foo
error: --avr expected none, sexs or ieeet1 but got 'foo'
[exit 2]
$ gridsim stability case9 --rms --pss
error: --pss needs an AVR (--avr sexs or --avr ieeet1).
[exit 2]

Parameters and defaults

Constructor defaults are those of the library; the CLI values are in the previous section. "-" means no default: the caller must supply the value.

Machine data (SubtransientInit.MachineData, SubtransientMachine.Parameters)

Name PSS/E symbol Unit Default Validation
H H s, machine base - > 0 or the unit is held
Damping D pu power / pu speed - (CLI 0) none
Xd Xd pu, machine base - none
Xdp X'd (Xpd) pu, machine base - > 0 in the SMIB Parameters
Xdpp X''d (Xppd) pu, machine base - > 0 in the SMIB Parameters; equal to Xqpp in the fleet
Xq Xq pu, machine base - none (the one-axis SMIB Parameters requires > 0)
Xqp X'q (Xpq) pu, machine base - > 0 in the SMIB Parameters
Xqpp X''q (Xppq) pu, machine base - > 0 in the SMIB Parameters; equal to Xdpp in the fleet
Tdop T'do (Tpdo) s - > 0
Tdopp T''do (Tppdo) s - > 0
Tqop T'qo (Tpqo) s - > 0
Tqopp T''qo (Tppqo) s - > 0
Saturation S(1.0), S(1.2) dimensionless null (none) 0 <= S1 < S12 when S1 > 0
Xl Xl pu, machine base 0 finite, >= 0 and < X''d; used only by the q-axis saturation scale
ExternalReactance (SMIB) - pu - >= 0
InfiniteBusVoltagePu (SMIB) - pu - none

The stator is not resolved below X''. The leakage reactance Xl (default 0, finite, at least 0 and below X''d) enters only the q-axis saturation scale (Xq - Xl)/(Xd - Xl). Saturation acts on the flux magnitude |E''| on both axes, as GENROU applies it.

Blocks and control models

Model Parameter (code) Symbol Unit Default Rule
FirstOrderLag gain, timeConstantSeconds, min, max K, T -, s, pu min = -inf, max = +inf max >= min
LeadLag leadSeconds, lagSeconds Ta, Tb s - Ta >= 0, Tb > 0
Washout timeConstantSeconds T s - > 0
Integrator gain, min, max K 1/s -inf, +inf max >= min
PiController proportionalGain, integralGain, min, max Kp, Ki -, 1/s -inf, +inf max >= min
Tgov1 droopPu R pu - > 0
valveTimeSeconds T1 s - <= 1e-12 is instant
reheatLeadSeconds, reheatLagSeconds T2, T3 s - T2 >= 0, T3 > 0
turbineDampingPu Dt pu 0 none
valveMinPu, valveMaxPu Vmin, Vmax pu 0, +inf max >= min
Ieeeg1 droopPu R (1/K) pu - > 0
governorLeadSeconds, governorLagSeconds T2, T1 s - T2 >= 0, T1 > 0
valveTimeSeconds T3 s - <= 1e-12 is instant
chestSeconds, reheatSeconds, crossoverSeconds, lpSeconds T4, T5, T6, T7 s - <= 1e-12 is instant
k1, k3, k5, k7 K1, K3, K5, K7 - 1, 0, 0, 0 none
valveMinPu, valveMaxPu Pmin, Pmax pu 0, +inf max >= min
HydroGovernor permanentDroopPu Rp (R) pu - > 0
transientDroopPu Rt (r) pu - finite, >= 0
resetTimeSeconds Tr s - > 0
gateTimeSeconds Tg s - finite; <= 1e-12 is instant (the gate and transient-droop loop is then solved exactly, g = (err + Rt xL) / (Rp + Rt)); a finite Tg below dt / ln(1 + Rt/Rp) is refused at the step, because the explicit step would ring or diverge
waterTimeSeconds Tw s - > 0
gateMinPu, gateMaxPu GMIN, GMAX pu 0, +inf max >= min
Sexs leadSeconds, lagSeconds TA, TB s - TA >= 0, TB > 0
gain K - - > 0
exciterTimeSeconds TE s - <= 1e-12 is instant
fieldMinPu, fieldMaxPu EMIN, EMAX pu -inf, +inf Emax >= Emin (Sexs, RmsExciter)
Ieeet1 regulatorGain KA - - > 0
regulatorTimeSeconds TA s - <= 1e-12 is instant
exciterConstant KE - - none
exciterTimeSeconds TE s - > 0
feedbackGain, feedbackTimeSeconds KF, TF -, s - TF > 0
regulatorMinPu, regulatorMaxPu VRMIN, VRMAX pu -inf, +inf Vrmax >= Vrmin (Ieeet1, RmsExciter)
saturationA, saturationB Aex, Bex (fit of E1, SE(E1), E2, SE(E2)) -, 1/pu 0, 0 Aex >= 0
Pss1a gain Ks - - none
washoutSeconds Tw s - > 0
lead1Seconds, lag1Seconds T1, T2 s - T2 > 0, or both 0 (bypass)
lead2Seconds, lag2Seconds T3, T4 s - T4 > 0, or both 0 (bypass)
outputMinPu, outputMaxPu VSMIN, VSMAX pu -inf, +inf Vsmax >= Vsmin

Converter plant (RmsConverterParameters)

Name Symbol Unit Default
Tg Tg (REGC_A) s 0.02
Tr voltage measurement lag s 0.02
Vdip Vdip pu 0.9
Kqv reactive boost gain - 2.0
Imax current limit k pu on rating Generator.DefaultConverterFaultCurrentPu = 1.2; the unit's own EffectiveConverterFaultCurrentPu in a fleet
LvPnt0, LvPnt1 Lvpnt0, Lvpnt1 pu 0.4, 0.8
RampUpPuPerSecond rrpwr pu/s on rating 10.0
HoldSeconds dip hold s 0.0
BlockInDip LCC blocking - false (true when k = 0)
GridForming - - false
VirtualInertiaH, DampingPu Hv, Dv s, pu on rating 2.0, 20.0
VirtualReactancePu Xv pu on rating 0.15
VoltageGain Kv 1/s 2.0
NominalHz - Hz 50.0

Study, search and network constants

Constant Value Source
StudyDefaultStepSeconds 0.005 s RmsTransientStability
StudyDefaultDurationSeconds 10.0 s RmsTransientStability
CctDefaultStepSeconds 0.002 s RmsTransientStability
CctDefaultMaxSeconds 1.0 s RmsTransientStability
CctDefaultOnsetSeconds 0.1 s RmsTransientStability
PostClearWindowSeconds 5.0 s RmsTransientStability
CctDefaultBisectionIterations 18 RmsTransientStability
DefaultSlipLimitRad 2 pi rad RmsTransientStability
CctSearch.DefaultScanSteps 16 CctSearch
CctSearch.MaxRefinementRounds 4 CctSearch
StageTimeToleranceSteps 1e-6 steps MultiMachineSubtransient
MaxConverterIterations 50 MultiMachineSubtransient
ConverterVoltageTolerancePu 1e-10 pu MultiMachineSubtransient
BoltedFaultShuntPu 1e7 pu SubtransientInit
SubtransientSaliencyRelativeTolerance 1e-9 SubtransientInit
MinVoltageSquaredPu 1e-9 pu SubtransientInit
IslandReferenceH, IslandReferenceX 1e4 s, 1e-3 pu SubtransientInit
RmsEventsExport.MaxEverySteps 1000000 steps src/GridSim.Core/IO/RmsEventsExport.cs
Ieeet1.ExciterPoleAtOriginTolerance 1e-12 Ieeet1
ControlBlocks.InstantThresholdSeconds 1e-12 s ControlBlocks

Invariants

Test files are in tests/GridSim.Tests/. "To N decimals" is the xUnit Assert.Equal(expected, actual, N) precision, that is |expected - actual| < 0.5 * 10^-N; "bit for bit" is == on every sample.

Blocks (ControlBlocksTests) - A lag step response equals K*(1 - exp(-t/T)) to 10 decimals at every sample (FirstOrderLag_step_response_matches_the_analytic_exponential_to_epsilon). - T = 0 is a bit-exact gain (FirstOrderLag_with_zero_time_constant_is_a_bit_exact_gain); Ta == Tb is a bit-exact pass-through (LeadLag_with_equal_time_constants_is_a_bit_exact_passthrough). - Lead-lag has unity DC gain and leads (LeadLag_has_unity_dc_gain, LeadLag_with_lead_over_lag_leads_the_input); the washout blocks DC and passes a change (Washout_blocks_dc_and_decays_to_zero, Washout_passes_a_change_unattenuated_then_decays). - Limits are non-windup: pinned at the limit, then below it on the very next reversed step (FirstOrderLag_non_windup_limit_holds_and_releases, Integrator_non_windup_limit_clamps_and_releases). - A mixed block chain run twice is bit for bit identical (Blocks_are_bit_for_bit_deterministic).

Control models (ControlBlocksTests, ControlModelFamiliesTests, R083Pss1aStageBypassTests) - TGOV1 is stationary to 13 decimals at dw = 0 and its settled droop matches -1/R - Dt to 6 decimals; its valve pins at Vmax (Tgov1_is_stationary_at_its_equilibrium, Tgov1_steady_droop_matches_the_analytic_gain, Tgov1_valve_limits_cap_the_response). - GAST (GastGovernorTests) is stationary to the bit at dw = 0; a held speed step follows the hand closed form of its two cascaded zero-order-hold lags to 1e-13; on the temperature limit it settles at AT for every KT and on the valve limit at VMAX; a start above AT or outside the valve limits is refused (Gast_is_stationary_at_its_equilibrium_to_the_bit, Gast_speed_step_follows_the_closed_form_of_its_two_cascaded_lags, Gast_on_its_temperature_limit_settles_at_AT_whatever_KT). - EXAC1 and ESAC1A (AcExciterTests): FEX and the saturation fit match hand values; the initial VE gives the field back on every FEX branch; the linear reduction follows the closed form of its two lags to 1e-13; the full model settles on the operating point solved by bisection; a reduced EXAC1 is IEEET1 (KE = 1, no saturation) to the bit through a whole case 9 study (A_reduced_exac1_is_ieeet1_in_the_rms_kernel_to_the_bit, The_full_exac1_is_stationary_and_settles_on_the_hand_solved_operating_point). - ESST4B (Esst4bTests): VE matches complex arithmetic done by hand; it starts at rest from its first measurements; its integrators force Efd = VRMAX/KG on the outer limit and VMMAX*VB on the inner one; VBMAX caps VB; case 9 stays at rest undisturbed (The_power_source_voltage_matches_complex_arithmetic_done_by_hand, The_integrators_force_efd_to_vrmax_over_kg_or_to_the_inner_limit). - SEXS holds K*Verr, clamps at the ceiling and starts at equilibrium (Sexs_steady_field_voltage_is_gain_times_error, Sexs_field_limits_clamp_the_ceiling, Sexs_initializes_to_equilibrium_and_holds). - IEEET1 reduces to a two-lag AVR without saturation or feedback, honours its ceiling, and saturation lowers the field a given error sustains (Ieeet1_reduces_to_a_two_lag_avr_without_saturation_or_feedback, Ieeet1_ceiling_limits_and_saturation_raises_the_required_regulator_voltage). - IEEEG1 is stationary, has droop -1/R and reduces to one stage at K1 = 1 (Ieeeg1_is_stationary_and_has_the_expected_droop, Ieeeg1_reduces_to_a_single_stage_when_k1_is_one). - The hydro governor is stationary and shows the inverse response (Hydro_governor_is_stationary_with_permanent_droop, Hydro_water_column_has_the_non_minimum_phase_inverse_response). - PSS1A washes out a sustained input, responds to a change and is limited (Pss1a_washes_out_a_sustained_input, Pss1a_responds_then_decays_and_is_deterministic); a switched-off stage is exactly unity and a zero lag with a non-zero lead is refused (A_switched_off_stage_is_exactly_unity, Both_stages_off_leaves_the_washed_out_gain, A_zero_lag_with_a_non_zero_lead_is_refused).

Machines (OneAxisMachineTests, TwoAxisMachineTests, SubtransientMachineTests, SaturationFieldIncrementTests) - Open-circuit flux decay follows Efd + (E'q0 - Efd)*exp(-t/T'do) to 10 decimals at every sample (Open_circuit_field_step_follows_the_exact_flux_decay_exponential); the q-axis and both subtransient decays do the same (Q_axis_flux_decays_on_the_exact_exponential, D_axis_subtransient_flux_decays_on_the_exact_exponential, Q_axis_subtransient_flux_decays_on_the_exact_exponential). - Reduction chain: the two-axis machine with X'q = Xq equals the one-axis machine to 10 decimals; the equilibrium, stator currents and power of the subtransient machine with X'' = X' equal those of the two-axis machine to 12 decimals at one operating point (no trajectory is compared) (With_transient_q_reactance_equal_to_synchronous_it_reduces_to_the_one_axis_machine, With_subtransient_reactances_equal_to_transient_it_reduces_to_the_two_axis_machine). - With Xd = X'd = Xq and a held field the one-axis swing conserves H*ws*omega^2 - Pm*delta - Pmax*cos(delta) to 1e-4 and oscillates at the analytic mode within 1 % of the period (Round_rotor_constant_field_swing_conserves_energy, Small_signal_oscillation_matches_the_analytic_SMIB_mode); the reluctance power equals its closed form exactly (Salient_pole_reluctance_power_matches_the_closed_form). - Every machine started at its equilibrium is stationary (Started_in_equilibrium_the_machine_is_stationary in OneAxisMachineTests, TwoAxisMachineTests and SubtransientMachineTests); the one-axis machine also with its AVR closed (Avr_holds_the_machine_stationary_at_its_regulated_setpoint), including saturated (Saturated_machine_started_in_equilibrium_is_stationary). - The saturation curve passes through both fit points to 12 decimals and is zero below the knee (Saturation_curve_fits_its_two_points); the field increment is 0.10 at 1.0 pu and 0.36 at 1.2 pu for a 0.10 / 0.30 curve (Field_increment_at_the_fit_points_is_the_PSSE_standard); a saturated equilibrium needs exactly the saturation term more field (Saturation_raises_the_equilibrium_field_by_the_saturation_term), and the seeded fleet carries the same increment as the integrator subtracts (Seeded_field_carries_exactly_the_field_increment, A_saturated_fleet_seeded_from_a_solved_case_stays_at_equilibrium). - Two identical runs are bit for bit equal (Two_identical_runs_are_bit_for_bit_equal in each machine file).

Network interface and multi-machine (SubtransientNetworkInterfaceTests, MultiMachineFluxDecayTests, MultiMachineSubtransientTests, GovernedMultiMachineTests) - With E''d = 0 the interface equals the round-rotor injection to 12 decimals; powers sum to zero on a lossless network; Pe = E''q*Iq + E''d*Id; Vt = |E''| at X'' = 0 (With_no_q_axis_emf_it_reduces_to_the_round_rotor_injection, On_a_lossless_network_the_powers_sum_to_zero, Air_gap_power_matches_the_internal_emf_current_product, Terminal_voltage_with_zero_subtransient_reactance_is_the_internal_emf). - Id = Qe/|E'| equals an independent phasor current solution to 12 decimals (Network_injection_matches_the_phasor_current_solution). - With flat reactances and a held field the six-state fleet reproduces the classical swing over a genuine transient (relative angle to 8 decimals, speed to 9) (Flat_reactances_and_held_field_reduce_to_the_classical_swing). - A governed run with no governor is the classical run bit for bit; an islanded governed pair settles within 1 % of dP/sum(1/R + D) at one common speed (Governed_swing_with_no_governors_is_bit_for_bit_the_classical_swing, Islanded_pair_settles_to_the_analytic_droop_speed). - A two-stage network schedule reproduces the single fault window bit for bit (A_two_stage_schedule_reproduces_a_fault_window). - A per-machine AVR holds each terminal voltage (Per_machine_avr_holds_the_terminal_voltages_stationary).

Initialisation (SubtransientInitTests, SubtransientKernelFixTests) - A fleet seeded from case9 is stationary: speed below 1e-6, angle and E'' unchanged to 5 decimals (Seeded_from_a_solved_case_the_fleet_is_stationary). - With flat reactances the seed equals ClassicalInit to 9 decimals: the same angle, |E''| = |E'|, E'd = E''d = 0 (Flat_reactances_reduce_to_the_classical_init). - Unequal X''d and X''q fail at initialisation; equal ones initialise (Unequal_subtransient_reactances_fail_loud_at_initialisation, Equal_subtransient_reactances_initialise_as_before). - A diverged run is never reported as in synchronism (ConvergenceContractStudyTests.A_diverged_subtransient_run_is_never_in_synchronism); the refusal of a non-converged power flow is the shared RequireConverged helper pinned in ConvergenceContractTests.

Study and search (RmsTransientStabilityTests, RmsCctStepQuantisedTests, CctFirstLossSearchTests, RmsExciterStudyTests, StabilityAvrFlagContractTests, SubtransientKernelFixTests) - Reference comparison: with every reactance equal to X'd the RMS critical clearing time at bus 7 of case9 agrees with the classical one within 0.02 s, and a clearing at half the CCT survives while one at twice it does not (Subtransient_critical_clearing_time_reduces_to_the_classical, A_short_fault_survives_and_a_long_fault_does_not). - The case9 bus 7 CCT is exactly 302 steps, the reported CCT survives a direct study and one step later does not, and dense and sparse networks return an equal CctBracket (Case9_bus7_cct_is_exactly_302_steps, The_cct_survives_in_a_direct_study_and_one_step_later_does_not, Dense_and_sparse_give_the_same_bracket_bit_for_bit). - The classical case9 CCT is the first loss of an exhaustive scan, pockets are flagged, and the RMS bus 7 search is monotone (Classical_case9_cct_is_the_first_loss_of_an_exhaustive_scan_and_pockets_are_flagged, Rms_case9_bus7_is_monotone_and_unchanged); the search fails loud on meaningless arguments (The_search_fails_loud_on_meaningless_arguments, A_window_shorter_than_a_step_or_a_bad_step_fails_loud). - A clearing time one rounding unit high clears on its step; a stage between grid points waits (A_clearing_time_rounded_one_ulp_high_still_clears_on_its_step, A_stage_genuinely_between_grid_points_still_waits_for_the_next_step). - Loss of synchronism is judged on the centre-of-inertia angle (A_spread_between_2pi_and_4pi_is_in_synchronism_for_both_kernels, A_spread_beyond_4pi_is_lost_for_both_kernels). - With an all-null exciter list the study is bit for bit the held-field study (No_exciters_reproduce_the_held_field_study_bit_for_bit); the CCT test compares an omitted list with null, the same code path, so the all-null list on the CCT search is not pinned (No_exciters_reproduce_the_held_field_cct_bit_for_bit); SEXS, IEEET1 and SEXS plus PSS start at equilibrium; after a fault the AVR raises E'q above the held run; a mis-sized list, a shared exciter or PSS, a fault at t = 0 with automatic references, an initial field outside the limits and inverted limits all throw (RmsExciterStudyTests). - The CLI source contains the --avr validation and passes the exciters to every RMS call; these are source-text checks of Program.cs that run nothing (Avr_flag_is_validated_and_none_passes_no_exciters, Every_rms_study_call_receives_the_exciters).

Networks and converters (RmsSparseNetworkTests, SubtransientSolveIntoBitIdentityTests, MachineAdmittanceSimdBitIdentityTests, RmsConverterTests, RmsGridFormingTests) - The sparse production network agrees with the dense Kron oracle within 1e-6 rad on every step and the CCT within 0.005 s (Sparse_network_run_matches_the_dense_kron_run, Sparse_critical_clearing_time_matches_dense); the two are different eliminations of one linear network and are not bit-identical, which is why production uses only the sparse one. - Event studies: a fault and its clearance reproduce the single-fault study bit for bit; the same events give the same bits twice; branch trips, load steps and generator trips move the fleet as expected; bad events are refused by name (Cf4RmsEventTests). The export carries the header, provenance and every sample exactly, lists the events in time order, and decimates exactly (Cf6RmsEventsExportTests). - The allocation-free solve is bit for bit the allocating solve, and every vector tier of the dense product equals the scalar product bit for bit (Trajectories_are_bit_identical_to_the_allocating_kernel, Dense_and_sparse_SolveInto_equal_their_Solve_bit_for_bit, Every_tier_matches_the_scalar_product_bit_for_bit, Dense_rms_runs_are_bit_identical_to_the_scalar_kernel). - A converter leaves the machine fleet; an undisturbed run is stationary; a fault at its bus rides through on the current limit; recovery is ramp-limited; an LCC link blocks and ramps back; opting out is the all-machine fleet exactly; held and zero-inertia units keep the run stationary; an island without a machine gets a reference; a converter-only fleet is refused (RmsConverterTests). - A grid-forming unit is stationary at flat start, holds its current limit in a fault, holds its terminal voltage better than a grid-following unit at onset, and its virtual speed swings and is damped (RmsGridFormingTests).

Worked example

One case9 machine is initialised by hand, then compared with a run of the library.

Inputs. The solved case9 power flow (Newton, 4 iterations) puts bus 1, the slack, at Vt = 1.04 pu angle 0 and net injection P = 71.6410214744825 MW, Q = 27.0459235334931 MVAr on the 100 MVA base. The generator at bus 1 has MBase = 247.5 MVA and H = 23.64 s, so H_sys = 23.64*247.5/100 = 58.509 s. The CLI data for the machine uses X'd = 0.0608 pu on its own base, so the base factor is 100/247.5 = 0.404040 and, on the system base:

Xd   = 3.0*0.0608*0.404040 = 0.0736970       Xq   = 2.5*0.0608*0.404040 = 0.0614141
X'd  = 0.0608*0.404040     = 0.0245657       X'q  = 1.5*0.0608*0.404040 = 0.0368485
X''d = X''q = 0.8*0.0608*0.404040 = 0.0196525

Terminal current. S = 0.716410 + j0.270459 pu, so It = conj(S/Vt) = 0.688856 - j0.260057 pu (|It| = 0.736310).

Rotor angle. Eq = Vt + j*Xq*It = 1.04 + j0.0614141*(0.688856 - j0.260057) = 1.055971 + j0.042305, so delta0 = atan2(0.042305, 1.055971) = 0.0400417 rad = 2.29422 deg.

dq quantities. With cos(delta0) = 0.999199, sin(delta0) = 0.040031:

Vq = 1.039166    Vd = 0.041632    Iq = 0.677893    Id = 0.287424
E'q  = 1.039166 + 0.0245657*0.287424 = 1.046227
E'd  = 0.041632 - 0.0368485*0.677893 = 0.016653
E''q = 1.039166 + 0.0196525*0.287424 = 1.044815
E''d = 0.041632 - 0.0196525*0.677893 = 0.028310
Efd  = 1.046227 + (0.0736970 - 0.0245657)*0.287424 = 1.060349
Pm   = 0.041632*0.287424 + 1.039166*0.677893 = 0.716410

Pm equals the solved bus-1 active power: the machine is lossless in the stator (Rs = 0), so air-gap power is terminal power. The four flux derivatives evaluate to -3.1e-17, 2.0e-16, -6.9e-18 and 0 by the equations of the model, a fixed point to double precision (the hand arithmetic above uses six digits; the checks used the full values).

The library run. docs/_captures/dynlib/init-case9.txt seeds the fleet with SubtransientInit.FromSolvedCase from the same solve and the same CLI machine data, runs it undisturbed for 2 s on the prepared network at the case frequency, collapses the reactances to X'd, and runs the critical-clearing-time search at bus 7. The script is docs/_captures/dynlib/init-case9.fsx (it calls the library directly, so its first line is dotnet fsi, not gridsim).

$ dotnet fsi docs/_captures/dynlib/init-case9.fsx
power flow converged=true iterations=4
bus 1 solved: Vm=1.04 VaDeg=0 P=71.6410214744825 MW Q=27.0459235334931 MVAr
machine 1 (bus 1): H=58.509 s on 100 MVA
  delta0=0.0400417046366223 rad (2.29422068018788 deg)
  E'q=1.04622713736649  E'd=0.0166528982585501  E''q=1.04481498500788  E''d=0.0283099270395352
  Efd=1.06034866095259  Pm=0.716410214744825
undisturbed 2 s: synchronism=true max|speed|=4.250e-017 pu max|delta-delta0|=3.886e-015 rad
flat reactances, machine 1: delta0=0.9265 deg |E|=1.0465 pu
bus 7 CCT: stable to 554 ms, lost at 556 ms (39 trials)
[exit 0]

Reading it against the hand calculation:

  • delta0, E'q, E'd, E''q, E''d, Efd and Pm agree with the six-digit hand values to the digits shown, and a full-precision evaluation of the same equations outside the library (Python, double precision) reproduces all seven to 15 significant figures.
  • Undisturbed for 2 s the largest speed deviation is 4.3e-17 pu and the largest angle excursion 3.9e-15 rad: the seed is a fixed point, as step 7 of the initialisation claims.
  • With every reactance equal to X'd, machine 1 starts at 0.9265 deg with |E| = 1.0465 pu. The classical verb prints the same machine as 0.9 deg and 1.047 pu in docs/_captures/stability/stability-case9.txt (its columns are rounded to one decimal and three decimals).
  • The library capture prints a bus 7 critical clearing time of 554 ms with 556 ms lost (277 steps of 2 ms, 39 trials). The script's call, RmsTransientStability.CriticalClearingBracket(model, pf, data, 7), passes no f0, so the library takes GridModel.FrequencyHz, which is 60 Hz for case9 (IeeeCases.Wscc9NominalFrequencyHz); the bracket is the one Fb1FinalBatchFollowUpsTests.Pin_case9_at_60_hz_rms_cct pins. On case9 re-set to 50 Hz the same search gives 302 steps, 604 ms (RmsCctStepQuantisedTests.Case9_bus7_cct_is_exactly_302_steps). The CLI makes the same call, and docs/_captures/stability/stability-case9-rms.txt prints 554 ms for gridsim stability case9 --rms:
$ gridsim stability case9 --rms
...
fault bus 7  *  critical clearing time = 554 ms
  (bracket: clearing at 554 ms holds synchronism, at 556 ms it is lost)
...

The library search ran 39 distinct simulations (Trials), the bisection plus the memoised downward and upward scans. Timings in captured output differ by machine and run; the single-study capture docs/_captures/stability/stability-case9-rms-clear.txt shows 0.1 s for one 400 ms fault-and-clear.

Source map

File Type Responsibility
src/GridSim.Core/Dynamics/Models/ControlBlocks.cs FirstOrderLag, LeadLag, Washout, Integrator, PiController Exact-ZOH blocks, limits, initialisation
src/GridSim.Core/Dynamics/Models/Tgov1.cs Tgov1 TGOV1 governor
src/GridSim.Core/Dynamics/Models/Ieeeg1.cs Ieeeg1 IEEEG1 governor
src/GridSim.Core/Dynamics/Models/HydroGovernor.cs HydroGovernor Transient-droop hydro governor
src/GridSim.Core/Dynamics/Models/Gast.cs Gast GAST gas-turbine governor
src/GridSim.Core/Dynamics/Models/AcExciter.cs AcExciter EXAC1 and ESAC1A alternator-rectifier exciters
src/GridSim.Core/Dynamics/Models/Esst4b.cs Esst4b ESST4B static exciter
src/GridSim.Core/Dynamics/Models/Sexs.cs Sexs SEXS exciter
src/GridSim.Core/Dynamics/Models/Ieeet1.cs Ieeet1 IEEET1 exciter
src/GridSim.Core/Dynamics/Models/Pss1a.cs Pss1a PSS1A stabiliser
src/GridSim.Core/Dynamics/Models/OneAxisMachine.cs OneAxisMachine One-axis SMIB machine
src/GridSim.Core/Dynamics/Models/TwoAxisMachine.cs TwoAxisMachine Two-axis SMIB machine
src/GridSim.Core/Dynamics/Models/SubtransientMachine.cs SubtransientMachine, SaturationCurve Six-state SMIB machine, saturation
src/GridSim.Core/Dynamics/Models/MultiMachineFluxDecay.cs MultiMachineFluxDecay Round-rotor multi-machine E'q model
src/GridSim.Core/Dynamics/Models/GovernedMultiMachine.cs GovernedMultiMachine TGOV1 on the classical swing
src/GridSim.Core/Dynamics/Models/SubtransientNetworkInterface.cs SubtransientNetworkInterface dq EMF to network current, Pe, Vt
src/GridSim.Core/Dynamics/Models/MultiMachineSubtransient.cs MultiMachineSubtransient, IRmsFieldController RMS integrator
src/GridSim.Core/Dynamics/Models/SubtransientInit.cs SubtransientInit Fleet seed, networks, held units, island references
src/GridSim.Core/Dynamics/Models/RmsNetwork.cs IRmsNetwork, DenseMachineNetwork, SparseRmsNetwork Network solves, stages
src/GridSim.Core/Dynamics/Models/MachineAdmittanceColumns.cs MachineAdmittanceColumns Bit-identical vectorised Y*E
src/GridSim.Core/Dynamics/Models/RmsConverter.cs RmsConverterParameters, RmsConverterState, ConverterNetwork Converter plant and its network coupling
src/GridSim.Core/Dynamics/Models/RmsTransientStability.cs RmsTransientStability, RmsExciter, CctBracket The study, exciter mapping, clearing-time bracket
src/GridSim.Core/Dynamics/Models/IRmsConverterModel.cs IRmsConverterModel, IRmsNetworkSolvedConverterModel, LegacyRmsConverterModel The kernel's converter interface
src/GridSim.Core/Dynamics/Models/RmsNetworkSolvedIteration.cs RmsNetworkSolvedIteration Exact network-interface pass for REGC_B units
src/GridSim.Core/Dynamics/Models/Wecc/Regca.cs, Regcb.cs Regca, Regcb REGC_A, REGC_B (and its exact network solution)
src/GridSim.Core/Dynamics/Models/Wecc/Reec.cs, Reecd.cs Reec, Reecd REEC_A/B/C, REEC_D
src/GridSim.Core/Dynamics/Models/Wecc/Repca.cs Repca, RepcaParameters REPC_A
src/GridSim.Core/Dynamics/Models/Wecc/WindMechanics.cs DriveTrain, Aerodynamics, PitchController, TorqueController WTGT_A, WTGAR_A, WTGPT_A, WTGTRQ_A
src/GridSim.Core/Dynamics/Models/Wecc/DerA.cs, RegfmA1.cs DerAState, RegfmA1State DER_A, REGFM_A1
src/GridSim.Core/Dynamics/Models/Wecc/WeccConverterState.cs WeccConverterState The composed REGC/REEC/REPC/wind unit
src/GridSim.Core/IO/Psse/PsseDyrRenewables.cs PsseDyrRenewables DYR records of the renewable models
src/GridSim.Core/Dynamics/Models/CctSearch.cs CctSearch Integer bisection, verification, probe
src/GridSim.Core/Dynamics/Distributed/ClassicalMultiMachine.cs ClassicalMultiMachine Classical swing and its hooks
src/GridSim.Core/Dynamics/Distributed/ClassicalInit.cs ClassicalInit Classical seed and CCT
src/GridSim.Cli/Program.cs RunRmsStability The stability --rms --avr --pss verb
src/GridSim.Cli/CliDefaults.cs CliDefaults Synthesised machine ratios, step and duration
docs/_captures/dynlib/init-case9.fsx script Worked-example run

Limits

  • The subtransient machine follows the GENROU saturation form, but no PSS/E trace of a saturated machine is compared against, so agreement with a PSS/E GENROU run on the same data is not demonstrated.
  • The leakage reactance Xl enters only the q-axis saturation scale. The machines have no stator resistance and no stator transients; the network is positive-sequence and algebraic.
  • The fleet needs X''d = X''q; SubtransientInit throws when they differ.
  • Governors come with the machine data: RmsTransientStability builds the mechanical-power hook from each machine's SubtransientInit.MachineData.Governor (TGOV1, IEEEG1, the hydro governor or GAST), and the CLI reads it from a machine template's governor slot in --dyn-data. A machine with no governor, and every machine of a run without --dyn-data, holds its seeded Pm. Tgov1 also runs on the classical swing through GovernedMultiMachine.
  • IEEEG1 has the valve rate limits Uo and Uc and the low-pressure shaft fractions K2, K4, K6, K8 (defaults: unlimited rates, K1 = 1 and the other fractions 0); the hydro governor omits the velocity limit, the filter Tf, At, Dturb and qNL.
  • PSS1A omits the input transducer T6 and the second-order low-pass filter A1 and A2, and takes speed deviation as its only input; IEEET1 omits the transducer TR and takes its saturation as Aex*exp(Bex*Efd), which the caller fits to E1, SE(E1), E2, SE(E2).
  • The exciters are SEXS, IEEET1, EXAC1, ESAC1A and ESST4B; there is no other ESAC, EXAC or ESST model, no GGOV1, no PSS2B, and no over- or under-excitation limiter.
  • Events are bolted three-phase faults, branch trips and recloses, load steps and generator trips; there is no unbalanced fault, fault impedance or breaker timing model.
  • Without --dyn-data the CLI synthesises every machine parameter from X'd, and it fixes the exciter and PSS settings, so its results are indicative; the case files carry no machine dynamics. A converter's energy store is an API option that SubtransientInit does not attach, so stability --rms runs every converter without one.
  • The integrator is fixed-step with first-order operator splitting.
  • WECC models against ANDES 2.0.0 (REGCA1 + REECA1, an infinite bus behind two lines, a 100 ms fault, 1 ms steps): at rest the two agree to 1.3e-10 pu in V and 5.4e-11 in P; during the fault to 1.9e-3 in V, 8.9e-4 in P, 3.7e-3 in Q (ANDES solves states and network together by the implicit trapezoid, GridSim advances the states from the start-of-step network); settled, to 2.7e-8 in P and Q (V 8.6e-6: GridSim's infinite bus is a 1,000,000 MVA machine). After clearing, P differs by up to 0.184 pu for about 40 ms because ANDES divides REEC_A's Pord by the raw terminal voltage, where the EPRI figure, OpenIPSL and GridSim use Vt_filt; with Trv = 0 that difference falls to 2.4e-2 at the first step after clearing and 3.6e-6 from 1.3 s. No published REGC_B, REEC_D, REPC_A, wind, DER_A or REGFM_A1 benchmark with numbers was obtainable (the EPRI REGC_B/REEC_D protocol lists tests without results), so those models are checked against their specifications' own equations and steady states only.
  • RMS step cost per WECC unit (IEEE 118, 400 steps of 5 ms with a 100 ms fault, Debug build, this development laptop): REGC_B + REEC_D about 140 us per unit per step (the exact network solution with its Newton step for several units); REGC_A + REEC_A 44 to 72 us per unit per step with 8 or 16 units, most of it in the steps the rescue re-solves.

See also