Distributed / multi-domain inertia model¶
Branch of origin: inertia2-distributed. Status: experimental, opt-in, additive. The lumped
scalar model remains the default and is untouched.
1. Why¶
Almost every frequency solver - GridSim's default path included - models system inertia as a
single lumped centre-of-inertia (COI) scalar: E = sum(H*MBase), one swing equation
df/dt = f0/(2E)*deltaP (FrequencyDynamics.Simulate). That is exact for the questions it answers, but
it erases where inertia sits, and it scores an evenly-spread fleet as adequate - when an even
spread is itself a fragmentation failure mode.
The TSGB "speed domain" thesis (corpus LOS sec. 2.7 / sec. 5.5) says the real fleet groups into speed
domains by mechanical speed / pole ratio; each domain has an apparent-power stiffness
GVad = sum(S_i*C_i); a domain is dominant when deltaGVa = (GVad1 - GVad2)/GVad2 >= 0.10 (an
engineering-judgement threshold, not a fitted constant - but empirically ~the 10th percentile of the GB
dominance gap, firing ~9.4% of the time over 103k samples; init-settable for calibration); and a
disturbance does not reach the whole system at once - it propagates between domains at a finite
electromechanical wave speed. None of that is visible to a scalar. This model makes it visible, as a
runtime-selectable alternative that reduces exactly to the lumped model in its degenerate limit.
2. The non-negotiables¶
- Lumped stays the default and is untouched. Distributed is purely additive. Every pre-existing
test stays green with zero behaviour change; the four
rocof = f0/(2*E)*deltaPlines are not edited. - Runtime switch, mirroring the
SolverKind/SolverBackendseam: anenum InertiaModel { LumpedScalar, Distributed }resolved byInertiaModelSelector, exposed on the API, CLI, WPF and Web. - GDA provides only data already present or streamed (per-machine
H,Bus,MBase,Type,Branch.R/X,Bus.X/Y, and the precomputed lake products). GridSim derives pole/speed, domains, distances, propagation, and integration. - Every validation tier is a fail-loud gate. Where there is no GB-scale ground truth, the result
is a bounded, mechanism-attributed divergence report tagged
unvalidated-at-scale- never an accuracy claim against a reference that does not exist. Machine-epsilon is relocated (to aggregates and reductions where an exact oracle exists), not fabricated.
3. The selectable seam¶
New under src/GridSim.Core/, mirroring PowerFlow/SolverSelector.cs:
| File | Role |
|---|---|
Abstractions/IInertiaModel.cs |
The seam: Simulate(...) -> FrequencyResponse; CoiInertiaGvaS(model); DistributedResult? LastDistributedResult. |
Dynamics/InertiaModel.cs |
enum InertiaModel { LumpedScalar, Distributed }. |
Dynamics/InertiaModelSelector.cs |
Resolve / Create / Label, one-to-one with SolverSelector. |
Dynamics/LumpedScalarInertiaModel.cs |
Delegates verbatim to FrequencyDynamics.Simulate; returns model.SystemInertiaGvaS. Identical old behaviour. |
Dynamics/Distributed/DistributedInertiaModel.cs |
The multi-mass model; returns a COI-collapsed FrequencyResponse and stashes a DistributedResult. |
DynamicsConfig gains InertiaModel InertiaModel { get; init; } = InertiaModel.LumpedScalar; and a
DistributedConfig? Distributed. Consumers opt in by routing through InertiaModelSelector instead
of calling FrequencyDynamics.Simulate directly.
4. The numerical model¶
One coupled multi-mass swing kernel spanning a spectrum, with LumpedScalar as its exact one-mass degenerate limit.
- Domain assignment (
Distributed/PoleMap.cs,DomainAssignment.cs,SpeedDomain.cs,DominanceReport.cs).PoleMapis a GridSim-ownedGenerator.Type -> (poles, rpm, DomainKind)lookup: nuclear/coal/CCGT -> 2-pole/3000 rpm synchronous; large hydro/pumped -> multi-pole synchronous; wind/solar/storage/interconnector ->Pll/virtual (no real pole).DomainAssignmentpartitions generators into domains, computes each domain's aggregate inertiaH_d = sum H_iandGVad = sum(S*C), and reportsdeltaGVa+ dominance. - The kernel (
Distributed/MultiDomainSwing.cs). Each domain is a coherent mass linked by Kron-reduced synchronising power. It keeps the COI equal to the lumped result by keying the aggregate forcing off the inertia-weighted COI and using antisymmetric tie power (sum = 0), and it integrates with symplectic (semi-implicit) Euler - forward Euler blows up under the stiff Kron coupling. The single-domain / reduction limit delegates toFrequencyDynamicsfor the exact reduction. - Physical coupling (
PowerFlow/KronReduction.cs,Distributed/DomainCoupling.cs). The inter-domain synchronising coefficients are Kron-reduced (star-mesh elimination) from theYBus- physically derived, not fitted - so the inter-area mode frequency is a property of the network, not a knob. - Propagation overlay (
Distributed/PropagationDelay.cs, off by default). Finite wave speed enters as a retardationdelta_j(t - tau_ij)on the coupling, read from per-mass angle ring buffers.tau = physical distance / wave speed, with the wave speed derived from local inertia density and clamped to the published 500-1500 km/s band. It is off by default because the retardation perturbs the COI (real physics), so the machine-eps COI invariant only holds with it off.
Why LumpedScalar is the exact limit. Summing the per-mass swing equations, the internal coupling
telescopes and the COI obeys (2E/omega_s)*domega/dt = deltaP with E = sum H_i*MBase_i - identical to today's
scalar ODE. Set #domains = 1, tau = 0, coupling -> inf => machine-eps reduction.
5. COI projection - every existing consumer keeps working¶
DistributedInertiaModel.Simulate returns the inertia-weighted COI collapse
f_COI = sum H_i f_i / sum H_i, equal to the lumped response to machine-eps when domains don't diverge. So
StabilityMetrics, InertiaEstimator, RocofScreening, TsgbSizer, RP1, MECHANICAL, the Web
FrameProjector, and the bridge protocol read CoiInertiaGvaS (== SystemInertiaGvaS) unchanged.
The new per-domain / per-bus outputs live on Distributed/DistributedResult.cs (DomainTrace[],
per-bus event RoCoF map, DominanceReport, wave-speed / delay matrix) for the spatial views.
SystemInertiaGvaS is retained verbatim - the distributed model projects onto it, never redefines
it.
6. Validation - the fail-loud gates¶
All in tests/GridSim.Tests, all pass-gates (484 tests green as of this writing).
| Tier | File | Asserts |
|---|---|---|
| T0 | DistributedReductionTests |
The degenerate {1 domain, no propagation, coupling -> inf} config == FrequencyDynamics.Simulate to machine-eps. |
| T1 | DistributedInvariantTests |
sum H_i f_i / sum H_i == lumped f to machine-eps; energy balance; identical settled steady state. |
| T2 | CanonicalDynamicsTests, KronReductionTests |
Kron-reduced coupling and inter-area mode frequency behave canonically. |
| T3 | DistributedQualitativeTests |
Dominance reproduces the LOS sec. 5.5 worked example (deltaGVa ~ 0.333); distant domains respond later; wave speed in 500-1500 km/s; an externally-provided tau map overrides the first-order model. |
| T4 | DistributedReplayTests |
The COI-projected distributed response reproduces recorded GB events within ReplayValidator tolerance. |
| T5 | DistributedScaleDivergenceTests |
gb-full lumped-vs-distributed divergence is bounded and mechanism-attributed, emitted as a DivergenceReport tagged ProvenanceTag.UnvalidatedAtScale. No accuracy assertion. |
| T6 | ClassicalMultiMachineTests |
The per-machine classical backbone (sec. 6a) against exact analytic references: SMIB mode frequency, equal-area critical clearing time, RK4 energy boundedness, COI conservation, and WSCC-9 solve->init->fixed-point. |
Machine-eps is retained for the T0 reduction and the T1 COI invariant; relocated to bands for T3 (published), T4 (recorded), and T5 (bounded, no reference), and to closed-form physics for T6.
6a. The classical multi-machine backbone¶
Alongside the GB-scale domain-reduced kernel, GridSim carries the per-generator classical
transient-stability model (ClassicalMultiMachine + ClassicalInit) for the small canonical cases.
Each machine is a constant E'angle delta behind its transient reactance X'd, swinging over the network
Kron-reduced to the generator internal nodes (Pe_i = sum_j |E'_i||E'_j|(G_ij cos + B_ij sin)), integrated
with classical RK4 for first-swing accuracy. ClassicalInit.FromSolvedCase builds the reduced inputs
from a solved power flow by the standard preparation: loads -> constant-impedance shunts, generator
internal nodes behind X'd, Kron reduction, E' = V_t + jX'd*I_t, and Pm = Pe(delta0) so an undisturbed
case is a fixed point.
It is validated against exact, published, self-contained references - no fabrication, no reliance on
a reference that doesn't exist: the single-machine-infinite-bus small-signal mode frequency
omega_n = sqrt(omega_s*P_s/2H) (to <1%), the equal-area critical clearing time (stable just below it, unstable
just above), undamped RK4 energy/amplitude boundedness over ~28 cycles, two-machine COI conservation, and
a WSCC-9 (Anderson-Fouad X'd) end-to-end check that the solved pre-fault point is a fixed point and a
rotor-angle bump oscillates while holding synchronism. It is additionally cross-validated against an
independent integrator: gridsim stability case9 --export <json> writes the reduced system and its RK4
trajectory, and tools/crossval/crossval_classical.py re-integrates the identical ODE with scipy's RK45
- the two full 3-machine coupled trajectories agree to ~3.7x10^-^8 rad (machine epsilon), validating
the coupling numerics the analytic SMIB/2-machine limits don't exercise. This backbone is reserved for
the small canonical cases; the domain-reduced kernel remains the GB-scale path.
7. GDA as the data provider¶
GDA precomputes the heavy, slow-changing physics; GridSim looks it up and owns the dynamics. Two lake products (GDA manual sec. 38.11) feed the model:
propagation_delays- a network-static, single-file product of corridor delays: real physical and electrical distance, real local inertia, and a modelled clamped wave speed -> tau per bus pair. Served over the bridge asop=propagation. The loop is closed end-to-end:GridBridgeClient. QueryPropagation(at)requests the corridors and projects them (PropagationData.TauByBusPair) into the(fromBus, toBus) -> taumap that drops straight intoDistributedConfig.ProvidedTauSeconds; where a domain pair's representative buses are found there, that tau is used instead of the first-order model, falling back to the model elsewhere (PropagationDelay.Compute). Corridors whose lake row carries no tau are omitted, and the honest provenance note (real distances/inertia; modelled wave speed) rides along onPropagationData.Provenance.speed_domains- the fleet decomposition precomputed from GridWatch alone (per-domain GVad + inertia +deltaGVa+ theis_too_evenly_spreadflag), a direct lake read the SPEED DOMAINS tabs can display for any past instant without recomputing.
The provenance split is honest and stated per column: real distances and inertia; modelled and
unvalidated-at-scale wave speed and delay. The lake product and GridSim's own first-order model use
the identical clamp(1000*sqrt(200/density), 500, 1500) relation, so they agree by construction.
8. Using it¶
- API:
new DynamicsConfig { InertiaModel = InertiaModel.Distributed, Distributed = new DistributedConfig { /* EnablePropagation, ProvidedTauSeconds, ... */ } }, then route throughInertiaModelSelector. DefaultLumpedScalar. - CLI: the global
--inertia-model=lumped|distributedswitch (wired intotrip, reported ontransient), plus the dedicatedgridsim domainsverb that prints the decomposition. Seedocs/manual/0019 CLI reference.md. - WPF: the SPEED DOMAINS tab (
Views/DomainsVm.cs+DomainsView.xaml), inserted before ASSETS - GVad and spinning-inertia bar charts, dominance against the 10% threshold, provenance badges. Degrades gracefully to a single-COI-domain summary when the lumped model is active. - Web: the SPEED DOMAINS tab in GridSim.Web (
Components/Tabs/DomainsTab.razor, fed byTabProjections.Domains->FrameEnvelope.Domains).
9. Honest limits¶
The propagation overlay is unvalidatable at scale: there is no GB-wide PMU/DFR corpus to check an
absolute electromechanical wave speed against, so the model asserts only the band, never a
scale-accurate figure, and the overlay is off by default. Domain assignment from type -> poles is
many-to-one and inverters have no real pole - a conservative, documented default, provenance-tagged.
The per-machine classical multimachine model and its RK4 integrator are now built and validated
(sec. 6a) for the canonical cases. Still deferred, not faked: pinning the full published IEEE-39 / A&F
first-swing rotor-angle curves (needs the exact exciter/governor/clearing sequence), a scipy
multimachine sidecar, and importing the open dynamic cases the research catalogue surfaced (ANDES
IEEE-39 / Kundur, Texas A&M ACTIVSg .dyr) as additional cross-checks. The GB-scale path remains the
domain-reduced multi-area COI, which is what the T0-T5 gates validate. When the distributed and lumped
results diverge at GB scale, that divergence is reported and bounded, never presented as "more
accurate".
Related¶
docs/validation/neso-rp1-and-mechanical.md- the situational-awareness tab template this follows.docs/manual/0019 CLI reference.md- the--inertia-modelswitch and thedomainsverb.docs/validation/solver-validation-report.md- the machine-epsilon validation discipline this relocates.- GDA manual sec. 38.11 and Chapter 66 - the