7. Three-phase distribution feeders

A distribution feeder is radial, carries unequal loads on its three phases, and has laterals that run on one or two phases only. The positive-sequence verbs of the other chapters assume a balanced network and cannot represent any of that. gridsim dist3ph is the verb for it. It reads a feeder written in the gridsim-dist3ph/1 file format or its JSON v2 form gridsim-dist3ph/2, or a radial positive-sequence case that it lifts into a balanced three-phase feeder, and runs one of four studies on it: sweep (the unbalanced power flow, the default), fault (sequence-network fault currents at one bus), estimate (three-phase state estimation from a measurement file) and harmonics (harmonic voltages from one balanced harmonic source). A fifth mode, to-v2, writes the feeder in the v2 form. The verb is marked EXPERIMENTAL in its own banner. This chapter covers the feeder file, the measurement file, the bundled feeders, each study with a captured run, and the figures that measure unbalance.

Every command here exits 0 on success, 1 for an input error, 2 for a usage error and 3 when a solve does not converge (see Exit codes). Timings do not appear in this verb's output. The iteration counts in the captures are those of this machine; a test checks that two runs on one machine give the same count.

Before you start

The feeder file

A feeder is one JSON file whose schema member is exactly gridsim-dist3ph/1. The reader is strict. Member names are case-sensitive, and an unknown member, a duplicate member, a missing required member, a wrong JSON type, a number that is not finite, a matrix that is not 3 by 3, a duplicate id, an unknown bus or line-code reference, a branch that joins a bus to itself and a network that is not one radial tree from the single source are all refused. Every refusal names the file and the JSON path of the offending value and exits 1. Comments are allowed in the file; trailing commas are not.

The top level holds these members. schema, name, description, baseMva and buses are required; the others are optional.

Member Holds
name, description Free text. Put the citation of the data source in description.
baseMva The three-phase MVA base, above 0. Per-phase power is per-unit on baseMva / 3.
buses At least two buses. Each has id (an integer), baseKvLL (line-to-line kV, above 0), an optional name (unique, shown in place of the id in reports, as RG1 is in the 123-node feeder) and, on exactly one bus, a source block.
lineCodes Impedance data shared by lines: id (unique, non-empty, named by a line's code), a 3 by 3 series matrix as r and x with unit ohm/mile or ohm/km, and optionally a symmetric 3 by 3 shunt susceptance b with bUnit uS/mile or uS/km (give both or neither).
lines id, from, to, code, length (above 0), lengthUnit (ft, mile, m or km) and an optional phases.
transformers id, from, to, connection, kva, kvLLFrom, kvLLTo, rPercent, xPercent.
switches id, from, to, closed (true or false, required) and an optional phases.
regulators id, from, to, an optional phases, tapStepPercent (above 0) and taps (one integer per phase).
capacitors id, bus and kvar, one value per phase.
loads id, bus, connection, model, kw and kvar, one value per phase.
converters Active-front-end converter units for the harmonic study: id, bus, kva, xPercent and an optional rPercent, the internal impedance in percent on the unit's own rating. Read only by harmonics --afe feeder.

Every element kind the reader supports is below. Nothing else is accepted.

The source. One bus carries source. It is an infinite bus of zero impedance. magnitudePu (three values, each above 0) and angleDeg (three values) are optional; with neither the source is the balanced 1.0 pu set at 0, -120 and +120 degrees. Give unequal magnitudes or angles to feed the feeder from an unbalanced source.

Lines. The impedance of a line is its code's matrix times its length, converted to per-unit on the line's own voltage level (impedance base baseKvLL^2 / baseMva ohm). A line joins two buses of the same baseKvLL; a line between voltage levels is refused with a message telling you to use a transformer. phases is abc when omitted. A single-phase or two-phase lateral gives a, b, c, ab, ac or bc; its code must be zero on every other phase and must have a non-zero self impedance on each phase it carries, or the file is refused. A bus has the phases of the branch that feeds it, and a branch that carries a phase its upstream bus lacks is refused by name. A b matrix adds line charging as a pi section, half the shunt admittance at each end.

Transformers. Six connections exist. gy-gy, grounded wye to grounded wye: in per-unit its leakage impedance on every phase, z = (rPercent + j xPercent) / 100 x (baseMva x 1000 / kva), with all three sequences passing and no phase shift. d-gy, delta to grounded wye with the delta on the from side: a step-down (1.95.251) when the delta side is the higher voltage, the grounded-wye side then lagging by 30 degrees, and a step-up (1.95.252) when it is the lower voltage, the grounded-wye side then leading by 30 degrees (the ANSI rule: the higher-voltage side leads); the delta side carries no zero-sequence current, and the leakage impedance sits on the wye side. Both reproduce the IEEE 4 Node Test Feeder's published D-GrY results (data/dist3ph/ieee4-dGy-stepdown-*.json and ieee4-dGy-stepup-*.json). Equal rated voltages on the two sides are refused (no ANSI direction). y-d (1.95.253), ungrounded wye (from) to delta, step-down or step-up by the rated voltages with the same 30 degree rule, and d-d (1.95.253), delta to delta with no phase shift: both with equal winding impedances, and both make the secondary a three-wire system (no neutral), so everything fed from it must be delta connected: a wye load, a capacitor bank, line charging, a regulator or a gy-gy transformer there is refused by name (a d-gy grounds it again). Voltages on a three-wire bus are reported as the equivalent line-to-neutral ones with no zero sequence. They reproduce the IEEE 4 Node Test Feeder's published Y-D and D-D results (data/dist3ph/ieee4-yD-*.json, ieee4-dD-*.json). Two open banks complete the set: oy-od, open wye / open delta with the two primaries on from-side phases A and B to earth, modelled as the step-down connection only (a step-up oy-od, the higher-voltage side leading, is refused), and od-od, open delta / open delta. y-d, d-d, oy-od and od-od take an optional windings array of per-winding rPercent and xPercent on the bank's kVA (three, ab / bc / ca, for y-d and d-d; two, ab / bc, for the open banks) in place of the bank's rPercent and xPercent, for unequal winding impedances; giving both is refused. Only the sweep models the transformer elements other than gy-gy; the estimators, the fault study and the harmonic penetration refuse them by name. kvLLFrom and kvLLTo are the rated voltages: equal to the two buses' baseKvLL for a transformer at its rated ratio, or (1.95.254) within 20 % of them for an off-nominal ratio (a tap), which is modelled as the per-unit ideal ratio t = (baseKvLL_from / kvLLFrom) x (kvLLTo / baseKvLL_to) with the nameplate impedance moved to the to bus base by (kvLLTo / baseKvLL_to)^2 (for gy-gy it is the regulator element's ideal ratio on every phase). A rated voltage more than 20 % from its bus base is refused as a data error. rPercent and xPercent must not be negative and must not both be 0. Any other connection is refused with a message listing the six, never approximated. The transformer element has no magnetising member; one given is refused as an unknown member.

Switches. A closed switch is a branch of zero impedance; the voltage and current pass through it unchanged. An open switch is not a branch: it is read, counted in the banner line and left out of the network, so a normally open tie never closes a loop. A switch joins two buses of one voltage level.

Regulators. An ideal step-voltage regulator from the from bus (the bus nearer the source) to its own output bus to, with no series impedance. Per phase the voltage ratio is 1 + (tapStepPercent / 100) x tap; taps holds one integer per phase, and a phase the regulator does not carry must read 0. Taps are given in the file and stay fixed: the regulator does not control anything.

Capacitors. A wye bank at a bus with kvar per phase, delivered at the bus's nominal voltage and held as a constant susceptance, so the reactive power it supplies falls with the square of the voltage. A value must not be negative, at least one must be above 0 and a bank cannot put a unit on a phase its bus lacks.

Loads. kw and kvar are per phase, taken at nominal voltage. connection is wye or delta; a delta load's three entries are the a-b, b-c and c-a branches. model is constant-power, constant-current or constant-impedance. A load with a non-zero entry on a phase its bus lacks is refused. A ZIP load is written as up to three loads on one bus, one of each model; the model name zip is refused with a message saying so.

Radial tree. After all the elements are read, n buses need exactly n - 1 branches (lines, transformers, closed switches and regulators together) and every bus must be reachable from the source. A wrong branch count (a loop, or a bus cut off) exits 1 with the counts, for example 4 buses need exactly 3 branches ... found 4. A feeder with n - 1 branches that still leaves buses unreached, because a loop sits elsewhere, exits 1 with the unreached bus numbers.

The measurement file

The estimate study reads a gridsim-dist3ph-measurements/1 file under the same strict rules. It holds up to three members and at least one of them must be present.

  • voltageMagnitudes: each entry gives bus, phase (a, b or c), valuePu (above 0) and sigmaPu (above 0). Voltages are per-unit on the bus's line-to-neutral base.
  • currents: each entry gives from, to, phase, realPu, imagPu and sigmaPu. The value is the current phasor into the from end, in rectangular form, per-unit on the per-phase power base baseMva / 3 and the bus line-to-neutral voltage base (the current base that fault prints). For wls and wlav the branch can be named in either orientation, and the reversed orientation is negated. --method branch-current does the same on a pure series branch, and refuses a reversed one across a regulator or a charged line (exit 1, naming the branch; see Branch-current estimation). A pair of buses that no branch joins is refused. sigmaPu applies to each rectangular component.
  • pseudoVoltage: valuePu and sigmaPu. Each non-source bus with no voltage measurement receives one pseudo-measurement per phase it has (a lateral only on its own phases) at that value. They are priors, not observations, and the sigma should be loose.

An optional description is read and ignored. The bundled data/dist3ph/ieee4-gyGy-stepdown-unbalanced.measurements.json is a synthetic set made from the sweep solution of the unbalanced 4-node feeder, rounded to 6 decimals, with sigma 0.001 pu throughout. It is not recorded telemetry.

The bundled feeders

data/dist3ph holds the IEEE 4 Node Test Feeder in each of its published transformer connections, the IEEE 123 Node Test Feeder, and the published results that the sweep is checked against. The shipped files are exempt from the bus limit of the installed licence tier.

File Feeder Content
ieee4-gyGy-stepdown-balanced.json IEEE 4 Node Test Feeder, grounded-wye / grounded-wye step-down, balanced load 4 buses, 3 branches, 1 load of 1800 kW per phase. 12.47 kV source, 2000 ft line, 6000 kVA 12.47/4.16 kV transformer, 2500 ft line.
ieee4-gyGy-stepdown-unbalanced.json The same feeder with the published unbalanced load Load of 1275, 1800 and 2375 kW on phases a, b and c.
ieee4-dGy-stepdown-balanced.json IEEE 4 Node Test Feeder, delta / grounded-wye step-down, balanced load (1.95.251) As the gy-gy feeder, but a d-gy transformer and a three-wire line 1-2 (the delta side has no neutral).
ieee4-dGy-stepdown-unbalanced.json The same D-GrY feeder with the published unbalanced load (1.95.251) Load of 1275, 1800 and 2375 kW on phases a, b and c.
ieee4-dGy-stepup-balanced.json, ieee4-dGy-stepup-unbalanced.json IEEE 4 Node Test Feeder, delta / grounded-wye step-up, balanced and unbalanced (1.95.252) As the step-down D-GrY feeders, but a 12.47/24.9 kV transformer (24.9 kV at nodes 3 and 4).
ieee4-yD-{stepdown,stepup}-{balanced,unbalanced}.json IEEE 4 Node Test Feeder, ungrounded-wye / delta, the four published cases (1.95.253) Four-wire line 1-2, three-wire line 3-4, delta load at node 4 (1275 / 1800 / 2375 kW on a-b / b-c / c-a when unbalanced).
ieee4-dD-{stepdown,stepup}-{balanced,unbalanced}.json IEEE 4 Node Test Feeder, delta / delta, the four published cases (1.95.253) Three-wire lines 1-2 and 3-4, delta load at node 4.
ieee123.json IEEE 123 Node Test Feeder 128 buses (including the four regulator output nodes RG1 to RG4), 127 branches, 85 loads (56 constant-power wye, 12 constant-current wye, 14 constant-impedance wye, and one each of constant-power, constant-current and constant-impedance delta), 4 capacitor banks, 4 regulators on the published taps, 5 closed and 2 open switches, 60 single- or two-phase branches.
ieee123.published-voltages.csv, ieee123.published-currents.csv The published 123-node voltage profile and branch currents The reference values the sweep is compared with.
ieee4-gyGy-stepdown-unbalanced.measurements.json Synthetic measurement set for the unbalanced 4-node feeder 9 voltage magnitudes and 9 current phasors.

The 4-node line code is the published conductor geometry reduced by Kersting's modified Carson equations and Kron reduction of the neutral, computed offline (GridSim has no Carson or phase Kron routine, so the values are data); the phase-a self impedance is 0.4576 + j1.0780 ohm/mile, and the file neglects line shunt capacitance. The sweep agrees with the published 4-node node voltages to the last printed digit of the publication (half a volt, 0.05 degree), and with the published 123-node voltages and currents within the asserted bounds of 6e-4 pu, 0.06 degree and 0.1 A (MultiPhaseJsonLoaderTests, MultiPhaseIeee123Tests). The remaining difference is attributed to the switches, which are ideal here while the published run gives them an impedance the data does not carry. The 123-node file omits the substation transformer (the published results start at node 150 at 1.0 pu), the switches that tie to nodes outside the feeder and the transformer XFM-1 with node 610, which serve no load; its description lists each choice.

The feeder argument can also be a radial positive-sequence case, a MATPOWER .m file or a JSON case folder, which is lifted into a balanced three-phase feeder (see Lifting a case).

Worked example

Solve the unbalanced IEEE 4-node feeder. The mode word defaults to sweep:

gridsim dist3ph data/dist3ph/ieee4-gyGy-stepdown-unbalanced.json
$ gridsim dist3ph data/dist3ph/ieee4-gyGy-stepdown-unbalanced.json
THREE-PHASE DISTRIBUTION (sweep) - IEEE 4-node test feeder, grounded-wye / grounded-wye step-down, unbalanced load   [EXPERIMENTAL]
  file: data/dist3ph/ieee4-gyGy-stepdown-unbalanced.json
  4 buses, 3 branches, 1 loads, base 6 MVA (three-phase)
  sweep CONVERGED in 39 iteration(s), max voltage change 7.191E-011 pu (tolerance 1.000E-010)
  | bus | kV LL | phase | |V| pu | |V| V (LN) | angle deg | VUF % |
  |-----|-------|-------|--------|------------|-----------|-------|
  | 1 | 12.47 | a | 1.000000 | 7199.56 | 0.000 | 0.0000 |
  | 1 | 12.47 | b | 1.000000 | 7199.56 | -120.000 |  |
  | 1 | 12.47 | c | 1.000000 | 7199.56 | 120.000 |  |
  | 2 | 12.47 | a | 0.995022 | 7163.72 | -0.140 | 0.3049 |
  | 2 | 12.47 | b | 0.987628 | 7110.48 | -120.185 |  |
  | 2 | 12.47 | c | 0.983675 | 7082.03 | 119.265 |  |
  | 3 | 4.16 | a | 0.959910 | 2305.49 | -2.258 | 1.9708 |
  | 3 | 4.16 | b | 0.938745 | 2254.66 | -123.625 |  |
  | 3 | 4.16 | c | 0.917157 | 2202.81 | 114.788 |  |
  | 4 | 4.16 | a | 0.905567 | 2174.97 | -4.123 | 6.3762 |
  | 4 | 4.16 | b | 0.803496 | 1929.82 | -126.798 |  |
  | 4 | 4.16 | c | 0.763044 | 1832.66 | 102.845 |  |
[exit 0]

The sweep converged in 39 iterations. Phase c at the load bus sits at 0.763 pu, the lowest voltage in the table, and phase a at 0.906 pu, a spread of 14.3 percentage points between two phases of the same bus. The positive- sequence tools of the other chapters would show one number for this bus. The voltage unbalance factor at bus 4 is 6.3762 %.

Reading the output

The sweep, the estimators and the lift all print the same layout, in this order.

Banner. THREE-PHASE DISTRIBUTION (sweep) - <feeder name> [EXPERIMENTAL]. The word in brackets after DISTRIBUTION is the mode that ran. The feeder name is the name member of the file, or the case name for a lifted case.

File line. The path as you gave it.

Size line. 4 buses, 3 branches, 1 loads, base 6 MVA (three-phase). Branches are the lines, transformers, closed switches and regulators that are in the network. base is baseMva. An open switch is not a branch.

Element line. Printed when the feeder holds a regulator, a closed or open switch, a capacitor, a single- or two-phase branch, line charging, a transformer element other than gy-gy, or a load that is not constant-power wye. A feeder with a d-gy transformer adds , N delta / grounded-wye transformer(s) at the end. It counts the regulators, the closed switches, the open switches (marked (not branches)), the capacitor banks and the single- or two-phase branches, so you can see that each was read. The 123-node feeder prints 4 regulator(s), 5 closed switch(es), 2 open switch(es) (not branches), 4 capacitor bank(s), 60 single- or two-phase branch(es). A feeder of three-phase lines, transformers and loads only prints no such line.

Convergence line. sweep CONVERGED in 39 iteration(s), max voltage change 7.191E-011 pu (tolerance 1.000E-010). One sweep is one backward pass that sums the load currents up the tree and one forward pass that drops voltage down it. The sweep stops when the largest change of any phase voltage between two successive sweeps is below the tolerance (--tol, default 1e-10 pu), or fails when it reaches --max-iter sweeps (default 200). The line reports the sweeps used and the last change. A feeder that does not converge prints no table (see Pitfalls).

Voltage table. One row per bus and phase, in the order the buses appear in the file.

Column Meaning
bus The bus id, or the bus name where the file gives one.
kV LL The bus's baseKvLL.
phase a, b or c.
\|V\| pu Voltage magnitude, per-unit of the bus's line-to-neutral base baseKvLL / sqrt(3), to 6 decimals.
\|V\| V (LN) The same magnitude in line-to-neutral volts, to 2 decimals: \|V\| pu times baseKvLL x 1000 / sqrt(3).
angle deg The phase angle in degrees, to 3 decimals. The balanced source puts phase a at 0.
VUF % The voltage unbalance factor of the bus, on the first row of a three-phase bus only (see below).

A phase that a bus does not have, because the bus is on a lateral, prints - in the three value columns and has no row in a result file. The VUF % cell is empty on the second and third rows of a bus and on every row of a bus with fewer than three phases, because the factor needs all three. In the 123-node feeder node 2 carries phase b only, so its a and c rows read -:

$ gridsim dist3ph data/dist3ph/ieee123.json
THREE-PHASE DISTRIBUTION (sweep) - IEEE 123 Node Test Feeder   [EXPERIMENTAL]
  file: data/dist3ph/ieee123.json
  128 buses, 127 branches, 85 loads, base 5 MVA (three-phase)
  4 regulator(s), 5 closed switch(es), 2 open switch(es) (not branches), 4 capacitor bank(s), 60 single- or two-phase branch(es)
  sweep CONVERGED in 10 iteration(s), max voltage change 1.167E-011 pu (tolerance 1.000E-010)
  | bus | kV LL | phase | |V| pu | |V| V (LN) | angle deg | VUF % |
  |-----|-------|-------|--------|------------|-----------|-------|
  | 1 | 4.16 | a | 1.031303 | 2476.96 | -0.636 | 0.2534 |
  | 1 | 4.16 | b | 1.041294 | 2500.96 | -120.310 |  |
  | 1 | 4.16 | c | 1.034887 | 2485.57 | 119.622 |  |
  | 2 | 4.16 | a | - | - | - | |
  | 2 | 4.16 | b | 1.041073 | 2500.42 | -120.314 |  |
  | 2 | 4.16 | c | - | - | - | |
...
  | RG1 | 4.16 | a | 1.043750 | 2506.85 | 0.000 | 0.0000 |
  | RG1 | 4.16 | b | 1.043750 | 2506.85 | -120.000 |  |
  | RG1 | 4.16 | c | 1.043750 | 2506.85 | 120.000 |  |
...
[exit 0]

The rows RG1 show the output node of regulator RG1, named in the file. Its three phases sit at 1.043750 pu, which is 1 + 0.00625 x 7: the published tap 7 on every phase at 0.625 % per step. Across the 123-node solution the lowest voltage is 0.985855 pu (bus 65, phase a), the highest 1.043870 pu (bus 83, phase a) and the highest unbalance factor 1.0781 % (bus 95).

Unbalance metrics

The verb reports unbalance through symmetrical components, the Fortescue transform with a = 1 at 120 degrees:

V0 = (Va + Vb + Vc) / 3
V1 = (Va + a Vb + a^2 Vc) / 3
V2 = (Va + a^2 Vb + a Vc) / 3

The voltage unbalance factor is VUF % = 100 x |V2| / |V1|, the ratio of the negative-sequence to the positive-sequence voltage. It is 0 for a perfectly balanced bus, and undefined for a dead bus with no positive-sequence voltage (printed and written as NaN). A sweep in which a constant-power or constant-current load sits on a phase at exactly zero voltage (a collapse) stops not converged with a non-finite status rather than letting that load draw nothing. It is printed in the sweep and estimate tables once per three-phase bus and stored unrounded in the result files (column vuf_pct). The two other unbalance views are in the other studies: harmonics prints |V0|, |V1| and |V2| at each harmonic order, and fault prints the Thevenin impedances Z0, Z1 and Z2 of the sequence networks.

Unbalance has three sources: the line, the load and the source. The bundled feeders show the first two. The balanced-load 4-node feeder, which draws 1800 kW on every phase, is not balanced at its load bus:

$ gridsim dist3ph data/dist3ph/ieee4-gyGy-stepdown-balanced.json sweep
THREE-PHASE DISTRIBUTION (sweep) - IEEE 4-node test feeder, grounded-wye / grounded-wye step-down, balanced load   [EXPERIMENTAL]
  file: data/dist3ph/ieee4-gyGy-stepdown-balanced.json
  4 buses, 3 branches, 1 loads, base 6 MVA (three-phase)
  sweep CONVERGED in 25 iteration(s), max voltage change 5.279E-011 pu (tolerance 1.000E-010)
  | bus | kV LL | phase | |V| pu | |V| V (LN) | angle deg | VUF % |
  |-----|-------|-------|--------|------------|-----------|-------|
  | 1 | 12.47 | a | 1.000000 | 7199.56 | 0.000 | 0.0000 |
  | 1 | 12.47 | b | 1.000000 | 7199.56 | -120.000 |  |
  | 1 | 12.47 | c | 1.000000 | 7199.56 | 120.000 |  |
  | 2 | 12.47 | a | 0.987081 | 7106.55 | -0.339 | 0.1523 |
  | 2 | 12.47 | b | 0.991687 | 7139.71 | -120.344 |  |
  | 2 | 12.47 | c | 0.989056 | 7120.77 | 119.629 |  |
  | 3 | 4.16 | a | 0.935730 | 2247.41 | -3.694 | 0.2928 |
  | 3 | 4.16 | b | 0.944511 | 2268.51 | -123.476 |  |
  | 3 | 4.16 | c | 0.939245 | 2255.86 | 116.395 |  |
  | 4 | 4.16 | a | 0.798479 | 1917.77 | -9.073 | 2.3654 |
  | 4 | 4.16 | b | 0.858224 | 2061.26 | -128.315 |  |
  | 4 | 4.16 | c | 0.824709 | 1980.77 | 110.856 |  |
[exit 0]

Its VUF at bus 4 is 2.3654 %, produced entirely by the untransposed line, whose self and mutual impedances differ between phases. The unbalanced-load run raises it to 6.3762 % at the same bus. (An unbalanced source, set in the source block, unbalances every bus.) The balanced-load figures also show why a feeder model needs three phases: the load is identical on every phase, yet phase a sits at 0.798 pu and phase b at 0.858 pu.

Variations

Fault currents

fault computes the fault currents at one bus from the sequence networks. Name the bus with --bus:

gridsim dist3ph data/dist3ph/ieee4-gyGy-stepdown-unbalanced.json fault --bus 4
$ gridsim dist3ph data/dist3ph/ieee4-gyGy-stepdown-unbalanced.json fault --bus 4
THREE-PHASE DISTRIBUTION (fault) - IEEE 4-node test feeder, grounded-wye / grounded-wye step-down, unbalanced load   [EXPERIMENTAL]
  file: data/dist3ph/ieee4-gyGy-stepdown-unbalanced.json
  4 buses, 3 branches, 1 loads, base 6 MVA (three-phase)
  fault at bus 4 (4.16 kV LL), Zf = 0 pu (resistive), prefault E1 = 1.0 pu, infinite source;
  each branch reduced to its transposed-equivalent sequence impedances (z1 = z2 = zs - zm, z0 = zs + 2 zm).
  Thevenin Z0 = 0.148286 + j0.406336 pu   Z1 = 0.064718 + j0.172093 pu   Z2 = 0.064718 + j0.172093 pu
  current base at this bus 832.717 A
  | fault | current pu | current A |
  |-------|------------|-----------|
  | 3ph | 5.438923 | 4529.08 |
  | slg | 3.748789 | 3121.68 |
  | ll | 4.710245 | 3922.30 |
  | llg (ground) | 2.860006 | 2381.57 |
[exit 0]

Reading the fault block, line by line:

  • fault at bus 4 (4.16 kV LL), Zf = 0 pu, prefault E1 = 1.0 pu, infinite source; names the bus, the fault resistance --zf in per-unit (a real number, at least 0; a reactive fault impedance cannot be given) (default 0, a bolted fault) and the fixed assumptions: a prefault positive-sequence voltage of 1.0 pu, behind an infinite source of zero impedance.
  • The next line states how each branch is reduced. A 3 by 3 phase impedance becomes its transposed-equivalent sequence impedances: z1 = z2 = zs - zm and z0 = zs + 2 zm, where zs is the mean of the three self impedances and zm the mean of the six mutual impedances. The Thevenin impedance at the fault bus is the sum of these along the path from the source.
  • Thevenin Z0, Z1 and Z2 are the zero-, positive- and negative-sequence impedances at the bus, in per-unit, each as a real part and an imaginary part. Z1 equals Z2 by construction. Z0 is the larger here because the mutual impedance between conductors adds in the zero sequence and subtracts in the other two; a lifted balanced case has no mutuals, so its Z0, Z1 and Z2 are equal. The grounded-wye transformer passes all three sequences, so it adds its leakage impedance to each.
  • current base at this bus 832.717 A is baseMva x 10^6 / (sqrt(3) x baseKvLL x 1000) at the faulted bus's voltage level. The amps column is the per-unit column times this number.
  • The table gives the magnitude of the fault current. 3ph is E1 / (Z1 + Zf). slg, single line to ground, is 3 E1 / (Z0 + Z1 + Z2 + 3 Zf). ll, line to line, is sqrt(3) E1 / (Z1 + Z2 + Zf). llg (ground), double line to ground, is the ground current 3 I0 with Zf as the impedance to ground. At bus 4, 3ph is 5.438923 pu, which is 1 / |Z1| for the printed Z1.

--type limits the table to one row (3ph, slg, ll or llg; the default is all). A fault resistance adds to the loop impedance and lowers the current:

gridsim dist3ph data/dist3ph/ieee4-gyGy-stepdown-unbalanced.json fault --bus 3 --type slg --zf 0.05
$ gridsim dist3ph data/dist3ph/ieee4-gyGy-stepdown-unbalanced.json fault --bus 3 --type slg --zf 0.05
THREE-PHASE DISTRIBUTION (fault) - IEEE 4-node test feeder, grounded-wye / grounded-wye step-down, unbalanced load   [EXPERIMENTAL]
  file: data/dist3ph/ieee4-gyGy-stepdown-unbalanced.json
  4 buses, 3 branches, 1 loads, base 6 MVA (three-phase)
  fault at bus 3 (4.16 kV LL), Zf = 0.05 pu (resistive), prefault E1 = 1.0 pu, infinite source;
  each branch reduced to its transposed-equivalent sequence impedances (z1 = z2 = zs - zm, z0 = zs + 2 zm).
  Thevenin Z0 = 0.021305 + j0.088314 pu   Z1 = 0.014473 + j0.069164 pu   Z2 = 0.014473 + j0.069164 pu
  current base at this bus 832.717 A
  | fault | current pu | current A |
  |-------|------------|-----------|
  | slg | 9.919461 | 8260.10 |
[exit 0]

The study neglects every shunt element: loads of every kind, shunt capacitors and line charging. The fault current is that of the series path alone. A closed switch is a zero impedance. A single-phase or two-phase branch, or a regulator, on the path from the source to the faulted bus is refused by name (exit 1); the same elements elsewhere in the feeder do not enter the study. A --zf below 0 exits 2. A fault at the source bus exits 1, because the infinite bus has zero impedance and the current has no finite value:

$ gridsim dist3ph data/dist3ph/ieee4-gyGy-stepdown-unbalanced.json fault --bus 1
THREE-PHASE DISTRIBUTION (fault) - IEEE 4-node test feeder, grounded-wye / grounded-wye step-down, unbalanced load   [EXPERIMENTAL]
  file: data/dist3ph/ieee4-gyGy-stepdown-unbalanced.json
  4 buses, 3 branches, 1 loads, base 6 MVA (three-phase)
error: bus 1 is the source (an infinite bus with zero impedance); a fault there has no finite current in this model.
[exit 1]

Estimating the state from measurements

estimate finds the three-phase voltages that best fit a measurement file. The default method is wls, a weighted least-squares fit of the node voltages. The bundled set measures every phase voltage magnitude at buses 2 to 4 and every phase current of the three branches:

gridsim dist3ph data/dist3ph/ieee4-gyGy-stepdown-unbalanced.json estimate --measurements data/dist3ph/ieee4-gyGy-stepdown-unbalanced.measurements.json
$ gridsim dist3ph data/dist3ph/ieee4-gyGy-stepdown-unbalanced.json estimate --measurements data/dist3ph/ieee4-gyGy-stepdown-unbalanced.measurements.json
THREE-PHASE DISTRIBUTION (estimate) - IEEE 4-node test feeder, grounded-wye / grounded-wye step-down, unbalanced load   [EXPERIMENTAL]
  file: data/dist3ph/ieee4-gyGy-stepdown-unbalanced.json
  4 buses, 3 branches, 1 loads, base 6 MVA (three-phase)
  measurements: 9 voltage magnitude(s), 9 current phasor(s), 0 nominal-voltage pseudo-measurement(s); method wls
  estimate CONVERGED in 4 iteration(s), objective J = 7.057361E-007
  | bus | kV LL | phase | |V| pu | |V| V (LN) | angle deg | VUF % |
  |-----|-------|-------|--------|------------|-----------|-------|
  | 1 | 12.47 | a | 1.000000 | 7199.56 | 0.000 | 0.0000 |
  | 1 | 12.47 | b | 1.000000 | 7199.56 | -120.000 |  |
  | 1 | 12.47 | c | 1.000000 | 7199.56 | 120.000 |  |
  | 2 | 12.47 | a | 0.995022 | 7163.72 | -0.140 | 0.3049 |
  | 2 | 12.47 | b | 0.987628 | 7110.48 | -120.185 |  |
  | 2 | 12.47 | c | 0.983675 | 7082.03 | 119.265 |  |
  | 3 | 4.16 | a | 0.959910 | 2305.49 | -2.258 | 1.9708 |
  | 3 | 4.16 | b | 0.938745 | 2254.66 | -123.625 |  |
  | 3 | 4.16 | c | 0.917157 | 2202.81 | 114.788 |  |
  | 4 | 4.16 | a | 0.905567 | 2174.97 | -4.123 | 6.3762 |
  | 4 | 4.16 | b | 0.803496 | 1929.82 | -126.798 |  |
  | 4 | 4.16 | c | 0.763044 | 1832.66 | 102.845 |  |
  | measurement | phase | measured pu | estimate pu | r/sigma |
  |-------------|-------|-------------|-------------|---------|
  | |V| bus 2 | a | 0.995022 | 0.995022 | 0.000 |
  | |V| bus 2 | b | 0.987628 | 0.987628 | 0.000 |
  | |V| bus 2 | c | 0.983675 | 0.983675 | 0.000 |
  | |V| bus 3 | a | 0.959910 | 0.959910 | 0.000 |
  | |V| bus 3 | b | 0.938745 | 0.938745 | 0.000 |
  | |V| bus 3 | c | 0.917157 | 0.917157 | 0.000 |
  | |V| bus 4 | a | 0.905567 | 0.905567 | 0.000 |
  | |V| bus 4 | b | 0.803496 | 0.803496 | 0.000 |
  | |V| bus 4 | c | 0.763044 | 0.763044 | 0.000 |
  | I 1->2 | a | 0.670785-j0.485777 | 0.670785-j0.485777 | 0.000 |
  | I 1->2 | b | -1.105339-j0.571979 | -1.105339-j0.571979 | 0.000 |
  | I 1->2 | c | 0.152737+j1.631040 | 0.152737+j1.631040 | 0.000 |
  | I 2->3 | a | 0.670785-j0.485777 | 0.670785-j0.485777 | 0.000 |
  | I 2->3 | b | -1.105339-j0.571979 | -1.105339-j0.571979 | 0.000 |
  | I 2->3 | c | 0.152737+j1.631040 | 0.152737+j1.631040 | 0.000 |
  | I 3->4 | a | 0.670785-j0.485777 | 0.670785-j0.485777 | 0.000 |
  | I 3->4 | b | -1.105339-j0.571979 | -1.105339-j0.571979 | 0.000 |
  | I 3->4 | c | 0.152737+j1.631040 | 0.152737+j1.631040 | 0.000 |
[exit 0]

The measurements: line counts what was read: voltage magnitudes, current phasors, and the nominal-voltage pseudo-measurements added for unmetered buses. After the voltage table a converged wls or wlav estimate prints one residual row per measurement in the fit, | measurement | phase | measured pu | estimate pu | r/sigma |: the voltage magnitudes first (|V| bus <id>), then the pseudo-measurements, then the currents (I <from>-><to>, written re+jim), with r/sigma the absolute residual over its sigma. A magnitude at the source bus is not in the fit and is not listed. The result file holds the same rows as a residuals table. estimate CONVERGED in 4 iteration(s), objective J = 7.057361E-007 gives the Gauss-Newton iterations and the objective. J is the sum over every measurement of the squared residual divided by the squared sigmaPu, where a current residual adds its real and imaginary parts. This set gives 7.06e-7; its values are rounded to 6 decimals against a sigmaPu of 0.001. The voltage table is the estimated state in the layout of the sweep, with the same VUF %. It equals the sweep solution of the same feeder to the printed digits, because the measurements were made from that solution.

The state is the complex voltage of every non-source bus and phase; the source is the fixed reference. Voltage magnitudes carry no angle, so the angles come from the current phasors, which are linear in the voltages through the inverse of each branch's 3 by 3 impedance. A set of magnitudes without enough currents is not observable, and the estimator says so:

$ gridsim dist3ph data/dist3ph/ieee4-gyGy-stepdown-unbalanced.json estimate --measurements docs/_captures/dist3ph/ieee4-vmag-only.measurements.json
THREE-PHASE DISTRIBUTION (estimate) - IEEE 4-node test feeder, grounded-wye / grounded-wye step-down, unbalanced load   [EXPERIMENTAL]
  file: data/dist3ph/ieee4-gyGy-stepdown-unbalanced.json
  4 buses, 3 branches, 1 loads, base 6 MVA (three-phase)
  measurements: 9 voltage magnitude(s), 0 current phasor(s), 0 nominal-voltage pseudo-measurement(s); method wls
dist3ph: the three-phase estimator did not converge after 0 iteration(s) (final max state update Infinity); the measurement set may be unobservable. No estimate reported.
[exit 3]

The message goes to stderr, no table is printed and the exit code is 3.

Pseudo-measurements. A pseudoVoltage member adds a prior for every non-source bus that has no voltage magnitude. This run uses the nine currents, the bus 4 magnitudes and a prior of 1.0 pu with sigma 0.05 pu for buses 2 and 3:

$ gridsim dist3ph data/dist3ph/ieee4-gyGy-stepdown-unbalanced.json estimate --measurements docs/_captures/dist3ph/ieee4-pseudo.measurements.json
THREE-PHASE DISTRIBUTION (estimate) - IEEE 4-node test feeder, grounded-wye / grounded-wye step-down, unbalanced load   [EXPERIMENTAL]
  file: data/dist3ph/ieee4-gyGy-stepdown-unbalanced.json
  4 buses, 3 branches, 1 loads, base 6 MVA (three-phase)
  measurements: 3 voltage magnitude(s), 9 current phasor(s), 6 nominal-voltage pseudo-measurement(s); method wls
  estimate CONVERGED in 4 iteration(s), objective J = 5.066665E+000
...
  | 4 | 4.16 | c | 0.763044 | 1832.66 | 102.845 |  |
...
[exit 0]

The state is unchanged to the printed digits except at bus 4 phase a, 0.905568 against 0.905567, because the currents pin it. J rises to 5.07 because the true bus 2 and bus 3 voltages (0.917 to 0.995 pu) sit away from the 1.0 pu prior, and the prior's residual is counted. A pseudo-measurement is a loose prior, not an observation of the feeder.

Robust estimation. --method wlav wraps the fit in a reweighting loop. A measurement with a large standardised residual gets a smaller weight (the reciprocal of the standardised residual, residual / sigma, with a floor of 0.001), for up to 8 outer passes or until no weight moves by more than 0.001. It is the method to use when a gross error is possible. The next file is the bundled set with one bad value: bus 4 phase b reads 0.9 pu where the truth is 0.803496 pu.

$ gridsim dist3ph data/dist3ph/ieee4-gyGy-stepdown-unbalanced.json estimate --measurements docs/_captures/dist3ph/ieee4-gross-error.measurements.json
...
  estimate CONVERGED in 5 iteration(s), objective J = 8.855827E+003
...
  | 4 | 4.16 | a | 0.903777 | 2170.67 | -4.306 | 6.4139 |
  | 4 | 4.16 | b | 0.808234 | 1941.20 | -126.797 |  |
  | 4 | 4.16 | c | 0.761118 | 1828.04 | 103.022 |  |
...
  | |V| bus 4 | b | 0.900000 | 0.808234 | 91.766 |
...
[exit 0]
$ gridsim dist3ph data/dist3ph/ieee4-gyGy-stepdown-unbalanced.json estimate --measurements docs/_captures/dist3ph/ieee4-gross-error.measurements.json --method wlav
...
  estimate CONVERGED in 23 iteration(s), objective J = 9.313081E+003
...
  | 4 | 4.16 | a | 0.905567 | 2174.97 | -4.123 | 6.3762 |
  | 4 | 4.16 | b | 0.803496 | 1929.82 | -126.798 |  |
  | 4 | 4.16 | c | 0.763044 | 1832.66 | 102.845 |  |
...
  | |V| bus 4 | b | 0.900000 | 0.803496 | 96.504 |
...
[exit 0]

The residual rows locate the bad value: its r/sigma, 91.766 in the least-squares fit and 96.504 in the robust one, stands out from the rest. The least-squares fit follows the bad value: phase b at bus 4 reads 0.808234 pu and the error spreads into phases a and c. The robust fit recovers the true state to the printed digits. Its J is the higher, 9313.081 against 8855.827, because J is always evaluated with the original weights at the final state, and the robust state leaves the bad measurement's residual in full: ((0.9 - 0.803496) / 0.001) squared is 9313. J after wlav is always at least the wls value, because wls minimises it; compare the two states instead, and a large shift with a rise in J points at a gross error. The iteration count of the robust run, 23, is the total over all outer passes. --robust-passes N (default 8, at least 1) and --robust-floor X (default 0.001, above 0) set the pass limit and the floor, with wlav only. When the last pass still moves a weight by 0.001 or more, the run prints WARNING: the robust re-weighting (IRLS) reached its cap of N pass(es) before the weights settled; ...; the exit code stays 0 and the result file carries irls_cap_reached.

Branch-current estimation. --method branch-current is a different estimator. It combines the current phasors of each branch and phase by weighted least squares, then makes one forward sweep from the source to give every voltage. It uses currents only and needs a current phasor on every phase of every tree branch. A branch phase with no phasor leaves the estimate not converged (exit 3), and the message lists the unobservable branch phases (1-2 b). A current named against the reversed endpoints is accepted as minus the from-end current, except across a regulator or a charged line (exit 1, naming the branch). Give it a measurement file with no voltage magnitudes and no pseudoVoltage:

$ gridsim dist3ph data/dist3ph/ieee4-gyGy-stepdown-unbalanced.json estimate --measurements docs/_captures/dist3ph/ieee4-currents-only.measurements.json --method branch-current
THREE-PHASE DISTRIBUTION (estimate) - IEEE 4-node test feeder, grounded-wye / grounded-wye step-down, unbalanced load   [EXPERIMENTAL]
  file: data/dist3ph/ieee4-gyGy-stepdown-unbalanced.json
  4 buses, 3 branches, 1 loads, base 6 MVA (three-phase)
  measurements: 9 current phasor(s); method branch-current
  estimate CONVERGED (one forward sweep over 3 measured branch(es))
...
  | 4 | 4.16 | a | 0.905568 | 2174.97 | -4.123 | 6.3762 |
  | 4 | 4.16 | b | 0.803496 | 1929.82 | -126.798 |  |
  | 4 | 4.16 | c | 0.763044 | 1832.66 | 102.845 |  |
[exit 0]

There is no iteration count and no J, because nothing iterates. Bus 4 phase a reads 0.905568 pu here and 0.905567 pu in the least-squares run, a difference in the last printed digit. A file that also holds voltage magnitudes is refused rather than having them ignored (exit 1), and --tol, --max-iter, --robust-passes and --robust-floor are refused with this method (exit 2):

$ gridsim dist3ph data/dist3ph/ieee4-gyGy-stepdown-unbalanced.json estimate --measurements data/dist3ph/ieee4-gyGy-stepdown-unbalanced.measurements.json --method branch-current
THREE-PHASE DISTRIBUTION (estimate) - IEEE 4-node test feeder, grounded-wye / grounded-wye step-down, unbalanced load   [EXPERIMENTAL]
  file: data/dist3ph/ieee4-gyGy-stepdown-unbalanced.json
  4 buses, 3 branches, 1 loads, base 6 MVA (three-phase)
error: dist3ph estimate --method branch-current uses current phasors only; data/dist3ph/ieee4-gyGy-stepdown-unbalanced.measurements.json also has 9 voltage magnitude(s), which it would ignore.
[exit 1]

The estimators differ in which feeder elements they accept, and a refused element is named, never dropped. The least-squares methods accept loads and capacitors, which do not enter a measurement model that has no injection measurements, and refuse laterals, line charging, regulators and closed switches. Pseudo-measurements go to buses with no voltage measurement on any phase, so a bus metered on one phase gets no prior on the others. The branch-current method models every element: a regulator and line charging are undone from the measured current at the From end, a lateral drops voltage on its own phases only and a closed switch has no drop. A regulator or a charged line must face away from the source, and a current on a phase that its branch does not carry is refused. The least-squares estimator is dense (a 6n by 6n gain inverted every iteration), so a feeder with more than 416 non-source buses (2,500 states) is refused with exit 1.

Harmonic voltages

harmonics places one balanced harmonic current source at a bus and reports the harmonic voltages it creates. It needs three flags: --bus, --spectrum and --current. The spectrum is a profile of the harmonic source library, the same names the harmonics verb of ch. 17 uses: 6-pulse, 12-pulse, pv-inverter, ev-charger, heat-pump-inverter, arc-furnace, saturated-transformer, 6-pulse-g5, 12-pulse-g5, afe-g5 and ideal. There is no default. --current is the fundamental current of the source in per-unit on the feeder base, above 0.

gridsim dist3ph data/dist3ph/ieee4-gyGy-stepdown-unbalanced.json harmonics --bus 4 --spectrum 6-pulse-g5 --current 0.2
$ gridsim dist3ph data/dist3ph/ieee4-gyGy-stepdown-unbalanced.json harmonics --bus 4 --spectrum 6-pulse-g5 --current 0.2
THREE-PHASE DISTRIBUTION (harmonics) - IEEE 4-node test feeder, grounded-wye / grounded-wye step-down, unbalanced load   [EXPERIMENTAL]
  file: data/dist3ph/ieee4-gyGy-stepdown-unbalanced.json
  4 buses, 3 branches, 1 loads, base 6 MVA (three-phase)
  balanced harmonic source at bus 4: spectrum 6-pulse-g5 (library profile, assumed-typical unless a G5-cited one [VERIFY]), fundamental current 0.2 pu;
  network only (series impedances, R + j h X; loads not modelled), source bus as the harmonic reference.
  | order | |Va| pu | |Vb| pu | |Vc| pu | |V0| pu | |V1| pu | |V2| pu | worst bus | worst |V| pu |
  |-------|--------|--------|--------|--------|--------|--------|-----------|-------------|
  | 5 | 0.054520 | 0.052327 | 0.056204 | 0.001835 | 0.004071 | 0.054190 | 4 | 0.056204 |
  | 7 | 0.026788 | 0.025126 | 0.027202 | 0.000855 | 0.026299 | 0.001979 | 4 | 0.027202 |
  | 11 | 0.026787 | 0.025516 | 0.027483 | 0.000888 | 0.001997 | 0.026518 | 4 | 0.027483 |
  | 13 | 0.017741 | 0.016711 | 0.018068 | 0.000573 | 0.017458 | 0.001315 | 4 | 0.018068 |
  | 17 | 0.015981 | 0.015189 | 0.016373 | 0.000527 | 0.001190 | 0.015802 | 4 | 0.016373 |
  | 19 | 0.012619 | 0.011905 | 0.012865 | 0.000409 | 0.012428 | 0.000936 | 4 | 0.012865 |
  | 23 | 0.008012 | 0.007607 | 0.008203 | 0.000264 | 0.000596 | 0.007917 | 4 | 0.008203 |
  | 25 | 0.008734 | 0.008247 | 0.008910 | 0.000284 | 0.008606 | 0.000648 | 4 | 0.008910 |
  | 29 | 0.006063 | 0.005753 | 0.006205 | 0.000199 | 0.000451 | 0.005989 | 4 | 0.006205 |
  | 31 | 0.007579 | 0.007160 | 0.007734 | 0.000247 | 0.007469 | 0.000563 | 4 | 0.007734 |
  | 35 | 0.007318 | 0.006941 | 0.007488 | 0.000240 | 0.000545 | 0.007228 | 4 | 0.007488 |
  | 37 | 0.006460 | 0.006105 | 0.006593 | 0.000210 | 0.006368 | 0.000480 | 4 | 0.006593 |
  | 41 | 0.005716 | 0.005420 | 0.005847 | 0.000188 | 0.000425 | 0.005645 | 4 | 0.005847 |
  | 43 | 0.006005 | 0.005676 | 0.006130 | 0.000196 | 0.005920 | 0.000446 | 4 | 0.006130 |
  | 47 | 0.004915 | 0.004660 | 0.005027 | 0.000161 | 0.000366 | 0.004853 | 4 | 0.005027 |
  | 49 | 0.003421 | 0.003234 | 0.003493 | 0.000112 | 0.003373 | 0.000254 | 4 | 0.003493 |
  RSS harmonic voltage at bus 4: a 0.074643 pu, b 0.071145 pu, c 0.076603 pu
[exit 0]

The description line names the source bus, the spectrum and the fundamental current. The library profiles are typical shapes, not measurements of a particular converter, and the [VERIFY] in the line marks that. The 6-pulse-g5, 12-pulse-g5 and afe-g5 profiles carry a citation for their shape, ENA Engineering Recommendation G5 Issue 5, Annex B. The second line states the network: the feeder's series impedances with the reactance scaled by the order, R + j h X, the source bus of the feeder as the harmonic reference (zero harmonic voltage), and no loads. A feeder with shunt capacitors, line charging or closed switches says so on this line and includes them: capacitors and line charging as susceptances scaled by the order, closed switches as one node.

One table row is printed for each order in the spectrum. The columns are:

Column Meaning
order The harmonic order h.
\|Va\| pu, \|Vb\| pu, \|Vc\| pu Harmonic voltage magnitude at the injection bus on each phase, per-unit on the line-to-neutral base.
\|V0\| pu, \|V1\| pu, \|V2\| pu The zero-, positive- and negative-sequence magnitudes of those three phase voltages.
worst bus, worst \|V\| pu The bus and magnitude of the largest harmonic voltage of this order over every bus and phase of the feeder.

The source is rotated by h x 120 degrees on phases b and c, so the sequence of each order follows from the order. Orders 5, 11, 17, 23 and 29 (6k - 1) come out negative-sequence: |V2| is large and |V1| small, as the table shows. Orders 7, 13, 19, 25 and 31 (6k + 1) come out positive-sequence. A triplen order (3, 9, 15) is in phase on all three phases and comes out zero-sequence, which a positive-sequence study cannot represent. The pv-inverter profile has an order 3 component:

$ gridsim dist3ph data/dist3ph/ieee4-gyGy-stepdown-unbalanced.json harmonics --bus 4 --spectrum pv-inverter --current 0.2
...
  | order | |Va| pu | |Vb| pu | |Vc| pu | |V0| pu | |V1| pu | |V2| pu | worst bus | worst |V| pu |
  |-------|--------|--------|--------|--------|--------|--------|-----------|-------------|
  | 3 | 0.004970 | 0.004990 | 0.004776 | 0.004912 | 0.000071 | 0.000066 | 4 | 0.004990 |
  | 5 | 0.006945 | 0.006666 | 0.007160 | 0.000234 | 0.000519 | 0.006903 | 4 | 0.007160 |
...

At order 3 the voltage is almost entirely |V0|. The small entries in the sequences that a pure rotation would leave at zero come from the line matrix, which is not perfectly symmetric. The last line, RSS harmonic voltage at bus 4: a 0.074643 pu, b 0.071145 pu, c 0.076603 pu, is the root-sum-square over every order in the table of the harmonic voltage at the injection bus, per phase. It does not include the fundamental.

Converter plant. --afe feeder stamps the feeder file's converters units into the harmonic admittance: each phase gets R + j h X between the phase and the converter's floating star point (positive and negative sequence, no zero sequence), and a line names the units. No default impedance exists for a converter unit, so every value comes from the file and is a [VERIFY] figure until sourced. A feeder with no converters section exits 1; any other value of the flag exits 2. Without the flag the units are not stamped.

harmonics refuses a bus that is not in the feeder, the source bus, a bus tied to the source through closed switches and a singular network (exit 1), and refuses a feeder with laterals or regulators by name (exit 1). It exits 2 for a missing flag, an unknown spectrum or a --current that is not above 0. The 123-node feeder holds both laterals and regulators:

$ gridsim dist3ph data/dist3ph/ieee123.json harmonics --bus 100 --spectrum 6-pulse --current 0.01
THREE-PHASE DISTRIBUTION (harmonics) - IEEE 123 Node Test Feeder   [EXPERIMENTAL]
  file: data/dist3ph/ieee123.json
  128 buses, 127 branches, 85 loads, base 5 MVA (three-phase)
  4 regulator(s), 5 closed switch(es), 2 open switch(es) (not branches), 4 capacitor bank(s), 60 single- or two-phase branch(es)
dist3ph harmonics: the three-phase harmonic penetration cannot model this feeder's single- or two-phase branches and step-voltage regulators, and will not solve it with them left out. It supports three-phase series-impedance lines and accepts constant-power wye loads, plus line charging, shunt capacitors, constant-current or constant-impedance (ZIP) loads, delta loads and closed switches (zero-impedance branches) (capacitors and line charging as susceptances scaled by the order, closed switches as one node; loads of every kind, constant-power wye included, are accepted and left out of Y(h): the study is network only). Use the three-phase sweep for this feeder.
[exit 1]

Lifting a case

dist3ph accepts a radial positive-sequence case in place of a feeder file: a MATPOWER .m file or a JSON case folder (one that holds system.json). The case is lifted into a balanced three-phase feeder. Each branch's resistance, reactance and charging go on every phase, each bus load is split equally per phase, a ZIP load becomes its constant-impedance, constant-current and constant-power parts, shunt capacitors are kept and the slack bus is the source. A generator at a PQ bus becomes a constant-power negative load, a generator at the slack is dropped, and out-of-service branches are left out. A case the sweep cannot model is refused with exit 1: a voltage-controlled (PV) bus, an off-nominal tap or phase shift, a shunt conductance or reactor, a bus without a kV base, or a network that is not one radial tree.

gridsim dist3ph data/matpower/dist/case33bw.m
$ gridsim dist3ph data/matpower/dist/case33bw.m
THREE-PHASE DISTRIBUTION (sweep) - case33bw   [EXPERIMENTAL]
  file: data/matpower/dist/case33bw.m
  33 buses, 32 branches, 32 loads, base 10 MVA (three-phase)
  sweep CONVERGED in 9 iteration(s), max voltage change 9.431E-011 pu (tolerance 1.000E-010)
  | bus | kV LL | phase | |V| pu | |V| V (LN) | angle deg | VUF % |
  |-----|-------|-------|--------|------------|-----------|-------|
  | 1 | 12.66 | a | 1.000000 | 7309.25 | 0.000 | 0.0000 |
...
  | 33 | 12.66 | a | 0.916590 | 6699.59 | 0.380 | 0.0000 |
  | 33 | 12.66 | b | 0.916590 | 6699.59 | -119.620 |  |
  | 33 | 12.66 | c | 0.916590 | 6699.59 | 120.380 |  |
note: case33bw.m: nominal frequency not given (MATPOWER files carry none); assumed 50 Hz - pass the real value if this is, for example, a 60 Hz system (gridsim: --frequency-hz 60).
note: case33bw.m: the file has 2 indexed assignment(s) after the matrices (mpc.branch, mpc.bus); MATLAB statements are not run, so they are not applied (a raw-unit distribution feeder is converted by the unit normaliser instead).
note: case33bw.m: read mpc.gencost (1 row(s)); the costs are carried on the generators and used by dcopf / acopf when asked (--costs case); without it the OPF uses the fuel-type merit order.
note: case33bw.m: skipped 5 out-of-service branch(es).
note: case33bw.m: raw engineering units detected (branch impedance in ohms, demand in kW / kVAr, as in the published distribution feeders); converted to per-unit and MW: R and X divided by Zbase = baseKV^2 / baseMVA of the from bus, Pd, Qd, Gs and Bs divided by 1000.
[exit 0]

The note: lines come from the case loader (see ch. 2). A lifted case is balanced, so its three phases carry equal magnitudes and the unbalance factor is 0.0000 at every bus. The lifted sweep agrees with the Newton power flow of gridsim data/matpower/dist/case33bw.m --once, which reads 0.917 p.u. at bus 33 and 0.38 degrees. The sweep, fault, estimate and harmonics all accept a lifted case, with the element limits above.

The JSON v2 form

to-v2 --to <out.json> writes the feeder as a gridsim-dist3ph/2 document (schemas/v2/dist3ph.schema.json), the per-unit, solver-authoritative form with provenance, then reads the written file back and compares it with the feeder bit for bit:

gridsim dist3ph data/dist3ph/ieee4-gyGy-stepdown-unbalanced.json to-v2 --to results/ieee4-unbalanced.v2.json

It prints wrote <file> (gridsim-dist3ph/2); read back: the same feeder, bit for bit and the provenance tag. A feeder read from a v1 file, or lifted from a case, carries no provenance, so it is written as CuratedPlaceholder with a note naming the source and [VERIFY]; set the tag before relying on the file. The v2 form holds the converter units too. to-v2 never overwrites a file (exit 2 when --to exists or is missing), exits 1 when the feeder holds something the v2 form cannot, and exits 3 when the written file does not read back to the same feeder. Every mode reads a v2 feeder as it reads a v1 one, and gridsim validate <file> checks one against the schema and the reader.

Result files

--json <file>, --csv <file> and --out <file> write the study's figures at full precision in addition to the console report (ch. 19, Result files). A sweep or an estimate writes a voltages table with the columns bus, kv_ll, phase, vm_pu, v_ln_volts, angle_deg and vuf_pct, plus a summary with the convergence figures. A fault study writes the Thevenin impedances, the current base and a faults table. A harmonics study writes a harmonic_voltages table (order, bus, phase, vm_pu, angle_deg) of every non-source bus, phase and order. The JSON document records the full command line, including the output path you gave.

Exit codes

Code Meaning
0 The study ran and, for sweep and estimate, converged.
1 An input error: the feeder or measurement file is unreadable or invalid, a bus is not in the feeder, a study refuses the input (the source bus, a refused element, a singular network), or a case cannot be lifted.
2 A usage error: no feeder, a mode word that is not sweep, fault, estimate, harmonics or to-v2, a flag that belongs to another mode, a missing required flag, or a flag value out of range. A feeder of your own over the licence's bus limit also exits 2.
3 The sweep, the estimator or the branch-current estimate did not converge, or a to-v2 file did not read back to the same feeder. Nothing is reported as a result.

A flag from another mode is refused, never ignored, so a sweep cannot pass for a fault study:

$ gridsim dist3ph data/dist3ph/ieee4-gyGy-stepdown-unbalanced.json sweep --bus 4
error: dist3ph sweep does not take --bus (allowed: --tol, --max-iter).
[exit 2]

An unknown mode word prints the usage:

$ gridsim dist3ph data/dist3ph/ieee4-gyGy-stepdown-unbalanced.json transient
error: dist3ph mode 'transient' is not one of sweep, fault, estimate, harmonics, to-v2.
usage: gridsim dist3ph <feeder.json> [sweep] [--tol 1e-10] [--max-iter 200]
       gridsim dist3ph <feeder.json> fault --bus ID [--type all|3ph|slg|ll|llg] [--zf PU]
       gridsim dist3ph <feeder.json> estimate --measurements <m.json> [--method wls|wlav|branch-current] [--tol 1e-10] [--max-iter 50]
                                      [--robust-passes 8] [--robust-floor 0.001]   (wlav only)
       gridsim dist3ph <feeder.json> harmonics --bus ID --spectrum TYPE --current PU [--afe feeder]
       gridsim dist3ph <feeder.json> to-v2 --to <out.json>   (N339: write the JSON v2 form, then prove it reads back bit for bit)
       (experimental; feeder format gridsim-dist3ph/1 or /2, see user manual ch. 7 and technical ch. 18; a radial .m case or JSON case folder is lifted balanced)
[exit 2]

The flags of every mode are in ch. 19, CLI reference; the exit codes shared by every verb are in ch. 19.

Pitfalls

  • A sweep that does not converge reports nothing. The sweep prints the banner and the size line, then one message on stderr, and exits 3. It never prints the last iterate as if it were a solution.
$ gridsim dist3ph data/dist3ph/ieee4-gyGy-stepdown-unbalanced.json sweep --max-iter 2
THREE-PHASE DISTRIBUTION (sweep) - IEEE 4-node test feeder, grounded-wye / grounded-wye step-down, unbalanced load   [EXPERIMENTAL]
  file: data/dist3ph/ieee4-gyGy-stepdown-unbalanced.json
  4 buses, 3 branches, 1 loads, base 6 MVA (three-phase)
dist3ph: the three-phase sweep did not converge (MaxIterations) after 2 sweep(s); final max voltage change 8.399E-002 pu against tolerance 1.000E-010. No result reported.
[exit 3]

The status word names the cause: MaxIterations for the iteration cap, NonFinite when a voltage became NaN or infinite. The unbalanced 4-node feeder needs 39 sweeps at the default tolerance, so a low --max-iter is a likely cause of a failure on a feeder that has a solution. - A transformer connection outside the six is refused, not approximated. The reader names the JSON path and exits 1 with $.transformers[0].connection: only "gy-gy" (grounded wye / grounded wye), "d-gy" (delta / grounded wye, the delta on the From side), "y-d" (ungrounded wye / delta), "d-d" (delta / delta), "oy-od" (open wye / open delta, primaries on phases A and B) and "od-od" (open delta / open delta) are supported (got "..."). A step-up oy-od is refused the same way. A rated voltage more than 20 % from its bus base is refused as a data error (an off-nominal ratio within 20 % loads). - A misspelt member is an error. An unknown member, such as sigma for sigmaPu, fails with its JSON path instead of falling back to a default. - A missing file exits 1 with a message that names it.

$ gridsim dist3ph data/dist3ph/nothere.json
error loading three-phase feeder: three-phase feeder file not found: 'data/dist3ph/nothere.json' (full path data/dist3ph/nothere.json).
[exit 1]

For a relative path the message adds the full path in brackets; the capture shows it repo-relative. - A regulator does not regulate. Its taps are the ones in the file. A change of load does not move them, so a heavily loaded feeder can sit outside any voltage band that a real regulator would hold. - A fault study ignores load and source impedance. The current comes from the series path and an infinite source at 1.0 pu, with no load, capacitor or line-charging contribution. Use iec60909 (ch. 19) where the source impedance matters. - A fault behind a regulator or on a lateral is refused. The 123-node feeder refuses a fault at bus 100, because the path from the source passes through a regulator:

$ gridsim dist3ph data/dist3ph/ieee123.json fault --bus 100
THREE-PHASE DISTRIBUTION (fault) - IEEE 123 Node Test Feeder   [EXPERIMENTAL]
  file: data/dist3ph/ieee123.json
  128 buses, 127 branches, 85 loads, base 5 MVA (three-phase)
  4 regulator(s), 5 closed switch(es), 2 open switch(es) (not branches), 4 capacitor bank(s), 60 single- or two-phase branch(es)
dist3ph fault: the sequence fault study cannot model the path to bus 100: branch 160-9004 has a step-voltage regulator, whose off-nominal (per-phase) ratio the series sum of sequence impedances does not hold. Use the three-phase sweep.
[exit 1]
- A bad --spectrum exits 2 after the header. The message lists every valid name.

$ gridsim dist3ph data/dist3ph/ieee4-gyGy-stepdown-unbalanced.json harmonics --bus 4 --spectrum nope --current 0.2
THREE-PHASE DISTRIBUTION (harmonics) - IEEE 4-node test feeder, grounded-wye / grounded-wye step-down, unbalanced load   [EXPERIMENTAL]
  file: data/dist3ph/ieee4-gyGy-stepdown-unbalanced.json
  4 buses, 3 branches, 1 loads, base 6 MVA (three-phase)
error: --spectrum expected one of 6-pulse, 12-pulse, pv-inverter, ev-charger, heat-pump-inverter, arc-furnace, saturated-transformer, 6-pulse-g5, 12-pulse-g5, afe-g5, ideal but got 'nope'
[exit 2]
- The VUF % column is empty on most rows. The factor is printed once per three-phase bus, on its phase a row, and not at all on a bus with fewer than three phases. - --bus takes the numeric id. A bus that the file names, such as RG1, is addressed by its id (9001 for RG1). - A feeder over the licence limit is refused. A feeder of your own whose bus count is above the installed tier's limit exits 2. The data/dist3ph folder is never counted (ch. 4). - Feeders are not network cases. The bare run and the positive-sequence verbs do not read gridsim-dist3ph/1 files (ch. 2).

Limits

  • The verb is experimental and its banner says so.
  • The transformer connections are gy-gy, d-gy, y-d, d-d, oy-od (step-down only) and od-od; magnetising branches are refused. Only the sweep models a connection other than gy-gy.
  • A regulator has fixed taps. There is no regulator control, line-drop compensator or voltage band, and no capacitor switching.
  • A switch has no impedance, and there is no distributed load along a line.
  • The feeder must be one radial tree with one source and no generation in a feeder file. A meshed feeder, a second source and a distributed generator are not supported.
  • The sweep prints voltages and unbalance only. It prints no branch currents, flows, losses or loading.
  • fault models an infinite source of zero impedance at 1.0 pu, neglects every shunt element, and refuses a lateral or regulator on the path to the fault.
  • estimate with wls or wlav refuses laterals, line charging, regulators and closed switches. It has no injection or angle measurement and no bad-data test: the residual rows show where J comes from, and the reading of them is yours. It is dense, so a feeder above 416 non-source buses is refused.
  • estimate --method branch-current needs a current phasor on every phase of every tree branch and takes no voltage measurement.
  • harmonics takes one balanced source, models no loads, and refuses laterals and regulators. Converter units enter only with --afe feeder.