NESO RP1 + MECHANICAL panels, drill-down, and the bridge map fix

Two situational-awareness control-room tabs added to GridSim (2026-07-09), streamed frame-by-frame from the GDA lake over the bridge, plus a reusable drill-down inspector and a fix for the bridge/replay map geolocation. Both panels are grounded in the TSGB corpus (W:\Code\TSGB-2026\Proposals\MIF, Policy/0021 - The 1,800 Megawatt Fiction.md).

NESO RP1 - "where am I now / where am I going / how long do I have"

A situational-awareness page, not a dashboard. Hero quantity is purchased time - seconds of frequency ride-through on real intrinsic mass.

  • Physics - new pure src/GridSim.Core/Dynamics/StabilityMetrics.cs:
  • PurchasedTimeSeconds(intrinsicGvaS, credibleLossMw, currentHz, thresholdHz=49.2) - t = deltaf/RoCoF, RoCoF = f0*deltaP/(2E). Threshold 49.2 Hz (deltaf 0.8 Hz) is the corpus working set-point (Policy 0021 sec. 6).
  • DynamicMifGvaS(loss, rocofLimit) = f0*deltaP/(2*RoCoF_limit) (S_base cancels).
  • RocofFor(...) wraps InertiaEstimator.PredictRocof; LargestCorrelatedGroup(groups, flows).
  • Tests (tests/GridSim.Tests/StabilityMetricsTests.cs) reproduce the corpus tables: 3,600 MW -> 720->6.4 s, 360->3.2 s, 155->1.4 s, 102->0.9 s; and the MIF 1,800 MW table.
  • Inertia split (fuel gauge, MIF 0001 sec. 10) - GVA.s total = (i) + (p) (additive, never petrol>tank). (i) intrinsic = synchronous mass (lake synchronous_inertia_gvas, else computed from the model's synchronous generators sum H*MBase/1000); (p) = NESO "Market Provided" (labelled market/contracted, not pure proxy - per MIF 0004 sec. 8 it can include real sync condensers).
  • Credible loss - shows both: the live largest-possible-now (biggest online synchronous unit + largest correlated HVDC group: Sellindge IFA+ElecLink, North-Sea NSL+Viking; the corridor table and the link-name matching live in GridSim.Core.Presentation.InterconnectorCorridors, shared by web and WPF, and recognise every source's spelling - gb-full's "IFA Interconnector", "NS Link interconnector", "Viking Link Denmark Interconnector", the reduced cases' "North Sea Link" / "Viking Link", and the bridge raw ids) and the hard 3,600 MW Dogger Bank design basis, with the 1,800 MW convention struck through (Policy 0021).
  • Also: inertia-by-source (seconds), 30-min stability trend, auto-generated handover narrative, BM Stability Delta (each acceptance green/red by inertia direction - needs the lake's BMU->fuel tag), interconnector summary with correlated-trip dots, LFDD traffic light (49.5/49.2/48.8 ladder from find_lfdd_events.py), and coherence-cost GBP/h by constraint (RIGHT column; gb-full has no boundary model so boundary bars are flagged absent, cost still shown).

MECHANICAL / Plant Engineer - "what the MACHINES are doing"

Per-machine, asset-level (Views/MachineEngineerVm.cs + MachineEngineerView.xaml + Visuals/PqDiagram.cs, a custom P-Q capability control). Five sections: per-machine state (risk-sorted by loading), shaft/torsional + thermal, protection envelope (P-Q dot + dual RoCoF-relay margin: current vs the original 0.125 AND relaxed 1.0 limit - Policy 0021 sec. 10), inertia-per-unit (sum asset KE vs reported (i), synthetic gap), fleet trajectory (MW/min + projected inertia +15 min).

Ramp identity and period: each machine's ramp is its own frame-to-frame change, tracked by generator index (checked against bus and name, GridSim.Core.Presentation.UnitRampHistory) because gb-full unit names are not unique; it is divided by the frame interval - the WPF view derives it from the frame clock, the web view follows the transport STEP picker (SimSession.SetStepMinutes).

Provenance is explicit and honest: MW / loading / inertia (H*MBase) / ramp / RoCoF-margin are REAL. MVAr, power factor, excitation, AVR/governor mode, shaft torsional stress, stator/rotor temps, certified-J + type-test dates, committed starts are shown "-" or flagged synthetic until a plant feed is wired. Do NOT reconstruct MVAr from per-bus net QInj - it misattributes shunt/line-charging reactive to a small co-located generator (an 11 MW CHP reads +368 MVAr). Filters to synchronous units

=10 MW to drop sub-MW embedded plant noise.

Drill-down (click a paused frame to explore it)

Views/InspectorVm.cs + InspectorView.xaml - a reusable overlay: headline stat tiles + constituent rows + a back-stack (< back) + > chevron (shown when a row is drillable) + x close.

  • RP1: dispatch-stack / inertia-by-source rows -> fuel breakdown (constituent units + combined totals/averages); BM row -> acceptance detail; interconnector row -> flow + correlated-trip corridor with the co-members drillable. Nested: a fuel's unit rows drill to a unit detail (whose Fuel row drills back up); interconnector members hop between each other.
  • MECHANICAL: machine row -> full per-machine card.
  • Wiring idiom (important): wrap the ItemsControl row DataTemplate in <Button Style="{StaticResource RowLinkBtn}" Command="{Binding DataContext.InspectXCommand, RelativeSource={RelativeSource AncestorType=ItemsControl}}" CommandParameter="{Binding [Fuel|/row]}">. A bare MouseBinding on the row Grid does not fire reliably inside a ScrollViewer. Per-row nested drill uses InspectRow.Drill (an ICommand set per row via new RelayCommand(() => ...)).

Bridge / lake wiring

  • Protocol (Core/IO/BridgeProtocol.cs): OperatorBlock gained SynchronousInertiaGvaS, OutturnInertiaGvaS, MarketInertiaGvaS; BalancingActionDto gained FuelType, Synchronous; BusDto gained X, Y. Fed via the existing MarketDataReceived side-channel + per-frame Update.
  • GDA builder (NetworkModel/build_operator_market_frames.py): enriches balancing_actions_json from DataSources/Elexon/Reference/bmunits_all.json (elexonBmUnit->fuelType; synchronous = {CCGT,OCGT,COAL, BIOMASS,NUCLEAR,GAS,OIL,PS,NPSHYD}) and as-of joins the inertia columns. The server's opmkt _load_scalar_table reads an EXPLICIT column list (bridge_server.py ~line 340) - new columns must be added there. Rebuild the table after editing the builder.

Map fix (bridge/replay geolocation)

Symptom: under the live bridge, gb-full stacked every node at the Cornwall corner. Cause: the presolved topology.json carried no per-bus x/y (gridsim_export.to_solve_export dropped the geolocated coords that out/<case>/buses.json already holds). Fix: to_solve_export now emits x/y; C# BusDto/BuildModel read them; existing topology.json for all 7 cases were patched in place by merging x/y from buses.json (no re-solve). Restart the bridge to reload topology.json. NB the bridge bus names are LTDS tower ids ("Tower 48CM13"), so C#-side GeoLocator.Apply name-matching is a dead end (0% match) - the coords must ride in the stream.

Run it

python W:\Code\GDA\v1\Applications\GridSim-Bridge\bridge_server.py          # :8770; restart to reload topology
dotnet build src/GridSim.Wpf/GridSim.Wpf.csproj -c Release                  # close the app first (file locks)
dotnet run --project src/GridSim.Wpf -c Release -- bridge --zone gb-full --back 30 --tab "NESO RP1"
- --zone = gb-full or a DNO zone; --back 30 lands in the presolved 2026-06-10 window; --tab boots a tab. - Tests: dotnet test tests/GridSim.Tests (451). Bridge acceptance: python W:\Code\GDA\v1\Applications\GridSim-Bridge\test_bridge_stream.py gb-full (asserts the inertia split + BM fuel tags). - Screenshot to iterate - capture with PowerShell PrintWindow (flag 2, PW_RENDERFULLCONTENT); it grabs the app window without stealing focus. Do NOT script mouse_event clicks while the user is at the keyboard - clicks need real foreground and will fight them (and miss).

Known follow-ups

  • Asset-sum-vs-reported "synthetic gap" (MECHANICAL sec. 4) shows 0 when the lake intrinsic side-channel is null for that period (SetIntrinsic timing) - wire more robustly.
  • Wire real plant SCADA to fill the flagged MVAr/PF/excitation/torsional/temps/certified-J fields.
  • RP1 boundary bars are empty for gb-full (no boundary model in the streamed case) - carry ETYS boundaries in the model or compute them.