13. Battery storage studies

A battery storage study answers one question: if a battery of this chemistry, power and energy were connected at this bus, what would it do over a day of demand, and what would that cost the battery? GridSim carries each site through a time series. State of charge, cell temperature and ageing persist from step to step, a dispatch policy decides what the site is asked to do, the chemistry model decides what it can actually deliver, and the delivered power is injected into the network before the AC power flow is solved. The report gives, for every site, the power it delivered at each step, the state of charge and temperature it ended each step at, which limit stopped it, the energy it moved, the balance-of-plant energy it drew, its round-trip efficiency, and how much capacity it aged. It gives, for the network, the slack-bus power and the lowest bus voltage at each step.

Two verbs take a battery. gridsim chain runs the study on a case under a synthetic or ramped load, and is the verb for sizing and comparing sites (the verb itself is in ch. 11). gridsim gda-replay adds the same battery to a replayed day of recorded demand, and tags the result COUNTERFACTUAL (see ch. 22). Both build the site from the same --bess specification and report it with the same summary lines. The model behind them (cell equivalent circuit, pack, ageing, dispatch) is in technical ch. 27.

Before you start

  • A case that loads. The examples use case9 (three generators, nine buses, 315 MW peak demand), whose bus numbers run 1 to 9. A site on a bus that is not in the case is refused.
  • A site specification, chemistry:bus:MW:MWh with an optional fifth field for the starting state of charge. lfp:5:5:10 is an LFP battery at bus 5, rated 5 MW, holding 10 MWh.
  • Nothing else. With no policy given, chain runs the peak-shave policy with thresholds derived from the case's peak demand.

The chemistry presets are representative cells, tagged CuratedPlaceholder with a [VERIFY] note, and every chain report prints that reminder on its second line (the gda-replay console output does not). Use them to compare chemistries and exercise a study. Replace them with a datasheet before quoting a result for a real asset. Technical ch. 27 owns that description.

Worked example

A 5 MW / 10 MWh LFP battery at bus 5 of case9, over a 24 h demand day in six 4 h steps, shaving the peak:

gridsim chain case9 --mode daily --steps 6 --bess lfp:5:5:10 --policy peak-shave
$ gridsim chain case9 --mode daily --steps 6 --bess lfp:5:5:10 --policy peak-shave
GridSim - storage time series  *  case9  *  6 x 4 h  *  mode=daily  *  policy=peak-shave
prices: none.  Chemistry presets are CuratedPlaceholder [VERIFY] (representative cells).

...
|---:|---:|---:|---:|---:|---|---:|---:|:-:|
| 0 | 0.0 | 0.700 | 220 | - |     0.0 / 0.500 / 25.0 | 49 | 1.024 | y |
| 1 | 4.0 | 0.600 | 189 | - |    -1.3 / 0.950 / 29.4 (SoC ceiling) | 43 | 1.025 | y |
| 2 | 8.0 | 0.700 | 220 | - |     0.0 / 0.950 / 28.6 | 49 | 1.024 | y |
| 3 | 12.0 | 0.900 | 283 | - |     0.0 / 0.950 / 28.0 | 64 | 1.005 | y |
| 4 | 16.0 | 1.000 | 315 | - |     2.4 / 0.050 / 29.6 (SoC floor) | 69 | 0.996 | y |
| 5 | 20.0 | 0.900 | 284 | - |     0.0 / 0.050 / 28.8 | 64 | 1.005 | y |

LFP 5MW/10MWh @5: out 9.7 MWh, in 5.3 MWh, aux 0.27 MWh, stored change -5.0 MWh, round trip 93.5 %, 0.75 equivalent full cycles
    ageing over the run: calendar 0.1372 %, cycle 0.0026 % (rainflow, depth-aware: 0.0020 %), deepest cycle 90 % SoC
[chain] done -> results\chain-storage-case9.md
[exit 0]

The report holds no timings and has no clock or random input, so the same command prints the same numbers run to run on one machine; no test compares a run across CPUs. The [chain] done line goes to standard error and names the report file.

What happened. The case's peak demand is 315 MW, so the default thresholds are 283.5 MW (90 %) to discharge above and 220.5 MW (70 %) to recharge below. Step 0 demand is exactly the 220.5 MW low threshold and the comparison is strict, so the battery is asked for nothing. Step 3 demand is 283.5 MW to the printed precision but one unit in the last place below the high threshold, so the battery is asked for nothing there too. At step 1 the demand is 189 MW, the battery is asked for the full 5 MW of recharge, and it stops at the SoC window ceiling: the mean over the 4 h step is 1.3 MW (the column shows it as -1.3, negative for charging), and the state of charge goes from 0.500 to 0.950. At step 4 the demand is 315 MW, the battery is asked for 5 MW and the SoC window floor stops it after a mean 2.4 MW, leaving 0.050. The slack bus falls from 72 MW with the battery idle at that load (see gridsim chain case9 --steps 3 --bess lfp:5:5:10 --policy idle, below) to 69 MW at step 4 (both rounded to whole MW). The battery moved 9.7 MWh out and 5.3 MWh in, finished 5.0 MWh down on the energy it started with, and returned 93.5 % through the round trip.

Reading the output

The report is a header, one table row per step, then a summary per site. The same text is written to a Markdown file.

Title line. GridSim - storage time series * case9 * 6 x 4 h * mode=daily * policy=peak-shave gives the case, the number of steps, the step length in hours, the load mode and the dispatch policy in force.

Prices line. prices: none., prices: Synthetic GB-shaped price day (not a market record). or prices: file <name>., followed by the reminder that the chemistry presets are CuratedPlaceholder [VERIFY] cells.

Step table. One row per step. The table has one column group per site, in the order the --bess flags were given.

Column Meaning
Step Step index from 0.
Hour Hour of day at the start of the step. Step index times the step length, wrapped at 24.
Load x The demand multiplier applied to every load this step. fixed is 1.000 throughout, ramp adds --ramp-pct percent per step, daily follows the 24 h demand curve (0.600 at 04:00, 1.000 at 16:00).
Demand MW Total system demand at that multiplier, before any battery auxiliary load.
Price The step's price in GBP/MWh, or - when there is no price series (see Policies).
Site column <chemistry> <MW>MW/<MWh>MWh @<bus>: MW / SoC / T deg C. Three values per step, described below.
Slack MW Real power the slack bus generates once the battery is in the case. It falls when the battery discharges and rises when it charges.
Vmin Lowest bus voltage of the solved step, in per-unit. - when the step did not converge, and so is Slack MW: such a step has no solved state.
Conv y if the power flow converged, N if not.

The site column reads MW / SoC / T, for example -1.3 / 0.950 / 29.4 (SoC ceiling).

  • MW is the AC power the site delivered to the bus, averaged over the step. Positive is discharge, negative is charge. It is after the converter, whose one-way efficiency is 0.98. A value of -0.0 is a small charge that rounds to zero (the battery is full and only self-discharge acts).
  • SoC is the state of charge at the end of the step, as a fraction of the cell's present capacity, so it already reflects fade. The window each chemistry may use is in the chemistry table.
  • T is the cell temperature at the end of the step in degrees Celsius (the header reads T deg C). The pack starts at an ambient of 25 C, heats under load, and sheds heat to ambient and to its cooling system.
  • The bracket, when present, names the first limit that stopped the site delivering what was asked at any point inside the step. The values are SoC floor, SoC ceiling, current limit (the chemistry's continuous C-rate), cut-off voltage, charge voltage, temperature derate, too cold to charge and maximum power transfer (the point beyond which no current delivers more power). No bracket means the request was met.

Each step is solved in 30 sub-steps inside the chemistry model, so a step that starts with room in the SoC window and ends at its edge is reported against the edge and delivers a lower mean power, as in step 4 above.

Summary lines. Two lines per site, after the table.

LFP 5MW/10MWh @5: out 9.7 MWh, in 5.3 MWh, aux 0.27 MWh, stored change -5.0 MWh, round trip 93.5 %, 0.75 equivalent full cycles
    ageing over the run: calendar 0.1372 %, cycle 0.0026 % (rainflow, depth-aware: 0.0020 %), deepest cycle 90 % SoC
  • out and in are the AC energy the site delivered and absorbed over the run, in MWh. out sums the positive deliveries and in the negative ones, each times the step length.
  • aux is the balance-of-plant energy the site drew from the grid, in MWh: a standby load (0.2 % of the rated MW for lithium chemistries, 0.1 % for lead-acid, 0.3 % for the flow battery), plus cooling when the cells exceed the chemistry's setpoint (heat removed divided by a coefficient of performance of 3.0, lithium chemistries only), plus the electrolyte pumps of a flow battery (4 % of the power moved). It is added to the site's bus as demand, and it is why an idle battery still shows an aux figure.
  • stored change is the energy above the SoC floor at the end less at the start, in MWh, at the nominal pack voltage and the present capacity, printed with its sign. Negative means the battery finished emptier than it began. A change that rounds to zero (self-discharge on an idle battery) prints +0.0.
  • round trip is (out + max(0, change)) / (in + max(0, -change)), which credits the net change in stored energy so that a run that ends empty or full is not flattered or penalised. Auxiliary energy is not in it. It prints - when in is below 1e-9 MWh, because a run that only discharges has no round trip.
  • equivalent full cycles is (out + in) / (2 x nominal pack energy). The nominal energy is the pack as sized (see Pitfalls), not the energy you asked for.
  • calendar is the capacity lost to time, in percent, following the square root of elapsed time at the cell's temperature and state of charge. One day is sqrt(1/365), 5.2 %, of a year's calendar fade at constant stress, so a one-day figure cannot be scaled linearly (LFP: 0.1369 % over the captured day, against 0.001 x sqrt(365) = 1.91 % for a year at 25 C and 50 % SoC).
  • cycle is the capacity lost to throughput, in percent: 20 % over the chemistry's N80 equivalent full cycles, scaled by temperature and C-rate.
  • rainflow, depth-aware is the cycle fade recomputed from the SoC trace with ASTM E1049-85 rainflow counting, each counted cycle costing (0.2 / N80) x depth^beta, so many shallow cycles age a cell less than one deep one.
  • deepest cycle is the depth of the largest rainflow cycle as a percentage of full SoC. 90 % is the whole LFP window (0.05 to 0.95).

Total fade is capped at 80 %, and the fade feeds back into the cell: capacity falls and resistance rises with it, so a long run delivers less than a short one.

Footer. WARNING: N step(s) did not converge. appears after the summary when any step failed, and the exit code is 3. The [chain] done -> <path> line names the Markdown report on standard error.

Files. chain writes results/chain-storage-<case>.md and, beside it, a CSV of the same run. --out <path> moves both (the CSV takes the same name with a .csv extension). The CSV carries every number to six significant figures, with NaN as an empty field, the fade as a fraction and the voltage extremes and losses the table omits:

$ head -4 results/bess-demo.csv
step,hour,load_factor,demand_mw,price,s0_request_mw,s0_delivered_mw,s0_aux_mw,s0_soc,s0_temp_c,s0_fade,s0_limited,slack_mw,vmin,vmax,loss_mw,converged
0,0,0.7,220.5,,0,0,0.01,0.499833,25,0.000408227,0,49.0992,1.02356,1.04076,2.18915,1
1,4,0.6,189,,-5,-1.32387,0.0109119,0.949994,29.3712,0.000796927,1,43.1443,1.025,1.04385,1.60956,1
2,8,0.7,220.5,,0,0,0.01,0.949828,28.5984,0.0010474,0,49.0992,1.02356,1.04076,2.18915,1
[exit 0]

There are seven columns per site, numbered s0, s1, ... in --bess order: request_mw (what the policy asked for), delivered_mw (what the pack gave), aux_mw, soc, temp_c, fade (total capacity fade as a fraction, so 0.000796927 is 0.0797 %) and limited (1 if a limit bound). After them come slack_mw, vmin, vmax, loss_mw (total network loss) and converged. In step 1 above the request is -5 MW and the delivery -1.32 MW, with limited 1: the policy asked for a full-rate recharge and the SoC ceiling cut it.

Variations

The six chemistries

--bess takes one of six chemistries, matched case-insensitively. The aliases are sodium-ion, naion and sib for na-ion, flow and vanadium for vrfb, and lead and vrla for lead-acid.

Chemistry What distinguishes it Cell (Ah) Nominal V Max C (discharge / charge) SoC window Cycles to 80 % (N80) Calendar fade (per sqrt day)
lfp Flat voltage plateau, thermally robust, the long-life lithium choice for 1C-class duty 280 3.29 1.0 / 0.5 5 - 95 % 6000 0.0010
nmc Higher voltage and power capability than LFP, shorter life, more temperature-sensitive 64 3.78 2.0 / 1.0 5 - 95 % 3500 0.0016
lto Very high rate (fast response duty), very long life, charges down to -20 C, lowest energy density 30 2.30 6.0 / 6.0 3 - 97 % 20000 0.0005
na-ion LFP-like energy, keeps more power in the cold, life still maturing 160 3.10 2.0 / 1.0 3 - 97 % 4000 0.0014
vrfb Vanadium flow: energy set by the tank, slow, pumps are a real load, lowest cycle fade (0.0006 % over the daily run below), CRateSensitivity 0 1000 (tank share) 1.40 0.25 / 0.25 15 - 85 % 20000 0.0002
lead-acid Valve-regulated lead-acid: strong rate effect, 90 % coulombic efficiency, short life at depth 1000 2.04 0.3 / 0.2 20 - 98 % 1200 0.0025

Nominal V is the open-circuit voltage at 50 % SoC. The C-rate is the BMS continuous limit as a multiple of the cell's Ah capacity, per cell, so the pack limit is that current times the parallel strings at the pack voltage. The 10 MWh LFP pack (304 x 40 cells, 280 Ah each) has a limit of 280 A per cell at discharge and 140 A at charge, which is 11.2 MW and 5.6 MW at the nominal 1000 V before sag, so the 5 MW rating applies. The effective power of a site is the lower of its MW rating and the pack's limit: a 2 MW / 4 MWh lead-acid site (490 x 5 cells, 1000 Ah each) has a 0.3C limit of 300 A per cell, which is 1.4 MW AC at 0.5 SoC. The report shows (current limit) and the first step of the capture below averages 1.3 MW. The full constants (open-circuit curves, impedances, time constants, thermal data, activation energies, auxiliary load) are in technical ch. 27.

The same 5 MW / 10 MWh site at bus 5 of case9, run through the same 24 h demand day in twelve 2 h steps under the default peak-shave thresholds, gives the comparison below (one capture per chemistry in docs/_captures/bess/, for example gridsim chain case9 --mode daily --steps 12 --bess vrfb:5:5:10):

Chemistry out MWh in MWh aux MWh Round trip Calendar fade Cycle fade Rainflow fade Deepest cycle
lfp 9.6 5.3 0.27 93.3 % 0.1369 % 0.0026 % 0.0020 % 90 %
nmc 9.6 5.4 0.28 93.3 % 0.1980 % 0.0043 % 0.0035 % 90 %
lto 9.8 5.3 0.24 94.6 % 0.0558 % 0.0007 % 0.0006 % 94 %
na-ion 9.5 5.6 0.32 90.1 % 0.1894 % 0.0042 % 0.0032 % 94 %
vrfb 7.6 6.1 0.91 68.9 % 0.0259 % 0.0006 % 0.0004 % 70 %
lead-acid 7.7 7.7 0.12 66.6 % 0.4087 % 0.0124 % 0.0082 % 78 %

Read it as the chemistries behave. LTO returns the most. The flow battery ages the least in all three fade columns and lead-acid the most. NMC matches LFP on round trip but fades 1.45 times faster by calendar and 1.65 times faster by cycle in this run. The flow battery and lead-acid return two thirds of what they absorb: the flow battery because its pumps draw 0.91 MWh and its power is capped well below the rating (maximum power transfer at 2.3 MW and 1.5 MW), lead-acid because its resistance and 90 % coulombic efficiency lose energy at rate and its 0.3C limit shows as current limit. Lead-acid also ends with a smaller stored change (-3.9 MWh against -5.0 MWh) because its SoC floor is 0.2: the battery holds only 3.9 MWh above the floor at the start, and it reaches the floor at step 8. The flow battery's -4.9 MWh follows from its 0.15 floor in the same way.

A single-chemistry run with the sodium-ion preset, for a short fixed-load case, is a second look at a site that is discharge-limited by its SoC floor rather than its rate:

$ gridsim chain case9 --steps 4 --bess na-ion:5:8:15
GridSim - storage time series  *  case9  *  4 x 0.5 h  *  mode=fixed  *  policy=peak-shave
prices: none.  Chemistry presets are CuratedPlaceholder [VERIFY] (representative cells).

...
|---:|---:|---:|---:|---:|---|---:|---:|:-:|
| 0 | 0.0 | 1.000 | 315 | - |     8.0 / 0.228 / 29.8 | 64 | 0.996 | y |
| 1 | 0.5 | 1.000 | 315 | - |     5.2 / 0.030 / 30.0 (SoC floor) | 66 | 0.996 | y |
| 2 | 1.0 | 1.000 | 315 | - |     0.0 / 0.030 / 29.8 (SoC floor) | 72 | 0.996 | y |
| 3 | 1.5 | 1.000 | 315 | - |     0.0 / 0.030 / 29.7 (SoC floor) | 72 | 0.996 | y |

Na-ion 8MW/15MWh @5: out 6.6 MWh, in 0.0 MWh, aux 0.07 MWh, stored change -7.5 MWh, round trip -, 0.22 equivalent full cycles
    ageing over the run: calendar 0.0414 %, cycle 0.0013 % (rainflow, depth-aware: 0.0009 %), deepest cycle 47 % SoC
[chain] done -> results\chain-storage-case9.md
[exit 0]

Here the demand is 315 MW at every step (fixed mode). The 8 MW battery delivers its full rating in step 0, runs into the SoC floor of 0.030 partway through step 1 (mean 5.2 MW), and delivers nothing afterwards. With no charge phase there is no round trip, so that field prints -. The cells heat to 30.0 C, the sodium-ion cooling setpoint, and the cooling load is part of the aux figure.

Policies

--policy selects the dispatch rule. Without it chain runs peak-shave. Every site in the run uses the same policy. The policy states what the site is asked for each step, in MW, discharge positive, capped at the site's rating; the chemistry then decides what is delivered.

idle. Request 0 MW. The site self-discharges and draws its standby load, so it is the baseline for what the battery costs by existing:

$ gridsim chain case9 --steps 3 --bess lfp:5:5:10 --policy idle
GridSim - storage time series  *  case9  *  3 x 0.5 h  *  mode=fixed  *  policy=idle
prices: none.  Chemistry presets are CuratedPlaceholder [VERIFY] (representative cells).

...
|---:|---:|---:|---:|---:|---|---:|---:|:-:|
| 0 | 0.0 | 1.000 | 315 | - |     0.0 / 0.500 / 25.0 | 72 | 0.996 | y |
| 1 | 0.5 | 1.000 | 315 | - |     0.0 / 0.500 / 25.0 | 72 | 0.996 | y |
| 2 | 1.0 | 1.000 | 315 | - |     0.0 / 0.500 / 25.0 | 72 | 0.996 | y |

LFP 5MW/10MWh @5: out 0.0 MWh, in 0.0 MWh, aux 0.02 MWh, stored change +0.0 MWh, round trip -, 0.00 equivalent full cycles
    ageing over the run: calendar 0.0250 %, cycle 0.0000 % (rainflow, depth-aware: 0.0000 %), deepest cycle 0 % SoC
[chain] done -> results\chain-storage-case9.md
[exit 0]

The SoC stays at 0.500, the site draws 0.015 MWh of standby power over 1.5 h (0.01 MW, printed 0.02), and the calendar fade is 0.0250 %, which is 0.001 x sqrt(1.5 / 24) as a percentage: calendar fade follows the square root of time.

peak-shave. Request the demand above a high threshold as discharge, and the headroom below a low threshold as charge, each capped at the rating: demand > high asks for min(rating, demand - high), demand < low asks for -min(rating, low - demand), anything between asks for nothing. The thresholds default to 90 % and 70 % of the peak demand of the run (the case's total load times the largest load multiplier). --shave-high MW and --shave-low MW set them in absolute MW:

gridsim chain case9 --mode daily --steps 6 --bess lfp:5:5:10 --policy peak-shave --shave-high 250 --shave-low 200
$ gridsim chain case9 --mode daily --steps 6 --bess lfp:5:5:10 --policy peak-shave --shave-high 250 --shave-low 200
GridSim - storage time series  *  case9  *  6 x 4 h  *  mode=daily  *  policy=peak-shave
prices: none.  Chemistry presets are CuratedPlaceholder [VERIFY] (representative cells).

...
|---:|---:|---:|---:|---:|---|---:|---:|:-:|
| 0 | 0.0 | 0.700 | 220 | - |     0.0 / 0.500 / 25.0 | 49 | 1.024 | y |
| 1 | 4.0 | 0.600 | 189 | - |    -1.3 / 0.950 / 29.4 (SoC ceiling) | 43 | 1.025 | y |
| 2 | 8.0 | 0.700 | 220 | - |     0.0 / 0.950 / 28.6 | 49 | 1.024 | y |
| 3 | 12.0 | 0.900 | 283 | - |     2.4 / 0.050 / 29.6 (SoC floor) | 62 | 1.005 | y |
| 4 | 16.0 | 1.000 | 315 | - |     0.0 / 0.050 / 28.8 (SoC floor) | 72 | 0.996 | y |
| 5 | 20.0 | 0.900 | 284 | - |     0.0 / 0.050 / 28.1 (SoC floor) | 64 | 1.005 | y |

LFP 5MW/10MWh @5: out 9.7 MWh, in 5.3 MWh, aux 0.28 MWh, stored change -5.0 MWh, round trip 93.5 %, 0.75 equivalent full cycles
    ageing over the run: calendar 0.1269 %, cycle 0.0026 % (rainflow, depth-aware: 0.0020 %), deepest cycle 90 % SoC
[chain] done -> results\chain-storage-case9.md
[exit 0]

With the high threshold at 250 MW the battery discharges at step 3 (demand 283 MW) and is empty before the true peak at step 4. The slack is 62 MW at step 3 against 64 MW in the default run, and 72 MW at the 315 MW peak in step 4 against 69 MW. A lower threshold draws the battery down earlier, so the thresholds, and not only the size of the battery, decide whether it is available at the peak.

hold. Response holding. The site keeps its state of charge near 0.5 so that it stays ready to deliver a frequency-response service in either direction: above 0.55 it discharges at 20 % of its rating, below 0.45 it charges at 20 % of its rating, inside the band it does nothing. The target 0.5, the band 0.05 and the 20 % are fixed. Start the site away from 0.5 to see it trickle back:

gridsim chain case9 --mode daily --steps 6 --bess nmc:5:5:10:0.75 --policy hold
$ gridsim chain case9 --mode daily --steps 6 --bess nmc:5:5:10:0.75 --policy hold
GridSim - storage time series  *  case9  *  6 x 4 h  *  mode=daily  *  policy=hold
prices: none.  Chemistry presets are CuratedPlaceholder [VERIFY] (representative cells).

...
|---:|---:|---:|---:|---:|---|---:|---:|:-:|
| 0 | 0.0 | 0.700 | 220 | - |     1.0 / 0.384 / 23.7 | 48 | 1.024 | y |
| 1 | 4.0 | 0.600 | 189 | - |    -1.0 / 0.734 / 27.3 | 43 | 1.025 | y |
| 2 | 8.0 | 0.700 | 220 | - |     1.0 / 0.367 / 25.3 | 48 | 1.024 | y |
| 3 | 12.0 | 0.900 | 283 | - |    -1.0 / 0.718 / 28.0 | 65 | 1.005 | y |
| 4 | 16.0 | 1.000 | 315 | - |     1.0 / 0.349 / 25.7 | 71 | 0.996 | y |
| 5 | 20.0 | 0.900 | 284 | - |    -1.0 / 0.701 / 28.0 | 65 | 1.005 | y |

NMC 5MW/10MWh @5: out 12.0 MWh, in 12.0 MWh, aux 0.24 MWh, stored change -0.5 MWh, round trip 95.6 %, 1.20 equivalent full cycles
    ageing over the run: calendar 0.1823 %, cycle 0.0065 % (rainflow, depth-aware: 0.0045 %), deepest cycle 40 % SoC
[chain] done -> results\chain-storage-case9.md
[exit 0]

The policy reads the SoC at the start of each step. The site starts at 0.750, above the band, so it discharges 1.0 MW (20 % of 5 MW) for the whole 4 h step and ends at 0.384. That is below the band, so the next step charges at 1.0 MW and ends at 0.734, and the SoC swings in a sawtooth either side of the band. A 4 h step moves the SoC 0.35, far more than the 0.10 band is wide, so it never settles. A step of 0.5 h moves it 0.04 and does. The policy does not deliver the response service. It keeps the SoC where a service could be delivered.

price. The price-threshold policy charges at full rating when the price is at or below --buy-below (default 40 GBP/MWh) and discharges at full rating when it is at or above --sell-above (default 90 GBP/MWh), and holds in between. It acts on a price series, so it needs --prices; without one it exits 2 with --policy price needs --prices (a price series): without one it never charges or discharges.

lp. The optimal-schedule policy plans the whole run as one storage schedule linear programme over the price series, with --degradation-gbp-per-mwh (default 0) as the cost of each MWh of throughput, then runs the schedule through the cell model step by step. It is the default policy when --prices is given. Without prices it exits 2 (--policy lp needs --prices); a schedule LP that does not solve to an optimum exits 3 and no schedule runs.

--prices synthetic|<file>. The price series, in GBP/MWh, one value per step:

gridsim chain case9 --mode daily --steps 6 --bess nmc:5:5:10 --policy price --prices synthetic
gridsim chain case9 --mode daily --steps 6 --bess nmc:5:5:10 --prices synthetic

synthetic is the labelled synthetic GB-shaped price day (SyntheticPrices.GbDay, sampled at the start of each step); it is not a market record, and the prices line says prices: Synthetic GB-shaped price day (not a market record). A file holds one price per line, or CSV lines whose last field is the price; blank lines and lines starting with # are skipped, values use . as the decimal point and may be negative, and the prices line reads prices: file <name>. Fewer values than steps exits 1; more is allowed, the first --steps are used and a note: on standard error says how many were not. A file that is missing, unreadable or holds a value that is not a number exits 1, naming the file and the line. With a price series the Price column holds each step's price and each site's summary line ends with revenue GBP <n>, the value of the energy it traded at the step prices.

The storage flags (--prices, --policy, --shave-high, --shave-low, --buy-below, --sell-above, --degradation-gbp-per-mwh, --step-hours) need at least one --bess; on plain chain each exits 2.

Several sites

Repeat --bess for each site. Each site has its own chemistry, bus, rating, starting state, SoC, temperature and ageing, and its own column in the table and its own summary lines. All sites share the verb's single policy and thresholds. Two sites at the same bus are allowed and add.

gridsim chain case9 --steps 3 --bess lead-acid:3:2:4 --bess lfp:5:5:10
$ gridsim chain case9 --steps 3 --bess lead-acid:3:2:4 --bess lfp:5:5:10
GridSim - storage time series  *  case9  *  3 x 0.5 h  *  mode=fixed  *  policy=peak-shave
prices: none.  Chemistry presets are CuratedPlaceholder [VERIFY] (representative cells).

...
|---:|---:|---:|---:|---:|---|---|---:|---:|:-:|
| 0 | 0.0 | 1.000 | 315 | - |     1.3 / 0.323 / 27.0 (current limit) |     5.0 / 0.266 / 26.9 | 65 | 0.995 | y |
| 1 | 0.5 | 1.000 | 315 | - |     0.9 / 0.200 / 28.8 (current limit) |     4.5 / 0.050 / 29.0 (SoC floor) | 66 | 0.996 | y |
| 2 | 1.0 | 1.000 | 315 | - |     0.0 / 0.200 / 28.8 (SoC floor) |     0.0 / 0.050 / 28.9 (SoC floor) | 72 | 0.996 | y |

Lead-acid 2MW/4MWh @3: out 1.1 MWh, in 0.0 MWh, aux 0.00 MWh, stored change -1.5 MWh, round trip -, 0.14 equivalent full cycles
    ageing over the run: calendar 0.0646 %, cycle 0.0023 % (rainflow, depth-aware: 0.0012 %), deepest cycle 30 % SoC
LFP 5MW/10MWh @5: out 4.7 MWh, in 0.0 MWh, aux 0.02 MWh, stored change -5.0 MWh, round trip -, 0.24 equivalent full cycles
    ageing over the run: calendar 0.0241 %, cycle 0.0008 % (rainflow, depth-aware: 0.0006 %), deepest cycle 45 % SoC
[chain] done -> results\chain-storage-case9.md
[exit 0]

The lead-acid site at bus 3 is held to a mean 1.3 MW by its 0.3C limit in step 0 (current limit) and again at 0.9 MW in step 1, and is at its SoC floor of 0.200 from step 1 onward. The LFP site at bus 5 delivers its full 5.0 MW in step 0, then reaches its SoC floor of 0.050 in step 1. Both sites then sit at their floors and the slack climbs back to 72 MW. Each site's summary is reported separately. Sites are compared by reading their two lines each.

Replaying recorded demand: gda-replay

gridsim gda-replay accepts --bess and --policy with the same site syntax. It adds the battery to a day of recorded demand and reports what the battery would have done, with the hypothetical status in the output:

gridsim gda-replay --synth --case case9 --bess lfp:5:5:10 --out results/bess-day
$ gridsim gda-replay --synth --case case9 --bess lfp:5:5:10 --out results/bess-day

=== Historical state estimate: case9 over synthetic-case9 ===
  reconstructed 48 timestamps  (2024-01-01T00:00:00.0000000Z .. 2024-01-01T23:30:00.0000000Z)
  non-converged: 0
  system loss over the series: 1.6 .. 4.6 MW
  COUNTERFACTUAL (Counterfactual): hypothetical storage on recorded history - not a reconstruction.
  LFP 5MW/10MWh @5: out 9.6 MWh, in 5.3 MWh, aux 0.27 MWh, stored change -5.0 MWh, round trip 93.1 %, 0.75 equivalent full cycles
      ageing over the run: calendar 0.1365 %, cycle 0.0026 % (rainflow, depth-aware: 0.0020 %), deepest cycle 90 % SoC

  -> results\bess-day
[exit 0]

--synth builds a synthetic daily load shape so the command runs without recorded data. With --series <ts.json> the replay runs on a real series, as in ch. 22. The differences from chain:

  • Policies are idle, peak-shave and hold. gda-replay takes no price series, so price and lp exit 2: --policy price needs a price series, and gda-replay takes none; use idle, peak-shave or hold.
  • Step length comes from the series. Each step is the gap to the next timestamp, the last step reuses the previous gap, and a one-step series uses 0.5 h. A replay with --step-min 120 runs the battery in 2 h steps and books its standby load accordingly (0.12 MWh over six steps in docs/_captures/bess/gda-replay-hourly.txt). The hour of day the policy sees is the UTC clock time of the timestamp. chain has --step-hours; gda-replay takes its step length from the series.
  • The peak-shave thresholds are 90 % and 70 % of the case's total load times the largest load factor in the series. --shave-high and --shave-low apply.
  • The output is a summary, not a step table. The console shows the state-estimate lines (timestamps reconstructed, non-converged count, the range of system losses), the COUNTERFACTUAL line, and the two summary lines for each site. The step-by-step values are in the files below.
  • Provenance. The result is tagged Counterfactual. The counterfactual CSV is not a time-series file that --series reads, so it cannot feed another replay. The line COUNTERFACTUAL (Counterfactual): hypothetical storage on recorded history - not a reconstruction. is the tag.

gda-replay writes to the directory given by --out (default results/gda-replay-<case>): state-estimate.csv, run-metadata.json, exports/, and, when --bess is given, storage-counterfactual.csv:

$ head -8 results/bess-gda/storage-counterfactual.csv
# COUNTERFACTUAL: hypothetical storage on recorded history (ProvenanceTag.Counterfactual)
index,site,request_mw,delivered_mw,aux_mw,soc,temp_c,limited
0,NMC 5MW/10MWh @5,1.000,1.000,0.0100,0.70571,24.80,0
1,NMC 5MW/10MWh @5,1.000,1.000,0.0100,0.66100,24.62,0
2,NMC 5MW/10MWh @5,1.000,1.000,0.0100,0.61586,24.45,0
3,NMC 5MW/10MWh @5,1.000,1.000,0.0100,0.57030,24.29,0
4,NMC 5MW/10MWh @5,1.000,1.000,0.0100,0.52429,24.13,0
5,NMC 5MW/10MWh @5,0.000,0.000,0.0100,0.52428,24.17,0
[exit 0]

Columns: index, site, request_mw, delivered_mw, aux_mw, soc, temp_c and limited (1 if a limit bound). The first line is a comment that marks the file as counterfactual. Exit code 3 means a step did not converge.

Refusals and exit codes

Every refusal below prints one line to standard error and exits 2, except where the table says 1.

Cause Message Exit
--bess with no value error: --bess expects chemistry:bus:MW:MWh[:soc] 2
Not four or five fields error: chain storage: --bess 'lfp:5:5': expected chemistry:bus:MW:MWh[:soc] (4 or 5 fields separated by ':'), got 3. 2
Unknown chemistry error: chain storage: --bess 'unknown-chem:5:5:10': unknown chemistry 'unknown-chem' (lfp, nmc, lto, na-ion, vrfb, lead-acid). 2
Bus not a number error: chain storage: --bess '...': bus 'abc' is not a bus number. 2
MW or MWh not a number above 0 error: chain storage: --bess '...': <MW or MWh> '<field>' must be a number above 0. 2
Starting SoC outside 0 to 1 error: chain storage: --bess '...': starting state of charge '1.5' must be a number from 0 to 1. 2
Bus not in the case error: chain storage: storage site 'LFP 5MW/10MWh @99' is at unknown bus 99. 2
Unknown policy error: chain storage: --policy 'magic': expected idle, peak-shave, price, hold or lp 2
--policy price or lp without prices error: chain storage: --policy lp needs --prices 2
--prices with no value error: chain storage: --prices expects a value: 'synthetic' or a price file (one GBP/MWh value per step). 2
A price file missing, unreadable, short or with a bad value error: chain storage: --prices <file>: ... naming the file and the line 1
A storage flag without --bess error: chain --policy is a storage flag: it needs at least one --bess site ... 2
--prices on gda-replay error: --prices applies to dcopf, acopf and chain (with --bess) only (got 'gda-replay'). 2
Unknown --mode error: --mode expected 'fixed', 'ramp' or 'daily' but got 'weird' 2
Unknown case name the shared unknown-case message 2

Three captures show the usual ones:

$ gridsim chain case9 --steps 2 --bess malformed-spec
error: chain storage: --bess 'malformed-spec': expected chemistry:bus:MW:MWh[:soc] (4 or 5 fields separated by ':'), got 1.
[exit 2]
$ gridsim chain case9 --steps 4 --bess unknown-chem:5:5:10
error: chain storage: --bess 'unknown-chem:5:5:10': unknown chemistry 'unknown-chem' (lfp, nmc, lto, na-ion, vrfb, lead-acid).
[exit 2]
$ gridsim chain case9 --steps 2 --bess lfp:99:5:10
error: chain storage: storage site 'LFP 5MW/10MWh @99' is at unknown bus 99.
[exit 2]

On gda-replay the same site errors read error: gda-replay storage: ..., and --policy lp and --policy price exit 2 because the verb takes no prices:

$ gridsim gda-replay --synth --case case9 --steps 4 --bess lfp:5:5:10 --policy lp
error: gda-replay storage: --policy lp needs a price series, and gda-replay takes none; use idle, peak-shave or hold.
[exit 2]

The run exit codes are:

  • 0: every step converged.
  • 3: at least one step did not converge, or the lp schedule LP did not solve to an optimum. A step that did not converge shows N in Conv and - in Slack MW and Vmin, and the footer reads WARNING: N step(s) did not converge. Nothing that did not converge is reported as success.
$ gridsim chain case9 --steps 3 --bess lfp:5:20000:40000:0.95 --shave-high -30000 --shave-low -40000
GridSim - storage time series  *  case9  *  3 x 0.5 h  *  mode=fixed  *  policy=peak-shave
prices: none.  Chemistry presets are CuratedPlaceholder [VERIFY] (representative cells).

...
|---:|---:|---:|---:|---:|---|---:|---:|:-:|
| 0 | 0.0 | 1.000 | 315 | - | 20000.0 / 0.720 / 26.9 | - | - | N |
| 1 | 0.5 | 1.000 | 315 | - | 20000.0 / 0.488 / 28.8 | - | - | N |
| 2 | 1.0 | 1.000 | 315 | - | 20000.0 / 0.253 / 30.0 | - | - | N |

LFP 20000MW/40000MWh @5: out 30000.0 MWh, in 0.0 MWh, aux 73.54 MWh, stored change -31136.6 MWh, round trip -, 0.38 equivalent full cycles
    ageing over the run: calendar 0.0316 %, cycle 0.0013 % (rainflow, depth-aware: 0.0010 %), deepest cycle 70 % SoC
WARNING: 3 step(s) did not converge.
[chain] done -> results\chain-storage-case9.md
[exit 3]

That run asks a single 20 GW / 40 GWh battery at bus 5 to inject 20 GW into a 315 MW case, which the power flow cannot solve. It shows the exit code, not a realistic study.

gda-replay also exits 2 when the series is rejected by the forward-inference guard or a --bess site is on a bus the replay case does not have (storage site '...' is at unknown bus N.), and 1 when the case or series file cannot be loaded.

Pitfalls

  • --prices makes lp the default policy. Give --policy as well when you want another one.
  • The synthetic price day is not a market record. Quote a revenue figure only from a price file you can source.
  • A bus number is the case's own number, not an index. case9 runs 1 to 9. Use the bus ids the case prints.
  • The pack is rounded to whole strings. The pack is sized to a series count (1000 V divided by the cell's nominal voltage, rounded) and a parallel count (energy divided by one string's energy, rounded), so the nominal energy is close to, not equal to, the MWh you gave. 10 MWh of LFP is 40 strings of 304 cells (12160 cells), 10.0247 MWh. The cycle count is measured against that nominal energy. The MW rating is exact.
  • A small battery is held by its C-rate, not its rating. A site whose MW exceeds its C-rate limit on its MWh (a 5 MW / 4 MWh lead-acid battery) is limited to the C-rate and reports current limit. Raise the MWh or lower the MW.
  • The step length changes the story. In daily mode the step is 24 / steps hours, in fixed and ramp mode it is 0.5 h, unless --step-hours is given. A 4 h step sees the SoC window edge mid-step and reports a low mean power. A 0.5 h step does not. --steps defaults to 48 with a storage site, not 50.
  • fixed mode holds demand at the peak. The load multiplier is 1.0 every step, so the peak-shave default thresholds (283.5 MW and 220.5 MW on case9) put the demand above the high threshold at every step. The battery discharges to its floor in the first steps and then stays there. Use --mode daily for a battery study.
  • The starting SoC is checked against 0 to 1, not against the chemistry's window. A value inside 0 to 1 but outside the chemistry's window (for LFP, outside 0.05 to 0.95) starts the site outside the window, where it can only move toward it.
  • Threshold flags act under their own policy only. --shave-high and --shave-low act under peak-shave, and --buy-below and --sell-above under price; under another policy they change nothing.
  • stored change reads +0.0 on an idle battery. Self-discharge leaves a change too small to show at one decimal.
  • Calendar fade over a short run is front-loaded. A day on a fresh pack reads 0.0259 % to 0.4087 % across the six chemistries above (0.1369 % for LFP) because the square-root law gives one day sqrt(1/365), 5.2 %, of a year's fade at constant stress (LFP: 0.1369 % for the day, 1.91 % for a year at 25 C and 50 % SoC). Do not scale a one-day figure linearly to a year.

Limits

  • gridsim gda-replay takes no price series, so its storage runs idle, peak-shave or hold only.
  • All sites in a run share one policy and one set of thresholds, and the demand is scaled uniformly across every load in the case.
  • The converter efficiency (0.98 one way), the pack DC voltage (1000 V) and the ambient temperature (25 C) are fixed; no flag changes them.
  • A storage site injects real power only: its reactive range is zero, and it holds the voltage set-point its bus already had.
  • hold keeps the SoC in a band for a response service; the study does not simulate the response itself.