5. Frequency dynamics

GridSim models system frequency with one centre-of-inertia (COI) swing equation. A power imbalance deltaP moves frequency at a rate set by the stored kinetic energy E of the synchronous fleet; load damping, governor droop, recorded response services, an optional fast-response device, an optional grid-forming virtual former and an optional authored inverter fleet add power terms that arrest the fall. This chapter specifies the equation as implemented, how E is built from the generator list, the integration method and step, every DynamicsConfig field, the response-service delivery curves, the grid-forming kernel, the distributed multi-domain model, the inertia inversion, the GB limit classifiers and the NESO trace path. It states which constants are fitted, which are not, and which numbers each of them can and cannot move.

The code is under src/GridSim.Core/Dynamics/, src/GridSim.Core/Frequency/ and src/GridSim.Core/Simulation/LiveSim.cs. The user-facing verbs (freq, replay, trip, transient, domains) are in manual ch. 14, Frequency studies. Where the inertia numbers of a real fleet come from is in ch. 13, Asset-dynamics data grounding; how the cascade model was blind-validated is in ch. 14, Blind cross-event validation of the asset-dynamics cascade; the detailed machine, governor and exciter models are in ch. 24, Standard dynamic-model library. None of those is repeated here.

Model

The swing equation

Per integration step, with df = f - f0 and every power in MW (negative deltaP is a loss of infeed):

rocof      = f0 / (2 * E) * pImbalance                                   Hz/s
pImbalance = pEvent + pStanding + pGov + pTsgb + pServices - d * df
f(next)    = f + rocof * dt                                              explicit Euler
Term Meaning Definition Unit
f0 Nominal frequency DynamicsConfig.NominalHz Hz
E Stored kinetic energy of the system max(1.0, systemInertiaMwS + DeviceRotationalInertiaMwS) MW.s
pEvent Imposed imbalance sum of FrequencyEvent.DeltaPMw over every event with AtSeconds <= t + 1e-6 * dt (the tolerance absorbs the rounding of t = k * dt, as the RMS stage times do); steps are cumulative and permanent MW
pStanding Pre-event balance 0 unless InitialFrequencyHz is set; then -(pGov0 + sum(pSvc0) - d*df0) MW
pGov Governor droop response first-order lag toward -(df/f0)/DroopPu * Presp MW
pTsgb Device fast response first-order lag toward the clamped, dead-banded fast-response target MW
pServices Recorded DC/DM/DR sum of one lagged state per SystemResponseService MW
d * df Load damping d = DampingPctPerHz / 100 * baseDemandMw MW

Presp = ResponsiveFraction * baseDemandMw is the capacity the droop term is scaled by. It is not a limit: the governor target is -(df / f0) / DroopPu * Presp, a straight line through zero with no dead-band and no clamp, so it equals Presp at |df| = f0 * DroopPu (2.5 Hz at the defaults) and keeps growing past it (a 5 Hz deviation gives 2 * Presp, 15,800 MW on the default case). A loss (pEvent < 0) drives df negative; the droop target and the load-relief term -d*df are then positive and oppose the loss.

The lagged terms are advanced before rocof is evaluated in the same step, using the frequency at the start of the step:

pGovTarget = -(df / f0) / DroopPu * Presp
pGov      += (pGovTarget - pGov) / max(dt, GovernorTimeConstantS) * dt

ffrTarget  = 0                                                   if FastResponseMw <= 0 or |df| <= FastResponseDeadbandHz
           = clamp(-(FastResponseMw / 0.5) * df, -FastResponseMw, +FastResponseMw)    otherwise
pTsgb     += (ffrTarget - pTsgb) / max(dt, FastResponseTimeConstantS) * dt

for each service s:
    pSvc[s] += (curve_s(df) - pSvc[s]) / max(dt, T_s) * dt        curve_s is defined under "Response services"
pServices   = sum of pSvc[s]

0.5 in the fast-response gain is the full-delivery deviation in Hz, SwingKernel.DeviceFullDeliveryHz: the device reaches FastResponseMw at 0.5 Hz deviation. Neither term has a knee. The governor is a straight line through zero with no dead-band and no cap. The fast response is zero inside FastResponseDeadbandHz, a straight line outside it, and clamped to +/-FastResponseMw; it is the only one of the two with a dead-band and a clamp.

At the step where an event first applies, every lagged state is still 0 and df is 0, so pImbalance = pEvent exactly and the first RoCoF is f0/(2E) * pEvent (see "What sets the initial RoCoF and the nadir").

The load-damping term is physical: load falls as frequency falls, so -d*df is a positive power when df < 0.

Inertia E

E is the sum of H * MBase over the generators that count as rotating mass, in MW.s. H is the inertia constant in seconds on the machine's own base MBase (MVA), so H * MBase is that machine's stored energy. A generator whose type the shared technology map (PoleMap.ForType) knows as converter plant (storage, battery or bess, wind, solar, tidal, interconnector, hvdc, converter) contributes nothing, whatever H its data carries: such an H is a synthetic inertia figure, and virtual inertia is not real mass. A unit of unknown or blank type keeps its H.

GridModel.SystemInertiaMwS  = sum over rotating-mass generators of (g.H * g.MBase)  MW.s   (fleet order)
GridModel.SystemInertiaGvaS = SystemInertiaMwS / 1000                                  GVA.s
systemInertiaMwS            = GridModel.SystemInertiaGvaS * 1000                       MW.s

(src/GridSim.Core/Model/Model.cs.) Generator.H defaults to 0 and Generator.MBase to 100, so a plant with H = 0 adds nothing, whatever its rating. The lumped and distributed callers that start from a GridModel pass SystemInertiaGvaS * 1000.0; the divide and multiply by 1000 are part of the computation and every such route uses the same pair. trip and screen read SystemInertiaMwS directly and take out the tripped unit's own share, GridModel.RotatingInertiaMwS(g) (H * MBase for rotating mass, exactly 0 for a known converter technology), because a tripped unit stops spinning. Every route therefore agrees on what inertia is.

Where H comes from for a GDA-built model is the representative value per fuel class in GridSim.Gda/FuelMap.cs:

Class H (s) Class H (s)
nuclear 5.0 biomass 4.0
ccgt 5.0 gas 4.0
ocgt 4.0 coal 4.0
pumped-storage 3.0 hydro 3.0
chp 2.5 recip 1.0
wind, solar, tidal, storage, interconnector, other 0.0

The floor and the substitutions that guard E:

  • Batch and live integrators. E = max(1.0, system + device). A system with no inertia is treated as 1 MW.s, which is a numerical guard, not a physical claim. The floor does not apply under grid-forming; see below.
  • Device inertia. DeviceRotationalInertiaMwS is real stored energy (1/2)*J*omega^2 of an added device and is summed into E, so it cuts RoCoF exactly as the same MW.s of system inertia would. The device's fast response is a separate power injection and never changes E. The two device terms are never merged.
  • Live fallback. LiveSim replaces E when the fleet carries no usable H. If E < LiveSolveSettings.MinInertiaMwS (100 MW.s), it uses LiveSolveSettings.FallbackInertiaH * sum(MBase) over the generators (|Pg| for a generator with MBase <= 0), with FallbackInertiaH = 4.0 s; if that is still below 100 MW.s it uses FallbackInertiaH * baseDemandMw. The substitution is suppressed when Forming != None, because a low real inertia is then the case under study. The batch simulator and the trip verb have no fallback.
  • Virtual inertia. VirtualInertiaMwS (Ev) is a control state. It enters only the grid-forming denominator and is never added to E.

Integration method and step

Every COI path is a fixed-step explicit (forward) Euler integration of the lagged states and of f. There is no adaptive step, no RK scheme and no iteration.

  • Batch (FrequencyDynamics.Simulate): step StepSeconds (0.02 s, the cadence the NESO upsampler produces, so simulated and recorded traces share a timeline) for round(DurationSeconds / StepSeconds) steps, k = 0..steps inclusive, so steps + 1 points. t = k * dt. Points[k] holds the frequency at the start of step k and the RoCoF computed in it. SettleHz is the frequency after the final update, one step past the last point.
  • Live (FrequencyIntegrator.Step(dtSeconds, eventMw)): the caller's step is split into equal sub-steps:
nSub = clamp(ceil(dt / min(dt, MaxInternalDt)), 1, MaxSubSteps)       MaxInternalDt = 0.02 s, MaxSubSteps = 4000
h    = dt / nSub

A step of 20 ms or less is one sub-step. A step above 80 s hits the 4000-sub-step cap, so the sub-step grows above 20 ms in proportion (a 1200 s step uses h = 0.3 s). The governor, fast-response and damping states are advanced per sub-step with h in place of dt. The droop equilibrium does not depend on h, so a clamped step settles where a fine sweep settles. - Grid-forming (Forming != None): the load-damping term is integrated implicitly and the step is sub-divided by FormingKernel.SubStepCount; see the grid-forming section. - Distributed (two or more swing masses): semi-implicit (symplectic) Euler on the same StepSeconds; see the distributed section.

Trajectory timestamps are synthetic, anchored at 2000-01-01T00:00Z. No simulator in this chapter reads the clock.

Batch simulator and live integrators

FrequencyDynamics.Simulate(systemInertiaMwS, baseDemandMw, events, config) returns a FrequencyResponse. The stateful integrators run the same equation one Step at a time for the live view (src/GridSim.Core/Simulation/LiveSim.cs). Every centre-of-inertia engine (FrequencyDynamics.Simulate, AssetFrequencyDynamics.Simulate, FrequencyIntegrator, AssetAwareFrequencyIntegrator, FleetDynamics.Simulate, MultiDeviceFrequencyIntegrator, MultiDomainSwing.Simulate) takes its responder states and the order their powers are added from one kernel, SwingResponders (src/GridSim.Core/Dynamics/SwingResponders.cs): the governor droop lag, the TSGB device lag, each recorded service's lag and the equilibrium start at a pre-event frequency. Each engine keeps only its own time loop, swing step and trace, so the live integrators reproduce the batch trace bit for bit when stepped at the batch step under the same event power.

Capability FrequencyDynamics.Simulate FrequencyIntegrator AssetAwareFrequencyIntegrator
Step StepSeconds, fixed caller dt, split to at most 20 ms (at most 4,000 sub-steps) same as FrequencyIntegrator
Governor, damping, device FFR yes yes yes
SystemResponseServices yes yes yes
InitialFrequencyHz (equilibrium start) yes yes yes
Base demand as given as given as given
Grid-forming yes yes yes
pAssetFleet AssetFrequencyDynamics.Simulate no yes

Every engine refuses a negative or non-finite demand and a non-finite or non-positive NominalHz or InitialFrequencyHz (ArgumentOutOfRangeException). A live Step refuses a step that is not finite and positive, or an event power that is not finite (SwingKernel.RequireLiveStep). LiveSim floors its own demand at 1 MW before it builds an integrator. MultiDomainSwing refuses a grid-forming config (MultiDeviceFrequencyIntegrator runs the forming step since N291).

IFrequencyIntegrator (FrequencyHz, RocofHzPerS, Step) is the contract LiveSim drives. LiveSim builds the asset-aware integrator only when EnableAssetDynamics is on and the model binds an asset-dynamics bundle or protections; otherwise it builds the plain FrequencyIntegrator. AssetFrequencyDynamics.Simulate is the batch twin of the asset-aware integrator.

FrequencyResponse:

Field Meaning
InitialRocofHzPerS The largest-magnitude RoCoF over all steps (the post-event spike), signed.
NadirHz, NadirSeconds The lowest frequency and the time t of the point that holds it.
SettleHz The frequency after the final update. It is the value at the end of the window, not an equilibrium.
Points The trajectory as FrequencyPoint(Time, Hz, RocofHzPerS).

SwingKernel (GovernorTarget, FastResponseTarget, SwingInertia, SortedEvents, ActiveEventMw, BatchStepCount, LiveSubStepCount) holds the targets and step rules every engine shares; SwingResponders calls GovernorTarget for the governor and FastResponseTarget for the services, and FleetUnitBank (src/GridSim.Core/Fleet/FleetUnitBank.cs) holds the fleet unit loop (deadband, lag, stagger arming) of the two fleet engines. A fleet unit re-arms its stagger once the frequency has stayed inside its deadband for that unit's own stagger, so every later excursion meets the detection latency again. Decision (GR-843, October 2026): the arming and re-arming times are compared with the clock to a millionth of a step, the rule the RMS and EMT event times use, so a stagger meant to land on the step grid (0.1 s + 0.3 s against 20 x 0.02 s) arms on that step, not one step late.

The model-based entry points (LumpedScalarInertiaModel, DistributedInertiaModel, AssetFrequencyDynamics, RocofScreening.Screen) resolve their config through SwingKernel.ConfigForModel: no config gives DynamicsConfig { NominalHz = model.FrequencyHz }, and a config whose NominalHz is not exactly the model's frequency is refused (ArgumentException).

LiveSim: how an event reaches the integrator

Each live tick calls _freqSim.Step(dtSeconds, ambient + tripDeficit):

ambient      = (u - 0.5) * 2 * AmbientNoiseFraction * baseDemandMw         u from a System.Random seeded with LiveSimSeed
tripDeficit *= exp(-dtSeconds / 300)           (SecondaryTauS = 300 s); set to 0 when |tripDeficit| < TripDeficitZeroMw (0.5 MW)

LiveSolveSettings.AmbientNoiseFraction is 0.0008 and LiveSolveSettings.LiveSimSeed is 20260605, so a live session is reproducible. LiveSim.TripInfeed(lostMw) subtracts |lostMw| from the deficit (negative = loss) under a lock and folds it in at the next step; trips accumulate. A reclosed or islanded topology contributes the net lost load minus lost generation of the blacked-out islands as a one-off imbalance. With asset dynamics on, the asset-aware integrator restores the fleet's trips and protection sheds with the same 300 s time constant (secondaryRestorationTauS: SecondaryTauS): the tripped units stay tripped (AssetTrippedMw still reports them), and what recovers is the balance as the rest of the system is redispatched. The live loop runs at the case's own nominal frequency and grades against FrequencyBands.ForModel(model). The transient verb integrates frequency through this same path at one step per slice.

Response services

SystemResponseService(Mw, DeadbandHz, FullDeliveryDeviationHz, TimeConstantS, KneeDeviationHz = 0, KneeFraction = 0) is one recorded frequency-response service as the swing model integrates it. Each is an independent first-order responder: the target is the delivery curve at the present df, the state lags it with max(dt, TimeConstantS), and the states sum into pServices. These model the response the real system held, not a device. The replay keeps them where it strips device terms and the counterfactuals keep them too, so a device is credited only for what it adds to reality.

The delivery curve (SwingKernel.FastResponseTarget, full form), with a = |df|:

a <= DeadbandHz                           target = 0
KneeDeviationHz <= 0                      target = -sign(df) * min(Mw * a / FullDeliveryDeviationHz, Mw)       line through zero
a <= KneeDeviationHz                      mag = Mw * KneeFraction * (a - DeadbandHz) / max(1e-9, KneeDeviationHz - DeadbandHz)
a >  KneeDeviationHz                      mag = Mw * (KneeFraction + (1 - KneeFraction) * (a - KneeDeviationHz) / max(1e-9, FullDeliveryDeviationHz - KneeDeviationHz))
otherwise                                 target = -sign(df) * min(mag, Mw)

The curve is symmetric: a negative df (under-frequency) gives positive injected power, a positive df gives the mirror. With the knee at the dead-band and a fraction of 0 the curve is a ramp from the dead-band to full output (the DM and DR shape).

GbResponseServices.Typical(scale = 1.0) (src/GridSim.Core/Dynamics/GbResponseServices.cs) is the GB arrest layer at grounded volumes:

Service Mw Dead-band (Hz) Knee (Hz, fraction) Full (Hz) Time constant (s) Delivery at selected deviations
DC, Dynamic Containment 950 0.015 0.2, 0.05 0.5 0.5 21.82 MW at 0.1 Hz, 47.5 MW at 0.2 Hz, 498.75 MW at 0.35 Hz, 950 MW at 0.5 Hz
DM, Dynamic Moderation 520 0.1 0.1, 0.0 0.2 2.0 0 at 0.1 Hz, 260 MW at 0.15 Hz, 520 MW at 0.2 Hz
DR, Dynamic Regulation 490 0.015 0.015, 0.0 0.2 10.0 225.14 MW at 0.1 Hz, 245 MW at 0.1075 Hz, 490 MW at 0.2 Hz

The curve parameters and time constants are literals in GbResponseServices.Typical. The only test that asserts any of them is GbResponseServicesTests.Grounded_volumes_match_the_eac_clears: Mw of all three services and FullDeliveryDeviationHz of DC and DM. The dead-bands, knees, knee fractions, DR full-delivery deviation and the time constants are pinned by no test.

The volumes are the NESO EAC auction clears held each direction (DC 944 to 993 MW, DM 515 to 547 MW, DR 480 to 500 MW; the constants are the nominal 950, 520 and 490). The curve shapes are the NESO published service terms. The three time constants are literature-typical and carry [VERIFY] (an unconfirmed figure; see ch. 8, Provenance and invariants). A per-event replay uses the volumes the system held at that event, not Typical. GridEvent.ApplyRecordedServices copies an event's services into the config, sets InitialFrequencyHz to the recorded pre-event frequency and, when the event marks its service list complete, sets ResponsiveFraction = 0 so the generic governor does not double-count the recorded response.

Equilibrium start. With InitialFrequencyHz set, Simulate starts at that frequency. It pre-loads the governor and each service state to their static targets at df0 = InitialFrequencyHz - f0, and sets the constant pStanding so that the pre-event derivative is exactly 0. Under grid-forming the standing term balances d + FormingDampingMwPerHz, the damping the forming step integrates against. Device terms start undeployed: a counterfactual device begins at zero.

Grid-forming formation

Forming selects how the frequency is built (FormingMode: None, Vsm, Droop). None runs the explicit Euler COI loop above verbatim. Under Vsm or Droop the grid frequency is the frequency of a virtual former locked to the real synchronous mass. The unified swing is

(2 * (E + Ev) / f0) * df/dt = pForcing - Dtot * (f - f0)

E      = systemInertiaMwS + DeviceRotationalInertiaMwS                  real stored energy, no floor
Ev     = VirtualInertiaMwS                                              virtual control inertia, MW.s
Dtot   = d + FormingDampingMwPerHz                                      load damping + former damping Dv
pForcing = pEvent + pStanding + pGov + pTsgb + pServices + FormingSetpointMw
         (asset-aware paths append  + pAssetFleet - tripDeficit)

pForcing holds every term not proportional to (f - f0); the proportional damping is integrated implicitly (FormingKernel.SemiImplicitStep, A-stable on that term):

gain      = f0 / (2 * Eform)                          Eform = E + Ev
rocof     = gain * (pForcing - Dtot * (f - f0))       the start-of-step value, which is what is reported
a         = h * gain
f(next)   = (f + a * (pForcing + Dtot * f0)) / (1 + a * Dtot)

The governor, fast response and services stay explicit inside pForcing, so fast high-gain responders at small Eform need a smaller step:

hMax   = min(MaxInternalDt, MaxStepGain / gain)             MaxInternalDt = 0.02 s, MaxStepGain = 0.02
nSub   = clamp(ceil(dt / min(dt, hMax)), 1, MaxSubSteps)    MaxSubSteps = 4000
h      = dt / nSub

FormingKernel.EffectiveFormingInertiaMwS returns E + Ev and throws InvalidOperationException when it is not greater than 0 (zero real and zero virtual inertia form nothing); there is no Math.Max(1, E) floor on this path. The kernels run Vsm and Droop through the same equation. A droop former is a pure P-f droop with Ev = 0, and SwingKernel.SwingInertia enforces it: Forming = Droop with any VirtualInertiaMwS other than 0 (NaN included) throws ArgumentException, which names Vsm as the form that carries inertia. Every engine of the swing family takes its forming denominator through that one gate. The CLI rejects --forming vsm without --forming-inertia greater than 0 (exit 2); --forming-inertia is given in GVA.s and converted to MW.s, and --forming-damping is in MW/Hz.

FormingAggregate.FromFleet re-interprets a grid-forming asset class as a former: Ev = sum(SynInertiaMwsPerHz * f0 / 2) and Dv = sum(DampingMwPerHz) over the grid-forming units. The re-interpretation is exact: moving the injection -SynInertia * df/dt to the left of (2E/f0) df/dt = P gives 2*(E + SynInertia*f0/2)/f0. It idealises away the state-of-charge and headroom cap that the fleet-injection path enforces. The H=0 counterfactual study uses it.

Per-asset fleet term: pAssetFleet

AssetFrequencyDynamics.Simulate is the batch loop with one extra pair of terms appended last in the sum, so that an empty or passive fleet adds 0.0 and leaves the trajectory bit-identical:

pBase      = pEvent + pStanding + pGov + pTsgb + pServices - d * df
rocofPred  = f0 / (2 * E) * pBase                                       predictor
pImbalance = pBase + pAssetFleet - assetTripDeficit
rocof      = f0 / (2 * E) * pImbalance

AssetDynamicsFleet.StepCoi advances every bound controller against the COI frequency, the predicted RoCoF and the accumulated phase phaseDeg += 360 * df * dt. pAssetFleet is the sum of the controllers' active power. A grid-forming unit (GridFormingInverter) delivers

target = clamp(-SynInertiaMwsPerHz * rocof - DampingMwPerHz * dfActive, -capDown, +capUp)       dfActive = df outside its dead-band, else 0
p     += (target - p) / max(dt, actuateTau) * dt

so its synthetic-inertia term lowers the initial RoCoF as a power injection while E is untouched. A grid-following unit trips on local RoCoF held past a confirmation time, on vector shift or on low voltage; its lost dispatched Pg joins assetTripDeficit, which is cumulative and never decays inside the integrator. The live asset-aware integrator is given the per-bus voltage and loading of the last solve for the voltage and thermal protections. Under grid-forming the predictor uses the unfloored Eform.

EnableAssetDynamics defaults off. The asset-control parameters are mostly curated placeholders. In data/gb-synthetic/asset-classes.json each class has a _default provenance of CuratedPlaceholder whose note carries [VERIFY], and a parameter without its own entry takes that default. The explicit entries are:

Class Parameter Tag
gfl-wind-2024 rocofTripHzPerS (1.0), deadbandHz (0.015) Recorded
gfl-solar-2024 rocofTripHzPerS (1.0) Recorded
legacy-dg-old-lom rocofTripHzPerS (0.125) Recorded
dg-alomcp rocofTripHzPerS (1.0) Recorded
legacy-dg-old-lom vectorShiftTripDeg (6.0) CuratedPlaceholder, [VERIFY]
gfm-bess-2024, gfm-vsm-study-2024 synInertiaMwsPerHz CuratedPlaceholder, [VERIFY]
prot-lom-legacy rocofTripHzPerS (0.125) Recorded
prot-lom-legacy localRocofUpliftFactor (1.16) DerivedFromRecorded
prot-lfdd-stage1 lfddStageHz (48.8) Recorded
prot-lfdd-stage1 lfddBlockMw (632) DerivedFromRecorded

Every other parameter of the six inverter classes (droop gains, latencies, actuator time constants, headrooms, slew rates, LVRT thresholds, the GFM inertia and damping gains, the gfm-bess-2024 and gfm-vsm-study-2024 RoCoF trips, the deadbandHz of every class except gfl-wind-2024) is CuratedPlaceholder with [VERIFY]. The two protection classes carry no _default: a parameter of theirs with no entry (rocofTripConfirmS, lfddDwellS) takes the library's own fallback, CuratedPlaceholder with a [VERIFY] unspecified provenance note. A claim about a real fleet is therefore an AssetEnvelope sweep tagged UnvalidatedAtScale, checked against a recorded trace by AssetValidation, never a point curve. How classes are authored is in manual ch. 29, Extending GridSim.

The distributed multi-domain model

src/GridSim.Core/Dynamics/Distributed/ resolves the swing into one mass per speed domain, coupled across the network. It is opt-in (InertiaModel.Distributed) and its outputs carry the UnvalidatedAtScale provenance tag (ch. 8, Provenance and invariants).

Speed domains. DomainAssignment.Assign(model, config) groups the generators by (poles, kind). PoleMap.ForType maps the type string; rpm is 120 * f / poles at the model's own frequency f (the speeds below are at 50 Hz; a 60 Hz two-pole unit is 3600 rpm):

Type Poles, speed Kind
nuclear, coal, biomass, ccgt, ocgt, chp, gas 2 pole, 3000 rpm Synchronous
recip 4 pole, 1500 rpm Synchronous
hydro, pumped-storage, pumped 8 pole, 750 rpm Synchronous
storage, battery, bess none SyntheticInertia
wind, solar, converter, interconnector, tidal, blank, unknown none Pll

The mapping is a modelling assumption: GDA supplies only the type label. A machine with H > 0 whose type is unknown or blank becomes a 2-pole synchronous unit. A named converter technology (wind, wind-onshore, wind-offshore, onshore, offshore, solar, pv, tidal, interconnector, hvdc, converter: PoleMap.MachineSpeed.IsKnownType) never becomes a swing mass, whatever its H. DistributedConfig.SingleDomain places every machine in one 2-pole synchronous domain. Domains are numbered in ascending (poles, kind) order. Each domain aggregates:

E_d    = sum(H * MBase)                       MW.s
S_d    = sum(MBase)                           MVA
GVad_d = sum(MBase * C)                       C = clamp(|Pg| / MBase, 0, 1); 0 when MBase <= 0

C is a dispatch-derived proxy for the availability and coupling coefficient. A domain is a swing mass (SpeedDomain.IsSwingMass) only when it is Synchronous with E_d > 0; the others count in dominance only.

Dominance. DominanceReport orders the domains by GVad descending and computes

deltaGVa = (GVad_1 - GVad_2) / GVad_2

A dominant domain exists when deltaGVa >= DominanceThreshold. When the runner-up or the only domain has GVad = 0, deltaGVa is +infinity and the top domain is dominant. The default threshold of 0.10 is an engineering-judgement value anchored on data: over 103,433 GB samples (GDA Derived/speed_domains, 2014 to 2026) the dominance gap has a 10th percentile of 0.106, so 0.10 flags the bottom decile of conditions (it fires on 9.4 % of samples; a threshold of 0.08 fires on 7.5 % and 0.12 on 11.4 %). DominanceThreshold is init-settable.

The swing. MultiDomainSwing.Simulate integrates one equation per swing mass i over n masses:

fCoi        = sum(E_i * f_i) / sum(E_i)            dfCoi = fCoi - f0
pResponse   = pStanding + pGov + pTsgb + pServices - d * dfCoi            all keyed off the COI, exactly as the lumped model
share_i     = E_i / sum(E_j)
tie_i       = sum over j != i of K_ij * (delta_i - delta_j(t - tau_ij))   MW
fi          = eventShare_i * pEvent + share_i * pResponse - tie_i          eventShare from the event placement (below)
rocof_i     = f0 / (2 * E_i) * fi
f_i        += rocof_i * dt                          frequency first
delta_i    += 2 * pi * (f_i - f0) * dt              then angle, with the updated frequency

delta is in rad and K in MW/rad. The inertia of the device (DeviceRotationalInertiaMwS) is folded into the masses in proportion so the total equals the lumped E. The governor, fast response, services and standing term use the same responder kernel as the lumped loop, evaluated on dfCoi.

Where an event lands. FrequencyEvent(AtSeconds, DeltaPMw, AtBus) carries an optional bus; only the distributed model reads it (the COI engines give identical numbers either way). DistributedInertiaModel places every event on the swing masses as a vector of shares (EventPlacement in DistributedResult.EventPlacements, each with its rule in words), and the swing adds share_i * pEvent to domain i:

  • At a bus that hosts swing-mass machines: wholly on the domain with the most inertia at that bus.
  • At any other bus: shared by synchronising coupling to the impact bus (DomainCoupling.ImpactShares: a Kron reduction onto the machine buses plus the impact bus, shares proportional to BaseMva * Im(Y_red[impact, g]) summed per domain), the distribution of a power impact by synchronising power coefficients.
  • With no bus: wholly on the domain of the single largest unit (the largest MBase among the swing-mass members; the first in domain, then member order, on a tie), the credible-loss home.

An unknown bus is refused (ArgumentException), and a bus with no path to any machine fails loud (InvalidOperationException). trip --inertia-model distributed places the loss at the tripped unit's bus and prints a Loss placed: line.

Coupling. DomainCoupling.SynchronisingMatrix Kron-reduces the bus admittance matrix onto the generator buses (KronReduction) and reads the cross-domain synchronising stiffness

K_ij = BaseMva * Im(Y_reduced[a,b])        flat 1 pu voltage; summed over bus pairs a in domain i, b in domain j; entries <= 0 ignored

Each generator bus belongs to the domain holding the most inertia there. Buses with no admittance path to any kept generator bus (an isolated bus, an island with no swing-mass machine) are left out of the reduction; they cannot change a reduced value. DomainCoupling.Synchronising returns the matrix with a CouplingReport: its CouplingSource (Kron, UniformNoBranchReactance, UniformReductionFailed, UniformNegligibleCoupling, NotNeeded), the reason, the count of buses dropped and the count of cross-domain pairs whose reduced coefficient was zero or negative (left out of K). DistributedResult.Coupling carries it; the divergence report and trip --inertia-model distributed (a Coupling: line) say so only when the coupling is not network-derived. If no branch has |X| > 1e-12, if the reduction fails, or if the summed stiffness is not above 1e-9, the model uses the uniform stiffness

K_uniform = omega^2 / (pi * f0 * sum(1 / E_d))        omega = 2 * pi * TargetInterAreaHz       f0 = GridModel.FrequencyHz

which places the single inter-area mode at TargetInterAreaHz. K is symmetric.

Propagation (off by default). PropagationDelay.ComputeWithLocation returns tau = 0 unless EnablePropagation is true, there are at least two masses, and the buses carry map coordinates. A bus at exactly (0, 0) has no position: it is left out of its domain's centroid, and a domain with no located member gets zero first-order delay (a supplied tau still applies) and is listed in PropagationReport.UnlocatedDomainIds. Then:

centroid_d = mean of (Bus.X, Bus.Y) over the domain's located generator buses; distance scales X by 660 km and Y by 1020 km
density    = sum(E_d) / maxCentroidDistanceKm                                         MW.s per km
v          = clamp(1000 * sqrt(200 / max(density, 1e-6)), MinWaveSpeedKmPerS, MaxWaveSpeedKmPerS)     km/s
tau_ij     = distance_ij / v       unless ProvidedTauSeconds holds the pair of representative buses (each domain's highest-inertia bus)

In the swing loop, tie i-j reads the far domain's angle round(tau / dt) steps back from a per-step angle history. The delay is 0 for a negative, NaN or infinite tau, and is clamped to the run length. tau = 0 reproduces the undelayed model exactly. The model asserts only that the wave speed lies in the band of MinWaveSpeedKmPerS = 500 to MaxWaveSpeedKmPerS = 1500 km/s; the absolute value is not validated. The arrival time of a domain is the first step time at which |f_i - fStart| exceeds 1 mHz, where fStart = InitialFrequencyHz ?? f0; -1 means it never did.

Outputs. DistributedInertiaModel.Simulate returns the COI-collapsed FrequencyResponse so every scalar consumer works with either model, and leaves the spatial detail in LastDistributedResult: one DomainTrace per swing mass, the DominanceReport, a per-bus event-RoCoF map (each generator bus gets its domain's peak RoCoF) and, when propagation is on, a PropagationReport (wave speed, largest delay, per-domain arrival times).

Delegation. Two cases never enter MultiDomainSwing and call the lumped FrequencyDynamics.Simulate with SystemInertiaGvaS * 1000:

  • Any run with Forming != None, whatever the domain count (the multi-domain swing has no virtual former).
  • Any model with at most one swing mass, including SingleDomain = true. The result is bitwise the lumped result.

Validation status. The distributed model passes its reduction gates (below). It has no field validation: the replay test that scores the distributed COI against a recorded event uses a synthetic, self-consistent event produced by the lumped model, and the per-domain spread and propagation need PMU or DFR data that the repository does not hold. DivergenceReport states the divergence between the lumped and distributed results, names its mechanism and tags it UnvalidatedAtScale; it makes no accuracy claim.

The inertia-model seam

IInertiaModel (src/GridSim.Core/Abstractions/IInertiaModel.cs) is the swappable frequency model, parallel to IPowerFlowSolver:

  • Simulate(model, baseDemandMw, events, config) returns the COI-collapsed FrequencyResponse;
  • CoiInertiaGvaS(model) returns the aggregate every scalar readout uses (SystemInertiaGvaS for both models);
  • LastDistributedResult is the spatial detail of the last solve, null for the lumped model.

InertiaModelSelector.Create resolves DynamicsConfig.InertiaModel (LumpedScalar, the default, or Distributed). There is no shape-based auto-selection: the model is an explicit choice. LumpedScalarInertiaModel.Simulate is FrequencyDynamics.Simulate(model.SystemInertiaGvaS * 1000, ...).

Under --inertia-model distributed only the trip verb integrates the distributed model, on the post-trip network; the half-inertia comparison it prints runs the lumped model. transient reports the speed-domain split on stderr and integrates the lumped live model; domains reports the split from DomainAssignment and integrates nothing; evidence, scenario, h0-study, fleet and replay-event run the lumped model and print a warning. --forming with --inertia-model distributed runs the lumped forming integrator and prints a warning. The trip verb applies --asset-dynamics before the distributed model: with asset dynamics on and a bundle or protections bound, the lumped asset loop runs.

Inverting the swing equation

InertiaEstimator recovers inertia from an observed excursion:

E = f0 * |deltaP| / (2 * |RoCoF|)           MW.s
  • EstimateInertiaMwS(deltaPMw, rocofHzPerS, nominalHz = 50) ignores both signs and returns +infinity when |RoCoF| < 1e-9;
  • EstimateInertiaGvaS divides by 1000;
  • EstimateHSeconds(deltaPMw, rocofHzPerS, baseMva) returns E / baseMva, or NaN for baseMva <= 0;
  • PredictRocof(inertiaMwS, deltaPMw) is the forward check, with E floored at 1 MW.s.

The estimate is clean because the first RoCoF sample precedes governor and fast-response action: at that instant the only imbalance is deltaP.

GB limits and assessment

FrequencyLimits (src/GridSim.Core/Dynamics/FrequencyLimits.cs):

Constant Value Meaning
OperationalLowHz, OperationalHighHz 49.8, 50.2 NESO operational band
StatutoryLowHz, StatutoryHighHz 49.5, 50.5 statutory band
LfddFirstStageHz 48.8 first stage of low-frequency demand disconnection
RocofLimitLegacyHzPerS 0.125 the pre-ALoMCP loss-of-mains relay setting
RocofLimitModernHzPerS 1.0 the GB relay setting after retuning
RocofLimitHzPerS 0.125 back-compatible alias, pinned to legacy
ActiveRocofLimitHzPerS 1.0 read-only; the limit the "active" flag scores against when the caller passes none

BreachesRocof(r, limit) is |r| > limit + 1e-9. An assessment reports the legacy and modern breaches independently plus an active flag. The retained RocofExceedsLimit and RocofLimitExceeded fields keep legacy semantics.

  • Assess(FrequencyResponse, activeLimit, bands) returns the headline RoCoF, nadir, settle and peak (FrequencyResponse.PeakHz), the flags BelowOperational (nadir below the operational low edge), BelowStatutory (below the statutory low edge), LfddAtRisk (nadir at or below the LFDD edge), AboveOperational and AboveStatutory (peak strictly above the high edges), and a one-line summary from the ladder LFDD, below statutory, above statutory, active RoCoF, legacy RoCoF, below operational, above operational, within limits.
  • AssessTrace(samples, activeLimit, bands) scans a measured trace: extremes, the sample counts below the operational and statutory floors and above the operational and statutory ceilings (SamplesAboveOperational, SamplesAboveStatutory), whether the LFDD edge was reached, and the worst sample-to-sample |df/dt| against the three thresholds.

The edges come from a FrequencyBands set (src/GridSim.Core/Dynamics/FrequencyBands.cs). FrequencyBands.Gb holds exactly the constants above; FrequencyBands.ForNominal(f0) (and ForModel(model)) moves every GB edge by the same number of hertz as the nominal, so a 60 Hz case is graded against 59.8 / 60.2, 59.5 / 60.5 and 58.8 Hz. At exactly 50 Hz it returns Gb itself. The overloads without bands use Gb. The RoCoF thresholds are relay settings in Hz/s and do not move with the nominal. NormalBandLowHz and NormalBandHighHz (49.9, 50.1) are the normal band the SCADA view alarms on.

The NESO trace path

FrequencySample(Time, Hz) is one recorded reading and FrequencyPoint(Time, Hz, RocofHzPerS) is a point on the fine timeline (src/GridSim.Core/Frequency/FrequencyTypes.cs).

NesoFrequencyCsv.Read streams a NESO dtm,f CSV one row at a time, so a month of 1 s data (2.7 million rows) reads without loading into memory. Blank lines and one header line are skipped; any other line with no comma, an unparseable timestamp or an unparseable number is refused with InvalidDataException, naming the file and the line number. Timestamps land in UTC: an offset-carrying stamp is converted and a naive stamp is assumed UTC. The replay validator compares recorded times with the UTC event instant by raw ticks, so a local-time stamp would drift by the offset in BST and could demote a Reproduced baseline to Marginal. Every row passes ForwardInferenceGuard.RejectFuture, so the reader cannot ingest a sample newer than the historical horizon.

RocofUpsampler:

  • Upsample(samples, subSamplesPerInterval = 50) takes each pair of consecutive samples with dt > 0, computes RoCoF = (f2 - f1) / dt and emits sub points f(t) = f1 + RoCoF * t at dt / sub spacing (50 per 1 s interval, so 20 ms). A closing point repeats the last sample with RoCoF 0.
  • Rocof(samples) is the per-interval RoCoF series, stamped at the later sample.
  • Summarize(samples) returns FrequencyStats (count, min, mean, max, worst |RoCoF| and when).
  • All three (and FrequencyLimits.AssessTrace) refuse a sample stamped before its predecessor (InvalidDataException, GR-572); a repeated time stamp has no interval and is skipped.

ReplayController is the playback cursor over the fine timeline (SlicesPerSecond clamped to 0.25 to 2000, 50 is real time). The CLI freq and replay verbs and ReplayValidator's per-sample RMSE use this path (ch. 7, The evidence engine).

Parameters and defaults

DynamicsConfig (src/GridSim.Core/Dynamics/FrequencyDynamics.cs) is an immutable record. Status is one of: firm (a documented figure), UNFITTED (a literature-typical value not fitted to a measured trip; uncertainty is a factor of two), structural (a mode or a physical quantity of the study, not a calibration), opt-in (default off).

Field Default Unit Status Meaning
NominalHz 50.0 Hz structural Nominal frequency f0.
DroopPu 0.05 pu firm Governor droop, 5 %, the GB Grid Code figure.
DampingPctPerHz 1.0 % of demand per Hz UNFITTED Load self-damping; d = value/100 * baseDemandMw.
ResponsiveFraction 0.20 fraction of demand UNFITTED Share of demand carrying droop headroom; Presp.
GovernorTimeConstantS 8.0 s UNFITTED Primary-response lag.
StepSeconds 0.02 s structural Batch step; equals the NESO upsampler cadence.
DurationSeconds 30.0 s structural Batch window; the replay validator extends it.
DeviceRotationalInertiaMwS 0.0 MW.s structural Device (1/2)*J*omega^2, summed into E.
FastResponseMw 0.0 MW structural Device fast-response capacity; 0 disables it.
FastResponseTimeConstantS 0.5 s structural Device fast-response lag.
FastResponseDeadbandHz 0.015 Hz structural Device fast-response dead-band.
InertiaModel LumpedScalar enum opt-in LumpedScalar or Distributed.
Distributed null DistributedConfig? opt-in Distributed settings; null uses the defaults below.
EnableAssetDynamics false bool opt-in The pAssetFleet term and its trips.
EnablePassivePlant false bool opt-in Delayed OLTC taps and thermal derate in the live loop; adds no swing power.
Forming None enum opt-in None, Vsm, Droop.
VirtualInertiaMwS 0.0 MW.s opt-in Virtual former inertia Ev; forming denominator only.
FormingDampingMwPerHz 0.0 MW/Hz opt-in Former damping Dv, added to d.
FormingSetpointMw 0.0 MW opt-in Former deviation setpoint, a forcing term.
SystemResponseServices empty list structural Recorded DC, DM, DR the system held.
InitialFrequencyHz null Hz structural Pre-event frequency; null starts at NominalHz with all lag states 0.

SyntheticInertiaMwS is an [Obsolete] alias that forwards to DeviceRotationalInertiaMwS.

DistributedConfig (src/GridSim.Core/Dynamics/Distributed/DistributedConfig.cs):

Field Default Unit Meaning
SingleDomain false bool One coherent domain; with EnablePropagation = false this is DistributedConfig.ReductionLimit.
EnablePropagation false bool Apply the inter-domain delay tau.
DominanceThreshold 0.10 ratio deltaGVa at or above which a domain is dominant.
MinWaveSpeedKmPerS 500.0 km/s Lower clamp of the wave speed.
MaxWaveSpeedKmPerS 1500.0 km/s Upper clamp of the wave speed.
TargetInterAreaHz 0.5 Hz Inter-area mode of the uniform fallback stiffness.
ProvidedTauSeconds null s External (fromBus, toBus) delay map; null uses the first-order model.

Constants in the swing loops and settings:

Name Value Unit Meaning Source symbol
Inertia floor 1.0 MW.s Floor on E outside grid-forming Math.Max(1.0, ...) in the integrators
Device and curve full delivery 0.5 Hz Deviation at which device fast response is full SwingKernel.DeviceFullDeliveryHz
Largest sub-step 0.02 s Live and forming sub-step ceiling FormingKernel.MaxInternalDt (the swing kernel's sub-stepping uses it too)
Sub-step cap 4000 steps Per-call cap MaxSubSteps
Forming step gain 0.02 - Cap on h * f0 / (2 * Eform) FormingKernel.MaxStepGain
Live inertia floor 100.0 MW.s Below this the live fallback applies LiveSolveSettings.MinInertiaMwS
Live fallback H 4.0 s H assumed on the fleet MVA LiveSolveSettings.FallbackInertiaH
Ambient jitter 0.0008 fraction of demand Live load-imbalance amplitude LiveSolveSettings.AmbientNoiseFraction
Live RNG seed 20260605 - Seed of the ambient jitter LiveSolveSettings.LiveSimSeed
Trip recovery 300 s Live trip-deficit decay time constant LiveSim.SecondaryTauS
Trip clear 0.5 MW Live deficit below this is zeroed LiveSolveSettings.TripDeficitZeroMw
Arrival threshold 1e-3 Hz Departure that marks a wave arrival local constant in MultiDomainSwing
GB map spans 660, 1020 km Scale of Bus.X, Bus.Y PropagationDelay.SpanXKm, SpanYKm
Wave-speed reference 1000 at 200 km/s at MW.s per km Inertia-density reference PropagationDelay.RefWaveSpeedKmPerS, RefInertiaDensityMwSPerKm

Fitted versus unfitted. DroopPu is firm. DampingPctPerHz, ResponsiveFraction and GovernorTimeConstantS are UNFITTED: the bundled NESO sample (data/neso/frequency-sample.csv) is ambient normal-operation data, spanning 49.921 to 50.106 Hz with no trip in it, so it cannot pin them. They set the nadir depth, the swing period and the recovery shape. The best and worst corners of the scenario engine bracket exactly these three. FrequencyConstantsFitter fits them by least squares over the FrequencyDynamics.Simulate trajectory to a measured loss-of-infeed trace with the lost infeed and the inertia known; gridsim fit-frequency <trace.csv> runs it (CLI reference). Damping alone is well identified from one trace; the three together are weakly identified. No bundled trace contains a trip, so the shipped defaults remain unfitted.

What sets the initial RoCoF and the nadir

Initial RoCoF depends only on E and deltaP. At the step where an event first applies the lagged states are 0 (or, with InitialFrequencyHz, cancel against pStanding) and df*d is 0 (or cancelled), so

rocof(0) = f0 / (2 * E) * deltaP

DroopPu, DampingPctPerHz, ResponsiveFraction, GovernorTimeConstantS, the device fast response and every response service leave it unchanged. For the four governor and damping constants this follows from the equation (each multiplies a state or a df that is 0 at the event step) and no test varies them. The tests pin the rest: the formula to 3 decimals (FrequencyDynamicsTests.Initial_rocof_matches_the_swing_equation, FrequencyCalibrationTests.Representative_trip_rocof_is_physically_sensible) and 4 decimals (FrequencyIntegratorTests.A_generation_loss_drops_the_frequency_with_the_expected_initial_rocof); the device fast response to 12 decimals (DynamicsConfigInvariantTests.Fast_response_does_not_reduce_inertia); the Typical services to 6 decimals (GbResponseServicesTests.The_arrest_layer_raises_the_nadir). Three things do move it, each through the denominator or the numerator and none through a response term: the size of deltaP; E, including DeviceRotationalInertiaMwS and, under grid-forming, Ev; and, with EnableAssetDynamics, a grid-forming unit's synthetic-inertia power. InitialRocofHzPerS is the largest-magnitude RoCoF over the run; for a single step event it is the RoCoF of the event step.

The nadir is shaped by the constants. The inertia sets how quickly the first swing falls. The response then builds with the governor lag. The default configuration (no dead-bands, no services, no device, no clamp reached) is linear, so a step loss has a closed-form solution. With x = df and pG the governor state:

M * dx/dt  = deltaP - d*x + pG            T * dpG/dt = -K*x - pG

Eliminating pG gives the second-order system:

M  = 2 * E / f0                                                          MW.s per Hz
K  = Presp / (DroopPu * f0)                                              governor gain, MW per Hz
(M*s + d) * (1 + s*T) + K = 0     ->     M*T*s^2 + (M + d*T)*s + (d + K) = 0       T = GovernorTimeConstantS
omega_n = sqrt((d + K) / (M*T))        zeta = (M + d*T) / (2 * M * T * omega_n)
equilibrium |df| = |deltaP| / (d + K)                                    reached only if the swing has damped out

With x(0) = 0 and dx/dt(0) = deltaP / M, and for zeta < 1, the step response is

alpha = (M + d*T) / (2*M*T)           omega_d = sqrt(omega_n^2 - alpha^2)
A     = deltaP / (d + K)              (the equilibrium offset, negative for a loss)
x(t)  = A + exp(-alpha*t) * (-A*cos(omega_d*t) + C*sin(omega_d*t))        C = (deltaP/M - alpha*A) / omega_d

Setting dx/dt = 0 gives tan(omega_d*t) = -omega_d / (1/T - alpha), so the first extremum (the nadir) is at t* = (pi - atan(omega_d / (1/T - alpha))) / omega_d after the event, and later extrema follow at pi / omega_d intervals. The worked example evaluates this for the default case and compares it with the run.

Raising Presp or lowering DroopPu raises K and lifts the nadir; raising T slows the arrest and deepens it; d adds load relief in proportion to df with no lag (on the default case 395 of the 3,555 MW/Hz static stiffness, 11 %). Response services and the device fast response add a dead-banded term to the numerator that acts within a second or two and lifts the nadir without changing the initial RoCoF. Halving E doubles the initial RoCoF and deepens the nadir (the half-inertia lines of the trip capture below).

Determinism

The COI frequency paths are written to give identical results on every run and every CPU, by construction. The sections below separate what is bitwise by design, what is tested bitwise, what is not bitwise, and what no test covers.

  • No clock, no random source. The simulators read no clock (timestamps are anchored at 2000-01-01T00:00Z) and have no random source. The one random source in the area is the LiveSim ambient jitter, which uses a System.Random seeded with the constant LiveSimSeed.
  • Scalar arithmetic only. The COI paths use IEEE double multiply, add, subtract, divide, Math.Clamp, Math.Max, Math.Min, Math.Abs, Math.Sign, Math.Round and Math.Ceiling. They call no SimdKernels routine, no Math.FusedMultiplyAdd and no parallel loop, so no instruction-set tier can change a result. The multi-domain loop adds Math.Sqrt in the propagation model, which is correctly rounded. DomainCoupling uses scalar System.Numerics.Complex arithmetic in the Kron reduction. The transcendental calls are Math.Exp in the LiveSim trip decay, which is the platform runtime's function, and DetMath.Expm1 (deterministic) in the live asset-aware integrator's restoration.
  • Fixed order of evaluation. Events are stably sorted by AtSeconds and summed in that order; domains are ordered by (poles, kind); members keep generator order; the tie sum runs j ascending; services sum in list order.
  • Bitwise, and tested with exact equality. Flag-off and empty-fleet paths add 0.0 (x + 0.0 - 0.0 == x) and the trajectories are compared point by point (AssetDynamicsReductionTests); the None path never reads the forming fields (FormingFrequencyTests.None_path_ignores_the_forming_params_byte_identically); the single-mass distributed model delegates to the lumped loop (DistributedReductionTests); routing through IInertiaModel is the direct call (InertiaModelSeamTests). FrequencyExportTests.Export_is_deterministic compares two exports built in the same process.
  • Not bitwise. The multi-mass COI equals the lumped trajectory to rounding: the tests allow 1e-6 Hz on every trajectory point and, in DistributedInvariantTests.Coi_trajectory_equals_the_lumped_model_to_machine_epsilon, on the nadir, the settle value and the initial RoCoF. The single zero-latency asset unit matches a fleet unit to 6 decimals (AssetDynamicsReductionTests.Single_zero_latency_grid_following_unit_reproduces_a_fleet_unit).
  • Untested. No automated test compares two process runs, CPU tiers, operating systems or machines for these paths. The cross-CPU and cross-machine claim rests on the arithmetic above, not on a test (ch. 8, Provenance and invariants).

Invariants

Invariant Pinned by
No event leaves frequency at nominal and RoCoF 0 FrequencyDynamicsTests.No_event_stays_at_nominal, FrequencyIntegratorTests.No_event_holds_at_nominal
Initial RoCoF equals f0 * deltaP / (2E) FrequencyDynamicsTests.Initial_rocof_matches_the_swing_equation (3 decimals), FrequencyIntegratorTests.A_generation_loss_drops_the_frequency_with_the_expected_initial_rocof (4 decimals), FrequencyCalibrationTests.Representative_trip_rocof_is_physically_sensible (3 decimals)
Lower inertia steepens RoCoF and deepens the nadir; frequency recovers above the nadir FrequencyDynamicsTests.Lower_inertia_steepens_rocof_and_deepens_nadir, FrequencyDynamicsTests.Frequency_recovers_above_the_nadir
A surplus drives frequency up FrequencyDynamicsTests.Generation_loss_drives_frequency_down_load_gain_up
NominalHz, DroopPu, DampingPctPerHz, ResponsiveFraction and GovernorTimeConstantS keep their documented defaults (9 decimals) FrequencyCalibrationTests.Documented_defaults_are_unchanged
The ambient sample is inside the operational band with max |RoCoF| below 0.05 Hz/s FrequencyCalibrationTests.Measured_trace_is_ambient_not_a_trip
A round trip of the swing equation at the ambient RoCoF: the imbalance implied by the sample (2E * RoCoF / f0, checked to lie in 1 to 500 MW) fed to Simulate returns that RoCoF (3 decimals). It is self-consistency of one equation, not independent validation FrequencyCalibrationTests.Model_reproduces_the_ambient_rocof_scale
Device rotational inertia is pure stored energy: adding it equals adding the same MW.s of system inertia DynamicsConfigInvariantTests.Device_inertia_is_pure_half_J_omega_squared (initial RoCoF, nadir and settle value, 12 decimals)
Fast response leaves the initial RoCoF unchanged (12 decimals) and lifts the nadir by more than 1e-4 Hz; zero device settings equal no device (9 decimals) DynamicsConfigInvariantTests.Fast_response_does_not_reduce_inertia, TsgbDynamicsTests.Fast_response_lifts_the_nadir, TsgbDynamicsTests.Defaults_match_no_device
The obsolete alias equals the canonical field DynamicsConfigInvariantTests.Renamed_field_and_obsolete_alias_are_identical
Live and batch integrators agree; large and 20-minute steps stay finite and settle where fine stepping settles FrequencyIntegratorTests.Matches_the_batch_simulate_trajectory_for_a_trip, Nadir_matches_the_batch_simulate, Large_step_stays_finite_and_matches_substepped_result, The_clamped_20_minute_step_still_settles_where_fine_stepping_does
A sub-dead-band deficit never engages fast response; state carries across a changed dt FrequencyIntegratorTests.A_sub_deadband_deficit_never_engages_fast_response, A_mid_run_dt_change_carries_state_and_settles_the_same
Service curves: full delivery at the declared deviation, the DC knee shape, the DM ramp, knee <= 0 falls back to the line ResponseServiceTests.Kernel_general_form_full_delivery_at_declared_deviation, Kernel_knee_form_matches_the_published_dc_curve
An empty service list is the identity; services raise the nadir; the fleet kernel integrates services identically to the scalar model ResponseServiceTests.Empty_service_list_is_the_identity, Services_arrest_the_nadir, Fleet_integrates_services_identically_to_the_scalar_model
Typical carries the volumes (exact), the DC and DM full-delivery deviations (exact), raises the nadir, leaves the initial RoCoF unchanged (6 decimals) and scales the DC volume GbResponseServicesTests.Grounded_volumes_match_the_eac_clears, The_arrest_layer_raises_the_nadir, Scale_reduces_the_held_volume
A complete recorded service list zeroes the generic governor ResponseServiceTests.ApplyRecordedServices_maps_and_completeness_zeroes_the_governor
Forming = None ignores every forming field, bit for bit FormingFrequencyTests.None_path_ignores_the_forming_params_byte_identically
Forming with Ev = 0, Dv = 0 reduces to the COI swing with O(dt) continuity FormingFrequencyTests.Forming_reduces_to_the_coi_swing_with_O_dt_continuity
An islanded former gives a bounded first-order frequency; nothing forming fails loud; virtual inertia never enters the real denominator; sub-steps grow as inertia shrinks FormingFrequencyTests.Islanded_former_gives_a_real_bounded_first_order_frequency, Grid_forming_with_nothing_forming_the_frequency_fails_loud, Virtual_inertia_never_leaks_into_the_real_denominator, Effective_forming_inertia_has_no_floor_and_fails_loud_at_zero, Substep_count_grows_as_inertia_shrinks, Small_inertia_with_a_fast_high_gain_service_and_ffr_stays_bounded
Asset dynamics off, or on with nothing bound, is bit-identical to the baseline, also under forming AssetDynamicsReductionTests.Flag_off_is_bit_identical_to_the_lumped_baseline, Enabled_but_nothing_bound_reduces_to_baseline, Enabled_with_only_unmatched_assets_reduces_to_baseline, Forming_flag_reduces_to_the_lumped_forming_baseline
A grid-forming asset's synthetic inertia lowers the initial RoCoF without changing E GridFormingInertiaTests.Synthetic_inertia_lowers_initial_rocof_without_touching_E
The lumped seam is bit-for-bit the direct call; the default is lumped InertiaModelSeamTests.Routing_through_the_seam_is_bit_for_bit_identical_to_calling_FrequencyDynamics, Default_dynamics_config_selects_the_lumped_scalar_model
T0: the reduction limit and a naturally single-domain case are identical to the lumped model DistributedReductionTests.Reduction_limit_config_is_identical_to_the_lumped_model, Single_domain_case_reduces_naturally_without_forcing
T1: the multi-domain COI equals the lumped trajectory to 1e-6 Hz, with and without services and with physical coupling (the first test's name says machine epsilon; its assertion is < 1e-6 Hz) DistributedInvariantTests.Coi_trajectory_equals_the_lumped_model_to_machine_epsilon, ResponseServiceTests.Distributed_coi_with_services_equals_the_lumped_model, CanonicalDynamicsTests.Coi_still_equals_lumped_with_physical_coupling
Per-domain frequencies diverge while the COI is preserved; the divergence is bounded, attributed and tagged UnvalidatedAtScale DistributedInvariantTests.Per_domain_frequencies_diverge_from_the_coi, DistributedScaleDivergenceTests.Scale_divergence_is_bounded_mechanism_attributed_and_unvalidated
Coupling: a single line gives BaseMva / X; stiffer coupling reduces divergence; the inter-domain mode matches the small-signal formula CanonicalDynamicsTests.Kron_coupling_of_a_single_line_equals_base_over_reactance, Stiffer_coupling_reduces_inter_domain_divergence, Inter_domain_mode_frequency_matches_the_small_signal_formula
Dominance reproduces the LOS worked example (deltaGVa 0.333) DistributedQualitativeTests.Dominance_reproduces_the_los_worked_example, DistributedInvariantTests.Dominance_report_flags_the_larger_domain
Propagation: distant domains respond later; wave speed within 500 to 1500 km/s; off by default; a provided tau overrides the model DistributedQualitativeTests.Propagation_makes_distant_domains_respond_later, Wave_speed_is_in_the_literature_band, Propagation_is_off_by_default_and_leaves_no_report, Provided_tau_map_overrides_the_first_order_model
The distributed COI reproduces a (synthetic, self-consistent) recorded event within the replay tolerance DistributedReplayTests.Distributed_coi_reproduces_a_recorded_event_within_replay_tolerance
The inertia inversion round-trips the simulator InertiaAndLimitsTests.Inertia_estimate_round_trips_the_simulator, Predict_and_estimate_are_consistent, Estimate_h_seconds_on_a_base
Limit classifiers and trace assessment InertiaAndLimitsTests.Mild_trip_stays_within_limits, Severe_low_inertia_trip_breaches_rocof, Trace_assessment_flags_a_dip_and_high_rocof, Steady_trace_reports_no_breaches
Case9 H and MBase and the system total are the published dynamic data Case9InertiaTests.Case9_system_inertia_matches_published_total, Case9_each_generator_stored_energy_matches_published_values, Case9_generator_H_and_MBase_are_the_published_dynamic_data
The frequency export is deterministic FrequencyExportTests.Export_is_deterministic

Worked example

The trip verb trips the non-slack unit with H > 0 and the largest dispatched Pg (not the largest rating) of the default case (data/uk, the GB reduced 10-zone model) at t = 1 s and runs the lumped swing with the default DynamicsConfig for 30 s.

$ gridsim trip
GridSim  -  contingency on GB reduced (10-zone)
================================================================
Tripped:        Hinkley Point Nuclear  (2880 MW lost, nuclear)
System inertia: 171.7 -> 158.9 GVAs after the trip
Peak RoCoF:     -0.453 Hz/s  (largest |df/dt| over the run)
Nadir:          48.340 Hz  (t+6.9 s)
Settling:       49.144 Hz

50.05 Hz |***+==-:,,..           ....,,,::::-----=========------------::::| 48.34 Hz (nadir)

...at HALF the inertia (79.5 GVAs): RoCoF -0.906 Hz/s, nadir 47.879 Hz
[exit 0]

(Captured in docs/_captures/frequency/trip.txt. The output has no timings; the captures of other chapters that carry timings differ by machine and run.)

Inertia, from data/uk/generation.json. Thirteen generators carry inertiaH > 0; every other generator has H = 0. MBase is capacityMva:

Generator H (s) MBase (MVA) H * MBase (MW.s)
North Scotland Hydro 3.0 1300 3,900
Torness Nuclear 4.0 1250 5,000
Heysham Nuclear 4.0 2400 9,600
North England CCGT 5.0 2000 10,000
Drax Biomass 4.0 2600 10,400
Yorkshire CCGT 5.0 4000 20,000
North Wales CCGT 5.0 3000 15,000
Midlands CCGT (marginal) 5.0 9000 45,000
Sizewell B Nuclear 4.0 1250 5,000
London CCGT 5.0 2000 10,000
South CCGT 5.0 3000 15,000
Hinkley Point Nuclear 4.0 3200 12,800
Pembroke CCGT 5.0 2000 10,000
Total 171,700

The total, 171,700 MW.s, is the 171.7 GVA.s of the first line. The tripped unit stops spinning: E = 171,700 - 12,800 = 158,900 MW.s, the 158.9 of the capture. The lost infeed is the unit's dispatch, Pg = 0.90 * 3200 = 2,880 MW, so deltaP = -2,880 MW.

Initial RoCoF by hand. At the event step every lagged state is 0 and df = 0, so

rocof = f0 / (2 * E) * deltaP = 50 * (-2880) / (2 * 158900) = -144000 / 317800 = -0.45312 Hz/s

which is the -0.453 of the capture. The exported trajectory (gridsim trip --export <file>, 20 ms rows, five decimals) agrees: frequency is 50.00000 Hz at t = 1.00 s and 49.99094 Hz at 1.02 s, and 50 - 0.45312 * 0.02 = 49.99094. Inverting the equation with the exact RoCoF gives E = 50 * 2880 / (2 * 0.4531152) = 158,900 MW.s (InertiaEstimator).

Half inertia. The verb reruns with E / 2 = 79,450 MW.s (79.45 GVA.s, printed as 79.5): 50 * 2880 / (2 * 79450) = 0.90623 Hz/s, the -0.906 of the capture, exactly twice the first value.

What the nadir depends on. The default config has no services and no device. The case's base demand is the sum of bus loads, 39,500 MW, so

d    = 1.0 / 100 * 39500                  = 395 MW/Hz
Presp = 0.20 * 39500                      = 7,900 MW
K    = 7900 / (0.05 * 50)                 = 3,160 MW/Hz
M    = 2 * 158900 / 50                    = 6,356 MW.s/Hz

The static droop equilibrium is |df| = 2880 / (3160 + 395) = 0.8101 Hz, that is 49.190 Hz. The linearised characteristic equation s^2 + 0.18715 s + 0.06991 = 0 ((M + d*T)/(M*T) and (d + K)/(M*T) with T = 8 s) gives omega_n = 0.2644 rad/s, zeta = 0.354, and a damped half-period of pi / (omega_n * sqrt(1 - zeta^2)) = 12.70 s.

The default run is linear (no dead-band engaged, no service, no clamp), so the step response has the closed form given under "What sets the initial RoCoF and the nadir". Its coefficients for this case are

alpha   = (M + d*T) / (2*M*T) = 9,516 / 101,696      = 0.093573 1/s
omega_d = sqrt(0.264413^2 - 0.093573^2)                = 0.247302 rad/s
A       = -2880 / 3555                                  = -0.810127 Hz
C       = (-2880 / 6356 - 0.093573 * (-0.810127)) / omega_d = -1.525701 Hz
x(t)    = -0.810127 + exp(-0.093573 t) * (0.810127 cos(0.247302 t) - 1.525701 sin(0.247302 t))

The nadir is at t* = (pi - atan(0.247302 / (0.125 - 0.093573))) / 0.247302 = 6.8629 s after the event, which is 7.8629 s on the run's clock (the event is at 1 s), and f = 50 + x(t*) = 48.33980 Hz. The first crest is pi / omega_d = 12.7035 s later, at 19.5663 s after the event (20.5663 s on the run's clock), at 49.44882 Hz.

The exported trajectory gives a trough of 48.34017 Hz at t = 7.86 s (the capture's t+6.9 s after the trip) and a first crest of 49.44867 Hz at t = 20.54 s. The run is above the closed form by 0.00037 Hz at the nadir and below it by 0.00015 Hz at the crest. The difference is the discretisation error of the explicit 20 ms Euler step (an independent 20 ms Euler recomputation of the two-state loop gives 48.34017 Hz at 7.86 s and 49.44867 Hz at 20.54 s), and the reported times are grid points. The run's crest-to-trough spacing is 12.68 s against 12.7035 s from the closed form, a difference of 0.024 s. The trajectory then falls back toward 49.190 Hz. The reported Settling of 49.144 Hz is the frequency one step after the 30 s window and is still below that equilibrium: it is the end of the window, not the steady state. The nadir depends on T, K and d, which are the UNFITTED constants.

Grid-forming. The same trip with a virtual former of 20 GVA.s and 100 MW/Hz of damping:

$ gridsim trip --forming vsm --forming-inertia 20 --forming-damping 100
GridSim  -  contingency on GB reduced (10-zone)
================================================================
Tripped:        Hinkley Point Nuclear  (2880 MW lost, nuclear)
System inertia: 171.7 -> 158.9 GVAs after the trip
Peak RoCoF:     -0.402 Hz/s  (largest |df/dt| over the run)
Nadir:          48.480 Hz  (t+7.2 s)
Settling:       49.215 Hz

50.05 Hz |***+==-:,,..             ....,,,:::::-----------------------::::| 48.48 Hz (nadir)

...at HALF the inertia (79.5 GVAs): RoCoF -0.724 Hz/s, nadir 48.147 Hz
[exit 0]

The denominator is Eform = 158,900 + 20,000 = 178,900 MW.s: 50 * 2880 / (2 * 178900) = 0.40246, the -0.402 shown. The half-inertia line is Eform = 79,450 + 20,000 = 99,450 and 0.72398, the -0.724 shown. The printed system inertia line is the real stored energy and does not include Ev.

Distributed. gridsim trip --inertia-model distributed runs the multi-domain swing on the post-trip network:

$ gridsim trip --inertia-model distributed
Inertia model:  distributed  (2 speed domain(s), dGVa 0.37)
GridSim  -  contingency on GB reduced (10-zone)
================================================================
Tripped:        Hinkley Point Nuclear  (2880 MW lost, nuclear)
System inertia: 171.7 -> 158.9 GVAs after the trip
Peak RoCoF:     -0.453 Hz/s  (largest |df/dt| over the run)
Nadir:          48.340 Hz  (t+6.9 s)
Settling:       49.144 Hz

50.05 Hz |***+==-:,,..           ....,,,::::-----=========------------::::| 48.34 Hz (nadir)

...at HALF the inertia (79.5 GVAs): RoCoF -0.906 Hz/s, nadir 47.879 Hz
[exit 0]

The COI-collapsed numbers equal the lumped run to the printed precision (invariant T1). The 2 in the Inertia model: line counts swing masses (dr.Domains.Count): the 2-pole and the 8-pole synchronous domains. gridsim domains counts every speed domain, including the Pll domain, so it prints 3. dGVa 0.37 is the dominance gap of the post-trip fleet. The speed-domain table of the intact fleet:

$ gridsim domains
GridSim  -  SPEED DOMAINS on GB reduced (10-zone)
==================================================================
3 speed domains  *  deltaGVa 56 %  *  dominant = Domain 1

Domain   Speed         Kind               Mach      GVA.s   GVad GVA
Domain 1 2p/3000rpm    Synchronous          12     167.80      24.34  *
Domain 0 inverter      Pll                  16       0.00      15.61
Domain 2 8p/750rpm     Synchronous           1       3.90       0.65

GVad = apparent-power stiffness sum(S*C); GVA.s = real spinning inertia. A domain is dominant
when deltaGVa >= 10% (LOS sec. 5.5). Distributed model: spatial spread & propagation are unvalidated at scale.
[exit 0]

The 12 two-pole machines hold 167.80 GVA.s and the one hydro machine 3.90, which sum to 171.7. The dominance gap is (24.34 - 15.61) / 15.61 = 0.559, shown as 56 %, which is above the 0.10 threshold, so Domain 1 is dominant. The Pll domain has no inertia and is not a swing mass, but its stiffness GVad counts in the dominance ratio.

The NESO anchor. gridsim freq summarises the bundled ambient sample and shows the upsampler:

$ gridsim freq
NESO frequency  -  frequency-sample.csv
================================================================
Samples      300  (1 s cadence)
Frequency    min 49.921 Hz  mean 49.991 Hz  max 50.106 Hz
Max |RoCoF|  0.0080 Hz/s  at 2024-08-01 00:00:02

vs GB limits:
  RoCoF 0.125 Hz/s: within  (worst 0.0080 Hz/s)
  operational 49.8 Hz: held    statutory 49.5 Hz: held    LFDD 48.8 Hz: clear

Upsample demo  -  1 s frames expanded to 20 ms by RoCoF interpolation:
  time            Hz         RoCoF (Hz/s)
  00:00:00.000   50.10500     0.0010
  00:00:00.020   50.10502     0.0010
  00:00:00.040   50.10504     0.0010
  00:00:00.060   50.10506     0.0010
  00:00:00.080   50.10508     0.0010
  00:00:00.100   50.10510     0.0010
  00:00:00.120   50.10512     0.0010
  00:00:00.140   50.10514     0.0010
[exit 0]

The interval RoCoF is 0.0010 Hz/s, so each 20 ms row adds 0.0010 * 0.02 = 0.00002 Hz, as shown. The worst ambient RoCoF, 0.0080 Hz/s, is 6.4 % of the 0.125 Hz/s legacy limit. Inverting the swing equation at the representative 200 GVA.s of FrequencyCalibrationTests gives an implied imbalance of 2 * 200000 * 0.0080 / 50 = 64 MW (63.6 to 64.4 MW across the rounding of the displayed 0.0080), against 1,320 MW for the largest normal infeed loss in that test. FrequencyCalibrationTests.Model_reproduces_the_ambient_rocof_scale derives the imbalance from the measured RoCoF with this inversion and then asserts that Simulate returns the same RoCoF to 3 decimals, so it is a round trip of one equation. Its only independent check is that the implied imbalance lies in 1 to 500 MW. It does not constrain the nadir constants.

Source map

File Type Responsibility
src/GridSim.Core/Dynamics/FrequencyDynamics.cs DynamicsConfig, SystemResponseService, FrequencyEvent, FrequencyResponse, FrequencyDynamics Config, batch swing loop, equilibrium start.
src/GridSim.Core/Dynamics/FrequencyIntegrator.cs FrequencyIntegrator Live stateful integrator, sub-stepping.
src/GridSim.Core/Dynamics/AssetAwareFrequencyIntegrator.cs, AssetFrequencyDynamics.cs AssetAwareFrequencyIntegrator, AssetFrequencyDynamics Live and batch loops with the pAssetFleet term.
src/GridSim.Core/Dynamics/IFrequencyIntegrator.cs IFrequencyIntegrator Contract LiveSim drives.
src/GridSim.Core/Dynamics/SwingKernel.cs SwingKernel Governor and delivery-curve targets.
src/GridSim.Core/Dynamics/GbResponseServices.cs GbResponseServices GB DC, DM, DR volumes and curve parameters.
src/GridSim.Core/Dynamics/Forming/FormingKernel.cs, FormingAggregate.cs, src/GridSim.Core/Dynamics/FormingMode.cs FormingKernel, FormingAggregate, FormingMode Semi-implicit forming step, sub-step count, fleet aggregate.
src/GridSim.Core/Dynamics/InertiaModel.cs, InertiaModelSelector.cs, LumpedScalarInertiaModel.cs, src/GridSim.Core/Abstractions/IInertiaModel.cs InertiaModel, InertiaModelSelector, LumpedScalarInertiaModel, IInertiaModel The model seam.
src/GridSim.Core/Dynamics/Distributed/DomainAssignment.cs, PoleMap.cs, SpeedDomain.cs, DominanceReport.cs DomainAssignment, PoleMap, SpeedDomain, DominanceReport Speed domains and dominance.
src/GridSim.Core/Dynamics/Distributed/MultiDomainSwing.cs, DomainCoupling.cs, PropagationDelay.cs MultiDomainSwing, DomainCoupling, PropagationDelay Multi-mass swing, Kron coupling, propagation.
src/GridSim.Core/Dynamics/Distributed/DistributedInertiaModel.cs, DistributedConfig.cs, DistributedResult.cs, DomainTrace.cs, DivergenceReport.cs DistributedInertiaModel, DistributedConfig, DistributedResult, DomainTrace, DivergenceReport Distributed model entry, settings, outputs.
src/GridSim.Core/Dynamics/InertiaEstimator.cs InertiaEstimator Inertia inversion.
src/GridSim.Core/Dynamics/FrequencyLimits.cs FrequencyLimits, FrequencyAssessment, FrequencyTraceReport GB limits and classifiers.
src/GridSim.Core/Dynamics/FrequencyConstantsFitter.cs FrequencyConstantsFitter Fitting tool for the nadir constants.
src/GridSim.Core/Assets/AssetDynamicsFleet.cs, GridFormingInverter.cs, GridFollowingInverter.cs AssetDynamicsFleet, GridFormingInverter, GridFollowingInverter The fleet behind pAssetFleet.
src/GridSim.Core/Model/Model.cs Generator, GridModel.SystemInertiaGvaS H, MBase, and the inertia sum.
src/GridSim.Core/Simulation/LiveSim.cs, LiveSolveSettings.cs LiveSim, LiveSolveSettings Live frequency loop, trip decay, inertia fallback.
src/GridSim.Core/Frequency/NesoFrequencyCsv.cs, RocofUpsampler.cs, FrequencyTypes.cs, ReplayController.cs NesoFrequencyCsv, RocofUpsampler, FrequencySample, FrequencyPoint, ReplayController NESO trace path and playback.
src/GridSim.Gda/FuelMap.cs FuelMap Representative H per fuel class.
src/GridSim.Cli/Program.cs RunTrip, RunDomains, PrintFrequency, RunReplay, RunTransientBatch, RunTransient The verbs that drive this chapter.

Limits

  • The nadir constants DampingPctPerHz, ResponsiveFraction and GovernorTimeConstantS are not fitted to any measured loss-of-infeed trace, and FrequencyConstantsFitter has no production caller (R079).
  • The no-device baseline of the recorded 2023-12-22 event reproduces only as Marginal (captured: RoCoF -0.123 against -0.102 Hz/s recorded, nadir 48.98 against 49.27 Hz), so gridsim h0-study refuses to run counterfactuals on it (exit 3).
  • A bus genuinely at map position (0, 0) is read as unlocated by PropagationDelay.
  • When the Kron reduction fails, or finds no usable coupling, DomainCoupling falls back to the uniform 0.5 Hz stiffness; the fallback and its reason are carried on the distributed result as a CouplingReport. The reduction works on the sparse admittance matrix.
  • The distributed model has no virtual former and no authored-asset term: a forming run delegates to the lumped model, and the per-domain asset sampling path is not wired in (R074).
  • The distributed model has no field validation: spatial spread and propagation await PMU or DFR data.
  • The lumped model has one frequency for the whole system: no inter-area swing, no local frequency, no network propagation unless the distributed model is selected.

See also