9. GDA integration

GridSim and the GDA data lake meet at five seams. The in-repo LTDS builder (src/GridSim.Gda) reads a distribution network operator's Long Term Development Statement from the lake and assembles it into a GridModel (gridsim gda). The case writer (GdaModelWriter) materialises that model as a GridSim case directory. The replay loop (GdaReplayLoop, gridsim gda-replay) re-solves a case at every timestamp of a historical demand series. The bridge is a WebSocket protocol, served by the GDA repository and spoken by GridBridgeClient, that streams reconstructed grid states and answers on-demand physics queries. The lake products (estimated state, presolved state, divergence, closure) are the Parquet stores the bridge streams from. This chapter specifies each seam as the code implements it, including the Python scripts in the GDA repository that sit on the far side of the wire (cited as GDA NetworkModel/..., GDA Applications/... and GDA Scripts/..., which abbreviate NetworkModel/, Applications/ and Scripts/ in the v1 directory of the GDA repository). Nothing from the lake is committed to this repository.

Two rules cross every seam. Every dated input and every streamed frame is held behind the same 169-hour no-forward-inference horizon, enforced independently on both ends of the bridge (ch. 8, Provenance and invariants). Every figure the builder cannot take from a published table is a named default in GdaBuildDefaults, and every row the builder drops is counted and named in a diagnostic note.

The lake is addressed by the --root flag, else the GDA_DATA_ROOT environment variable, else GDA_ROOT (D06). This chapter writes the lake root as $GDA_ROOT. The GDA repository's Python builders and the bridge server read no environment variable for the lake; each resolves it as DataSources/ in the v1 directory of the repository, from its own location. User-level procedures are in ch. 22, ch. 23 and ch. 24; the verbs' flags are in the CLI reference.

GDA lake (read-only)                         GridSim.Gda / GridSim.Core
--------------------                         --------------------------
NationalGrid/RAWData  (NGED LTDS, CSV)  -->  GdaPaths + LtdsReader  --\
UkPowerNetworks/RAWData (CSV)           -->  UkpnSource ---------------+--> LtdsDataset
NorthernPowerGrid/{Parquet,RAWData}     -->  NpgSource ---------------/        |
                                                                              v
NationalGrid/.../Network Capacity/substations.csv --> GeoLocator <--- GdaModelBuilder.Build
                                                                              |
                                      GridModel + GdaDiagnostics -------------+
                                           |                |
                              GdaModelWriter (case dir)   SteadyStateSolver (--solve)
                                           |
                                    GdaReplayLoop (gda-replay)

Derived/{estimated_state,presolved_state,...}  <-- GDA Python builders
        |                                            |
        +-- bridge_server.py --WebSocket--> GridBridgeClient --> SimFrame --> desktop / web views

Model

The lake and its paths

GdaPaths (src/GridSim.Gda/GdaPaths.cs) resolves logical dataset names under the root. The constructor throws DirectoryNotFoundException for a missing root. A required file that is absent throws FileNotFoundException naming the path; the builder never substitutes a default for a missing required table.

Property Location under the root Read by
LtdsNodes NationalGrid/RAWData/LTDS Tabular Model/ltds-attachment-8-node.csv NGED builder: node code -> bus name
LtdsCircuits .../LTDS Tabular Model/ltds-table-1-circuit.csv NGED builder
LtdsTwoWinding .../LTDS Tabular Model/ltds-table-2a-two-winding-transformer.csv NGED builder
LtdsThreeWinding .../LTDS Tabular Model/ltds-table-2b-three-winding-transformer.csv NGED builder
LtdsDemand newest *table-3*.csv in the same folder NGED builder
LtdsGeneration .../LTDS Tabular Model/table-5-generation.csv NGED builder; optional (absent means no generation)
Substations NationalGrid/RAWData/Network Capacity/substations.csv geolocation
TecRegister newest tec-register-*.csv in NESO/RAWData/Transmission Entry Capacity (TEC) register --fleet
InterconnectorRegister newest interconnector-register-*.csv in NESO/RAWData/Interconnector Register --fleet
EmbeddedRegister newest embedded-register-*.csv in NESO/RAWData/Embedded Register --fleet
ConstraintLimits24Mo newest 24-months-ahead-constraint-limit*.csv in NESO/RAWData/24 Months Ahead Constraint Limits --fleet boundary table
LtdsFaultLevel, BusMapping ltds-table-4-fault-level.csv; Curtailment Bus Index/bus_mapping.csv declared, read by no verb

Register vintage. Publication dates are carried in file names (tec-register-05-may-2026.csv), parsed by GdaPaths.TryParseDateFromName as d-MMMM-yyyy or d-MMM-yyyy. GdaPaths.PickNewest orders candidates by that date. Modification times are never used (they differ between machines, as for DataSourceTable below): a single candidate is taken whether or not its name is dated, but when there are several, every one must carry a name date, otherwise the pick throws InvalidDataException naming the undated candidates. Equal dates break by descending case-insensitive name. When the paths carry an as-of instant (AsOfUtc), every candidate whose name proves a later publication is excluded first, so a model materialised for a historical replay cannot draw on a register published inside the replayed window. An undated name is never excluded by the as-of (it has no publication date to compare); a lone undated file under an as-of may therefore post-date it, which the name cannot rule out. gridsim gda sets the as-of to ForwardInferenceGuard.Horizon(UtcNow) (now minus 169 h); --as-of overrides it and accepts yyyy-MM-dd, yyyy-MM-ddTHH:mm, yyyy-MM-ddTHH:mm:ss, yyyy-MM-ddTHH:mm:ssZ or o, read as UTC. Any other text is a usage error (exit 2). The as-of governs the NGED demand glob and the four NESO registers. The UKPN and NPg readers do not take it.

Directory datasets. DataSourceTable.Open (src/GridSim.Gda/Csv/Tabular.cs) accepts a .parquet file, a .csv file, or a directory. A directory holding Parquet parts reads all of them in ordinal path order. A directory holding CSVs picks the one whose name carries the strictly newest publication date and throws, naming the candidates, when two files tie or any candidate is undated. Enumeration order and modification times are never consulted, so the Windows and Linux builds read the same file. A Parquet column absent from one part reads as null on that part's rows and never shifts the others. Nested Parquet columns read as null.

CSV reading. CsvTable (src/GridSim.Gda/Csv/Csv.cs) is a streaming RFC-4180 reader. It strips a UTF-8 byte-order mark, trims and tab-folds header names, accesses cells by case-insensitive column name, and supports quoted commas, doubled quotes, embedded newlines and short rows (missing trailing cells read as empty). A row with more cells than headers is refused when an extra cell is not blank (an unquoted comma in a value would shift the rest of the row), and a column named twice in the header (after trimming and case folding) is refused when it is read; the Parquet reader refuses a doubly named column the same way. CsvRow.Double (and the Parquet and UKPN readers' text cells, through GdaNumber) removes % and thousands commas, parses with NumberStyles.Float and the invariant culture and returns the fallback for a blank cell or text that is not a number in any form. NGED's - placeholder therefore reads as 0. Decision (GR-379, October 2026): a number written in a form GridSim would have to guess at is refused with an InvalidDataException naming the column and cell: a comma that is not a thousands separator in its proper place (0,5, a decimal comma, used to read as 5), parentheses ((5) used to read as -5), a trailing sign or a currency symbol. Refusing stops the build where silently reading the wrong value would have built a wrong model.

LTDS records

Every operator is normalised into one LtdsDataset: a name, an ImpedanceConvention, node, circuit, two-winding, three-winding, demand and generation lists, and the flag TransformerPercentOnRating (src/GridSim.Gda/GdaModelBuilder.cs, src/GridSim.Gda/Ltds/LtdsModel.cs).

Record Fields
LtdsNode Licence, Code, Name, BspGroup, GspGroup, Status
LtdsCircuit Licence, GspGroup, BspGroup, Node1, Node2, Status, KvBase, CircuitCode, R1Ohm, X1Ohm, B1MicroS, R0Ohm, X0Ohm, WinterRatingMva, SummerRatingMva, LengthKm, Equipment
LtdsTransformer2 Licence, GspGroup, Node1, Kv1, Node2, Kv2, Status, VectorGroup, R1Ohm, X1Ohm, X0Ohm, MinTap, MaxTap (percent of nominal ratio), NominalRatingMva, EmergencyRatingMva
LtdsTransformer3 Licence, GspGroup, Node1, Kv1, Node2, Kv2, Node3, Kv3, Status, VectorGroup, R1Ohm, X1HvLvOhm, X1LvTertOhm, X1HvTertOhm, MinTap, MaxTap, NominalRatingMva, EmergencyRatingMva (no X0Ohm; the builder does not use MinTap and MaxTap)
LtdsDemand GspGroup, BspGroup, PrimarySubstation, Node, Kv, MaxDemandMw, PowerFactor, FirmCapacityMva, Status
LtdsGeneration GspGroup, Bsp, PrimarySubstation, Kv, ExportCapacityMw, FuelType, Status

The field names carry the unit the builder assumes. LtdsCircuit.IsSeries is true when |R1| + |X1| exceeds GdaBuildDefaults.TieImpedanceThresholdOhm (1e-9 ohm). The field is named ...Ohm for the ohmic convention and holds a percent figure under the percent convention.

Assembly, step by step

GdaModelBuilder.Build(LtdsDataset, GdaBuildOptions) is a pure function of its two arguments. The steps run in this order. Every count named below is a field of GdaDiagnostics and is printed by the verb.

1. Region and status filters. A circuit or transformer is in region when its Licence equals GdaBuildOptions.Licence (case-insensitive; null passes everything) and its GSP group equals GspGroup after canonicalisation. GspKey lower-cases the name, turns punctuation into spaces, deletes a voltage token (\b\d{2,3}( \d{2})?\s*kv\b) and the station words s g p, g s p, gsp, sgp, s stn, stn, grid supply point, power station, grid, substation, bsp, main, then removes whitespace. The circuit table's "Berkswell 132kV" and the generation table's "Berkswell 132 kV S Stn" therefore carry the same key. An element is alive unless EnergisedOnly is set (default true) and its status contains, case-insensitively, one of out of service, decommiss, removed, future, planned, abandon, proposed. Node-table statuses are not tested: the node table only supplies names.

2. Voltage cut. Circuits are kept when KvBase >= MinKv, two-winding transformers when max(Kv1, Kv2) >= MinKv, three-winding transformers when the largest of the three voltages is at or above it. The region-and-status-filtered lists are retained alongside the cut lists because the elements removed only by the cut are the network below the cut, which step 7 needs.

3. Node voltages. Every endpoint of a retained element records a voltage, the circuit's KvBase or the winding's voltage, keeping the maximum per node code. An endpoint with a non-positive voltage records nothing and so never enters the union-find; an element touching it is skipped.

4. Busbar ties. A union-find (Dsu, case-insensitive node codes, path compression) merges the two nodes of every retained circuit that is not series. BusbarTiesMerged counts the unions that joined two different sets. A zero impedance row cannot be a branch (its admittance is infinite), so it is always merged. When no word of its Equipment text starts with any of busbar, bus bar, bus-bar, bus section, coupler, disconnector, isolator, switch, breaker, jumper, link (so "Switchgear" is a tie and "Interlink cable" is not), the row is a cable or line whose R and X cells were blank. It is still merged, counted in ZeroImpedanceNonTieCircuits, and the first five are named in a WARNING ties note. The UKPN and NPg readers label every row Circuit, so every zero-impedance row of those datasets is reported. The kV of a merged group is the maximum kV of its members.

5. Buses. GetBus(code) assigns bus ids lazily, in creation order, to union-find roots when an element touches them. The order is: series circuits in file order (from-node first), two-winding transformers (first node first), then three-winding transformers (first node, second node, star node, third node). An element whose two ends sit in one tie group still creates that bus before it is skipped, so a bus can carry no branch; it is isolated and counted in Buses and Islands. A tie group that no series circuit or transformer touches never becomes a bus. A bus takes the voltage of its group, the name of the root's node-table entry (the root's own code when the table has none), and the GSP group of the first element that reached it. The root is the set a merge keeps, so a bus name depends on the order of the tie rows; the order is the file order and is therefore reproducible. A synthesised three-winding star node is named STAR <first node prefix>, carries the highest winding voltage and is never a slack candidate.

6. Branches. The equations below use Zbase = kV_ref^2 / BaseMva with kV_ref = RefKv when positive and otherwise GdaModelBuilder.ParseGspKv(gspGroup). ParseGspKv returns the first of 400, 275, 132, 66, 33, 25, 11 that equals any integer token in the group name, else GdaBuildDefaults.DefaultGspKv (132 kV). RefKv is an option of the library; the verb does not expose it.

ohmic convention (no shipped reader uses it)     percent convention (NGED, UKPN, NPg)
  R_pu = R1_ohm / Zbase                            s       = BaseMva / 100
  X_pu = X1_ohm / Zbase                            R_pu    = R1_pct / 100 * s          (circuits)
  B_pu = B1_uS * SusceptanceToSiemens * Zbase      X_pu    = X1_pct / 100 * s
                                                   B_pu    = B1_pct / 100 / s          (admittance: the inverse factor)
  transformer R_pu, X_pu = ohm / Zbase             transformer, percent on rating (no reader uses it now):
  (the rating plays no part)                         Z_pu = Z_pct / 100 * BaseMva / rating_MVA
                                                     (rating <= 0 -> TransformerRatingFallbackMva = 100 MVA)
                                                   transformer, percent on 100 MVA (NGED, UKPN, NPg):
                                                     Z_pu = Z_pct / 100 * BaseMva / 100
  • Series circuits. Each retained, live, series circuit becomes a Branch(from, to, R_pu, X_pu, B_pu) with RateAMva = WinterRatingMva and name <node1 prefix>-<node2 prefix> <kV>kV. A circuit whose two ends merged into one bus is skipped. Names are made unique by appending #2, #3, ... in order. The prefix is the node code up to its first underscore.
  • Two-winding transformers. The branch is a series impedance at tap 1.0 with no shunt and no phase shift, because the per-unit bases carry the voltage ratio. A reactance with |X_pu| below 1e-6 is replaced by 1e-4 (DegenerateTransformerXPu, MinTransformerXPu) so the admittance stays finite. Every transformer branch is built high voltage to low voltage: when Kv1 < Kv2 the ends are swapped. The solver's OLTC loop lowers a tap to raise the bus it controls, which is correct only when that bus is the To end, so the swap puts every regulated bus on the To end. Bus ids still follow listing order. RateAMva is the nominal rating. A transformer with Kv1 == Kv2 is not swapped and gets no OLTC.
  • Three-winding transformers. A star (T) equivalent from the three measured reactances:
xH = 0.5 * (X_HL + X_HT - X_LT)       xL = 0.5 * (X_HL + X_LT - X_HT)       xT = 0.5 * (X_HT + X_LT - X_HL)
leg(x) = x                                      if x > 0
leg(x) = 0.01 * |X_HL| + 1e-6                   if x <= 0       (StarLegFloorFraction, StarLegFloorAbs)
H leg: branch  Node1 bus -> star  R_pu = TxPu(R1),  X_pu = TxPu(leg(xH))
L leg: branch  star -> Node2 bus  R_pu = 0,         X_pu = TxPu(leg(xL))
T leg: branch  star -> Node3 bus  R_pu = 0,         X_pu = TxPu(leg(xT))       (only when Node3 is on the network and Kv3 > 0)

The builder compares no voltages for the legs: the table is taken to list the high-voltage winding first and the low-voltage winding second. The largest of the three voltages sets only the star bus kV. All three legs carry the unit's nominal rating. The star bus is created for every retained three-winding unit whose first two nodes are on the network. A three-winding unit gets no OLTC. The NGED and UKPN readers produce three-winding records (UKPN from its Table 2b file). - OLTCs. With CreateOltcs (default true) every two-winding transformer with Kv1 != Kv2 is classified by its published tap range, in percent of nominal ratio. Valid: finite, min <= max, min <= 0 <= max, both within +/-50 %, and not 0 %/0 %. The OLTC is then Oltc(name, lv_bus, TargetVpu 1.0, MinTap 1 + min/100, MaxTap 1 + max/100, StepPu 0.0125, DeadbandPu 0.01). The tap is on the high-voltage (From) end, so +5 % is ratio 1.05, which lowers the low-voltage voltage, the sense the solver uses. A published -10 %/+10 % gives the limits 0.9 and 1.1 exactly. A range of 0 %/0 % is an off-load unit: no OLTC, counted in OltcsWithoutTapRange with an OLTC: note. Every other range (not finite, minimum above maximum, excluding 0 %, or beyond +/-50 %, which is where tap positions such as 1..17 land) is invalid: no OLTC, counted in OltcsWithInvalidTapRange, with a WARNING OLTC: note naming the first five units. The builder asserts, throwing InvalidOperationException, that every OLTC it emits controls the To end of its branch.

7. Below-cut owner map. When MinKv > 0, the network below the cut is not built, but its demand is real load drawn through the boundary. A simultaneous breadth-first search starts from every boundary node, a node that lies in the below-cut graph and is also a built bus, over the in-region, live elements that only the cut removed (circuits below the cut, transformers whose larger voltage is below it, three-winding units whose largest voltage is below it). Seeds are enqueued in ascending bus id, then ascending node code; neighbours in data order. A node equidistant in hops from two boundary buses therefore goes to the lower bus id. The result is node -> boundary bus.

8. Demand. Every LtdsDemand row with MaxDemandMw > 0 and a live status is joined by node code alone; the GSP group does not filter demand. A node on the built network adds to its bus. A node not on the network but in the owner map adds to its boundary bus (AggregatedDemand, AggregatedDemandMw). Any other node is off-network (OutOfScopeDemand, OutOfScopeDemandMw; a Demand: note under a --gsp or --licence carve, a WARNING demand: note in an uncarved build). A node that is in the union-find but whose group never became a bus is a dangling leaf (UnmatchedDemand). For each matched row:

pf = PowerFactor                      if 0 < PowerFactor <= 1
pf = DemandPowerFactor (0.98)         otherwise
Pd += MaxDemandMw                     Qd += MaxDemandMw * tan(acos(pf))

A blank NGED or UKPN power-factor cell reads as 1.0 and gives Qd = 0; the 0.98 default replaces only an impossible figure. A row with a real PrimarySubstation name (at least one letter or digit; - and blanks are NGED null markers) also records (GspKey(group), key(primary)) -> bus for the generation join, where the key is NormKey (lower-case with whitespace removed) for NPg, UKPN and caller-built datasets, and for NGED (LtdsDataset. CanonicalPrimaryJoin, set by LoadNged; N184, October 2026) CanonicalPrimaryKey: lower-case, a . between digits kept and any other punctuation a space, voltage tokens with or without kV removed (33 11 kV, 66/11kV, 11, 6.6), the station words s stn, stn, substation, primary, prim, p s, ps, s s, ss, grid, bsp, main and a lone t removed, then only letters and digits kept (Wigston Magna 33 11 kV S Stn and Wigston Magna 11 both give wigstonmagna). A name the key empties is not a join key. The canonical key folds a site's voltages together (Courthouse Green 11 and Courthouse Green 6.6), which the Demand: note below counts. Within one group the last-listed row's bus wins, and a primary whose rows sit on more than one bus is counted in PrimariesOnSeveralBuses with a Demand: note. DemandPoints counts matched plus dangling rows, and TotalDemandMw the matched MW.

9. Embedded generation. A dataset-wide register maps each normalised primary name to the set of GSP groups that list it in the demand table (every live row, whatever the carve, so a carve cannot make a colliding name look unique). For each generation row with ExportCapacityMw > 0:

  1. Under a --gsp carve, a row whose group key differs from the carve's is skipped without a count.
  2. A - or blank primary is unmatched. A primary absent from the register is unmatched.
  3. The owning group is the row's own group when that group lists the primary. Otherwise, when exactly one group lists it, that group (GenJoinedByUniqueName, Generation join: note). Otherwise the row is left unplaced (GenAmbiguousPrimary, GenAmbiguousPrimaryMw, WARNING generation join: note naming five).
  4. (owner, primary) must be in the demand map, else the row is unmatched.
  5. With ConnectedGenerationOnly (default true; --all-gen clears it) the status is classified. The not-connected words are tested first, because several contain "connected" and commissioned sits inside decommissioned.
Class Status contains (case-insensitive) Treatment
Not connected accept, offer, not yet, not connected, unconnected, disconnect, pending, contract, applied, application, enquir, quot, consent, scoping, construct, withdrawn, terminat, out of service, decommiss, removed, future, planned, abandon, proposed Left out; GenNotConnected, GenNotConnectedMw, Generation: note listing the statuses
Connected connected, energised, energized, in service, commissioned, operational Built
Unknown anything else, including blank Left out, never guessed; GenUnknownStatus, GenUnknownStatusMw, WARNING generation: note
  1. The fuel string is classified by FuelMap.Classify into a type and an inertia constant H (the keywords are Core's one fuel taxonomy, GridSim.Core.Model.FuelTypes, GDA reader, matched as whole words by their start; the H per canonical type is FuelMap.InertiaH), and the unit's dispatch is output = capacity * FuelMap.CapacityFactor(type) (nameplate is not dispatched). Without --neg-gen, the builder emits Generator(bus, Pg = output, Qg = 0, Vg = 1.0, Qmin = -0.4 * cap, Qmax = +0.4 * cap, Pmin = 0, Pmax = cap, MBase = cap, H, name = "<primary> <type>") (EmbeddedGenQRatio = 0.4). With --neg-gen it instead subtracts output from the bus Pd, so a bus can end up with negative demand. TotalGenCapacityMw accumulates capacity in both modes.

The counts cover only rows that joined a bus, so the reported MW is exactly what left the model; unplaced rows stay in UnmatchedGen.

Fuel rule (tested in this order) Type H (s) Capacity factor
nuclear nuclear 5.0 0.90
pumped, pump storage, pump-storage pumped-storage 3.0 0.10
ccgt, combined cycle ccgt 5.0 0.45
ocgt, open cycle, gas turbine ocgt 4.0 0.05
chp, cogen chp 2.5 0.55
coal coal 4.0 0.00
biomass, biogas, anaerobic, landfill, waste, energy from waste biomass 4.0 0.65
hydrogen, fuel cell, fuel-cell, electrolys, electrolyz (tested before hydro) storage 0.0 0.05
hydro hydro 3.0 0.35
tidal, wave, marine tidal 0.0 0.20
wind offshore, offshore wind wind-offshore 0.0 0.45
wind wind-onshore 0.0 0.30
solar, photovoltaic, pv solar 0.0 0.10
storage, battery, bess storage 0.0 0.05
interconnector, hvdc interconnector 0.0 0.50
gas gas 4.0 0.35
diesel, oil, reciprocating, engine recip 1.0 0.10
blank or anything else other 0.0 0.30

10. Slack buses and island labelling. A DNO network is fed from the transmission system at every grid supply point, so the builder makes one slack per GSP group, not one per model. For each non-star bus the key is the normalised GSP group of the bus (NormKey), or _isl<component> when the bus has none. Per key the slack is the bus with the highest voltage; a voltage tie within 1e-6 kV goes to the bus with more branches, and a remaining tie to the lowest bus id. Islands are the connected components of the branch graph, labelled by an iterative depth-first traversal. A dataset with InfeedPerGspGroupPerIsland (UKPN and NPg; false for NGED) instead keys each bus by GSP group and island, treats a bus whose name begins with a group's name (trailing voltage word removed, whole words) as a site bus of that group whatever its own tag, and makes every site bus at the highest site voltage of a key a slack (each is a section of the GSP board); a key with no site bus keeps the single choice above. Any island with no slack gets its highest-voltage non-star bus (lowest id on a tie). Every other bus is Pq. Slack buses start at Vm = 1.0, VaDeg = 0. The report's "primary" slack is the highest-voltage slack in the largest island. A model with several slack buses is a multi-island model; the validator says so as a warning.

11. Model, geolocation, validation. The model name is <dataset name>[ [<gsp>]][ >=<kV>kV], BaseMva is the option, FrequencyHz is 50 (SystemFrequencyHz). With Geolocate (default true) and an existing, non-empty SubstationsPath, GeoLocator.Apply places the buses (see Geolocation); an empty file or a reader exception becomes a note and never fails the build. GridModel.Validate() findings are appended to the notes as validation: ... and never block the build.

GdaDiagnostics fields, all printed or noted by the verb:

Field Meaning
RawNodes, Buses, BusbarTiesMerged Node-table rows, built buses, effective ties
SeriesBranches, Transformers2, Transformers3, StarNodes Retained element counts after the cut (Transformers2 and Transformers3 count retained rows, including any whose ends merged)
DemandPoints, TotalDemandMw, UnmatchedDemand Matched plus dangling rows; matched MW; dangling rows
AggregatedDemand(Mw), OutOfScopeDemand(Mw) Folded below the cut; off-network
Generators, TotalGenCapacityMw, UnmatchedGen Built units, their capacity, unplaced rows
GenNotConnected(Mw), GenUnknownStatus(Mw), GenJoinedByUniqueName, GenAmbiguousPrimary(Mw), PrimariesOnSeveralBuses Generation filters and join outcomes
OltcsWithoutTapRange, OltcsWithInvalidTapRange, ZeroImpedanceNonTieCircuits Tap-range and tie warnings
Islands, LargestIslandBuses, BusesByKv, Notes Components, largest component, bus count per rounded kV, the note list

Source adapters

NGED (GdaModelBuilder.LoadNged, src/GridSim.Gda/Ltds/LtdsReader.cs) is the reference schema and the default (--dno nged). Convention PercentOn100Mva (GdaModelBuilder.NgedCircuitConvention) for the circuits, with R1, X1 and B1 read together on one base, and TransformerPercentOn100Mva for the transformers: every impedance is a percentage on 100 MVA, whatever the voltage. The proof is on the constant: for circuits that NGED's LTDS Table 4 also lists as a single-circuit impedance, the percent reading matches the table's per-unit value in both R and X to the four published decimals at 33, 66 and 132 kV, while the GSP-referred ohmic reading misses by the factor Zbase / 100 (10.89 at 33 kV, 1.7424 at 132 kV). Columns read, by name:

Table Columns
Nodes Licence, Code, Name, BSP Group, GSP Group, Status
Circuits Licence, GSP Group, BSP Group, Node 1, Node 2, Circuit Status, Operating Voltage (kV), Circuit Code, R1, X1, B1, R0, X0, Winter, Summer, Circuit Length (km), Equipment
Two-winding Licence, GSP Group, Node 1, Operating Voltage 1, Node 2, Operating Voltage 2, Status, Vector Group, R1, X1, X0, Min Tap, Max Tap, Nominal Rating, Emergency Rating
Three-winding the same with Node 3, Operating Voltage 3, X1 HV-LV, X1 LV-Tertiary, X1 HV-Tertiary
Demand GSP Group, BSP Group, Primary Substation, Node, Operating Voltage, Current Year Max Demand, Current Year Power Factor, Firm Capacity of Substation, Status
Generation GSP Group, Bulk Supply Point, Primary Substation, Connection Voltage, Agreed Export Capacity, Fuel Type, Connection Status

The NGED reader skips a row at read time when: a node-table row has an empty Code; a circuit, two-winding or three-winding row has an empty Node 1 or Node 2 (an empty Node 3 is kept); a demand row has an empty Node and an empty Primary Substation; a generation row has an empty Primary Substation and an empty Bulk Supply Point. The UKPN and NPg adapters below apply their own row rules. The licences in the Licence column are EMIDS, WMIDS, SWEST and SWALES.

UKPN (UkpnSource.Load(root), --dno ukpn) reads UkPowerNetworks/RAWData. Convention PercentOn100Mva with TransformerPercentOnRating = false (Table 2a X falls with rating and X x rating / 100 has median 23.0 %, so the published percent is on 100 MVA, as NPg's headers for the same table state) and InfeedPerGspGroupPerIsland = true. Files are found by name anywhere under that folder, with or without the ukpn- prefix: ltds-table-1-circuit-data.csv, ltds-table-2a-transformer-2w.csv, ltds-table-3a-load-data-observed.csv and the optional ltds-table-5-generation.csv. Two equally close matches throw, naming them. UKPN publishes no node dictionary, so nodes are the circuit and transformer end nodes; each substation resolves to its lowest-voltage node, which is where load connects. Circuits read FromNode, ToNode, OperatingVoltage (kV), GridSupplyPoint, LicenceArea, Positive_Sequence_Impedance_R_Percent, Positive_Sequence_Impedance_X_Percent, the susceptance column Susceptance_B_ Percent (the header carries a stray space; two spellings are also tried) and the ratings in amperes, converted by MVA = sqrt(3) * kV * A / 1000. Transformers read HV_Node, LV_Node, Voltage_HV (kV), Voltage_LV (kV), Vector_Group, the percent R, X and zero sequence X, Tap_Range_Min_Percent, Tap_Range_Max_Percent and Transformer_Rating_MVA_Winter and _Summer. UKPN publishes the tap range as percent OF the nominal ratio (90 / 110), not as the offset NGED and NPg publish (-10 / +10), so the reader subtracts 100 (exact for whole numbers; 100 / 100 becomes 0 / 0, a fixed-ratio unit; a blank cell becomes NaN, which the tap-range check refuses with a WARNING naming the unit). Demand takes the newest column matching Maximum_Demand_YY_YY_MW (and its _PF partner) and keeps, per substation, the season with the largest demand. Generation reads InstalledCapacity_MVA as the export capacity in MW, Connection_Voltage_kV, FuelType and the status column Connected_Accepted. Status is always Energised, so EnergisedOnly removes nothing. For UKPN only, the reader also takes the optional three-winding table ltds-table-2b-transformer-data-3w.csv (HV, LV1, LV2 nodes; X HV-LV1, LV1-LV2, HV-LV2; R HV-LV1; the HV tap range and ratings); node codes used for different substations in different licence areas are keyed <code>@<area> (a code whose rows in every area share the first word of the substation and of the GSP name is one boundary node); a demand row is shared over the LV nodes of the transformers whose LV substation it is, in proportion to their winter ratings (a row whose node no transformer feeds moves to the one feeder node); a row whose board reaches, through circuits only, the HV side of a transformer feeding another substation with its own demand row is the sum of those rows and is kept as a join-only LtdsDemand (no load; generation naming it still joins its bus). The reader's notes on these go into LtdsDataset.SourceNotes, which the builder prints first among its notes. A table with no demand column, or no positive demand on any known substation, throws InvalidDataException: an empty network that "converged" is never produced. The UKPN CSVs on the reference lake hold headers only, so --dno ukpn exits 1 there (see "A failing source" in the worked example).

NPg (NpgSource.Load(root), --dno npg) reads NorthernPowerGrid. Convention PercentOn100Mva with TransformerPercentOnRating = false: transformer percents are on 100 MVA, unlike UKPN. Each dataset (LTDS_Appendix_3_Circuit_Data, LTDS_Appendix_4_Transformer_Data, LTDS_Appendix_5_Load_Information, LTDS_Appendix_7_Generation) is opened Parquet-first from Parquet/<dataset>, falling back to the CSV in RAWData/<dataset> when Parquet is absent or unreadable. A node is the pair (busbar name upper-cased with whitespace collapsed, kV formatted 0.#), so a circuit joins two same-voltage busbars and a transformer joins one substation's primary and secondary busbars (a transformer with equal voltages or a non-positive voltage is skipped). A transformer winding whose own pair names no node joins, by site name (NpgSource.SiteName, with no T<n> dropped: T1 and T2 are different units), the circuit busbar of that site whose voltage is nearest the winding's within 5 %, when exactly one is nearest: the transformer table writes Harrogate GT2B where the circuit table writes Harrogate GT2B 132kV and Harrogate GT2B 33kV, and without the site join 308 windings would name no busbar. The build notes open with the count (Transformer windings: <n> named no busbar ...). NPg sets InfeedPerGspGroupPerIsland. A load row joins the node its own (name, kV) pair names; when that pair names no circuit or transformer node, it joins by site name (NpgSource.SiteName: voltage tokens with kV such as 66/20kV removed, upper-cased, whitespace collapsed, and a trailing T<n> dropped from the load's name) the node of that site whose voltage is nearest the load's within 5 % (SiteJoinVoltageTolerance; NPg publishes transformer secondaries at 11.5 kV where the load table says 11.0), else it keeps its own key and stays off-network. The GSP group is S/S Group (circuits, transformers, load) or Grid Supply Point (generation). Demand takes the newest column matching YYYY/YY Net (Observed) Maximum Load (MVA) (an unversioned name is the fallback), takes the power factor from the (PF) partner (default 0.98 when outside 0 to 1) and sets MaxDemandMw = MVA * PF. Generation reads Installed Capacity (MVA) as MW and the status column Connected/Accepted. As for UKPN, a missing demand column or a table with no positive demand throws.

NESO (src/GridSim.Gda/Neso) is the transmission overlay, read by gridsim gda --fleet and not by the network build. NesoReader reads three CSV registers and one limits table:

Reader Columns Connected rule
Tec -> TecEntry Project Name, Customer Name, Connection Site, Stage, MW Connected, Cumulative Total Capacity (MW), Project Status, HOST TO, Plant Type, Project ID status or stage contains Connect, or MW Connected > 0; capacity is MW Connected when positive, else the cumulative figure
Interconnectors -> InterconnectorEntry Project Name, Connection Site, MW Import - Total, MW Export - Total, MW Import - Current, MW Export - Current, Project Status, HOST TO status contains Built or Connect, or current capacity > 0; capacity is the larger current figure (connected fleet) or the larger total figure
Embedded -> EmbeddedEntry Project Name, Connection Site, MW Connected, Cumulative Total Capacity (MW), Project Status, HOST TO, Plant Type status contains Built or Connect, or MW Connected > 0; capacity as for TEC
BoundaryLimits -> BoundaryLimit the wide 24-months-ahead table: one column per boundary code beyond YEAR, Week No per boundary: minimum, median (middle sample of the sorted positive values), maximum, sample count

NationalFleetBuilder.Build(paths, connectedOnly: true) classifies each unit with FuelMap (TEC and embedded by Plant Type, interconnectors always interconnector with H = 0) and builds NationalFleet: total capacity, synchronous capacity (H > 0), converter capacity, InertiaGvaS = sum(H * capacity) / 1000, and per-technology categories with dispatch capacity * CapacityFactor. --fleet then prints the category table, the inertia at full dispatch (the whole synchronous fleet online) and at typical dispatch (sum(H * capacity * CapacityFactor) / 1000 over the synchronous units), the largest-infeed trip (RoCoF, nadir, limits assessment, TSGB sizing), an N-1 RoCoF screen of the fleet and the boundary limit table. The reference lake holds the NESO registers as Parquet only, so --fleet exits 1 there (see Limits). The verb checks --fleet before --schema and --dno, and it is independent of the DNO source. PhaseAngleInferedReader and QuarantineLiveStore also live in GridSim.Gda; they serve the estimator's angle reference (ch. 6) and the RTU interposer (ch. 20) respectively and are not part of the network build.

Geolocation

GeoLocator (src/GridSim.Gda/Geo/GeoLocator.cs) gives a built model real coordinates on the unit square used by the map views.

key(name)   = upper-case, whitespace collapsed, then cut at the first voltage token  \s*\d+(\s*/\s*\d+)*\s*KV\b.*$
X           = (lon - (-8.2)) / (1.9 - (-8.2)),      Y = (lat - 49.8) / (59.0 - 49.8)     both clamped to [0, 1]

ReadSubstations keeps, per key, the first row whose longitude and latitude fall inside the box (-8.2 to 1.9, 49.8 to 59.0); out-of-box, blank and unparseable rows are skipped. A bus whose normalised name matches takes the projected position. Draping runs only when at least one bus matched and at least one did not: for up to 60 passes, each unplaced bus takes the mean of its already-placed branch neighbours, and a bus never reached keeps its coordinates. With no match no bus is placed, so none moves and none is jittered. Finally every placed bus is offset by a deterministic jitter, (hash(id, salt) mod 1000) / 1000 - 0.5 times 0.004 on each axis, with hash = id * 2654435761 + salt * 40503 in 32-bit unsigned arithmetic (salt 1 for X, 2 for Y), to separate co-located buses. The verb passes the NGED substations.csv whenever it exists; --no-geo skips it. The projection is equirectangular and serves layout only. The note Geolocated m/n buses from substations.csv. reports the match rate.

Case writer

GdaModelWriter.WriteDirectory(model, dir, addGridInfeed) (src/GridSim.Gda/GdaModelWriter.cs) writes the multi-file JSON case that JsonGridLoader.LoadDirectory reads (ch. 10). Property names are camelCase, output is indented, null properties are omitted. The gda verb writes exactly seven files:

File Content
system.json name, baseMva, frequencyHz
buses.json per bus id, name, baseKv, type (slack, pv, pq), vm, vaDeg, gs, bs, x, y; when set, zip, vminPu, vmaxPu (GR-332)
generation.json grid infeeds first, then embedded units: name, bus, type, capacityMva, outputMw, voltageSetpoint, qMinMvar, qMaxMvar, inertiaH, role
demand.json one entry per bus with non-zero Pd or Qd: name, bus, pMw, qMvar
transmission.json the non-transformer branches: name, from, to, rPu, xPu, bPu, ratingMva, circuits (always 1); when not at the loader's default, ratingBMva, ratingCMva, tapRatio, phaseShiftDeg, rPu0, xPu0 (GR-332)
transformer.json the transformer branches: name, from, to, rPu, xPu, tapRatio, phaseShiftDeg, ratingMva; when given, ratingBMva, ratingCMva. A transformer's shunt B and zero-sequence data have no field here and are counted in a note
onloadtapchanger.json transformer, controlsBus, targetVpu, minTap, maxTap, stepPu, deadbandPu

An embedded unit on a Pq bus is written with role = "pq" (a fixed injection on reload); on any other bus "pv". With addGridInfeed true (every gda write) a synthetic grid infeed is inserted at each slack bus: type grid, role = "slack", outputMw = 0, voltage setpoint 1.0, inertiaH = 0, name Grid infeed @ <bus name>, and capacity and symmetric reactive limits of

infeed_MW = max(GridInfeedFloorMw = 1000, demand of the island the slack sits in)
capacityMva = qMaxMvar = -qMinMvar = infeed_MW * GridInfeedHeadroomFactor (5)

The infeed is an oversized source that must never bind. GdaModelWriter.IslandDemandBySlack computes the island demand as the sum of bus Pd over the connected component, using a union-find over every written branch (union by smaller root id, summation in bus order), and fails loud with InvalidOperationException when a branch names a bus the model lacks; GridInfeedSizingMw throws ArgumentOutOfRangeException for a non-finite demand. Several slacks in one island each receive that island's whole demand. The synth verb calls the writer with addGridInfeed: false, and the model's own generator at a slack bus then takes role = "slack". The writer emits no boundaries.json, diagnostics.json or MODEL_CARD.md; those belong to the Python assembler below.

Algorithm

The gda verb

RunGda (src/GridSim.Cli/Program.cs) runs, in order: root resolution, the register as-of, geolocation switch, --fleet, --schema, source load, --all-gsps, build, report, --out, --solve.

  • Root. --root, else GDA_DATA_ROOT, else GDA_ROOT (D06: GdaRootEnvironment.Resolve in GridSim.Gda). With none, the usage text prints and the exit code is 2. A root that does not exist prints GDA root error: ... and exits 1; for a variable the message names the variable, never its value, and a set-but-missing GDA_DATA_ROOT is not replaced by GDA_ROOT.
  • Source. --dno nged|ukpn|npg (default nged; anything else is exit 2). A load failure prints Load failed: ... and exits 1. A build exception prints Build failed: ... and exits 1.
  • --gsp check. After the source load and before the build, a --gsp name must select something: GdaModelBuilder.IsKnownGspGroup compares its canonical key (GspGroupKey, the carve's own key) with the keys of every group name on the circuits and transformers (GspGroups). An unknown name prints error: --gsp '<name>' is not a GSP group of <dataset>. Nearest: ... (up to three names from SuggestGspGroups, Levenshtein distance between keys, ties by name) and exits 2.
  • Empty carve. A build with 0 buses prints error: the carve selected no live element (0 buses) ... after the report and exits 3 before --out and --solve, so no empty model is written.
  • Report. Header, build time, then the counts Raw LTDS nodes, Electrical buses, Series circuits, Transformers (2w/3w), Total branches, Demand points, Generators, System inertia, OLTCs, Connected islands, Buses by voltage and every note.
  • --out <dir> calls GdaModelWriter.WriteDirectory.
  • --solve solves with PowerFlowOptions { MaxIterations = 60, EnforceQLimits = false } through SteadyStateSolver (OLTC loop default passes). --dense selects the dense backend and --sparse the sparse one; otherwise the shared backend rule applies: sparse on the CPU (SolverSelector.DefaultSparseThreshold is 0), and on a GPU backend dense up to 200 buses (SolverSelector.DenseSparseCrossoverBuses) and sparse above. A non-converged solve prints DID NOT CONVERGE and exits 3; a solver exception prints Solve failed: ... and exits 1.
  • --all-gsps builds every GSP group named in the circuit table, with no region or status filter, in turn from the in-memory dataset (carrying --minkv, --base, --no-oltc, --neg-gen and --all-gen; --licence and geolocation do not apply), solves each with the shared dense/sparse rule, and prints a table. Spellings with the same GspGroupKey select the same elements, so each key is built once, under its first spelling, and the other spellings are listed after the table (Iron Acton 132 kV and Iron Acton 132kV are one area). A name whose build has 0 buses is set aside, listed after the table with a spelling variant of hint when another group name begins with it, and not counted. It exits 3 when any area that builds fails to build or converge, or when no area builds.
  • --schema <path> prints the column names and row count of a CSV or Parquet dataset and exits.
  • An unknown flag prints error: unknown flag '<name>' (misspelled?). followed by a pointer to the help, and exits 2; a malformed --as-of or --dno exits 2.

Exit codes: 0 success, 1 load, build, root or solve-exception failure, 2 usage, 3 non-convergence.

The replay loop

GdaReplayLoop.Replay(baseModel, series, kind, warmStart, utcNow, onSolved, storage, passivePlant) (src/GridSim.Core/Simulation/GdaReplayLoop.cs) reconstructs the grid state at every timestamp of a GdaTimeSeries (src/GridSim.Core/Gda/GdaTimeSeries.cs). It cannot nowcast: ForwardInferenceGuard.AssertHistorical is applied to every stamp at ingestion, again inside Replay, and by GdaTimeSeries.Load.

Series. A series is JSON { "name", "steps": [ { "timeUtc", "systemLoadFactor", "perBusFactor"? } ] }, camelCase and case-insensitive on read, with null properties omitted on write. perBusFactor maps bus id to factor. Synthetic(name, start, steps, stepMinutes) generates the shape of LoadProfile.DailyFactor:

x = ((hour - 4 + 24) mod 24) / 24          factor(hour) = 0.60 + 0.40 * (0.5 - 0.5 * cos(2 * pi * x))

a daily shape with trough 0.60 at 04:00 and peak 1.00 at 16:00.

Per step. For step i:

  1. step.ApplyTo(base). Without per-bus factors this is GridScenario.AtLoad: every bus Pd and Qd scaled by the factor, every generator not on the first slack bus scaled by the factor, then Dispatcher.Balance re-balances the slack. With per-bus factors each listed bus is scaled by its own factor, then Dispatcher.Balance.
  2. With storage, StorageFleet.Advance and Apply inject the hypothetical sites. The step length is the gap to the next timestamp (the last step reuses the previous gap; a one-step series uses 0.5 h), floored at GdaMinStepHours (1e-6 h).
  3. With passive plant, PassivePlantFleet.WithoutSupersededOltcs hands governed transformers' tap regulation to the delayed passive controllers (it removes a solver OLTC record only when the transformer the record drives, matched by name and end bus as the solver matches it, is one the fleet binds, GR-137), and ApplyTo applies the taps and derated ratings left by the previous converged step.
  4. With warmStart and a previous converged result, GridScenario.WithSolvedVoltages seeds the voltages. A non-converged result never seeds the next step.
  5. SteadyStateSolver.Solve. The engine comes from SolverSelector.Create(kind, base, 1500): a radial network (in-service branches = buses - 1 and exactly one slack) uses the sweep, a network of more than 1500 buses uses sparse Newton (MaxIterations = 40, EnforceQLimits = false), anything else dense Newton. The sweep and sparse Newton run no OLTC loop; dense Newton runs the solver's default OLTC passes.
  6. With passive plant and a converged solve, the plant advances over the step's length against that solve's loading and controlled-bus voltage. A non-converged solve leaves the previous updates in force.
  7. The step records TimeUtc, SystemLoadFactor, Converged, Iterations, MaxMismatch, TotalLossMw, and the minimum and maximum bus voltage, then onSolved(i, step, solvedModel, result, trace) fires.

Result. GdaReplayResult holds the series name, step count, non-converged count and the step list. Its Provenance is DerivedFromRecorded, or Counterfactual when storage was supplied (see Provenance tags below).

Passive plant. The bound passive plant is the transformer on-load tap changers and the line and transformer thermal classes that a case's asset-bindings.json binds (ch. 13). The tap delay and thermal derate act step to step. A case with nothing bound takes exactly the path of the flag off.

Storage. --bess chemistry:bus:MW:MWh[:soc] (repeatable) adds a hypothetical battery site (ch. 27). The chemistries are lfp, nmc, lto, na-ion, vrfb and lead-acid; the initial state of charge defaults to 0.5; the pack is sized on a 1000 V DC bus. --policy accepts idle, peak-shave (default; discharge above 0.9 and charge below 0.7 of the peak demand, the peak being the case's total Pd times the series' largest load factor), price and hold; lp needs prices that gda-replay does not take and exits 2.

The verb. RunGdaReplay requires --series or --synth (neither: usage, exit 2). --case (default case118) is resolved by LoadNamed: case9/ieee9, case14, case30, case57, case118, case300, case145, case24/rts, cigre, uk/gb/gb-reduced, gb-full, gb-synthetic/synthetic, or a file name under data/matpower. The synthetic series takes --start (default 2024-01-01), --steps (48) and --step-min (30.0). When both --series and --synth are given, --synth is used. The output directory is --out, else results/gda-replay-<case> resolved against the executable's directory. It contains:

File Content
run-metadata.json the run header (timestamp, backend, git commit, build, runtime, SIMD tier, machine, run description)
state-estimate.csv # header lines, then index,time_utc,load_factor,converged,iterations,max_mismatch,total_loss_mw,vmin_pu,vmax_pu, one row per step
exports/state-NNNNNN.json a gridsim-solve-export/1 document (ch. 10) for step 0 and for every step divisible by --export-every N (N > 0)
storage-counterfactual.csv with --bess: index,site,request_mw,delivered_mw,aux_mw,soc,temp_c,limited, headed by a COUNTERFACTUAL comment

Exit codes: 0 every step converged, 1 case or series load failure, 2 usage, a forward-inference rejection, or a bad storage specification, 3 one or more non-converged steps. A rejection prints REJECTED (forward inference): <message>; a series whose first offending stamp is newer than now minus 169 h is refused before any solve.

The bridge protocol

Transport and roles

The server is GDA Applications/GridSim-Bridge/bridge_server.py, a FastAPI application served by uvicorn. It binds BRIDGE_HOST (default 127.0.0.1) on BRIDGE_PORT (default 8770). One WebSocket, /ws/bridge, carries both the state stream and request/response. Every frame is one JSON object in a text message. The server serialises with allow_nan = False after replacing every non-finite number by null; the model block's "Infinity" and "NaN" string tokens (generator limits) pass through unchanged. Three HTTP routes exist: GET / returns {app, ws, cases, horizonCutoffUtc}; GET /meta returns {cases, scalar_min_timestamp, scalar_max_timestamp, frequency_min_timestamp, frequency_max_timestamp, horizon_cutoff_utc}; GET /favicon.ico returns 204. Cases are gb-full, gb-spine and every NetworkModel/zones/zone-* directory found at start-up.

The client is GridBridgeClient (src/GridSim.Core/Net/GridBridgeClient.cs); the wire schema is src/GridSim.Core/IO/BridgeProtocol.cs. The desktop app connects to BridgeEndpoint in its settings (default empty: no bridge, and no Live bridge source, until it is set; a local server is ws://127.0.0.1:8770/ws/bridge); the web app reads GridSim:BridgeEndpoint. The client sends through one semaphore-guarded send path, assembles each received message from 64 KiB chunks until end-of-message, and decodes UTF-8. BridgeProtocol.JsonOptions is case-insensitive on read, camelCase on write, skips comments and trailing commas, omits null properties and accepts the named literals Infinity, -Infinity and NaN. Instants go out as ISO-8601 UTC (GridBridgeClient.Iso: an unspecified-kind DateTime is relabelled UTC, never shifted by the machine's offset). On connect the server sends {type:"info", message:"GridSim-Bridge connected", cases:[...]}.

Client to server

Every command is {action, ...}; the server lower-cases action.

Action Fields Server behaviour
start case, start, fps, source, loop Stops any running stream, then streams case from start. case defaults to the connection's current case (initially zone-nged, else the first sorted case). start must be a string (otherwise info "Missing start timestamp") and is an ISO instant or, for stored lakes, "first" or "earliest". fps is clamped to 1..144 (integer part); an omitted fps keeps the connection's current rate (4 on a new connection) and an fps that is not an integer is ignored without a reply. source is live (default when absent or unknown), presolved, estimated, solves or raw, case-insensitive. loop (default false) wraps a stored replay.
stop none Sets the stream's stop event and replies info "Stop requested", or "No active stream". A stopped stream still ends with done.
set_speed fps Clamps to 1..144 and replies info "Playback speed updated to N FPS"; an unparseable value replies "Invalid fps value".
seek start, optional case, optional source As start with the new instant (it does not read fps or loop); replies info "Seeking to ". A missing start replies "Missing seek timestamp".
query op, at, params, id Runs one on-demand query as an independent task, alongside any stream. Answered by one result.

A body that is not valid JSON replies info "Invalid JSON command"; an unknown action replies info "Unknown action: ". Neither closes the connection. The client API is StartAsync (an instant, default source presolved, or a literal "first" with loop), StopAsync, SetSpeedAsync, SeekAsync and Query(op, at, params).

Server to client

GridBridgeClient.Dispatch routes by the top-level type, read by BridgeProtocol.PeekType, a forward-only Utf8JsonReader scan that is case-insensitive on the key and returns null for a truncated frame or a non-string value.

type Fields Client handling
topology case, model Builds and caches the GridModel, resets the tick counter, raises TopologyReceived.
state t, result, scalars, overlays, operator, market, source, estimate, generationMix, weather, interconnectors Guarded, then raises the frame events.
result op, id, at, payload Completes the pending query with that id.
error message Faults the client: Faulted with a BridgeStreamException.
info message, and cases on connect A well-formed message of a type the client does not route: ignored.
done framesSent, optional source Ignored by the client; the server sends it when a stream ends, including after stop.

A message of any other type is also a no-op, so a newer server stays compatible. A message that is not valid JSON, or has no string type, makes Dispatch throw InvalidDataException. DispatchGuarded turns that, and every other unreadable-message error listed under "Faults and rejections", into a MessageRejected event and an increment of RejectedMessages; the stream continues. A ForwardInferenceException is the one content error that ends the receive loop.

topology. model is exactly the model block of a gridsim-solve-export/1 document, which gridsim_export.to_solve_export (GDA NetworkModel/gridsim_export.py) produces. BridgeProtocol.BuildModel rebuilds it, and it is the same reader SolveImport uses. Fields: name, baseMva (default 100; a non-positive value reads as 100), frequencyHz (optional; absent reads as 50 Hz, a present value must be finite and positive or the build throws), buses (id, type, baseKv, pd, qd, gs, bs, vm, name, x, y, optional zip with ap, bp, cp, aq, bq, cq), generators (bus, pg, qg, vg, qmin, qmax, pmin, pmax, mBase, h, type, name), branches (from, to, r, x, b, tap where 0 reads as 1, phaseShiftDeg, rateAMva, name, isTransformer, inService default true, r0, x0, fromWinding, toWinding, fromNeutralXPu, toNeutralXPu; an unrecognised winding name throws), oltcs (transformer, controlsBus, targetVpu, minTap, maxTap, stepPu, deadbandPu) and boundaries (name, limitMw, branches of branch and direction; a boundary with no branches is dropped). Bus x and y are the 0..1 layout coordinates; without them a streamed model draws at one point. An unknown bus type reads as Pq. The field-by-field reference is ch. 10.

state. The result block is slim; the network is not resent.

{ "type": "state", "t": "<iso-utc>",
  "result":   { "converged", "iterations", "maxMismatch", "totalLossMw", "totalLossMvar",
                "buses":     [ { "id", "vm", "vaDeg", "pInjMw", "qInjMvar" } ],
                "lineFlows": [ { "from", "to", "pFromMw", "qFromMvar", "pToMw", "qToMvar",
                                 "pLossMw", "qLossMvar", "name", "ratingMva", "loadingPercent" } ] },
  "scalars":  { "freqHz", "rocofHzPerS", "genMw", "demandMw", "inertiaMwS", "conditionIndex", "rocofHeadroomHzS" },
  "overlays": { "stressByBranch": { "<branch name>": frac }, "conditionByBus": { "<bus id>": frac } },
  "operator": { ... }, "market": { ... },
  "source":   "presolved" | "estimated" | "solves",
  "estimate": { ... } }

BridgeProtocol.StateMessage.ToSimFrame assembles the SimFrame. An absent converged reads as true and absent iterations, maxMismatch and loss totals as 0. Generation falls back to the sum of positive bus injections when genMw is absent. An absent freqHz reads as the topology's nominal frequency, an absent rocofHzPerS as 0. An absent demandMw reads as 0 (unknown), never the cached topology's load-time demand, which is frozen at topology time and wrong for other ticks. A line flow with an empty name or a ratingMva of 0 is backfilled from the cached topology in order: the k-th flow on a bus pair (either orientation) takes the k-th topology branch on that pair, the order the solver emits flows in, so parallel circuits keep their own names and ratings. A flow that needs a backfill but has no branch left on its pair means the state does not match the topology and throws InvalidDataException. The clock hour of the frame is the time of day of t.

source names the reconstruction: presolved (the demand-scaled re-solve lake), estimated (the measurement-fitted WLS lake) or solves (the GDA-SOLVES library). The live and raw paths send no source, which reads as null. The estimate block rides estimated frames and solves frames:

Wire key Lake column Meaning
objectiveJ objective_j WLS objective J at the fitted state
chiThreshold chi_threshold the estimator's Wilson-Hilferty approximation of the 95 % chi-square quantile for the fit's degrees of freedom
chiPassed chi_passed whether J is at or below the threshold; a bool, so an absent key reads as false
chiTest chi_test optional (N214): passed, failed or not-run; when present both shells show chi-square not run for a test that did not run (it used to read FAIL). Absent (an older bridge) reads exactly as before from chiPassed. An unknown value, or one that contradicts chiPassed, rejects the frame
dof dof degrees of freedom (integer)
measurementsN measurements_n measurements in the set (integer)
removedN removed_n bad-data removals (integer)
iterations iterations Gauss-Newton iterations (integer)
reducedChi2 reduced_chi2 solves frames only: the reduced chi-square of the stored solve; the client's EstimateBlock has no field for it and ignores it

The server writes the four integer keys as JSON integers, because the client binds them to int? and refuses 632.0.

operator and market are per-tick side channels joined from Derived/operator_market_frames, every field nullable: operator carries largestLossMw, responseMw, reserveMw, deratedMarginMw, netInterconnectorMw, synchronousInertiaGvaS, outturnInertiaGvaS, marketInertiaGvaS, warning, balancingActions, constraints, warnings; market carries the imbalance, system sell, market index, day-ahead and BSUoS prices, net imbalance volume, constraint cost, carbon intensity, demand forecast, the balancing-cost and balancing-mechanism totals and counts, a feed of timed acceptances and per-interconnector flows. The raw source adds generationMix (gas, coal, nuclear, wind, windEmb, hydro, imports, biomass, other, solar, storage), weather (temperatureC, windSpeed100mKph, solarRadiationWm2) and interconnectors (ifa, ifa2, britNed, moyle, eastWest, nemo, nsl, elecLink, viking, greenlink, net), raised through RawDataReceived; its result is degenerate (empty buses and lineFlows). Fields are listed in ch. 10.

The client raises, for each accepted state, FrameReceived, StateReceived (frame, scalars, overlays), RawDataReceived, MarketDataReceived (frame, operator, market) and EstimateReceived (frame, source, estimate), in that order, after the horizon guard has passed.

result. {type:"result", op, id, at, payload}. Every reply, including every rejection, echoes the request's op, id and at verbatim. The client (GridBridgeClient.HandleResult) pairs a reply with its query by id only. A reply with no id, or with an id that matches no pending query, completes nothing and is reported through MessageRejected; a reply whose id names a query of a different op fails that query at once; a paired reply whose payload cannot be read fails its query at once with the read error. (Before D-DOC-078 an id-less reply was paired with the oldest pending query of the same op, which could hand one query another's answer.) payload.solveExport, when present, is a whole gridsim-solve-export/1 document captured raw and read by SolveImport.Read into QueryResult.Solve. payload.verdict, bindingConstraint and violations[] (kind, element, value, limit, message) are projected into QueryResult. Other payload keys (scalars, summary, frequency, headroom, reportPaths) are not projected by the client.

Query operations

The server runs each query in a worker thread as an independent task, so replies may complete out of order. case in params selects the network (an unknown case falls back to gb-full); queries on a state solve at the settled demand scale QUERY_DEMAND_SCALE = 0.70. inertia and condition with no at use the horizon cutoff.

op params Payload
inertia, condition none the nearest record at or before at (backward only, tolerance 3600 s) from the reconstructed-inertia or condition-index table in scalars; verdict is OK, or NO_DATA
scenario trip (or selector), required; a case-insensitive substring of the name is matched against non-slack generators, then lines, then transformers; a name that matches none is solved as a generator trip that removes nothing the trip is solved on the base state; verdict is SECURE, INSECURE (the first violation is the bindingConstraint) or NON_CONVERGENT; solveExport; scalars (action, removed, lost_mw, vm_min, vm_max, losses_mw); optional frequency and headroom
feasibility kind: new_load (bus, mw, pf default 0.95), loss (selector or trip, largest_interconnector, largest_generator) or dispatch (sync_fraction or target_sync_mw) the engine's verdict and binding constraint, violations, solveExport for the network kinds
post_event event_id (or event), else at; window_min (default 20) verdict OK, summary, scalars, reportPaths; violations when peak RoCoF is at or above 0.5 Hz/s or the frequency deviation is at or above 0.5 Hz
asset busId or bmUnit, optional case bmUnit, busId and four row lists, envelope, bessSoc, tapWear, consumers, whose snake_case Parquet columns are projected to camelCase; a block the unit lacks is omitted. The client renders each row as key/value fields.
propagation optional fromBus, toBus corridors[] (from, to, tau seconds, km, vKmS, class), count and provenance; with both bus ids the server answers with one corridor and provenance instead, and when the table is unbuilt with an empty corridors, count 0 and a note. The client's QueryPropagation sends no parameters and reads only corridors[] and provenance.

Violation limits used by the engines: voltage 0.94 to 1.06 pu, thermal loading 100 %, RoCoF 0.5 Hz/s (ROCOF_LIMIT_HZ_S). The client validates propagation at the protocol boundary: a corridor tau that is negative, non-finite or above PropagationData.MaxPlausibleTauSeconds (10 s) is dropped and counted in the provenance note, never passed to the swing model. GridBridgeClient.QueryPropagation returns the surviving (from, to) -> tau map for DistributedConfig.ProvidedTauSeconds.

Error replies carry verdict = "ERROR" and a bindingConstraint message: an unknown op (unknown op '<op>'. Available: [...]), an unparseable at, a missing mandatory parameter (scenario requires params.trip, new_load requires params.bus and params.mw, post_event requires params.event_id or at), an unknown feasibility kind, or an engine failure (<op> failed: <exception>). A query-level error rides a result; it does not fault the stream.

Sources

source What the server streams Cadence
live One converged sparse-NR plus OLTC solve of the case (nr_check.compute, 60 iterations, 10 OLTC passes, cached per case) re-emitted every tick; only scalars, operator and market vary 30-minute settlement periods from the next half hour at or after start to the earlier of the horizon cutoff and the newest scalar record (scalar_max_timestamp); a start later than that record is moved to 7 days before it
presolved Stored frames of Derived/presolved_state/<case> one per stored settlement period
estimated Stored frames of Derived/estimated_state/<case>, with the estimate block; scalars the row lacks are filled from the reconstructed-scalar tables one per stored period
solves The GDA-SOLVES library (gb-spine only), rebuilt per period from stored per-bus WLS states, one day at a time one per period, paging 35-day windows
raw The public-data replay: the 1 Hz frequency clock with generation mix, demand, interconnectors, weather, inertia and market joined backward; no solve one per 1 Hz sample

A presolved or estimated start with an instant falls back to the live path, with an info message naming the builder to run, when the case has no topology.json or no frame lies in the window. start = "first" snaps to the case's earliest stored partition; when the case has none, the reply is info "No frames stored for '' yet; nothing to replay." and no stream starts, with no done and no fallback. A presolved or estimated replay is capped at MAX_REPLAY_DAYS = 35 days per stream (info "Replay window capped ..."); live has no cap. With loop the frames repeat until stopped, still horizon-masked. Frames are paced at 1 / fps seconds. solves serves only gb-spine (an info otherwise). Scalars attached to a tick come from a strictly backward lookup, never a record after the tick, and freqHz in a settled snapshot is the constant 50.0.

Sessions

State is per connection: the current case, fps, loop, the active stream task and the in-flight query tasks. Starting a stream or seeking stops the previous stream first. Query tasks are cancelled on disconnect. The client caches one GridModel per connection, replaced by each topology; state frames build against it. Frames carry UTC instants and the client does no local-time conversion. Queries are correlated by id, never by arrival order: the client assigns an increasing integer string per request, awaits the matching result for at most QueryTimeout (60 s, then TimeoutException), and cancels the awaiter on cancellation or disposal. A reply whose id matches no pending query (an absent id, or one already removed after a timeout) is matched to a pending query of the same op; which one is taken follows the enumeration order of the pending table and is not defined. Server-side lazy caches (case bundles, scalar tables, engines, asset tables) are guarded by locks so two concurrent first requests do not each launch the same multi-second solve.

The 169-hour horizon, on both ends

The no-forward-inference horizon is ForwardInferenceGuard.HorizonHours = 169.0 hours (7 days plus 1 hour; src/GridSim.Core/Diagnostics/ForwardInferenceGuard.cs). A stamp is rejected when it is strictly newer than now - 169 h; the stamp exactly on the boundary passes.

Server (GDA Scripts/horizon.py, HORIZON_DAYS = 7 + 1/24, cutoff() = now minus that):

  • start and seek with an instant after the cutoff reply error "start ... is past the no-forward-inference horizon (cutoff ..., now - 7d 1h). Rejected." for live, presolved, estimated and solves. For presolved and estimated the instant is the resolved one, so first is rejected when the earliest stored frame is newer than the cutoff; solves with first skips the check and skips every frame newer than the cutoff.
  • No tick newer than the cutoff is sent: a stored or generated tick with t after the cutoff ends the stream (its done follows), even when a lake holds a newer row. The window end is the cutoff.
  • The live window runs from the next half hour at or after start to the earlier of the cutoff and the newest scalar record, the newest datetime_utc of the three scalar tables (scalar_max_timestamp). When start is later than that record, the server moves the start to 7 days before the record, no earlier than the oldest scalar record, and sends info "Requested start is past available scalar data; clamped to -> ". A window with no settlement period replies error "No settlement periods in range." and then done with framesSent 0.
  • A query whose at is after the cutoff replies payload.verdict = "INFEASIBLE_HORIZON" and runs no engine.
  • raw does not reject: its frequency bounds are clamped to the cutoff, and a start beyond the newest bounded sample is moved to two hours before it with an info. Every raw-lake context table is clamped to the cutoff on load.
  • Scalar lookups are backward-only. The same constant is built into the GDA presolve, estimated-state and measurement builders, which refuse a period after the cutoff.

Client: GridBridgeClient.HandleState first refuses an undated frame (t missing parses to DateTime.MinValue, which would pass any guard by construction), then calls ForwardInferenceGuard.RejectFuture(t, DateTime.UtcNow). The comparison is exact against the client's own clock with no skew allowance: a tick newer than now minus 169 h is refused, and a tick at or older than that instant is accepted. A server whose clock runs ahead and sends a tick newer than the client's cutoff has it refused. The check precedes every frame build and event, so a future tick never reaches a view. A violation throws ForwardInferenceException, which DispatchGuarded re-throws: it ends the receive loop, fails every pending query and raises Faulted. The socket stays open but nothing reads it, so a later start on the same connection is never answered and recovery needs a new connection. This is the only content-level error that is loop-fatal. A server error message also raises Faulted, but the receive loop keeps running.

The two enforcements are independent and use the same constant, so each is a complete defence if the other fails.

Faults and rejections

Condition Where Effect
Unknown case, invalid start, start newer than the cutoff, an empty live window ("No settlement periods in range.", followed by done) server error; client Faulted (BridgeStreamException with the message); the stream is dead and the receive loop keeps running
presolved or estimated start with an instant: lake missing for the case or empty for the window server info; the live solve streams instead
first with no stored frames, solves for another case or without a library server info; no stream starts and no done follows
Unexpected exception in a stream server error "Stream error: ..." (stored: "Presolved replay error: ...", solves: "Solves replay error: ...", raw: "Raw stream error: ...")
start/seek missing its timestamp, invalid JSON, unknown action server info; connection stays open
Query error, horizon rejection, engine failure server result with verdict ERROR or INFEASIBLE_HORIZON
Remote close client pending queries fail with BridgeStreamException "The bridge closed the connection."; Faulted
Socket failure client pending queries fail with the exception; Faulted
Tick newer than now minus 169 h client ForwardInferenceException; loop-fatal as above
Unreadable single message: invalid or truncated JSON, no string type, a bad or missing t or unparseable timestamp, a state before any topology, a flow that cannot be backfilled, an invalid winding name, an invalid frequencyHz client MessageRejected raised with the first 120 characters of the message, RejectedMessages incremented, the stream continues

DispatchGuarded treats JsonException, InvalidDataException, FormatException, InvalidOperationException, ArgumentException, KeyNotFoundException and OverflowException as a bad message; any other exception propagates as a genuine bug.

Case assembly on the GDA side

The GDA repository assembles the GB case directories the bridge serves and the estimator fits (each a case folder JsonGridLoader.LoadDirectory reads).

Normalised tables to gb-full. Ingestion normalises each licence's LTDS into six parquet tables per licence, nodes, circuits, tx2, tx3, demand and gen, under GDA NetworkModel/normalized/{licence}_{table}.parquet (assemble/run.py:TABLE_NAMES). python -m assemble.run gb-full then loads the England and Wales licences (EMID, WMID, SWEST, SWALES, EPN, LPN, SPN, NPGN, NPGY, SPM, SEPD) and the ENW synthetic subnet (repairing NaN primary demand and implausible synthetic line charging at load), runs assemble.core.assemble with an append-only bus-id registry (ids.BusIdRegistry: the same physical node always receives the same id across rebuilds), --min-kv 132 by default and a national slack, geolocates (assemble.geo), integrates the transmission spine (assemble.spine.integrate; the Scottish DNO meshes attach as equivalent BSP infeeds at spine GSPs and are not assembled directly), writes the case (assemble.writer.write_case: system.json, buses.json, generation.json, demand.json, transmission.json, transformer.json, onloadtapchanger.json, boundaries.json, diagnostics.json, MODEL_CARD.md) plus the AssetGraph parquets, and bakes a warm start (assemble.warmstart.bake: the converged vm, vaDeg and settled OLTC taps, skippable with --no-warm-start). The result, GDA NetworkModel/out/gb-full, has 3539 buses and 5918 branches (3298 lines and 2620 transformers), the same case as data/gb-full in this repository.

The spine. GDA NetworkModel/spine/build_spine.py builds one spine bus per deduplicated NESO GSP site with a synthetic-topology, real-nodes branch set: a Delaunay triangulation filtered to the Gabriel graph, pruned above PRUNE_KM = 120 km and re-unioned with the Euclidean minimum spanning tree so the graph stays one island. A curated overlay (spine/corridors.yaml, provenance curated-corridor) fixes the voltage and circuit counts of known corridors, and electrify converts per-kilometre typical impedances to r/x/b/rating. Boundary sets (B4, B6, B7, B8, SEIMP) are classified by documented geographic and PES rules, their limits set to the median of the NESO 24-months-ahead columns, and circuit counts raised until each boundary's capacity meets its limit. Outputs: spine_out/spine_nodes.parquet, spine_out/spine_branches.parquet and a GridSim-shaped boundaries.json. With SPINE_ETYS=1, apply_etys_circuits replaces synthetic edges with the real ETYS Appendix B circuits (resolved/etys_circuits.parquet): the parallel combination z_eq = 1 / sum(1 / z) with susceptances and winter ratings summed, tagged etys-appendix-b. The overlay is off by default because ETYS describes today's network and its precision exposes reinforcements that did not exist on historical days.

gb-spine. GDA NetworkModel/emit_spine_case.py folds gb-full onto its spine buses: 316 buses, one per anchor GSP, matching the per-GSP measurement layer one to one. A simultaneous breadth-first search from all spine buses over the gb-full branch and transformer graph (seeds in ascending spine-bus id) gives every other bus an owner. Each folded bus's demand and generation sum onto its owner; sub-GSP impedances are dropped, so the reduced case supplies topology and demand proportions and the measurements supply the physics. Units of type grid (the national slack and the var-only GSP voltage-control units) are not folded; interconnectors are kept. The slack is Melksham (MELK_1). Bus ids are the gb-full registry ids (NGET:<gsp> keys), so the measurement join is identical across both cases. fold_map.json ({owner: {gb-full bus -> spine bus}, pes: {spine bus -> PES group}}) is written to both case directories, and boundaries.json is copied verbatim from gb-full.

The lake products

All four are weekly-partitioned Parquet under $GDA_ROOT/Derived/<product>/<case>/year=YYYY/week=WW/, with year and week both from the ISO calendar. Each builder writes to a temporary file and os.replaces it, merges new rows into an existing partition (deduplicated on the key, last wins), and re-checks the horizon per period. Field tables are in ch. 10.

Product Grain Builder Reads Notes
presolved_state one row per 30-minute instant (48 a day) GDA NetworkModel/presolve_lake.py the case, the scalar tables A deterministic demand-scaled re-solve. demand_scale = clamp(0.70 * demandMw(t) / demand_ref, 0.30, 1.00), where demand_ref is the median reconstructed system demand; 0.70 when the demand is unknown. Each period is solved by nr_check.compute (60 iterations, 10 OLTC passes). Row: datetime_utc, case, converged, iterations, max_mismatch_pu, vm_min, vm_max, the seven scalars, demand_scale, result_json. A once-per-case topology.json holds the model block.
estimated_state one row per settlement period (46, 48 or 50 a day) GDA NetworkModel/build_estimated_state.py B1610 and interconnector measurements, the case The WLS fit of that period's telemetry. Periods that run and do not converge are stored as converged = False with no result block; a period whose gridsim estimate call writes no export aborts the day and stores nothing. Columns: datetime_utc, case, status, converged, iterations, max_state_update, objective_j, chi_threshold, chi_passed, dof, measurements_n, removed_n, removed_json ([{kind, bus, rn}]), vm_min, vm_max, boundary_json ([{name, flowMw, limitMw}]: the signed sum of each cut branch's from-end MW), result_json. topology.json carries the case's boundaries.json, merged in because the solve export does not carry boundaries.
state_divergence one row per period that both lakes cover with a converged estimate GDA NetworkModel/build_state_divergence.py the two lakes above buses_compared, flows_compared, dvm_max_pu, dvm_mean_pu, dva_max_deg, dflow_max_mw, worst_vm_bus, worst_va_bus, worst_flow_from, worst_flow_to, and the estimate's est_objective_j, est_chi_passed, est_removed_n. Where the solve and estimate routes disagree, the divergence localises model or dispatch error.
estimation_closure one row per day GDA NetworkModel/report_estimation_closure.py estimated_state, demand_all_srcs periods, converged_n, chi_passed_n, removed_total, est_gen_gwh, est_load_gwh (each converged period's positive and negative bus injections, times 0.5 h), nd_gwh (the NESO national demand series), load_vs_nd_pct, and outlier_league, the five measurements removed most often as kind@busN xCOUNT.

The estimated-state builder composes the measurement set (build_estimator_measurements.build) and runs

gridsim estimate <case-dir> --measurements m.json --prior solve --warm-start --export-solve --max-iter 100 --lean
        --backfill-removals --out <dir>

per period. It locates the CLI through the GRIDSIM_CLI environment variable. estimate writes estimated-solve-export.json only for a converged fit and exits 3 for a fit that does not converge or a network that is unobservable (ch. 6).

The measurement products. build_gsp_measurements.py reads one settlement day's B1610 file once and emits three products by merge-only aggregation (no interpolation, no gap filling), allocated through the BMU crosswalk. Unallocated energy is reported, never smeared.

Product Content and sigma
gsp_generation_measurements one row per period and GSP: generation_mw = 2 * MWh, sigma_mw, units_n, min_confidence, provenance. Physical production units only; interconnectors excluded. A per-period gsp = NULL row holds the energy the crosswalk could not bind at the confidence floor. Sigma = max(2 MW, 2 % * abs(MW)) / min_confidence; the NULL row 30 % * abs(MW).
gsp_group_demand 14 PES-group net demand series: demand_mw = -2 * sum(quantity) over supplier legs, net of embedded export behind the meter; sigma max(10 MW, 3 % * abs(MW)).
gsp_ic_flows interconnector flow at each landing GSP: ic_mw = 2 * sum(MWh), import positive. Applied in the estimator as max(5 MW, 2 % * abs(MW)).

A day with no B1610 file, or fewer than 40 periods, is built from Physical Notification levels (time-weighted period means over the levelFrom/levelTo ramps) with provenance = "pn", sigma max(10 MW, 10 % * abs(MW)) / min_confidence, and no group-demand product. The crosswalk (build_bmu_crosswalk.py, resolved/bmu_crosswalk.parquet) binds each BM unit once by its best method; allocation requires confidence at or above --min-confidence (default 0.6).

Confidence Method Rule
0.9 name-match bmUnitName against Derived/demand_consumers.name, giving the register asset's GSP and bus id
0.75 tec-register (strong) for T_* units, a curated station-code entry or a match of at least two project-name tokens
0.7 osuked-nearest OSUKED Power Station Dictionary coordinate to the nearest NESO anchor GSP, haversine, capped at 60 km
0.75 tec-register (weak) T_* units OSUKED does not know: token match of lead party and unit name, with ordinal disambiguation, after the coordinate rung
0.6 interconnector, interconnector-landing I_* units by curated id, register tokens, then the curated landing-substation table
0.5 gsp-group-only the Elexon gspGroupId, one of 14 regions
0.0 unmapped nothing bound the unit

Provenance tags applied

ProvenanceTag is defined in ch. 8. The GDA seams apply it in exactly two places. GdaReplayResult.Provenance is DerivedFromRecorded for a plain replay, and Counterfactual when hypothetical storage ran: a "what if a battery had been there" run on real history is a conclusion and never an input to another replay. The --bess run also writes a COUNTERFACTUAL comment into state-estimate.csv and storage-counterfactual.csv and prints a COUNTERFACTUAL summary line. A model assembled by gridsim gda carries no tag in its case files. On the GDA side the measurement products record their own provenance column (observed for B1610, pn for Physical Notification) and the propagation payload carries a provenance note that distances and inertia are real while wave speed and tau are modelled. The engine defaults in GdaBuildDefaults are engineering defaults for missing data; a published figure always replaces them.

Parameters and defaults

Name Value Unit Meaning Source symbol
System base 100 MVA per-unit base of the built model; --base GdaBuildOptions.BaseMva
Reference voltage 0 (auto) kV NGED referred-impedance voltage; 0 reads it from the GSP-group name GdaBuildOptions.RefKv, GdaModelBuilder.ParseGspKv
Default GSP voltage 132 kV when a group name carries no system voltage GdaBuildDefaults.DefaultGspKv
Voltage cut 0 (none) kV keep elements at or above; --minkv GdaBuildOptions.MinKv
GSP / licence carve none - --gsp, --licence GdaBuildOptions.GspGroup, .Licence
Susceptance unit 1e-6 S per LTDS unit NGED B1 is microsiemens GdaBuildOptions.SusceptanceToSiemens
Energised only true - drop dead-status elements GdaBuildOptions.EnergisedOnly
OLTCs true - one per unequal-voltage two-winding transformer; --no-oltc clears GdaBuildOptions.CreateOltcs
Embedded generation as load false - --neg-gen GdaBuildOptions.EmbeddedGenAsNegativeLoad
Connected generation only true - --all-gen clears GdaBuildOptions.ConnectedGenerationOnly
Substation table none; the verb sets it to NationalGrid/RAWData/Network Capacity/substations.csv when the file exists - --no-geo leaves it null; Geolocate (default true) has no effect without a path GdaBuildOptions.SubstationsPath, GdaBuildOptions.Geolocate
Tie threshold 1e-9 ohm abs(R1) + abs(X1) at or below is a tie GdaBuildDefaults.TieImpedanceThresholdOhm
Demand power factor 0.98 - when the published figure is outside (0, 1] GdaBuildDefaults.DemandPowerFactor
Embedded Q capability 0.4 x capacity Qmin = -0.4 cap, Qmax = +0.4 cap GdaBuildDefaults.EmbeddedGenQRatio
OLTC target 1.0 pu regulated voltage literal in GdaModelBuilder.Build
OLTC step 0.0125 pu tap step GdaBuildDefaults.OltcStepPu
OLTC deadband 0.01 pu GdaBuildDefaults.OltcDeadbandPu
Largest plausible tap 50 percent beyond it a range is invalid GdaModelBuilder.MaxPlausibleTapPercent
Degenerate transformer X 1e-6 / 1e-4 pu threshold / replacement DegenerateTransformerXPu, MinTransformerXPu
Star-leg floor 0.01 and 1e-6 x abs(X_HL), then ohm non-positive star leg StarLegFloorFraction, StarLegFloorAbs
Transformer rating fallback 100 MVA percent-on-rating with no rating TransformerRatingFallbackMva
Model frequency 50 Hz SystemFrequencyHz
Grid infeed floor / headroom 1000 / 5 MW / x infeed sizing GridInfeedFloorMw, GridInfeedHeadroomFactor
Examples named per note 5 rows GdaModelBuilder.NoteExampleLimit
Geo box lon -8.2 to 1.9, lat 49.8 to 59.0 degrees maps to the unit square GeoLocator.LonMin ... LatMax
Geo drape passes / jitter 60 / 0.004 passes / unit GeoLocator.Apply
Register as-of now - 169 h - --as-of overrides ForwardInferenceGuard.Horizon
Horizon 169.0 hours 7 days plus 1 hour ForwardInferenceGuard.HorizonHours
gda --solve 60 iterations, no Q limits - dense with --dense, sparse with --sparse; otherwise sparse on the CPU, and on a GPU backend dense up to 200 buses SolverSelector.DefaultSparseThreshold, DenseSparseCrossoverBuses
Replay sparse threshold 1500 buses sparse above it LiveSolveSettings.SparseThresholdBuses
Replay sparse iterations 40 - LiveSolveSettings.SparseMaxIterations
Replay OLTC passes (dense) 25 - SteadyStateSolver.DefaultMaxOltcPasses
Single-step / minimum step 0.5 / 1e-6 h storage and plant step LiveSolveSettings.GdaSingleStepHours, GdaMinStepHours
Synthetic series start 2024-01-01, 48 steps, 30 min - --start, --steps, --step-min GdaTimeSeries.Synthetic
Default replay case case118 - --case RunGdaReplay
Storage defaults initial SoC 0.5; peak-shave 0.9 / 0.7 of peak; 1000 V pack - StorageCli.DefaultInitialSoc, PeakShaveHighFraction, PeakShaveLowFraction, DefaultPackDcVoltage
Query timeout 60 s GridBridgeClient.QueryTimeout
Largest plausible tau 10 s PropagationData.MaxPlausibleTauSeconds
Idle interconnector cut 0.001 MW display only BridgeProtocol.MinDisplayFlowMw
Bridge bind 127.0.0.1:8770 - BRIDGE_HOST, BRIDGE_PORT
Playback rate 1 to 144 fps server clamp bridge_server.py
Replay window cap 35 days per presolved or estimated stream MAX_REPLAY_DAYS
Query demand scale 0.70 - QUERY_DEMAND_SCALE
Presolve demand scale 0.70, clamp 0.30 to 1.00 - presolve_lake.py:BASE_SCALE, SCALE_LO, SCALE_HI
Scalar lookup tolerance 3600 s backward only bridge_server.py:_nearest
Crosswalk floor 0.6 confidence --min-confidence build_gsp_measurements.py
B1610 minimum periods 40 periods below it the PN fallback is used B1610_MIN_PERIODS

Invariants

Invariant Pinned by
A zero-impedance busbar tie collapses to one bus and is counted once GdaBuildTests.Collapses_busbar_tie_into_one_bus
An ohmic impedance is referred to the GSP voltage: X_pu = X_ohm / (132^2 / 100) GdaBuildTests.Refers_transformer_impedance_to_gsp_voltage
A percent circuit is pu on 100 MVA; a percent transformer is on its rating PercentConventionTests.Circuit_percent_is_pu_on_100mva, Transformer_percent_is_on_rating, Percent_model_solves_in_band
Demand folds onto the bus and generation attaches with its fuel type GdaBuildTests.Folds_demand_and_attaches_generation
A single-GSP build has one slack, at the highest-voltage bus GdaBuildTests.Picks_highest_voltage_bus_as_single_slack
A three-winding star node is never a slack AdversarialReviewGdaTests.Three_winding_star_node_is_not_a_slack
The built network is one island and solves in band GdaBuildTests.Builds_a_single_connected_island_that_solves_in_band
The materialised case reloads and solves GdaBuildTests.Materialised_model_round_trips_through_the_json_loader
Every transformer is built high to low voltage and every OLTC controls the To end, whatever the listing order GdaBuildDataContractTests.R014_lv_first_transformer_is_oriented_hv_to_lv_and_the_oltc_controls_the_to_end, R014_every_emitted_oltc_controls_the_to_end_of_its_transformer, R014_listing_order_of_the_windings_does_not_change_the_regulated_answer
OLTC limits come from the published range; -10/+10 percent is bit-identical to 0.9/1.1; 0/0 and invalid ranges build no OLTC and say so R097_published_tap_range_sets_the_oltc_limits, R097_symmetric_ten_percent_range_is_bit_identical_to_the_old_hard_coded_limits, R097_zero_tap_range_creates_no_oltc_and_says_so, R097_invalid_tap_range_creates_no_oltc_and_warns_loudly (class GdaBuildDataContractTests)
A zero-impedance cable is merged and reported; a busbar or switch is a silent tie R097_zero_impedance_cable_is_merged_but_reported, R097_zero_impedance_busbar_or_switch_is_a_tie_without_warning
Only connected generation is built; an unknown status is excluded with a warning; the status vocabulary is classified exactly R015_accepted_and_offered_generation_is_excluded_by_default, R015_blank_or_unrecognised_status_is_left_out_with_a_warning, R015_status_vocabulary_is_classified_connected_or_not, R015_opting_out_restores_the_old_every_row_behaviour
Below-cut demand folds onto the nearest boundary bus, deterministically (lower bus id on a tie), and is reported when unreachable or off-network R047_minkv_folds_downstream_demand_onto_the_boundary_bus, R047_equidistant_boundary_buses_resolve_deterministically_to_the_lower_bus_id, R047_below_cut_load_reachable_only_through_a_removed_circuit_is_reported_not_folded, R047_demand_on_a_node_with_no_element_is_reported_in_a_full_build
Generation joins on (GSP group, primary), never the name alone R048_same_named_primaries_in_two_gsps_each_receive_their_own_generation, R048_unique_primary_name_still_joins_when_the_gsp_spelling_does_not_match, R048_ambiguous_primary_name_is_left_unplaced_with_a_warning, R048_licence_carve_does_not_import_another_licences_same_named_plant
A - primary and a Removed demand row never join AdversarialReviewGdaTests.Dash_placeholder_generation_is_unmatched_not_collapsed_onto_one_bus, Removed_demand_status_is_excluded
The GSP carve matches the generation table's differently spelled group AdversarialReviewGdaTests.Gsp_carve_matches_generation_tables_different_spelling
The newest demand vintage is read; no demand column, or no demand, fails loud; ambiguous files fail loud GdaDeterministicInputTests.Ukpn_reads_the_newest_demand_vintage, Ukpn_with_no_demand_column_fails_loud, Ukpn_with_a_demand_column_but_no_demand_fails_loud, Ukpn_with_two_equally_good_file_matches_fails_loud, Two_undated_csvs_in_a_dataset_folder_are_ambiguous_and_fail_loud, The_csv_with_the_strictly_newest_date_in_its_name_is_chosen
A Parquet column missing from a middle part does not shift later rows GdaDeterministicInputTests.A_column_missing_from_a_middle_part_does_not_shift_later_rows
The connected fleet excludes unbuilt embedded projects NationalFleetEmbeddedTests.Connected_fleet_excludes_unbuilt_embedded_projects_and_counts_connected_mw, Embedded_entry_connection_and_capacity_rules
Each grid infeed is sized on its own island's demand; a single island is unchanged FrequencyRiskPresenterTests.R200_each_infeed_is_sized_on_its_own_island_demand, R200_a_single_island_model_is_bit_identical_to_the_old_whole_network_sizing, R200_fails_loud_on_a_branch_to_a_missing_bus_and_on_non_finite_demand
Geolocation projects the GB box to the unit square, north up; an unmatched bus keeps its coordinates GeoLocatorTests.Project_maps_corners_of_gb_box_to_unit_square_corners, Northern_substation_gets_higher_Y_than_southern, Unmatched_bus_keeps_existing_coordinates
Replay reconstructs every timestamp, heavier demand gives more loss, the callback fires once per step GdaReplayLoopTests.Reconstructs_every_timestamp_of_a_synthetic_day, Heavier_demand_reconstructs_higher_loss, OnSolved_fires_once_per_step
A future-dated series is rejected at ingestion and on load; the exact boundary loads GdaReplayLoopTests.A_future_dated_series_is_rejected_at_ingestion, Load_itself_rejects_a_series_dated_just_inside_the_horizon, ForwardInferenceGuardTests.The_horizon_boundary_is_exactly_HorizonHours
Storage in a replay is counterfactual; passive plant with nothing bound is bit-identical to off StorageLoopTests.Replay_with_hypothetical_storage_is_counterfactual, PassivePlantWiringTests.Replay_with_passive_plant_on_but_nothing_bound_is_bit_identical_to_off, Replay_with_bound_passive_plant_is_deterministic
The bridge state binds topology plus state by id, backfills parallel circuits in order, and fails loud when it cannot BridgeProtocolTests.State_maps_bus_voltages_and_injections_by_id, SolveExportRoundTripTests.Parallel_circuits_each_get_their_own_name_and_rating, More_unnamed_flows_than_circuits_on_a_pair_fails_loud
The topology carries branch service state, ZIP, OLTCs, boundaries and frequency, and an older document reads with model defaults SolveExportRoundTripTests.Every_carried_network_field_round_trips_exactly, The_bridge_topology_reads_an_opened_branch, An_older_document_without_the_new_fields_reads_with_model_defaults, BridgeProtocolTests.Topology_boundaries_ride_the_model_block, Q13WsThirteenDecisionTests.A_model_block_without_frequency_reads_as_50_Hz_exactly_as_before, An_invalid_model_block_frequency_fails_loud
The estimate block, operator and market blocks and propagation payload bind and validate BridgeProtocolTests.Estimate_block_rides_the_state_message, A_state_carries_the_operator_and_market_blocks_streamed_from_the_lake, Propagation_result_projects_to_a_provided_tau_map
A query result runs its solveExport through SolveImport BridgeProtocolTests.Query_result_runs_the_payload_solveExport_through_SolveImport
A tick newer than now minus 169 h is refused before a frame is built and ends the receive loop, exactly at 169 h, with no skew allowance; a tick just older is accepted BridgeProtocolTests.A_state_with_a_future_timestamp_is_rejected_before_a_frame_is_built, Real_zone_state_stamped_now_is_rejected_by_the_forward_inference_guard, BridgeClientRobustnessTests.A_forward_inference_violation_is_still_loop_fatal, A_frame_inside_the_horizon_by_ten_minutes_is_refused, A_frame_just_outside_the_horizon_is_accepted
One unreadable message is rejected and counted and the stream continues; an untyped message is an error; an unknown type is a no-op BridgeClientRobustnessTests.A_malformed_message_is_rejected_and_counted_and_the_stream_carries_on, A_state_with_an_unreadable_timestamp_is_rejected_not_loop_fatal, A_state_before_any_topology_is_rejected_through_the_guard, A_message_with_no_type_is_an_error_not_a_silent_skip, A_well_formed_message_of_an_unknown_type_is_still_a_forward_compatible_no_op
A request instant is sent as the same UTC instant, never shifted BridgeClientRobustnessTests.Iso_sends_an_unspecified_instant_as_that_same_utc_instant, Normalise_relabels_unspecified_as_utc_without_shifting_it

Worked example

All timings in the captures differ by machine and run; the counts and numbers hold on the reference lake. The lake root is written $GDA_ROOT: gda reads --root, else the GDA_ROOT environment variable. The capture directory is docs/_captures/gda/.

A small NGED carve: Hindlow and Eyam, hand-recomputed

$ gridsim gda --root $GDA_ROOT --gsp "Stalybridge 132kV" --no-geo --out results/gda-stalybridge --solve
GridSim  -  GDA ingestion from $GDA_ROOT  (NGED)
==========================================================================
Built in 200 ms  -  GB/NGED ex-GDA [Stalybridge 132kV]

  Raw LTDS nodes          22,590
  Electrical buses             9   (busbar/disconnector ties merged: 18)
  Series circuits              5   (cables & lines)
  Transformers (2w/3w)         4 / 0   (+0 star nodes)
  Total branches               9
  Demand points                5   matched 5, total 0.02 GW
  Generators                   0   (0.00 GW capacity, 0 unmatched)
  System inertia             0.0 GVAs
  OLTCs                        4
  Connected islands            1   (largest 9 buses)

  Buses by voltage:
       33 kV         6
       11 kV         3

   No embedded generators matched; GSP infeeds carry all supply.
   1 GSP infeed(s) modelled as slack buses; primary = bus 0 (BUXT3_REDUCED_3, 33 kV).
   Demand: 2113 row(s), 23210.9 MW are on nodes outside this build's network (other areas of the carve, or nodes on no in-scope element) and were not included.
   GSP group = Stalybridge 132kV.

Materialised replica -> results\gda-stalybridge (git-ignored). Run it: gridsim --dir "results/gda-stalybridge"

Solving with the dense backend...
Converged in 28 ms (3 NR, 1 OLTC, mismatch 1.51E-011)
Generation 0.02 GW  Demand 0.02 GW  Losses 0.1 MW  V 0.991-1.000 p.u.
[exit 0]

(Capture: gda-stalybridge.txt.) Recomputing the build from the raw LTDS rows, independently of the builder:

  • Counts. The group has 28 circuit rows; 5 are Removed and are dropped (step 1), leaving 23. Of those, 18 have R1 and X1 of - (read as 0), so they are ties; 5 are series. The 23 live circuits and 4 live transformers (5 rows, 1 Removed) touch 27 distinct node codes. The 18 ties merge 27 nodes into 9 groups, so 9 buses, matching Electrical buses 9 and ties merged: 18. Branches are 5 series plus 4 transformers, 9, with no star nodes.
  • A circuit. BUXT3_#9L5 -> HINL3_TA, 33 kV, R1 6.4093, X1 21.0502, B1 0.3141, all percent on 100 MVA. With BaseMva 100, s = 1:
R_pu = 6.4093 / 100 * 1           = 0.064093
X_pu = 21.0502 / 100 * 1          = 0.210502
B_pu = 0.3141 / 100 / 1           = 0.003141

ratingMva is 484 from the Winter column. - A transformer. HINL3_TA (33 kV) -> HINL5_#1T0 (11 kV), R1 4.119, X1 65.579, 15 MVA: R_pu = 4.119 / 100 = 0.04119, X_pu = 65.579 / 100 = 0.65579, tap 1.0, rating 15, high voltage first (bus 3 to bus 8). The rating plays no part in the conversion, because the percentages are on 100 MVA, not on the unit's rating.

The captured run above and its results/gda-stalybridge/transmission.json are from an earlier build that read the NGED tables as ohms referred to the 132 kV GSP voltage (Zbase = 132^2 / 100 = 174.24 ohm), so the stored branch has rPu 0.0367843204775023, xPu 0.1208115243... and bPu 5.4728784e-05, and the transformer 0.0236398 and 0.376372. The current build writes the values above; the run (and its solve line) has not been retaken. - Its OLTC. The published range is -12 % to +4 %, so minTap = 1 - 0.12 = 0.88 and maxTap = 1 + 0.04 = 1.04, step 0.0125, deadband 0.01, controlling bus 8. This is the onloadtapchanger.json entry. - Demand. Bus 8 gathers HINL5_BB_1 (6.24 MW) and HINL5_BB_2 (4.58 MW), both at power factor 0.96: Pd = 10.82 MW, Qd = 10.82 * tan(acos(0.96)) = 10.82 * 0.291667 = 3.1558 MVAr. Five demand rows land on three buses: demand is matched by node, so Eyam (TA) (3.79 MW, listed under the Chesterfield 132kV group) joins bus 6 beside Eyam (TB) (2.95 MW), giving 6.74 MW there. - Slack. One GSP group gives one slack: among the 33 kV buses, bus 0 and bus 1 both have three branches; the first in id order, bus 0, wins. The writer sizes its infeed on this island's demand, 20.78 MW, which is below the floor, so capacityMva = qMaxMvar = 5 * 1000 = 5000. - Solve. Three Newton iterations and one OLTC pass reach mismatch 1.51e-11 pu with voltages 0.991 to 1.000 pu.

The writer's files are captured as gda-stalybridge-system.txt, gda-stalybridge-buses.txt, gda-stalybridge-transmission.txt, gda-stalybridge-transformer.txt, gda-stalybridge-oltc.txt, gda-stalybridge-demand.txt and gda-stalybridge-generation.txt. For example, the grid infeed:

$ cat results/gda-stalybridge/generation.json
[
  {
    "name": "Grid infeed @ BUXT3_REDUCED_3",
    "bus": 0,
    "type": "grid",
    "capacityMva": 5000,
    "outputMw": 0,
    "voltageSetpoint": 1,
    "qMinMvar": -5000,
    "qMaxMvar": 5000,
    "inertiaH": 0,
    "role": "slack"
  }
]
[exit 0]

With geolocation left on, the same carve reports Geolocated 3/9 buses from substations.csv. (capture gda-stalybridge-geo.txt): three buses matched the substation table by normalised name and the other six were draped from them.

The voltage cut and the three-winding units

$ gridsim gda --root $GDA_ROOT --licence EMIDS --minkv 132 --no-geo
GridSim  -  GDA ingestion from $GDA_ROOT  (NGED)
==========================================================================
Built in 209 ms  -  GB/NGED ex-GDA >=132kV

  Raw LTDS nodes          22,590
  Electrical buses           474   (busbar/disconnector ties merged: 770)
  Series circuits            323   (cables & lines)
  Transformers (2w/3w)       190 / 2   (+2 star nodes)
  Total branches             519
  Demand points              824   matched 824, total 8.90 GW
  Generators                   2   (0.00 GW capacity, 894 unmatched)
  System inertia             0.0 GVAs
  OLTCs                      190
  Connected islands            3   (largest 418 buses)

  Buses by voltage:
      132 kV       280
       66 kV         1
       33 kV       147
       25 kV         6
       11 kV        40

   16 GSP infeed(s) modelled as slack buses; primary = bus 3 (Warwick 132kV Main 2, 132 kV).
   ...
   Demand: 814 row(s), 8699.8 MW below the 132 kV cut were folded onto their nearest boundary bus (losses and voltage drop below the cut are not modelled).
   Demand: 1294 row(s), 14331.8 MW are on nodes outside this build's network (other areas of the carve, or nodes on no in-scope element) and were not included.
   Filtered to >=132 kV.
   Licence = EMIDS.
   validation: warning: 16 slack (reference) buses  -  treating as a multi-island system.
[exit 0]

(Capture: gda-emids-132.txt, with the intermediate notes elided here.) Of the 824 East Midlands demand rows, 814 sit below the 132 kV cut and are folded onto their nearest boundary bus (8699.8 MW), so the 474-bus model still carries the whole licence's load; the other 1294 rows belong to other licences. Sixteen GSP groups give sixteen slacks over three islands. The 2 three-winding units add 2 star nodes and 6 branches, so Total branches is 323 + 190 + 6 = 519 (each three-winding unit contributes an H leg, an L leg and, when a tertiary is on the network, a T leg), and there are 190 OLTCs for the 190 two-winding transformers because no published range was zero or invalid. The embedded generation join is the weak point of the NGED tables (see Limits): 894 of the 897 generation rows are unmatched.

Connected generation only is the default. --all-gen readmits the one accepted unit that the default run reports as 1 matched row(s), 5.0 MW ... not connected yet (capture gda-emids-132-all-gen.txt: Generators 3).

A failing source

$ gridsim gda --root $GDA_ROOT --dno ukpn --no-geo
Load failed: UKPN ukpn-ltds-table-3a-load-data-observed.csv: column Maximum_Demand_24_25_MW gave no positive demand on any known substation, so the replica would have no load.
[exit 1]

(Capture gda-ukpn.txt, taken on a lake whose UKPN LTDS CSVs contain headers only.) The reader refuses to build a network with no load.

Replay on the real GB case

$ gridsim gda-replay --synth --case gb-full --start 2024-01-01 --steps 6 --export-every 3 --out results/gda-replay-gbfull

=== Historical state estimate: gb-full over synthetic-gb-full ===
  reconstructed 6 timestamps  (2024-01-01T00:00:00.0000000Z .. 2024-01-01T02:30:00.0000000Z)
  non-converged: 0
  system loss over the series: 199.9 .. 257.9 MW

  -> results\gda-replay-gbfull
[exit 0]

The case has 3539 buses, so the replay selects sparse Newton. The CSV (gda-replay-gbfull-csv.txt):

$ cat results/gda-replay-gbfull/state-estimate.csv
...
index,time_utc,load_factor,converged,iterations,max_mismatch,total_loss_mw,vmin_pu,vmax_pu
0,2024-01-01T00:00:00.0000000Z,0.7000,True,6,3.528E-011,257.944,0.97135,1.04571
1,2024-01-01T00:30:00.0000000Z,0.6782,True,2,2.201E-009,242.344,0.97318,1.04572
2,2024-01-01T01:00:00.0000000Z,0.6586,True,2,1.412E-009,228.665,0.97482,1.04572
3,2024-01-01T01:30:00.0000000Z,0.6413,True,2,8.048E-010,217.002,0.97624,1.04572
4,2024-01-01T02:00:00.0000000Z,0.6268,True,2,3.930E-010,207.417,0.97742,1.04572
5,2024-01-01T02:30:00.0000000Z,0.6152,True,2,1.538E-010,199.945,0.97835,1.04573
[exit 0]

The load factors are the daily shape recomputed by hand: at 00:00, x = 20 / 24, 0.60 + 0.40 * (0.5 - 0.5 * cos(2 * pi * 20/24)) = 0.60 + 0.40 * 0.25 = 0.7000; at 00:30, x = 20.5 / 24, giving 0.678248, shown as 0.6782. Step 0 is solved cold (6 iterations); every later step warm-starts from the previous converged state and needs 2. Loss falls with the load factor. exports/state-000000.json and exports/state-000003.json are gridsim-solve-export/1 documents for steps 0 and 3.

The same replay with --passive-plant (capture gda-replay-passive-csv.txt) differs from step 1 on, because the bound transformer taps move with delay from the previous converged state; step 0 is identical:

$ cat results/gda-replay-passive/state-estimate.csv
...
0,2024-01-01T00:00:00.0000000Z,0.7000,True,6,3.528E-011,257.944,0.97135,1.04571
1,2024-01-01T00:30:00.0000000Z,0.6782,True,3,2.505E-011,242.349,0.98182,1.04572
2,2024-01-01T01:00:00.0000000Z,0.6586,True,3,3.478E-011,228.657,0.98323,1.04572
...
[exit 0]

Hypothetical storage on a 48-step day of case118 (capture gda-replay-bess.txt) prints the counterfactual summary:

$ gridsim gda-replay --synth --case case118 --steps 48 --bess lfp:10:20:40 --policy peak-shave --out results/gda-replay-bess

=== Historical state estimate: case118 over synthetic-case118 ===
  reconstructed 48 timestamps  (2024-01-01T00:00:00.0000000Z .. 2024-01-01T23:30:00.0000000Z)
  non-converged: 0
  system loss over the series: 50.3 .. 132.5 MW
  COUNTERFACTUAL (Counterfactual): hypothetical storage on recorded history - not a reconstruction.
  LFP 20MW/40MWh @10: out 38.5 MWh, in 21.2 MWh, aux 1.09 MWh, stored change -20.2 MWh, round trip 93.1 %, 0.75 equivalent full cycles
      ageing over the run: calendar 0.1365 %, cycle 0.0026 % (rainflow, depth-aware: 0.0020 %), deepest cycle 90 % SoC

  -> results\gda-replay-bess
[exit 0]

The horizon, enforced

A series stamped inside the 169-hour window is refused before any solve. The capture gda-replay-rejected.txt was taken more than 169 hours after its 2026-10-01 stamps, so on that run the series is historical and replays, exit 0:

$ gridsim gda-replay --synth --start 2026-10-01 --steps 4 --out results/gda-replay-rejected

=== Historical state estimate: case118 over synthetic-case118 ===
  reconstructed 4 timestamps  (2026-10-01T00:00:00.0000000Z .. 2026-10-01T01:30:00.0000000Z)
  non-converged: 0
  system loss over the series: 56.7 .. 66.6 MW

  -> results\gda-replay-rejected
[exit 0]

Run within 169 hours of 2026-10-01, the same command prints REJECTED (forward inference): ... with the horizon, the run's UTC clock minus 169 hours, and exits 2. A stamp exactly on the horizon loads.

One stored estimated frame

The estimated-state lake on the reference machine holds one gb-spine period (capture lake-estimated-state-row.txt):

$ python (read one partition of the estimated_state lake; result_json, removed_json and boundary_json omitted)
partition: $GDA_ROOT/Derived/estimated_state/gb-spine/year=2026/week=36/estimated_state.parquet
rows: 1  columns: 17
...
datetime_utc      2026-09-01 11:00:00+00:00
case              gb-spine
status            Converged
converged         True
iterations        8
max_state_update  1.4822059173716063e-09
objective_j       225.414916686831
chi_threshold     359.5207249007415
chi_passed        True
dof               317
measurements_n    948
removed_n         0
vm_min            0.999361616293283
vm_max            1.051805170833602
[exit 0]

The row checks by hand. gb-spine has 316 buses, so the state has 2 * 316 - 1 = 631 unknowns (every voltage magnitude and every angle but the reference), and dof = 948 - 631 = 317. The estimator's 95 % threshold is the Wilson-Hilferty cube-root approximation 317 * (1 - 2/(9 * 317) + z * sqrt(2/(9 * 317)))^3 with z = 1.6448536, the 95 % normal quantile, which is 359.52072; the stored value is 359.5207249 (ChiSquare.Quantile in src/GridSim.Core/Estimation/ChiSquare.cs, which takes z from Acklam's rational approximation). The exact chi-square 95 % quantile for 317 degrees of freedom is 359.52184, so the approximation sits 0.0011 below it. J = 225.4 < 359.5 is why chi_passed is true. Manual ch. 22 re-runs the same period and reaches J = 330.37 after 10 iterations; the stored row is a separate run. The result_json of that row holds 316 buses and 579 line flows, which is what a bridge state frame carries for the estimated source.

Source map

GDA Applications, GDA Scripts and GDA NetworkModel abbreviate Applications/, Scripts/ and NetworkModel/ in the v1 directory of the GDA repository.

File Type or script Responsibility
src/GridSim.Gda/GdaPaths.cs GdaPaths Logical dataset paths, publication-date parsing, as-of newest-file selection
src/GridSim.Gda/Csv/Csv.cs, Csv/Tabular.cs, Csv/VintageColumns.cs CsvTable, DataSourceTable, VintageColumns CSV and Parquet readers, deterministic file choice, newest-vintage column choice
src/GridSim.Gda/Ltds/LtdsModel.cs, Ltds/LtdsReader.cs Ltds* records, LtdsReader NGED row types and reader
src/GridSim.Gda/Ukpn/UkpnSource.cs, Npg/NpgSource.cs UkpnSource, NpgSource UKPN and NPg normalisation into LtdsDataset
src/GridSim.Gda/Neso/NesoReader.cs, NesoModel.cs, NationalFleet.cs NesoReader, TecEntry, NationalFleetBuilder NESO registers, boundary limits, the national fleet
src/GridSim.Gda/Neso/PhaseAngleInferedReader.cs PhaseAngleInferedReader System phase-angle series for the estimator (ch. 6)
src/GridSim.Gda/Interpose/QuarantineLiveStore.cs QuarantineLiveStore Live-telemetry quarantine store (ch. 20)
src/GridSim.Gda/FuelMap.cs FuelMap Fuel string to type, inertia constant and capacity factor
src/GridSim.Gda/GdaBuildDefaults.cs GdaBuildDefaults Named engineering defaults and guards
src/GridSim.Gda/GdaModelBuilder.cs GdaModelBuilder, GdaBuildOptions, GdaDiagnostics, Dsu The assembly of section "Assembly, step by step"
src/GridSim.Gda/Geo/GeoLocator.cs GeoLocator Name join, projection, draping, jitter
src/GridSim.Gda/GdaModelWriter.cs GdaModelWriter Case directory writer, grid infeed sizing
src/GridSim.Core/Gda/GdaTimeSeries.cs GdaTimeSeries, GdaTimeStep Series load with horizon, synthetic series, per-step case
src/GridSim.Core/Simulation/GdaReplayLoop.cs GdaReplayLoop, GdaReplayResult The replay loop
src/GridSim.Core/Diagnostics/ForwardInferenceGuard.cs ForwardInferenceGuard The 169-hour horizon
src/GridSim.Core/IO/BridgeProtocol.cs BridgeProtocol and its message, block and DTO classes The wire schema and its projection to GridModel, SimFrame, QueryResult
src/GridSim.Core/Net/GridBridgeClient.cs GridBridgeClient The client: connection, commands, receive loop, guard, faults
src/GridSim.Cli/Program.cs RunGda, RunGdaReplay, RunGdaFleet, RunGdaAllGsps, RunSchema The verbs
GDA Applications/GridSim-Bridge/bridge_server.py, raw_replay.py bridge server WebSocket and HTTP routes, streams, query dispatch, horizon masking
GDA Scripts/horizon.py horizon guard The server-side 169-hour cutoff
GDA NetworkModel/gridsim_export.py to_solve_export The gridsim-solve-export/1 writer used by the bridge
GDA NetworkModel/validate/nr_check.py nr_check.compute The sparse Newton plus OLTC solve behind live and the presolved lake
GDA NetworkModel/assemble/, spine/, emit_spine_case.py assembler, spine, fold gb-full, spine, gb-spine
GDA NetworkModel/presolve_lake.py, build_estimated_state.py, build_state_divergence.py, report_estimation_closure.py lake builders The four lake products
GDA NetworkModel/build_gsp_measurements.py, build_bmu_crosswalk.py, build_estimator_measurements.py measurement builders Measurement products and the BMU crosswalk
tests/GridSim.Tests/Gda/, GdaReplayLoopTests.cs, BridgeProtocolTests.cs, BridgeClientRobustnessTests.cs, SolveExportRoundTripTests.cs tests The invariants above

Limits

  • Embedded generation joins on the primary-substation name: for NGED on the canonical primary key (N184, October 2026), because its generation table names primaries differently from its demand table. On the full NGED lake (no carve) the whitespace key built 2 generators (3 rows joined, one left out as not connected; 894 unmatched); the canonical key builds 284 (1.09 GW of capacity; 297 rows joined, 13 left out as not connected, 600 unmatched). 214 named primaries in the generation table have no demand-table primary at all. The East Midlands captures above predate N184.
  • NPg demand joins a circuit or transformer node by its (name, kV) pair, else by site name and the nearest voltage within 5 % (N184): 86 of the 657 positive-load rows (2.27 GW) on the full lake, the most the published tables allow (it was 34, 0.26 GW); most other loads are 11 kV primaries whose 11 kV busbar is in neither Appendix 3 nor 4. The rest is reported as off-network demand and not modelled. With that demand the full-lake NPg build's power flow stopped converging (60 iterations, mismatch 4.63E-001, exit 3): a 26-bus, 33 kV-only island carried Harrogate 33kV (51.9 MW) and Wormald Green 33kV (70.8 MW) from one infeed at Coneythorpe T1 33kV (voltage down to 0.519 pu). The island had no path to 132 kV because the two sites' grid transformers were built floating (the winding names above). Since N202 the windings join their busbars and NPg takes the per-island infeed rule: 3,197 -> 2,892 buses, 649 -> 364 islands (largest 137 -> 174 buses), 652 -> 461 GSP infeeds, and the power flow converges (sparse Newton 4 iterations, 12 OLTC passes, mismatch 1.16E-010; losses 23.3 MW; V 0.948-1.017 pu; worst grid infeed 5.98 % of its 5,000 MVA, West Boldon 66kV, 298.9 MVA). The infeed rule alone did not converge (751 infeeds, mismatch 1.84E-001, V 0.464-1.024 pu).
  • Below a --minkv cut, losses and voltage drop are not modelled; the folded demand sits on the boundary bus.
  • gda --all-gsps does not apply --licence or geolocation, and takes its group list from every GSP name in the circuit table.
  • A three-winding unit is built with Node1 as the high-voltage end and Node2 as the low-voltage end whatever their voltages.
  • The NESO reader reads CSV registers from NESO/RAWData/..., so a lake that holds them only as Parquet makes gda --fleet fail with "GDA dataset folder not found".
  • The UKPN and NPg readers ignore --as-of and take the files as found.
  • Only the NGED and UKPN readers produce three-winding transformers.
  • gda-replay --case accepts case9 (ieee9), case14, case30, case57, case118, case300, case145, case24 (rts), cigre, uk (gb, gb-reduced), gb-full, gb-synthetic (synthetic), a file name under data/matpower, and a JSON case directory holding system.json, such as one written by gda --out. Its default --out is results/gda-replay-<case> under the current directory.
  • When --series and --synth are both given, --synth is used without a message.
  • gb-spine is a documented fold of gb-full, not a boundary equivalent: sub-GSP impedances are dropped.
  • The ETYS circuit overlay (SPINE_ETYS=1) is off by default because it is not era-aware.
  • A stored-source start of first on a case whose lake holds frames but no topology.json falls back to live with the literal first, which replies error "Invalid start date".
  • The client matches a reply with an unknown or absent id to any pending query of the same op, not the oldest.
  • build_estimated_state.py finds the GridSim CLI from GRIDSIM_CLI and otherwise from a fixed default location that does not exist on every machine.