Branch of origin: inertia2-distributed. Status: experimental, opt-in, additive. The lumped scalar model remains the default and is untouched.

1. Why

Almost every frequency solver - GridSim's default path included - models system inertia as a single lumped centre-of-inertia (COI) scalar: E = sum(H*MBase), one swing equation df/dt = f0/(2E)*deltaP (FrequencyDynamics.Simulate). That is exact for the questions it answers, but it erases where inertia sits, and it scores an evenly-spread fleet as adequate - when an even spread is itself a fragmentation failure mode.

The TSGB "speed domain" thesis (corpus LOS sec. 2.7 / sec. 5.5) says the real fleet groups into speed domains by mechanical speed / pole ratio; each domain has an apparent-power stiffness GVad = sum(S_i*C_i); a domain is dominant when deltaGVa = (GVad1 - GVad2)/GVad2 >= 0.10 (an engineering-judgement threshold, not a fitted constant - but empirically ~the 10th percentile of the GB dominance gap, firing ~9.4% of the time over 103k samples; init-settable for calibration); and a disturbance does not reach the whole system at once - it propagates between domains at a finite electromechanical wave speed. None of that is visible to a scalar. This model makes it visible, as a runtime-selectable alternative that reduces exactly to the lumped model in its degenerate limit.

2. The non-negotiables

  • Lumped stays the default and is untouched. Distributed is purely additive. Every pre-existing test stays green with zero behaviour change; the four rocof = f0/(2*E)*deltaP lines are not edited.
  • Runtime switch, mirroring the SolverKind/SolverBackend seam: an enum InertiaModel { LumpedScalar, Distributed } resolved by InertiaModelSelector, exposed on the API, CLI, WPF and Web.
  • GDA provides only data already present or streamed (per-machine H, Bus, MBase, Type, Branch.R/X, Bus.X/Y, and the precomputed lake products). GridSim derives pole/speed, domains, distances, propagation, and integration.
  • Every validation tier is a fail-loud gate. Where there is no GB-scale ground truth, the result is a bounded, mechanism-attributed divergence report tagged unvalidated-at-scale - never an accuracy claim against a reference that does not exist. Machine-epsilon is relocated (to aggregates and reductions where an exact oracle exists), not fabricated.

3. The selectable seam

New under src/GridSim.Core/, mirroring PowerFlow/SolverSelector.cs:

File Role
Abstractions/IInertiaModel.cs The seam: Simulate(...) -> FrequencyResponse; CoiInertiaGvaS(model); DistributedResult? LastDistributedResult.
Dynamics/InertiaModel.cs enum InertiaModel { LumpedScalar, Distributed }.
Dynamics/InertiaModelSelector.cs Resolve / Create / Label, one-to-one with SolverSelector.
Dynamics/LumpedScalarInertiaModel.cs Delegates verbatim to FrequencyDynamics.Simulate; returns model.SystemInertiaGvaS. Identical old behaviour.
Dynamics/Distributed/DistributedInertiaModel.cs The multi-mass model; returns a COI-collapsed FrequencyResponse and stashes a DistributedResult.

DynamicsConfig gains InertiaModel InertiaModel { get; init; } = InertiaModel.LumpedScalar; and a DistributedConfig? Distributed. Consumers opt in by routing through InertiaModelSelector instead of calling FrequencyDynamics.Simulate directly.

4. The numerical model

One coupled multi-mass swing kernel spanning a spectrum, with LumpedScalar as its exact one-mass degenerate limit.

  • Domain assignment (Distributed/PoleMap.cs, DomainAssignment.cs, SpeedDomain.cs, DominanceReport.cs). PoleMap is a GridSim-owned Generator.Type -> (poles, rpm, DomainKind) lookup: nuclear/coal/CCGT -> 2-pole/3000 rpm synchronous; large hydro/pumped -> multi-pole synchronous; wind/solar/storage/interconnector -> Pll/virtual (no real pole). DomainAssignment partitions generators into domains, computes each domain's aggregate inertia H_d = sum H_i and GVad = sum(S*C), and reports deltaGVa + dominance.
  • The kernel (Distributed/MultiDomainSwing.cs). Each domain is a coherent mass linked by Kron-reduced synchronising power. It keeps the COI equal to the lumped result by keying the aggregate forcing off the inertia-weighted COI and using antisymmetric tie power (sum = 0), and it integrates with symplectic (semi-implicit) Euler - forward Euler blows up under the stiff Kron coupling. The single-domain / reduction limit delegates to FrequencyDynamics for the exact reduction.
  • Physical coupling (PowerFlow/KronReduction.cs, Distributed/DomainCoupling.cs). The inter-domain synchronising coefficients are Kron-reduced (star-mesh elimination) from the YBus - physically derived, not fitted - so the inter-area mode frequency is a property of the network, not a knob.
  • Propagation overlay (Distributed/PropagationDelay.cs, off by default). Finite wave speed enters as a retardation delta_j(t - tau_ij) on the coupling, read from per-mass angle ring buffers. tau = physical distance / wave speed, with the wave speed derived from local inertia density and clamped to the published 500-1500 km/s band. It is off by default because the retardation perturbs the COI (real physics), so the machine-eps COI invariant only holds with it off.

Why LumpedScalar is the exact limit. Summing the per-mass swing equations, the internal coupling telescopes and the COI obeys (2E/omega_s)*domega/dt = deltaP with E = sum H_i*MBase_i - identical to today's scalar ODE. Set #domains = 1, tau = 0, coupling -> inf => machine-eps reduction.

5. COI projection - every existing consumer keeps working

DistributedInertiaModel.Simulate returns the inertia-weighted COI collapse f_COI = sum H_i f_i / sum H_i, equal to the lumped response to machine-eps when domains don't diverge. So StabilityMetrics, InertiaEstimator, RocofScreening, TsgbSizer, RP1, MECHANICAL, the Web FrameProjector, and the bridge protocol read CoiInertiaGvaS (== SystemInertiaGvaS) unchanged. The new per-domain / per-bus outputs live on Distributed/DistributedResult.cs (DomainTrace[], per-bus event RoCoF map, DominanceReport, wave-speed / delay matrix) for the spatial views. SystemInertiaGvaS is retained verbatim - the distributed model projects onto it, never redefines it.

6. Validation - the fail-loud gates

All in tests/GridSim.Tests, all pass-gates (484 tests green as of this writing).

Tier File Asserts
T0 DistributedReductionTests The degenerate {1 domain, no propagation, coupling -> inf} config == FrequencyDynamics.Simulate to machine-eps.
T1 DistributedInvariantTests sum H_i f_i / sum H_i == lumped f to machine-eps; energy balance; identical settled steady state.
T2 CanonicalDynamicsTests, KronReductionTests Kron-reduced coupling and inter-area mode frequency behave canonically.
T3 DistributedQualitativeTests Dominance reproduces the LOS sec. 5.5 worked example (deltaGVa ~ 0.333); distant domains respond later; wave speed in 500-1500 km/s; an externally-provided tau map overrides the first-order model.
T4 DistributedReplayTests The COI-projected distributed response reproduces recorded GB events within ReplayValidator tolerance.
T5 DistributedScaleDivergenceTests gb-full lumped-vs-distributed divergence is bounded and mechanism-attributed, emitted as a DivergenceReport tagged ProvenanceTag.UnvalidatedAtScale. No accuracy assertion.
T6 ClassicalMultiMachineTests The per-machine classical backbone (sec. 6a) against exact analytic references: SMIB mode frequency, equal-area critical clearing time, RK4 energy boundedness, COI conservation, and WSCC-9 solve->init->fixed-point.

Machine-eps is retained for the T0 reduction and the T1 COI invariant; relocated to bands for T3 (published), T4 (recorded), and T5 (bounded, no reference), and to closed-form physics for T6.

6a. The classical multi-machine backbone

Alongside the GB-scale domain-reduced kernel, GridSim carries the per-generator classical transient-stability model (ClassicalMultiMachine + ClassicalInit) for the small canonical cases. Each machine is a constant E'angle delta behind its transient reactance X'd, swinging over the network Kron-reduced to the generator internal nodes (Pe_i = sum_j |E'_i||E'_j|(G_ij cos + B_ij sin)), integrated with classical RK4 for first-swing accuracy. ClassicalInit.FromSolvedCase builds the reduced inputs from a solved power flow by the standard preparation: loads -> constant-impedance shunts, generator internal nodes behind X'd, Kron reduction, E' = V_t + jX'd*I_t, and Pm = Pe(delta0) so an undisturbed case is a fixed point.

It is validated against exact, published, self-contained references - no fabrication, no reliance on a reference that doesn't exist: the single-machine-infinite-bus small-signal mode frequency omega_n = sqrt(omega_s*P_s/2H) (to <1%), the equal-area critical clearing time (stable just below it, unstable just above), undamped RK4 energy/amplitude boundedness over ~28 cycles, two-machine COI conservation, and a WSCC-9 (Anderson-Fouad X'd) end-to-end check that the solved pre-fault point is a fixed point and a rotor-angle bump oscillates while holding synchronism. It is additionally cross-validated against an independent integrator: gridsim stability case9 --export <json> writes the reduced system and its RK4 trajectory, and tools/crossval/crossval_classical.py re-integrates the identical ODE with scipy's RK45 - the two full 3-machine coupled trajectories agree to ~3.7x10^-^8 rad (machine epsilon), validating the coupling numerics the analytic SMIB/2-machine limits don't exercise. This backbone is reserved for the small canonical cases; the domain-reduced kernel remains the GB-scale path.

7. GDA as the data provider

GDA precomputes the heavy, slow-changing physics; GridSim looks it up and owns the dynamics. Two lake products (GDA manual sec. 38.11) feed the model:

  • propagation_delays - a network-static, single-file product of corridor delays: real physical and electrical distance, real local inertia, and a modelled clamped wave speed -> tau per bus pair. Served over the bridge as op=propagation. The loop is closed end-to-end: GridBridgeClient. QueryPropagation(at) requests the corridors and projects them (PropagationData.TauByBusPair) into the (fromBus, toBus) -> tau map that drops straight into DistributedConfig.ProvidedTauSeconds; where a domain pair's representative buses are found there, that tau is used instead of the first-order model, falling back to the model elsewhere (PropagationDelay.Compute). Corridors whose lake row carries no tau are omitted, and the honest provenance note (real distances/inertia; modelled wave speed) rides along on PropagationData.Provenance.
  • speed_domains - the fleet decomposition precomputed from GridWatch alone (per-domain GVad + inertia + deltaGVa + the is_too_evenly_spread flag), a direct lake read the SPEED DOMAINS tabs can display for any past instant without recomputing.

The provenance split is honest and stated per column: real distances and inertia; modelled and unvalidated-at-scale wave speed and delay. The lake product and GridSim's own first-order model use the identical clamp(1000*sqrt(200/density), 500, 1500) relation, so they agree by construction.

8. Using it

  • API: new DynamicsConfig { InertiaModel = InertiaModel.Distributed, Distributed = new DistributedConfig { /* EnablePropagation, ProvidedTauSeconds, ... */ } }, then route through InertiaModelSelector. Default LumpedScalar.
  • CLI: the global --inertia-model=lumped|distributed switch (wired into trip, reported on transient), plus the dedicated gridsim domains verb that prints the decomposition. See docs/manual/0019 CLI reference.md.
  • WPF: the SPEED DOMAINS tab (Views/DomainsVm.cs + DomainsView.xaml), inserted before ASSETS - GVad and spinning-inertia bar charts, dominance against the 10% threshold, provenance badges. Degrades gracefully to a single-COI-domain summary when the lumped model is active.
  • Web: the SPEED DOMAINS tab in GridSim.Web (Components/Tabs/DomainsTab.razor, fed by TabProjections.Domains -> FrameEnvelope.Domains).

9. Honest limits

The propagation overlay is unvalidatable at scale: there is no GB-wide PMU/DFR corpus to check an absolute electromechanical wave speed against, so the model asserts only the band, never a scale-accurate figure, and the overlay is off by default. Domain assignment from type -> poles is many-to-one and inverters have no real pole - a conservative, documented default, provenance-tagged. The per-machine classical multimachine model and its RK4 integrator are now built and validated (sec. 6a) for the canonical cases. Still deferred, not faked: pinning the full published IEEE-39 / A&F first-swing rotor-angle curves (needs the exact exciter/governor/clearing sequence), a scipy multimachine sidecar, and importing the open dynamic cases the research catalogue surfaced (ANDES IEEE-39 / Kundur, Texas A&M ACTIVSg .dyr) as additional cross-checks. The GB-scale path remains the domain-reduced multi-area COI, which is what the T0-T5 gates validate. When the distributed and lumped results diverge at GB scale, that divergence is reported and bounded, never presented as "more accurate".

  • docs/validation/neso-rp1-and-mechanical.md - the situational-awareness tab template this follows.
  • docs/manual/0019 CLI reference.md - the --inertia-model switch and the domains verb.
  • docs/validation/solver-validation-report.md - the machine-epsilon validation discipline this relocates.
  • GDA manual sec. 38.11 and Chapter 66 - the propagation_delays / speed_domains lake products and the op=propagation bridge channel.