IEEE C37.118.2 Synchrophasor Ingest + Phasor Data Concentrator - Technical Design

Status (verified 1.95.169): Partly implemented and experimental: the C37.118.2 DATA decoder, CONFIG-1/2 parser, phasor data concentrator, PDC-to-MeasurementSet mapper, linear PMU-only estimator and hybrid SCADA/PMU scheduler exist as Core API with tests. The pmu-ingest verb decodes a recorded multi-PMU capture file (technical ch. 33). There is no live frame transport, no stateful decoder and no per-PMU stream configuration type. Implemented in: src/GridSim.Core/Synchrophasor/C37118Decoder.cs (C37118Decoder, C37118DataFrame, FrameDecodeStatus), C37118ConfigFrame.cs (C37118ConfigParser, C37118ConfigFrame, PmuConfig), C37118Frame.cs (C37118FrameType, C37118DataFormat, Phasor, C37118CommonHeader, C37118Crc), PhasorDataConcentrator.cs (PmuSample, PdcSuperframe, PhasorDataConcentrator), PmuMeasurementSetMapper.cs (PmuChannelMap, PmuVoltageChannel, PmuCurrentChannel, PmuAngleReference, PmuMeasurementSetMapper); src/GridSim.Core/Estimation/LinearPmuStateEstimator.cs (LinearPmuStateEstimator, PmuVoltageMeasurement, PmuCurrentMeasurement, LinearPmuResult); src/GridSim.Core/Estimation/Measurement.cs (MeasurementKind.IAngDeg); src/GridSim.Core/Simulation/HybridMultiRateScheduler.cs (HybridMultiRateScheduler, ScheduledUpdate). Design-to-code name map:

Design name Implemented as
C37118FrameType.cs, C37118DataFormat.cs, C37118Crc.cs, C37118CommonHeader.cs, Phasor.cs all in C37118Frame.cs
ConfigFrame2.cs, PmuConfig.cs C37118ConfigFrame.cs (C37118ConfigFrame, PmuConfig; the parser is C37118ConfigParser)
PhasorDescriptor.cs not implemented; PmuConfig.PhasorUnits and PmuConfig.PhasorScale(index) carry the PHUNIT scaling
DataFrame.cs, PmuData.cs C37118DataFrame in C37118Decoder.cs (first PMU block only; analogue and digital channels are not decoded)
PmuStatus.cs not implemented; the STAT word is the raw ushort C37118DataFrame.Stat
stateful C37118Decoder holding CONFIG-2 not implemented; the static decoder takes the parsed PmuConfig per call
PdcSuperframe.cs PdcSuperframe in PhasorDataConcentrator.cs (Samples by PMU id, Dropped list)
IPmuFrameSource.cs, FileReplayPmuFrameSource.cs not implemented
PmuStreamConfig.cs PmuChannelMap with PmuVoltageChannel, PmuCurrentChannel, PmuAngleReference in PmuMeasurementSetMapper.cs
MeasurementKind.cs MeasurementKind is declared in Estimation/Measurement.cs

This is a design record. The current behaviour is documented in the technical manual chapter 18. Real-time, distribution and dynamic estimation (section 18.6).

Governing constraint: UnderstandingRestrictions.md (no forward inference) and RestrictionReview.Reviewed (src/GridSim.Core/Diagnostics/RestrictionReview.cs) (the Dynamics->Estimation review gate). Read those first; every decision below is subordinate to them.

This document specifies, to the level an implementer follows without further research: (a) a byte-exact C37.118.2 frame decoder (CONFIG-2 and DATA frames), (b) a Phasor Data Concentrator (PDC) that time-aligns several PMU streams with a bounded wait-window and survives dropouts and latency, (c) the adapter that maps concentrated phasors into the existing estimator as voltage-magnitude, voltage-angle and current-phasor measurement rows, (d) a linear single-shot PMU-only state estimator, and (e) a hybrid multi-rate SCADA(~5 s) + PMU(~0.5 s) fusion scheduler that fits the RealtimeEstimatorEngine cadence. No C# is written here - types are named and specified so they land in the existing code style.


1. Restriction posture (read this before any code)

This feature ingests synchrophasors, which in the field are a live, sub-second telemetry stream - exactly the kind of data the one rule forbids GridSim from using to see the present or future of the real GB grid. The design is built so the capability is real (a validated C37.118 decoder + PDC + linear/hybrid PMU estimator) while the forbidden operation is structurally impossible.

The three things this design guarantees, mechanically:

  1. Every dated synchrophasor input passes ForwardInferenceGuard.RejectFuture before it is estimated. A PMU frame carries an absolute UTC timestamp (SOC + FRACSEC, section 4.4). The PDC stamps each aligned superframe with that UTC instant and the mapping adapter (PmuMeasurementSetMapper, section 10) calls the guard on it. A frame newer than UtcNow - 169 h is recorded and skipped, never mapped, never estimated. Because a live PMU frame is by definition seconds old, the guard rejects every live frame by construction: there is no code path that turns a live synchrophasor into a state estimate.
  2. The feature runs on replay or permitted-age captures only. The transport layer (IPmuFrameSource, section 9.1) is fed by a recorded C37.118 byte stream (a capture file / pcap payload replayed frame by frame). A live-socket source may exist as an interface implementation, but its frames still transit the guard, so it can only ever deliver frames that are >= 169 h old - which a live socket never produces. "Real-time" here means the engineering (streaming parse, resident PDC, sub-cycle cadence, resilience), never live sight, exactly as UnderstandingRestrictions.md sec. 3 permits.
  3. Every estimator introduced here is a filter, not a predictor. The linear single-shot PMU estimator (section 11) and the hybrid scheduler (section 12) are measurement-only: they resolve the state at the frame's own timestamp from that frame's observations. They emit a state stamped at the (present/past) measurement time, never a future-dated claim. Neither fuses a Dynamics/ process model, so per the review log they are static filters, unconditionally permitted and need no RestrictionReviewEntry. (RestrictionReview.Reviewed already lists linear-PMU and branch-current among the permitted static methods; this design realises the first of those.) If a future variant ever adds a dynamic predict step (e.g. a PMU-rate EKF tracker), it becomes a Dynamics->Estimation fusion and section 13.3's gate applies - stop and review.

Invariant mapping (against UnderstandingRestrictions.md "rules, as testable invariants"): #1 - the PDC/mapper is a new dated ingestion seam behind the guard (section 13); #2 - no output is stamped later than its newest input frame (section 12.4); #4 - proven on replay/permitted-age only (sections 1.2, 15); #5 - no Dynamics/ fusion, so the DSE gate is untouched (section 13.3).


2. Scope, non-goals, and standard baseline

In scope. C37.118.2-2011 mapping of the 2005 frame syntax: the common frame header, CONFIG-2 configuration frames, DATA frames, fixed (16-bit integer) and floating-point (32-bit IEEE-754) formats, phasors in rectangular and polar form, FREQ/DFREQ in integer and float, the STAT word and its time-quality/sync bits, CRC-CCITT frame integrity, and TVE-aware sigma assignment. A PDC that aligns N PMU streams by timestamp. Mapping to estimator rows. A linear PMU-only estimator and a hybrid multi-rate scheduler.

Out of scope (named as future seams, section 17). CONFIG-1 and CONFIG-3 frames (CONFIG-3 is decoded to the extent needed to reject it cleanly); HEADER frames (skipped, logged); the command channel (CMD frames) beyond a documented request enum - GridSim never drives a live PMU, it replays captures; analog and digital channels are parsed and carried but not mapped to estimator rows; TCP/UDP/multicast socket transport internals (the interface is defined; a file-replay source is the reference implementation).

Standard. IEEE Std C37.118.2-2011 "for Synchrophasor Data Transfer for Power Systems". All multi-byte integers are network byte order (big-endian). This is the single most common decoder mistake; use System.Buffers.Binary.BinaryPrimitives big-endian readers throughout, never BitConverter (which is host-endian).


3. Namespace and file layout

New code lives under two existing conventions: transport/decoder/PDC in a new GridSim.Core.Synchrophasor namespace (folder src/GridSim.Core/Synchrophasor/), the estimator/scheduler additions in the existing GridSim.Core.Estimation and GridSim.Core.Simulation namespaces so they sit beside WlsStateEstimator and RealtimeEstimatorEngine.

src/GridSim.Core/Synchrophasor/
  C37118FrameType.cs        enum: Data, Header, Config1, Config2, Config3, Command
  C37118DataFormat.cs       [Flags] enum for the CONFIG FORMAT word (4 bits)
  C37118Crc.cs              static CRC-CCITT (poly 0x1021, init 0xFFFF)
  C37118CommonHeader.cs     readonly struct: Sync/Type/Version/FrameSize/IdCode/Soc/FracSec/TimeQuality
  C37118Decoder.cs          the parser: ReadOnlySpan<byte> -> parsed frames; stateful (holds CONFIG-2)
  ConfigFrame2.cs           sealed record: TimeBase, DataRate, PmuConfig[]
  PmuConfig.cs              sealed record: StationName, IdCode, Format, phasor/analog/digital descriptors, FNom, CfgCount
  PhasorDescriptor.cs       sealed record: Name, Kind(Voltage/Current), ConversionFactor, ScalePu
  DataFrame.cs              sealed record: CommonHeader-derived TimeUtc + PmuData[]
  PmuData.cs                sealed record: StatWord, Phasor[], FreqHz, RocofHzPerS, Analog[], Digital[]
  Phasor.cs                 readonly struct: Real, Imag (engineering units) + Magnitude/AngleRad accessors
  PmuStatus.cs              readonly struct wrapping the STAT word (DataValid, SyncOk, UnlockedTime, ...)
  PhasorDataConcentrator.cs the time-aligner (wait-window buffer -> PdcSuperframe stream)
  PdcSuperframe.cs          sealed record: TimeUtc + per-PMU aligned PmuData (+ per-PMU present/dropped flags)
  IPmuFrameSource.cs        transport seam: IEnumerable<ReadOnlyMemory<byte>> of raw frames
  FileReplayPmuFrameSource.cs   reference source: length-delimited capture file
  PmuMeasurementSetMapper.cs    PdcSuperframe -> MeasurementSet (guarded); PMU->bus/branch crosswalk
  PmuStreamConfig.cs        per-PMU crosswalk + base kV/A + performance class -> sigma policy

src/GridSim.Core/Estimation/
  MeasurementKind.cs        + IAngDeg member (branch current phase angle) - section 10.2
  LinearPmuStateEstimator.cs   rectangular constant-gain single-shot PMU-only WLS - section 11

src/GridSim.Core/Simulation/
  HybridMultiRateScheduler.cs  SCADA(~5 s) + PMU(~0.5 s) window interleaver - section 12

Style rules the new files follow (matching the existing tree): sealed record for immutable value carriers, readonly struct for hot parse structs, XML doc comments on every public member (the 0-warning gate requires them, section 16), internal for anything the CLI/UI does not need, culture-invariant parsing, no unsafe.


4. The C37.118.2 frame model

4.1 Common frame header (14 bytes, all frame types)

Every frame begins with the same header. Offsets are from frame start.

Off  Size  Field       Meaning
0    2     SYNC        byte0 = 0xAA (leading sync);
                       byte1: bit7 reserved(0);
                              bits6..4 = frame type (see 4.2);
                              bits3..0 = version number (1 = 2005 mapping, 2 = 2011)
2    2     FRAMESIZE   total bytes in the frame, header..CHK inclusive (uint16 BE)
4    2     IDCODE      data stream / PMU / PDC id (uint16 BE)
6    4     SOC         second-of-century: UNIX time, seconds since 1970-01-01T00:00:00Z (uint32 BE)
10   4     FRACSEC     bits31..24 = message time-quality flags;
                       bits23..0  = fraction-of-second, raw count of 1/TIME_BASE (from CONFIG)
... body ...
end-2 2   CHK          CRC-CCITT over bytes [0 .. FRAMESIZE-3] (uint16 BE)

C37118CommonHeader is a readonly struct parsed by C37118CommonHeader.Parse(ReadOnlySpan<byte> frame); it exposes FrameType, Version, FrameSize, IdCode, Soc, FracSecRaw (lower 24 bits), TimeQuality (top byte of FRACSEC). It does not convert to UTC (that needs TIME_BASE from CONFIG - see 4.4).

4.2 Frame type discrimination

C37118FrameType from SYNC byte1 bits 6..4:

000 = Data     001 = Header    010 = Config-1
011 = Config-2 100 = Command    101 = Config-3

The decoder switches on this. Config-1 is treated as Config-2 syntactically (same layout for our fields); Config-3, Header and Command are decoded to a typed "unsupported/ignored" outcome (section 6.4), never a throw in the resident loop.

4.3 CRC-CCITT (frame integrity)

C37.118 uses CRC-CCITT: width 16, polynomial 0x1021, initial value 0xFFFF, no input/output reflection, no final XOR. Computed over every byte of the frame from SYNC through the last data byte (i.e. bytes [0 .. FRAMESIZE-3]), and compared to the trailing 2-byte CHK.

crc = 0xFFFF
for each byte b in frame[0 .. FRAMESIZE-3]:
    crc = crc XOR (b << 8)
    repeat 8 times:
        if (crc AND 0x8000) != 0: crc = (crc << 1) XOR 0x1021
        else:                     crc = (crc << 1)
        crc = crc AND 0xFFFF
return crc

C37118Crc.Compute(ReadOnlySpan<byte> bytes) -> ushort. The decoder verifies CHK before trusting any field; a CRC mismatch yields FrameDecodeStatus.CrcMismatch (section 6.4), and the PDC treats that PMU as dropped for that timestamp (section 9.4). A table-driven variant is permitted for speed but must be cross-checked bit-for-bit against the bitwise form above in a unit test.

4.4 Timestamp: SOC + FRACSEC -> UTC

fraction_seconds = FracSecRaw / TIME_BASE      (TIME_BASE from CONFIG-2, typically 1_000_000)
TimeUtc = DateTime(1970,1,1,0,0,0, DateTimeKind.Utc)
          + TimeSpan.FromSeconds(Soc)
          + TimeSpan.FromSeconds(fraction_seconds)

Implemented with DateTime.UnixEpoch.AddSeconds(Soc).AddTicks(...); prefer ticks math on the fraction to avoid double rounding (ticks = FracSecRaw * 10_000_000L / TIME_BASE, integer). This UTC instant is the timestamp the PDC aligns on and the guard checks. It is always absolute UTC - never local, never relative.

The FRACSEC top byte (time quality) and the STAT unlocked-time bits (section 6.3) feed the sigma policy: a frame whose PMU clock is unlocked gets inflated sigma or is dropped.


5. CONFIG-2 frame decoding

CONFIG-2 is stateful context: the decoder must hold the most recent CONFIG-2 per IDCODE, because DATA frames are self-descriptionless and are only decodable against their CONFIG. C37118Decoder keeps Dictionary<ushort, ConfigFrame2> keyed by IDCODE and refuses to decode a DATA frame for an IDCODE it has not yet seen a CONFIG for (FrameDecodeStatus.NoConfig).

5.1 CONFIG-2 body layout (after the 14-byte common header)

Off   Size            Field       Meaning
14    4               TIME_BASE   resolution of FRACSEC; lower 24 bits significant (uint32 BE)
18    2               NUM_PMU     number of PMU blocks that follow (uint16 BE)
20    ...             PMU blocks  NUM_PMU repetitions of the block below
...   2               DATA_RATE   > 0: frames/second; < 0: seconds/frame (int16 BE)
end-2 2               CHK

Per-PMU block (repeated NUM_PMU times):

Size                        Field     Meaning
16                          STN       station name, ASCII, space-padded
2                           IDCODE    this PMU's data-source id (uint16 BE)
2                           FORMAT    format word (section 5.2)
2                           PHNMR     number of phasors (uint16 BE)
2                           ANNMR     number of analog values (uint16 BE)
2                           DGNMR     number of digital status words (uint16 BE)
16*(PHNMR+ANNMR+16*DGNMR)   CHNAM     channel names, 16 ASCII bytes each
4*PHNMR                     PHUNIT    per-phasor conversion factor (section 5.3)
4*ANNMR                     ANUNIT    per-analog conversion factor
4*DGNMR                     DIGUNIT   per-digital mask/valid words
2                           FNOM      nominal line frequency: bit0 0=60 Hz, 1=50 Hz
2                           CFGCNT    configuration change count (uint16 BE)

5.2 FORMAT word (C37118DataFormat, a [Flags] enum)

Lower 4 bits (bits 15..4 unused):

bit0  phasor number format:   0 = 16-bit integer, 1 = 32-bit IEEE float
bit1  analog number format:   0 = 16-bit integer, 1 = 32-bit IEEE float
bit2  freq/dfreq format:      0 = 16-bit integer, 1 = 32-bit IEEE float
bit3  phasor coordinate:      0 = rectangular,    1 = polar

The decoder reads FORMAT per PMU and dispatches phasor/freq parsing (section 6) on these four bits. All four combinations (int/float x rect/polar, int/float freq) must be supported and each covered by a decode test (section 15).

5.3 PHUNIT (phasor scale + type)

Each 4-byte PHUNIT: top byte = phasor type (0 = voltage, 1 = current); lower 3 bytes (24-bit uint BE) = scale factor. For integer phasor format the scale is in units of 10^-5 volts or amperes per bit (multiply the raw integer by scale * 1e-5 to get engineering volts/amps). For float format the phasor is already in engineering units and the scale is informational (still carries the voltage/current flag, which the mapper needs to decide bus-voltage vs branch-current row). PhasorDescriptor records Kind (Voltage/Current from the top byte), Name (from CHNAM), the raw ConversionFactor, and a mapper-supplied ScalePu (section 8) that turns engineering units into per-unit.

FNOM sets each PMU's nominal frequency for FREQ reconstruction (section 6.2).


6. DATA frame decoding

A DATA frame body is a concatenation of per-PMU blocks in the exact order the PMUs appear in the governing CONFIG-2. There are no delimiters; sizes come from CONFIG (PHNMR/ANNMR/DGNMR and FORMAT). C37118Decoder.DecodeData(span) looks up the CONFIG by IDCODE, then walks each PMU block.

6.1 Per-PMU DATA block

Size                    Field    Meaning
2                       STAT     status word (section 6.3)
phasor-size * PHNMR     PHASORS  phasor-size = 8 (float) or 4 (int) bytes each
freq-size               FREQ     4 (float) or 2 (int) bytes
freq-size               DFREQ    4 (float) or 2 (int) bytes
analog-size * ANNMR     ANALOG   4 (float) or 2 (int) bytes each
2 * DGNMR               DIGITAL  16-bit words

6.2 Phasors, frequency, ROCOF

Phasor, rectangular integer (4 bytes): int16 BE real, int16 BE imag; engineering value re = raw_re * scale * 1e-5, im = raw_im * scale * 1e-5.

Phasor, polar integer (4 bytes): uint16 BE magnitude, int16 BE angle; mag_eng = raw_mag * scale * 1e-5, angle_rad = raw_angle * 1e-4 (the angle unit is 10^-4 radians, range -pi..+pi). Convert to rectangular for the Phasor struct: re = mag_eng * cos(angle_rad), im = mag_eng * sin(angle_rad).

Phasor, rectangular float (8 bytes): float32 BE real, float32 BE imag, already engineering units.

Phasor, polar float (8 bytes): float32 BE magnitude (engineering units), float32 BE angle (radians). Convert to rectangular as above.

Phasor always stores rectangular engineering units (Real, Imag) with Magnitude => hypot(Real, Imag) and AngleRad => atan2(Imag, Real) accessors, so downstream code is format-agnostic.

FREQ. Integer: int16 BE = deviation from nominal in millihertz; actual Hz = FNom + FREQ_raw / 1000.0. Float: float32 BE = the actual frequency in Hz, nominal included (IEEE C37.118.2-2011 Table 5, FREQ: fixed point is the deviation from nominal in mHz, floating point is the actual frequency in Hz; the standard is not on disk, so this is from the published table, as in pyPMU and openPDC); Hz = FREQ_float. Store FreqHz absolute. (N038, 1.95.239: this section used to say the float field is a deviation from nominal and proposed a per-stream PmuStreamConfig.FreqIsAbsolute switch. That was wrong against Table 5 and was never built; C37118Decoder reads the float field as absolute Hz, which is the standard's rule.)

DFREQ (ROCOF). Integer: int16 BE = ROCOF * 100 in Hz/s; RocofHzPerS = DFREQ_raw / 100.0. Float: float32 BE = ROCOF in Hz/s directly.

6.3 STAT word and TVE awareness (PmuStatus)

The 16-bit STAT word:

bit15     data valid       0 = good, 1 = invalid/error
bit14     PMU error        1 = device error
bit13     PMU sync         0 = in sync, 1 = out of sync
bit12     data sorting      0 = by timestamp, 1 = by arrival
bit11     PMU trigger detected
bit10     configuration change pending
bit09     data modified (post-processed)
bits08..06 PMU time quality
bits05..04 unlocked time:   00 sync locked / <10 s since unlock;
                            01 <10 s, 10 <100 s, 11 >100 s unlocked
bits03..00 trigger reason

PmuStatus exposes DataValid, SyncOk (bit13 clear), UnlockedTime (enum), ConfigChangePending. These drive the sigma policy (section 8.3) and the PDC drop rule (section 9.4).

TVE (Total Vector Error) awareness. C37.118.1 defines a phasor's accuracy by TVE = sqrt((Xr_meas - Xr_true)^2 + (Xi_meas - Xi_true)^2) / |X_true|, with 1 % the compliance limit. GridSim never measures TVE (there is no truth), but it uses the TVE budget as the sigma model: a phasor at compliance carries at most 1 % magnitude error and about 0.01 rad (~0.573 deg) angle error, because for a pure angle error TVE ~= |angle_error_rad|. So (section 8.3) magnitude sigma is set to tve_budget * |V| and angle sigma to tve_budget radians, where tve_budget comes from the declared performance class (P vs M) and is inflated when STAT reports unlock/error. This is how "TVE awareness" enters the estimator: as principled, class- and status-derived measurement weights, not as a discarded diagnostic.

6.4 Decode outcome

C37118Decoder returns a discriminated outcome rather than throwing in the hot loop:

enum FrameDecodeStatus { Ok, CrcMismatch, NoConfig, UnsupportedFrameType,
                         TruncatedFrame, VersionUnsupported }
readonly struct DecodeResult { FrameDecodeStatus Status; C37118FrameType Type;
                               DataFrame? Data; ConfigFrame2? Config; }

A TruncatedFrame (FRAMESIZE says more bytes than the buffer holds, or a PMU block overruns) is a hard protocol violation for that frame only; it is recorded and the frame skipped. Only genuinely un-parseable program states (a null buffer) throw. This mirrors RealtimeEstimatorEngine's "record and skip, never tear down the resident loop" resilience doctrine.


7. Parsed data structures (named to fit the tree)

sealed record ConfigFrame2(
    uint TimeBase, double DataRateFramesPerSec, IReadOnlyList<PmuConfig> Pmus,
    ushort IdCode, uint Soc, uint FracSecRaw);

sealed record PmuConfig(
    string StationName, ushort IdCode, C37118DataFormat Format,
    IReadOnlyList<PhasorDescriptor> Phasors, int AnalogCount, int DigitalCount,
    double FNomHz, ushort ConfigCount);

sealed record PhasorDescriptor(string Name, PhasorKind Kind, uint ConversionFactor);
enum PhasorKind { Voltage, Current }

readonly struct Phasor { double Real; double Imag;
    double Magnitude => Math.Sqrt(Real*Real + Imag*Imag);
    double AngleRad  => Math.Atan2(Imag, Real); }

readonly struct PmuStatus { ushort Raw; bool DataValid; bool SyncOk;
    UnlockedTime UnlockedTime; bool ConfigChangePending; }

sealed record PmuData(ushort IdCode, PmuStatus Status, IReadOnlyList<Phasor> Phasors,
    double FreqHz, double RocofHzPerS, IReadOnlyList<double> Analog,
    IReadOnlyList<ushort> Digital);

sealed record DataFrame(DateTime TimeUtc, ushort IdCode, IReadOnlyList<PmuData> Pmus);

Engineering-unit values are stored; per-unit conversion happens at the mapper (section 8), keeping the decoder a pure, protocol-faithful layer that a decode test can pin against reference vectors independent of any grid model.


8. Phasor scaling and per-unit mapping (PmuStreamConfig)

A C37.118 stream carries engineering volts/amps (secondary or primary, per-device), with no knowledge of the estimator's per-unit base or the network topology. The bridge between the two is a curated, static crosswalk - PmuStreamConfig - authored once per capture, exactly as the GDA GSP/BMU crosswalk authors SCADA measurement sets today.

8.1 Crosswalk contents

sealed record PmuStreamConfig(
    IReadOnlyList<PmuChannelMap> Channels, PmuSigmaPolicy Sigma);

sealed record PmuChannelMap(
    ushort PmuIdCode, int PhasorIndex,       // which stream, which phasor in it
    PmuChannelTarget Target,                 // bus voltage, or branch current end
    double PrimaryToBase);                   // engineering-units -> per-unit factor

// Target is one of:
//   BusVoltage(int BusId)
//   BranchCurrent(int From, int To, BranchEnd End, string? Circuit)

Target reuses the estimator's addressing exactly: bus id for voltages, (From, To, End, Circuit) for branch currents - the same fields Measurement/MeasurementSet.TryResolveBranch already validate, so a bad crosswalk fails in the existing validation path with the existing diagnostics.

8.2 Per-unit factors

Voltage phasor -> pu: Vpu = V_eng * PrimaryToBase, where for a bus at base kV V_base_LN (line-to-neutral), PrimaryToBase = 1 / (V_base_LN in the same unit as V_eng). The mapper carries this as one authored scalar per channel so the design does not assume a specific PT ratio.

Current phasor -> pu: Ipu = I_eng * PrimaryToBase, with base current I_base = S_base_3ph / (sqrt(3) * V_base_LL) = BaseMva * 1e6 / (sqrt(3) * V_base_LL_volts). PrimaryToBase = 1 / I_base. Per-unit current magnitude is directly the IMagPu measurement unit the estimator already uses.

8.3 Sigma policy (TVE + status derived)

sealed record PmuSigmaPolicy(
    double TveBudgetP,      // performance-class P TVE budget, e.g. 0.01 (1 %)
    double TveBudgetM,      // performance-class M budget
    double UnlockInflation, // multiply sigma when unlocked-time > 0, e.g. 10x
    double DropOnInvalid);  // if data invalid, drop the row (true) vs inflate

// Per phasor at magnitude |V| (pu) or |I| (pu):
//   sigma_mag_pu   = tve * |mag|            (relative magnitude error)
//   sigma_angle_rad = tve                    (angle error ~ TVE for small angles)
//   tve = (class == M ? TveBudgetM : TveBudgetP) * (unlocked ? UnlockInflation : 1)

If PmuStatus.DataValid is false, the mapper drops that PMU's rows for that timestamp (a NaN/garbage phasor must never reach the gain matrix - the same doctrine as MeasurementSet.Validate). Angle-magnitude coupling (a large phasor has a tighter absolute angle need) is captured adequately by the two independent sigmas above; a full 2x2 phasor covariance is a documented future refinement (section 17) - the estimator currently takes scalar per-row sigmas.


9. The Phasor Data Concentrator

The PDC turns several asynchronous single-PMU DATA streams into one time-aligned sequence of PdcSuperframes, each carrying every PMU's data for one reporting instant, with explicit present/dropped flags. It is the classic PDC wait-window aligner, made deterministic.

9.1 Transport seam

interface IPmuFrameSource { IEnumerable<ReadOnlyMemory<byte>> Frames { get; } }

The reference implementation FileReplayPmuFrameSource reads a length-delimited capture file (each record = uint32 BE length + raw C37.118 frame bytes, optionally a leading CONFIG-2 then DATA frames), yielding frames in file order. This is the replay source that section 1.2 relies on. A socket source is a future implementation of the same interface; its frames still pass the guard downstream, so it cannot deliver a processable (>=169 h old) live frame.

9.2 Reporting grid and alignment key

Each PMU reports at a fixed rate (CONFIG DATA_RATE, e.g. 50 fps -> 20 ms; a downsampled 0.5 s stream -> 2 fps). The PDC quantises every frame's TimeUtc onto a common reporting grid of period T_report (the slowest common cadence we align to - for the hybrid scheduler, the 0.5 s PMU tick). The alignment key is

slot = round((TimeUtc - Epoch) / T_report)     // integer slot index

Round-to-nearest (not truncate) so a frame arriving 1 ms early/late still lands in its intended slot. Frames whose residual |TimeUtc - slot*T_report| exceeds T_report/2 are logged as off-grid and dropped (a misconfigured rate).

9.3 Wait-window buffer

The PDC holds a bounded, ordered buffer of partially-filled superframes keyed by slot. For each incoming decoded PmuData:

  1. Compute its slot. If slot is older than the newest already-emitted slot (a late straggler past the window), record LateArrivalsDropped++ and discard.
  2. Otherwise insert the PMU's data into the superframe for slot (creating it if new).
  3. A superframe is complete when all expected PMUs (from PmuStreamConfig) are present.

Emission is driven by a wait window W = WaitSlots * T_report (author-set, e.g. 2-3 report periods). A slot is emitted when either it is complete, or the watermark (newest observed slot) has advanced beyond slot + WaitSlots - i.e. we have waited W for the missing PMUs and give up. Emission is strictly in increasing slot order, so downstream sees a monotonic timestamp sequence (load-bearing for invariant #2 and warm-start chaining).

sealed record PdcSuperframe(
    DateTime TimeUtc,                         // slot * T_report, absolute UTC
    IReadOnlyList<PdcPmuSlot> Pmus);          // one per expected PMU, in config order

sealed record PdcPmuSlot(ushort PmuIdCode, PmuData? Data, PmuSlotState State);
enum PmuSlotState { Present, Dropped, Late, CrcFailed, StatusInvalid }

9.4 Dropouts, latency, and quality

  • Dropout (a PMU absent when the window closes): PdcPmuSlot.State = Dropped, Data = null. The mapper simply authors no rows for it - the estimator handles missing measurements natively (that is the entire point of an estimator vs a power flow; a dropped PMU degrades redundancy, not correctness). If dropouts make the PMU-observable island unobservable, the linear estimator reports Unobservable honestly (section 11.4) and the hybrid scheduler falls back to the last SCADA state as prior (section 12.3).
  • Latency: bounded by W. A frame later than W is a Late straggler, counted and dropped, never retro-applied to an emitted slot (that would emit a second, out-of-order superframe for a past instant - forbidden). Choosing W trades completeness against emission delay; it is an authored knob, not adaptive (determinism, section 14).
  • CRC / status quality: a frame that failed CRC at decode never reaches the PDC as data; the PDC marks that slot CrcFailed if it knows a frame was expected. A frame present but StatusInvalid (STAT data-invalid) is carried as StatusInvalid and dropped at the mapper per the sigma policy.

9.5 Determinism of alignment

Given the same multiset of decoded frames, the emitted PdcSuperframe sequence is identical regardless of arrival interleaving, because slotting is a pure function of TimeUtc and emission order is by slot. There is no wall-clock in the alignment math; the "watermark" is the max observed frame slot, not real time. A test feeds the same frames in several shuffled orders and asserts identical superframe output (section 15.4).


10. Mapping concentrated phasors to estimator rows

PmuMeasurementSetMapper.Map(PdcSuperframe sf, PmuStreamConfig cfg, DateTime? utcNow) -> MeasurementSet produces a gridsim-measurements/1 set stamped TakenUtc = sf.TimeUtc. The guard is called here (section 13). The set is then handed to the existing WlsStateEstimator (hybrid path) or converted to the linear estimator's rectangular input (section 11).

10.1 Voltage phasor -> VmPu + VaDeg

Each voltage phasor mapped to a BusVoltage(busId) target authors two rows:

  • MeasurementKind.VmPu, value |V|_pu, sigma sigma_mag_pu, Bus = busId, Source = "pmu".
  • MeasurementKind.VaDeg, value = the re-referenced angle in degrees, sigma sigma_angle_rad * 180/pi, Bus = busId, Source = "pmu".

Re-referencing (the reference problem). All synchrophasor angles in one superframe share the C37.118 common time reference (a cosine at nominal frequency at TimeUtc); the estimator's datum is the slack bus. They differ by a common, slowly-drifting offset delta(t). Exactly as the Gridradar design note prescribes, the mapper carries only angle differences against an authored datum PMU bus, anchored to the estimator's own current view of that datum:

Va_row(node) = angle_pmu(node) - angle_pmu(datum) + Va_prior(datum_bus)

Va_prior(datum_bus) is the datum bus angle from the warm-start prior state the scheduler already threads (section 12). Differences cancel delta(t) exactly; the anchor puts the row in the slack frame. The estimator does not solve for a per-feed offset state (one feed, few nodes: the offset would consume a measurement of information for no gain). A VaDeg row on the slack bus is legal and structurally empty (existing behaviour) and is skipped by the mapper as uninformative.

10.2 Current phasor -> IMagPu + IAngDeg (one new MeasurementKind)

A current phasor carries information the existing IMagPu row alone discards: its angle. To use the full phasor without abandoning the estimator's polar state and its validated nonlinear kernels, add one measurement kind:

// added to MeasurementKind (Estimation/MeasurementKind.cs):
IAngDeg   // Branch current phase angle into the measured end, degrees, slack-referenced.
          // Pairs with IMagPu to represent a full current phasor. Addresses a branch
          // (From/To/End/Circuit), like the flow/current-magnitude kinds.

h(x) for IAngDeg. The current at end a is I_a = conj(S_a / V_a), so its angle is angle(I_a) = angle(V_a) - angle(S_a) = Va[a] - atan2(Q_a, P_a), where P_a, Q_a are the branch's real/reactive flow into end a (per-unit) computed by the existing FlowP/FlowQ kernels. Thus

h_IAngDeg(x) = Va[a] - atan2( Qflow(a), Pflow(a) )        (radians internally; ingest deg->rad)

This deliberately mirrors IMagPu (|I| = sqrt(P^2+Q^2)/Vm[a]), reusing the same flow kernels - no copy-drift, the same discipline as CurrentMagRow.

Jacobian row d h_IAngDeg / dx. With S2 = P_a^2 + Q_a^2:

d/dx [ atan2(Q, P) ] = ( P * dQ/dx - Q * dP/dx ) / S2

=> row = e_{Va[a]} - ( P * dQ/dx - Q * dP/dx ) / S2

e_{Va[a]} is the unit entry in end a's angle column (omitted if a is the slack - then the current-angle row is measured purely through the flow terms). dP/dx and dQ/dx are the exact partials FlowRow already emits (captured via the existing PairSink pattern, precisely as CurrentMagRow does). A branch carrying no flow (S2 ~ 0) contributes a structural near-zero row and is skipped, same guard as CurrentMagRow. StructuralColumns for IAngDeg is identical to IMagPu/flow rows (the four columns: both end angles + both end Vm). The residual back-conversion in WlsStateEstimator.Assemble gets one switch arm: IAngDeg => 180/pi (it is an angle, like VaDeg).

The current phasor angle is re-referenced identically to the voltage angle (section 10.1) because h already lives in the slack frame (Va[a] is slack-referenced state): author I_ang_row = angle_pmu(I) - angle_pmu(Vdatum) + Va_prior(datum_bus).

10.3 Why this mapping is the right seam

It keeps the estimator's state polar and its kernels untouched-but-reused, adds exactly one measurement kind, and lets the same WlsStateEstimator fuse PMU and SCADA rows in one solve (the hybrid path). Voltage phasors become the cheapest, linear VaDeg/VmPu rows; current phasors reuse the flow algebra. Bad-data detection, chi-square, observability and warm-start all apply unchanged.


11. Linear single-shot PMU state estimator

When a subnetwork is fully observed by PMUs (voltage and current phasors), the measurement equation is linear in the rectangular bus-voltage state, so the estimate is a single non-iterative solve of a constant-gain system - the classic Phadke linear PMU estimator. This is LinearPmuStateEstimator (Estimation/LinearPmuStateEstimator.cs), a static, measurement-only filter (the linear-PMU method the review log already lists as unconditionally permitted; no DSE entry).

11.1 State and measurement model (rectangular)

State: complex bus voltages of the PMU-observable island, x = [Vr_1..Vr_p, Vi_1..Vi_p] (real then imaginary parts, p buses). All phasors in a superframe are in one common reference (section 10.1), so no per-bus angle datum is needed within the linear solve; the whole solution is rotated into the slack frame afterward (section 11.3).

  • Voltage phasor at bus k: measures V_k directly. Rows: Vr_k = Re(V_k), Vi_k = Im(V_k). Constant, trivially linear.
  • Current phasor on branch k->m, measured end k: from the pi-model, I_km = (y_series + y_shunt_k) V_k - y_series V_m, complex-linear in the voltages. With y_series = g + jb, y_shunt_k = jb_c/2 (and tap/phase-shift folded into the same yff/yft stamps MeasurementModel already computes), the real/imag rows are linear combinations of Vr_k, Vi_k, Vr_m, Vi_m.

Stacking real and imaginary parts gives a real linear system z = H x + e with a constant real matrix H (built once from the Y-bus stamps, reused for every superframe - the standout property of linear PMU SE).

11.2 Weighted least squares (single shot)

x_hat = (H^T W H)^-1 H^T W z          W = diag(1/sigma_i^2)

Formed once: Gain = H^T W H (constant if the sigma structure is constant), and per superframe only the right-hand side H^T W z changes. Solve with the existing ILinearSolver (DenseLuSolver, or the sparse backend above the bus threshold) - the same solver seam the WLS estimator pivots on, so the linear PMU estimator inherits the validated linear algebra and its machine-epsilon behaviour. Because H is constant, the gain can be factored once and back-substituted each superframe (the natural real-time cadence); the design keeps a cached factorisation keyed by the sigma vector, invalidated when the observed-PMU set or sigma policy changes.

11.3 Output in the estimator's convention

Convert x_hat (rectangular, common reference) to (Vm, VaDeg) per bus: Vm_k = hypot(Vr_k, Vi_k), Va_k = atan2(Vi_k, Vr_k). Rotate all angles by the common offset so the datum bus matches the warm-start prior: Va_k <- Va_k - Va_hat(datum) + Va_prior(datum_bus). Emit an EstimationResult in the identical shape WlsStateEstimator produces (so replay/UI/export and ToPowerFlowResult work unchanged), with Iterations = 1, MaxStateUpdate = 0 (single shot), and residuals/chi-square computed against the same declared sigmas.

11.4 Observability and honesty

If the PMU set does not observe every state direction, H^T W H is singular; the estimator reports EstimationStatus.Unobservable (never NaN), exactly as the WLS estimator does on a singular gain - the reported state is the prior, not an estimate. This is what the hybrid scheduler uses to decide when the PMU-only fast path is trustworthy vs when to defer to the last SCADA state.


12. Hybrid multi-rate SCADA(~5 s) + PMU(~0.5 s) fusion scheduler

HybridMultiRateScheduler (Simulation/HybridMultiRateScheduler.cs) produces the IEnumerable<MeasurementSet> window stream that RealtimeEstimatorEngine.Run already consumes - so it plugs into the resident engine without changing it. It interleaves two cadences and threads one warm-start state through both, honouring the guard on every window.

12.1 Cadences and window construction

  • PMU tick every T_pmu (~0.5 s): drain the PDC of any newly-complete/expired PdcSuperframes, map each to a MeasurementSet (section 10) tagged with source "pmu", timestamp = superframe UTC.
  • SCADA tick every T_scada (~5 s, a multiple of T_pmu): pull the aligned SCADA measurement window (the existing GDA/SCADA row set) for that instant.

The scheduler emits windows in strict timestamp order. It supports two fusion modes (author-selected):

Mode A - single hybrid WLS (recommended default). At each SCADA tick, emit one combined MeasurementSet containing SCADA rows and the concurrent PMU rows (VmPu/VaDeg/IMagPu/IAngDeg), estimated in one nonlinear WlsStateEstimator solve. Between SCADA ticks, at each PMU tick emit a PMU-only window; the engine runs the linear PMU estimator on it (via a scheduler-selected estimator, section 12.2) for the PMU-observable buses, warm-started from the last full state so unobserved buses simply retain the prior. This gives full-network accuracy at 5 s and fast angle/observed-bus tracking at 0.5 s.

Mode B - two-stage / hierarchical. SCADA WLS produces the full state at 5 s; each PMU tick runs the linear estimator on the PMU island and corrects only those buses, leaving the rest at the SCADA state. Simpler, but the PMU update does not re-weight against SCADA rows; documented as the lighter option.

12.2 Estimator selection per window

The window carries a tag (MeasurementSet.Note or a scheduler side-channel) saying whether it is PMU-only or hybrid. The scheduler drives estimation by choosing the estimator per window: PMU-only -> LinearPmuStateEstimator; hybrid -> WlsStateEstimator with PMU + SCADA rows. Both are static filters; neither touches the DSE gate. (If a future variant wants the resident RealtimeEstimator- Engine to own the selection, extend it with an IStateEstimator seam - section 17 - rather than branching inside the engine.)

12.3 Warm-start threading and dropout fallback

Each converged estimate becomes the next window's warm-start prior (via ToPowerFlowResult), exactly as RealtimeEstimatorEngine already chains. The prior also supplies the angle anchor Va_prior(datum_bus) the mapper needs (section 10.1). If a PMU tick is Unobservable (dropouts), the scheduler does not emit a bad state: it carries the prior forward unchanged and marks the frame skipped, so the fast path degrades gracefully to "hold last state until the next SCADA solve".

12.4 Cadence, timestamps, and the no-future guarantee

Every emitted window's TakenUtc is a real measurement instant (a PDC slot or a SCADA instant), always <= the newest input frame's time - the scheduler never fabricates a future-dated window, and never interpolates ahead of data (it may hold the last state, which is a present/past claim, never a forward one). The 0.5 s "real-time" cadence is wall-clock pacing done by the host loop; the scheduler and engine process each window as a pure function of its (already- historical, guard-checked) contents, so the whole pipeline is deterministic and replay-testable. This is invariant #2 (no output stamped later than its newest input) and #4 (real-time proven on replay/permitted-age), realised in the scheduler.


13. Horizon guard integration and the guarded-seam registry

13.1 Where the guard is called

The synchrophasor pipeline introduces one new dated ingestion seam: PmuMeasurementSetMapper.Map, which calls ForwardInferenceGuard.RejectFuture(sf.TimeUtc, utcNow, "PMU superframe") before producing any MeasurementSet. Because the produced set carries TakenUtc = sf.TimeUtc, MeasurementSet.Load's existing guard also fires if the set is ever round-tripped through disk. Belt and braces: a PMU observation cannot reach an estimator without passing the horizon at least once, by construction.

The PDC itself (PhasorDataConcentrator) may additionally guard at slot emission as defence in depth (reject a superframe whose slot time is newer than the horizon), but the mapper is the canonical, tested seam.

13.2 Registry updates (must ship with the code)

The seam table of technical ch. 31 lists the guarded seams. Add PmuMeasurementSetMapper.Map (and, if implemented, the PDC emission guard) to that list. Add a per-seam test to RestrictionInvariantTests / ForwardInferenceGuardTests that feeds a superframe stamped UtcNow - 1 h and asserts ForwardInferenceException (the same shape as the existing GdaReplayLoopTests seam pin), and one stamped UtcNow - 200 h that passes.

13.3 DSE gate: explicitly not triggered

The linear PMU estimator and the hybrid scheduler consume no Dynamics/ process model - they are measurement-only filters. Per RestrictionReview.AssertPermitted, a method that does not use a dynamics model is permitted unconditionally, so no RestrictionReviewEntry is added and RestrictionReview.Reviewed is unchanged. The design note for reviewers: should anyone later add a PMU-rate recursive tracker (an EKF/UKF predicting between frames), that does fuse a process model, and section "How a new DSE method gets added" in the review log applies - a row plus a RestrictionReviewEntry before it may run. This design deliberately stops short of that line.


14. Determinism requirements

The whole pipeline is a pure function of (raw frame bytes, crosswalk, sigma policy, injected utcNow). No wall clock, no ambient culture, no floating-point nondeterminism beyond IEEE-754.

  • No wall-clock in the math path. utcNow is always injected (as RealtimeEstimatorOptions.UtcNow already is) so the guard boundary is fixed in tests. PDC slotting uses frame timestamps only; the watermark is the max observed slot, not real time.
  • Fixed iteration structure. The linear estimator is single-shot; the WLS path has its existing deterministic loop. No adaptive wait-window, no random tie-break in alignment (slot order is total; ties within a slot resolve by PMU config order).
  • Byte-exact parsing. Big-endian reads via BinaryPrimitives; polar->rect and int-scale conversions are fixed formulae; float32 read is exact IEEE-754. Given the same bytes, the parsed DataFrame is bit-identical across runs and machines.
  • Deterministic ordering. Measurement rows are authored in a fixed order (PMU config order, then phasor index, VmPu before VaDeg, IMagPu before IAngDeg), so the gain matrix assembly order - and thus the last-bit summation - is stable (the same bit-for-bit doctrine MeasurementModel already upholds).

15. Validation and test plan

All new tests live beside the existing suites in tests/GridSim.Tests. The bar is the project's: machine-epsilon cross-checks against an independent reference, and determinism.

15.1 Decoder conformance (independent reference vectors)

  • Reference frame vectors. Decode CONFIG-2 and DATA byte vectors taken from an independent encoder (IEEE C37.118.2 Annex examples and/or an openPDC / pypmu capture checked into data/synchrophasor/). Assert every parsed field matches the reference to the bit (int fields exactly; float fields exactly, since the bytes are exact IEEE-754). This is the independent cross-check that the decoder is standard-faithful, not self-consistent.
  • CRC. Cross-check C37118Crc.Compute against the CHK embedded in every reference frame, and cross-check the fast table-driven form (if used) against the bitwise form over 10k random buffers - byte-exact.
  • Format matrix. One decode test per FORMAT combination (int/float x rect/polar, int/float freq), asserting the same engineering phasor within rounding for int forms and exactly for float forms.
  • Timestamp. SOC/FRACSEC -> UTC checked against hand-computed instants for several TIME_BASE values; assert no double-rounding drift (ticks form).
  • Resilience. Truncated frame, wrong CRC, DATA-before-CONFIG, unsupported frame type each yield the correct FrameDecodeStatus and never throw.

15.2 Encode->decode->estimate round-trip (machine epsilon)

The end-to-end truth test. Take a solved PowerFlowResult on a small case (case9 / case14). Synthesise a C37.118 DATA frame whose voltage phasors are the solved bus voltages and whose current phasors are the solved branch currents (computed from the same Y-bus stamps), with a chosen TIME_BASE/FORMAT. Decode it, concentrate it, map it (section 10). Then:

  • Linear PMU estimator on a fully-PMU-observed case must recover the solved state to ~1e-9 (the analogue of the existing Voltage_only_pmu_set_recovers_the_state_exactly, extended to include current phasors). This is the machine-epsilon cross-check.
  • Hybrid WLS with the same PMU rows plus a redundant SCADA row set must recover the same state to solver tolerance, and the residuals of the exact rows must be ~0.
  • Cross-estimator agreement. On a case observable by both the linear PMU estimator and the nonlinear WLS (PMU rows fed to WlsStateEstimator via the new IAngDeg/IMagPu rows), the two estimates must agree to ~1e-8 - an independent numerical cross-check of the new Jacobian against the linear formulation.

15.3 New Jacobian correctness (IAngDeg)

Finite-difference h_IAngDeg(x) against the analytic Jacobian row (section 10.2) at several random feasible states on case14/case118; assert max abs error <~1e-6 (central differences), matching how the other measurement-kind Jacobians are pinned. Also assert StructuralColumns(IAngDeg) exactly equals the columns the analytic row writes (no missing/extra structural entry - the sparse backend depends on it).

15.4 PDC alignment determinism

  • Feed the same multiset of decoded frames to PhasorDataConcentrator in several shuffled arrival orders; assert byte-identical PdcSuperframe sequences.
  • Drop one PMU for a slot; assert the slot emits at window close with that PMU Dropped and the rest Present, and that a late straggler for an already- emitted slot is counted and discarded (no out-of-order emission).
  • Assert emitted superframe timestamps are strictly increasing.

15.5 Restriction invariants

  • A superframe stamped UtcNow - 1 h fed to PmuMeasurementSetMapper.Map throws ForwardInferenceException; one at UtcNow - 200 h maps cleanly. (New rows in ForwardInferenceGuardTests / RestrictionInvariantTests, section 13.2.)
  • RealtimeEstimatorEngine.Run over a HybridMultiRateScheduler window stream containing one too-fresh window records it as WindowsRejectedFresh and never estimates it (reuses the engine's existing behaviour - assert the summary).
  • Assert no emitted RealtimeEstimateFrame.StateTimeUtc exceeds the newest input frame time (invariant #2).
  • Assert RestrictionReview.Reviewed is unchanged (the static-filter methods add no DSE entry) and that RestrictionInvariantTests still passes green.

15.6 Determinism regression

Run the full replay pipeline twice with a fixed utcNow; assert bit-identical EstimationResults (Vm, VaDeg, ObjectiveJ) across runs.


16. 0-warning build gate compliance

The new code compiles clean under the project's warnings-as-errors gate:

  • Nullable reference types enabled and honoured; the decode outcome uses the DecodeResult/FrameDecodeStatus struct rather than nullable returns for the hot path, and PmuData? Data on a dropped slot is explicitly nullable and null-checked at every use.
  • XML docs on every public member (types, records, enum members, public methods) - the decoder, PDC, mapper, estimator and scheduler all expose only documented public surface; internals are internal.
  • No unsafe, no BitConverter for multi-byte reads - BinaryPrimitives big-endian readers only, so there is no host-endianness or alignment warning surface.
  • Culture-invariant parsing/formatting; ASCII station/channel names decoded with an explicit encoding.
  • No unused usings, no unreachable arms; the FORMAT/kind switches are exhaustive with an explicit default that throws InvalidOperationException naming the unhandled case (the pattern MeasurementModel uses).
  • No analyser suppressions introduced; if a span-based parser trips a CA1062/CA1031-style rule, the code is restructured, not suppressed.
  • Deterministic, allocation-conscious parsing (ReadOnlySpan<byte>, stackalloc for small fixed buffers) so no perf-analyser noise.

The design adds no dependency: C37.118 is decoded with the BCL (System.Buffers.Binary, System.Numerics for phasors) only - no external NuGet, consistent with the self-contained core.


17. Seams to extend (future work, explicitly deferred)

  • CONFIG-3 (fractional scaling, long names, baseline PMU coordinates): decode path parallels CONFIG-2; C37118Decoder already discriminates the type and rejects it cleanly, so support drops in behind the same interface.
  • Command channel / live socket source: IPmuFrameSource has a socket implementation shape; it remains guard-bounded (cannot deliver processable live frames). A CMD-frame request enum is documented but GridSim never drives a live device - it replays captures.
  • Full 2x2 phasor covariance (magnitude/angle correlation) instead of two scalar sigmas: needs a block-weighted WLS row; a documented refinement of the sigma policy, not a change to the mapping.
  • Rectangular current-phasor kinds (IRePu/IImPu) as an alternative to IMagPu+IAngDeg for better conditioning near zero flow: an additive measurement-kind option, same kernel reuse.
  • IStateEstimator seam so RealtimeEstimatorEngine can own linear-vs-WLS selection internally rather than the scheduler choosing; a clean refactor when a third estimator (e.g. branch-current DSSE) arrives.
  • PMU-rate recursive tracker (EKF/UKF): the moment a predict step integrates a process model this becomes a Dynamics->Estimation fusion - it must go through the review-log gate (section 13.3) before it can run.

18. Implementation checklist (order of work)

  1. C37118Crc + CRC tests against reference frames.
  2. C37118CommonHeader, C37118FrameType, C37118DataFormat, SOC/FRACSEC->UTC + tests.
  3. ConfigFrame2 decode (C37118Decoder config path) + config-vector tests.
  4. DataFrame/PmuData/Phasor/PmuStatus decode (all four FORMAT combos) + format-matrix tests.
  5. PhasorDataConcentrator + PdcSuperframe + alignment/determinism/dropout tests.
  6. MeasurementKind.IAngDeg + MeasurementModel h/Jacobian/StructuralColumns arms
  7. Assemble residual arm + finite-difference Jacobian test.
  8. PmuStreamConfig/PmuMeasurementSetMapper (with the guard call) + mapping and guard-seam tests; update the seam table of technical ch. 31.
  9. LinearPmuStateEstimator + machine-epsilon recovery and cross-estimator agreement tests.
  10. HybridMultiRateScheduler + end-to-end round-trip and no-future invariant tests over RealtimeEstimatorEngine.
  11. FileReplayPmuFrameSource + a small checked-in capture for the round-trip replay test.

Each step lands with its tests green and the 0-warning gate intact before the next begins.