This chapter specifies the harmonic-analysis subsystem in src/GridSim.Core/Harmonics/: the frequency-dependent network admittance Y(h), the linear penetration solve Y(h) V(h) = I(h), the driving-point impedance scan and the fine sweep with golden-section refinement, the distortion indices and compliance tables, the coupled iterative harmonic power flow, the three-phase penetration, the harmonic state estimator and the complex linear-solver seam they share. The command-line verb harmonics and its console and export formats are in ch. 17 of the user manual; this chapter gives the mathematics and the code behind them.

The design rests on one split. Everything that depends on the network is derived from the network model: Y(h) is built from the same branch stamp as the fundamental YBus, the response is Kirchhoff's current law at each order, and the indices are arithmetic over the result. The one quantity the engine cannot derive is the injected harmonic current phasor I_h per bus per order, because it is a property of the connected equipment. That quantity is a first-class, versioned, provenance-tagged input (HarmonicSourceSet), and every output echoes its tag. A study on assumed spectra and a study on metered spectra have the same shape and run the same code; a bus upgrades from assumed to metered in place.

Model

Notation

h is the harmonic order (frequency h * f0, with f0 = GridModel.FrequencyHz). n is the bus count. Y(h) is the n x n complex nodal admittance matrix at order h in per-unit on GridModel.BaseMva. I(h) is the nodal injection vector and V(h) the nodal voltage vector, in per-unit. A voltage magnitude of 1.0 is the nominal fundamental voltage of the bus.

Provenance of the source spectrum

Each HarmonicSource carries a ProvenanceTag.

Tag Meaning
CuratedPlaceholder An assumed-typical spectrum from the built-in library (HarmonicSourceLibrary). An engineering default, not a measurement. The library values are marked [VERIFY] in the XML comments of HarmonicSource.cs; no runtime field carries that marker.
Recorded A spectrum metered at the point of connection by a power-quality meter.
DerivedFromRecorded A metered spectrum transformed (rescaled to another operating point, aggregated over a feeder) but traceable to metered data.

The export's headline provenance is Recorded when every source is Recorded or DerivedFromRecorded, and CuratedPlaceholder otherwise (HarmonicExport.ToJson). The tag is data; it changes no number in the solve.

Source injection

A source at bus b with fundamental current I1 (FundamentalCurrentPu) and a spectrum of components (order, magnitudePercent, phaseDeg) injects, at order h (HarmonicSource.InjectionAt):

I_src(h) = (magnitudePercent / 100) * I1 * exp(j * phaseDeg * pi / 180)      for the component with Order == h
         = 0                                                                 when no component has Order == h

Several sources on one bus add as phasors (inj[bi] += ih). Only the first component with a given order is read. The fundamental (h = 1) carries no harmonic injection: every driver reports exactly zero voltage at h = 1.

The frequency-dependent admittance Y(h)

FrequencyDependentYBus.Build(model, h, options) assembles Y(h) as a ComplexCsr matrix. It is not the fundamental YBus scaled by a scalar: each element scales by its own physics. Only in-service branches are stamped. The sections below list the contribution of each element.

Branch pi-model with tap and phase shift. For a branch with series R, X, total line charging B, tap ratio TapRatio and phase shift PhaseShiftDeg, AdmittanceStamp.Branch(R, X, B, tap, shift, h, rFactor) computes:

ys  = 1 / (R * rFactor + j * h * X)             series admittance: reactance scales with h
bc  = j * h * B / 2                             half the line charging at each end: scales with h
a   = TapRatio  (a = 1 when TapRatio <= 0)
T   = a * exp(j * s * theta)                    theta = PhaseShiftDeg in radians, s = +1 or -1 (see "Sequence")
Yff = (ys + bc) / a^2
Ytt = ys + bc
Yft = -ys / conj(T)
Ytf = -ys / T

The four terms are added to cells (from,from), (to,to), (from,to) and (to,from). The tap ratio is independent of h. The fundamental YBus uses the same stamp with h = 1, rFactor = 1.

Skin effect (opt-in). The series-resistance factor is

rFactor(h) = 1 + k * sqrt(max(h - 1, 0))
k = CableSkinCoefficient   when branch.Equipment equals "cable" (case-insensitive) and CableSkinCoefficient > 0
k = SkinCoefficient        otherwise

Both coefficients default to 0, so rFactor = 1 in the bare builder and in the study model (HarmonicModelOptions.SkinFactor).

Bus shunts. For a bus with Gs, Bs (MW and MVAr at 1 pu voltage):

Y_shunt(h) = ( Gs + j * (Bs >= 0 ? Bs * h : Bs / h) ) / BaseMva

The conductance is independent of h. A capacitor bank (Bs > 0) has a susceptance that grows with h; a reactor (Bs < 0) has one that falls as 1/h.

Loads as damping shunts (IncludeLoadShunts). A bus with Pd, Qd (MW, MVAr) adds, at 1 pu voltage:

g = max(Pd, 0) / BaseMva
b = Qd >= 0 ?  -(Qd / h) / BaseMva           lagging load: a reactor, |b| falls as 1/h
             :  -(Qd * h) / BaseMva          leading load (Qd < 0): a capacitor, b grows as h
Y_load(h) = g + j b

A net-exporting bus (Pd < 0) adds no conductance; a negative resistance could manufacture a resonance.

Machine source impedance (IncludeGeneratorSources). Every generator that is neither PowerFlowOnly nor IsConverterInterfaced adds a shunt to ground

X_sys     = ( X2 + X_unit ) * BaseMva / MBase               MBase = BaseMva when the generator's MBase <= 0
X2        = NegativeSeqXPu when > 0, else the effective X''d (fallback GeneratorFallbackXdPu = 0.20 pu)
X_unit    = max(0, UnitTransformerXPu)
y_g(h)    = 1 / (j * h * X_sys) = -j / (h * X_sys)           no conductance

(Generator.FaultSourceNegativeSeqReactancePu, the reactance the fault studies use, so the two cannot drift apart). No machine resistance is stamped because the data carries none; this makes resonance peaks sharper, never flatter. Converter-interfaced plant is a controlled current source with no EMF behind a reactance and is not stamped. A non-positive or non-finite X_sys throws InvalidOperationException naming the unit.

Long-line (distributed-parameter) correction (LongLineCorrection, opt-in). For a branch with B != 0, the lumped pi is replaced by the exact equivalent pi of the transmission-line equations:

z   = R * rFactor + j * h * X
y   = j * h * B
gl  = sqrt(z * y)                                  the line length cancels; no length data is needed
zc  = z * sinh(gl) / gl                            zc = z when |gl| < 1e-9
ycH = (y / 2) * tanh(gl / 2) / (gl / 2)            ycH = y / 2 when |gl| < 1e-9
ys  = 1 / zc                                       ys = 0 when zc = 0

AdmittanceStamp.FromAdmittance(ys, ycH, tap, s * theta) then stamps the branch exactly as above.

Sequence handling and the transformer phase shift

A balanced harmonic of order h rotates as a symmetrical-component sequence (HarmonicSequence.Of):

h mod 3 == 1   positive sequence   (7, 13, 19, ...)
h mod 3 == 2   negative sequence   (5, 11, 17, ...)
h mod 3 == 0   zero sequence       (the triplens: 3, 9, 15, ...; also 6, 12, ...)

A transformer phase shift theta (a Dy winding, a quad booster) moves the positive and negative sequence sets in opposite directions at every frequency. With BalancedHarmonicSequences = true, Y(h) stamps T = a*exp(+j*theta) for a positive-sequence order and T = a*exp(-j*theta) for a negative-sequence order (FrequencyDependentYBus.BalancedShiftSign). A triplen is zero sequence. Its network is the zero-sequence network (line Z0, transformer winding and earthing), which the positive-sequence data model does not carry. The code therefore refuses it at every entry:

  • Build for a triplen order throws ArgumentException ("Order N is a triplen (zero sequence)").
  • Build for a non-integer order, or an order below 1, throws ArgumentException in balanced mode.
  • HarmonicPenetration.Solve and CoupledHarmonicPowerFlow.Solve call RefuseTriplensIfBalanced first: any source whose spectrum has a triplen component with non-zero MagnitudePercent throws ArgumentException naming the bus, the SourceType and the order. The check covers every spectrum entry, whether or not the order is in the analysed set.
  • A triplen order with no source current is skipped: its voltage is exactly zero and no Y(h) is built.
  • HarmonicImpedanceScan skips triplen orders.

Outside balanced mode the builder is a plain positive-sequence frequency operator (s = +1). The impedance-stability assembler needs that form, with signed and fractional frequencies. BuildSequence(model, h, kind, options) builds the positive (s = +1) or negative (s = -1) sequence network at any positive finite h, fractional included, and ignores the balanced flag; the frequency sweep uses it. A zero-sequence request throws.

Three-phase injections and unbalanced networks are the three-phase penetration (below).

The study model

HarmonicModelOptions.Study is the model that the CLI harmonics verb, the Web HARMONICS tab and the scheduled harmonics analysis job run: machine source impedance on, loads as damping shunts on, balanced sequences on, default orders, no skin effect, no long-line correction. Machines ground the network and set the resonances; the loads are the main resistive damping.

Singular networks

Y(h) is singular when part of the network has no path to ground at that order: a radial feeder or island with no line charging, shunt, machine or load of its own and no connection to a grounded bus. A feeder fed from a bus that a machine grounds is not singular. There is then no unique voltage for an injected current. Every driver reports it as SingularHarmonicNetworkException, naming the study and the order, and never substitutes a zero response. The CLI prints harmonics: FAILED - <message> to standard error and exits 1, with no THD and no verdict (the capture is docs/_captures/harmonics/case-singular.txt). A penetration run throws for the lowest singular order among the orders that carry injected current, whatever the order of execution.

Algorithm

The complex-solver seam

Harmonic penetration is a complex linear solve, so the subsystem has its own interface, IComplexLinearSolver (src/GridSim.Core/Abstractions/IComplexLinearSolver.cs), parallel to the real ISparseLinearSolver of the power flow (ch. 4, Sparse and GPU numerics). Its members are Name, Solve(ComplexCsr a, Complex[] b) (null when the matrix is singular or the method breaks down) and Factor(ComplexCsr a), which returns an IComplexLinearFactorization for repeated right-hand sides against one matrix.

Implementation Method Role
DenseComplexLuSolver Dense complex LU with partial pivoting; singular when a pivot is at or below NumericTolerances.RelativePivotFloor (1e-12) times the largest |A_ij|; null on singular. The oracle: exact reference for small cases.
RealExpandedComplexSolver The real 2n x 2n expansion below, solved by the real SparseLu (Gilbert-Peierls with an RCM fill-reducing ordering). The default. Scales to gb-full (3539 buses).
SparseComplexBiCgStabSolver Native complex Jacobi-preconditioned BiCGSTAB with Hermitian inner products; relative residual tolerance 1e-12, iteration cap 4n + 200; null on breakdown or stagnation. A third independent path that cross-validates the other two.

The real expansion of (G + jB)(Vr + jVi) = (Ir + jIi) is

[ G  -B ] [ Vr ]   [ Ir ]
[ B   G ] [ Vi ] = [ Ii ]

The ordering of the 2n pattern is cached per solver instance and reused across the orders of a scan, which share one topology. Every driver defaults to RealExpandedComplexSolver. A caller can pass another IComplexLinearSolver to penetration, the scan, the coupled flow and the estimator; the sweep always uses the real-expanded solver, and a caller-supplied solver runs sequentially.

Linear penetration

HarmonicPenetration.Solve(model, sources, options, solver) runs, for each order h in options.Orders:

inj[b]   = sum over sources at bus b of I_src(h)
if h == 1 or inj is all zero:   V(h) = 0 at every bus, no Y(h) is built
else:                           V(h) = solve( Y(h), inj )

An order with no injected current has exactly zero voltage. The result is HarmonicPenetrationResult(Orders, BusIds, Voltage[orderIndex][busIndex]). The solve is linear and superposition-based: a linear network does not couple orders. Source components whose order is not in options.Orders are not read.

With the default solver and more than one order the orders run in parallel (Parallel.For, one RealExpandedComplexSolver per worker through ThreadLocal) and write by index. A caller-supplied solver runs the orders sequentially.

Impedance scan

HarmonicImpedanceScan.DrivingPoint(model, busId, options, solver) computes, at bus k, for each order in the options (triplens removed in balanced mode):

solve  Y(h) x = e_k                    e_k is a unit current injected at bus k
Z(h)   = x[k]                          the driving-point impedance, pu on BaseMva

The solution x is column k of Y(h)^-1. The peak is the order with the largest |Z(h)|, with ties broken to the first (lowest) order, after the parallel solves have finished. The result holds ResonanceOrder, PeakMagnitude and Participation: the full column x at the peak order, the transfer impedance from bus k to every bus. An unknown bus throws ArgumentException; a singular order throws for the lowest such order.

Fine frequency sweep

The scan samples only whole orders, so a sharp resonance between two orders is under-reported at the nearest order. HarmonicFrequencySweep.DrivingPoint(model, busId, options, sweep) sweeps a grid of fractional orders and refines the peak. The grid settings are FrequencySweepOptions.

points   = floor( (MaxOrder - MinOrder) / Step + 1e-9 ) + 1
grid[p]  = MinOrder + p * Step                     computed, never accumulated
Zpos[p]  = [ Y_pos(grid[p])^-1 ]_kk                positive-sequence network (BuildSequence, s = +1)
Zneg[p]  = [ Y_neg(grid[p])^-1 ]_kk                swept only when some in-service branch has PhaseShiftDeg != 0

The negative-sequence network differs from the positive one only through transformer phase shifts, so without a phase shifter NegativeZ is null. The grid peak is the first (lowest) maximum of |Zpos|; the negative network replaces it only if a point is strictly larger. With the default settings the grid has 486 points.

The refinement is a golden-section search for the maximum of |Z(h)| on [lo, hi], the neighbouring grid points of the grid peak (clamped at the ends of the grid), on the sequence network that holds the peak:

invPhi = (sqrt(5) - 1) / 2
steps  = ceil( ln(RefineTolerance / (hi - lo)) / ln(invPhi) )
c = hi - invPhi*(hi - lo);  d = lo + invPhi*(hi - lo)
repeat `steps` times: keep [lo, d] when |Z(c)| >= |Z(d)|, else [c, hi]; add one interior point
result = the best (h, |Z|) seen, never worse than the grid peak

The refinement runs sequentially for a fixed step count. With hi - lo = 0.2 and a tolerance of 1e-6 it takes 26 steps (28 evaluations of |Z|). PeakHz = PeakOrder * FundamentalHz. The sweep refuses (with ArgumentException) non-positive or non-finite bounds, step or tolerance, MaxOrder not above MinOrder, a grid of fewer than 2 or more than MaxGridPoints (100,000) points, and an unknown bus. A singular grid point throws, lowest frequency first.

Coupled iterative harmonic power flow

Linear penetration treats a source as a fixed current. CoupledHarmonicPowerFlow.Solve(model, sources, coupling, options, solver, tol, maxIter) lets a converter's emission depend on its terminal voltage through an IHarmonicCouplingModel, which has two parts: a linear shunt admittance ShuntAdmittance(order) (the converter's Norton admittance) and an Injection(order, terminalVoltage, baseInjection) that may depend nonlinearly on the voltage.

For each order h != 1 that carries injected current:

Yc(h)   = Y(h) + ShuntAdmittance(h) at every source bus      (skipped when the admittance is exactly 0)
factor Yc(h) once
V0      = solve( Yc, Injection(h, 0, base) )
loop up to maxIter times:
    V'  = solve( Yc, Injection(h, V[b], base[b]) at each source bus b )
    d   = max over buses of |V'[i] - V[i]|
    V   = V'
    stop when d < tol
Iterations = the largest zero-based index of the converging pass over the orders
Converged  = false when any order used all maxIter passes

tol defaults to 1e-10 and maxIter to 50. Factoring once and back-substituting per pass matches a re-factoring solve bit for bit. The same triplen refusal as penetration applies. A singular Yc(h) throws.

NortonCouplingModel(couplingConductance = 0.05, couplingSusceptancePerOrder = 0) is the only implementation: ShuntAdmittance(h) = g + j * b * h and Injection = baseInjection, so the iteration settles on the first pass. Its provenance is CuratedPlaceholder: the admittance and the voltage-to-emission law describe a converter's internal control, which the grid model does not contain. The network physics folding it in is grounded; the converter model is the assumption and is labelled. The coupled flow is Core API with no CLI verb and is marked experimental.

Three-phase harmonic penetration

ThreePhaseHarmonicPenetration.Solve(MultiPhaseModel model, sources, orders, solver, activeFrontEnds) runs the penetration on the multi-phase feeder model (Distribution/), which carries a full 3 x 3 series impedance per branch, instead of the positive-sequence equivalent. Buses flagged IsSource are the harmonic ground (V = 0); every other bus carries three unknowns, so the reduced system has 3m rows for m non-source buses. For each order h in the caller's list:

Z_br(h)[p][q] = R[p][q] + j * h * X[p][q]          every element of the 3x3, self and mutual
Ys_br(h)      = Z_br(h)^-1                         3x3 series admittance
branch between non-source buses f, t:  block (f,f) += Ys, (t,t) += Ys, (f,t) -= Ys, (t,f) -= Ys
branch to a source bus:                the non-source end gets block += Ys on its diagonal only
shunt at node u (capacitor, line charging): block (u,u) += G + j*h*B, per entry of its 3x3 fundamental admittance
active front end at node u:            y = 1 / (R + j*h*X);  block (u,u) += (y/3) [[2,-1,-1],[-1,2,-1],[-1,-1,2]]
solve Y(h) V(h) = I(h)                             I(h) = the per-phase injections of ThreePhaseHarmonicSource

A branch with both ends at source buses is skipped. Shunt capacitors (j h B per phase) and line charging (half the pi shunt at each end, its susceptance scaled by h) are stamped on the diagonal block of their node. A closed switch (a branch with zero series impedance) has no admittance: union-find over the closed switches makes its two buses one node with one set of unknowns, and a bus switched onto the source bus is part of the harmonic reference; a harmonic source on such a bus is refused rather than lost. An active-front-end converter, when activeFrontEnds names one, is a balanced three-wire shunt (each phase reactor R + j h X on the feeder base to a floating star point), so it takes positive- and negative-sequence current and no zero-sequence current; null or empty stamps nothing. Loads of every kind (constant-power wye, ZIP and delta) are accepted and left out of Y(h): the study is network only. There is no machine or transformer-shift term, and no triplen refusal: a triplen is a legitimate zero-sequence quantity here. ThreePhaseHarmonicSource.Balanced builds a balanced injection with the harmonic rotation

a    = (magnitudePercent / 100) * I1 * exp(j * phaseDeg * pi / 180)
rot  = exp( -j * h * 2*pi/3 )
phases (A, B, C) = ( a,  a * rot,  a * conj(rot) )

so phase B lags A by h * 120 degrees. ThreePhasePenetrationResult.Sequence(orderIndex, busIndex) applies the Fortescue transform and returns [zero, positive, negative] (SymmetricalComponents.ToSequence: V0 = (Va + Vb + Vc)/3, V1 = (Va + a*Vb + a^2*Vc)/3, V2 = (Va + a^2*Vb + a*Vc)/3, a = exp(j*2*pi/3)). On a balanced network a balanced triplen is pure zero sequence and a balanced 5th is pure negative sequence; on an unbalanced network the orders mix sequences, and only this solve gives the neutral and per-phase distortion. A MultiPhaseModel loads from a gridsim-dist3ph/1 file (see ch. 18, the gridsim-dist3ph/1 feeder file). The three-phase penetration is experimental; it is on the CLI as gridsim dist3ph <feeder> harmonics --bus ID --spectrum TYPE --current PU (one balanced library source; manual ch. 7). It refuses, by name, a feeder with an element it does not model: a single- or two-phase lateral, a step-voltage regulator, or a transformer of any connection.

Harmonic state estimation

HarmonicStateEstimator.Estimate(model, order, measurements, candidateSourceBuses, options, solver) recovers the source injections that best explain a set of metered harmonic voltages. At a fixed order the network is linear, so the estimate is one complex weighted least-squares solve. With s candidate source buses and m measurements (HarmonicVoltageMeasurement(Bus, Voltage, Sigma = 1e-3)):

Y(h) zcol_j = e_(source bus j)         one factorisation of Y(h), s back-substitutions
H[i][j]     = zcol_j[ bus of measurement i ]               the m x s measurement matrix
w[i]        = 1 / sigma_i^2
(H^H W H) x = H^H W z                  the Gram system, solved by the dense complex LU on its honest path
residual    = sqrt( sum_i w[i] * |z[i] - sum_j H[i][j] x[j]|^2 )

It throws ArgumentException when m < s, SingularHarmonicNetworkException for a singular Y(h), and InvalidOperationException when the Gram matrix is singular to working precision (candidate sources the measurements cannot distinguish). It never returns a zeroed source. The options default to the bare model (new HarmonicModelOptions()), not Study; pass Study to estimate on the study network. The estimator is Core API with no CLI verb and is marked experimental.

Indices

HarmonicIndices reduces a penetration result to the standard scalars. With V_h the complex harmonic voltage at a bus and V_1 the fundamental magnitude (1.0 pu unless the caller supplies solved fundamental voltages; the CLI and the Web tab both supply them through HarmonicIndices.SolvedFundamentalVm, which matches the power-flow result to the study's buses by id and throws InvalidOperationException on a non-converged fundamental or a missing or non-positive magnitude):

THD_V   = sqrt( sum over h > 1 of |V_h|^2 ) / V_1 * 100             percent
IHD_V(h)= |V_h| / V_1 * 100                                         percent
K       = sum_h ( I_h^2 * h^2 ) / sum_h I_h^2                       over a source spectrum, fundamental included
sharp   = PeakMagnitude / median over the scan of |Z(h)|            median of an even count is the mean of the middle two

The THD sum runs over the order index in ascending order, so its rounding is fixed. A worst-THD bus is the first bus in model order with the strict maximum; with all THD zero it is the first bus. The K-factor is the UL transformer de-rating weight: a pure fundamental gives K = 1. The library 6-pulse spectrum (I_h = I_1/h at 5, 7, 11, 13, 17, 19, 23, 25) gives K = 9 / 1.0843104 = 8.3002, and a source-current THD of 29.04 %. sharp = 1 is a flat response; there is no pass or fail threshold. IndividualDistortionPct returns 0 for an order that is not in the result.

Damping sharpness and the synchronous fleet

Synchronous machines are the network's harmonic sink: the study model stamps each as a reactance to ground, so each is a stiff path that absorbs harmonic current and sets where the network resonates. Removing a machine removes its path to ground from Y(h). How the scan peak and DampingSharpness change depends on the network (a removed shunt can move a resonance as well as raise it), and no test pins the direction; compare the two runs. This is the harmonic counterpart of the inertia in ch. 5, Frequency dynamics: the same fleet retirement that erodes inertia removes the machine paths to ground. A machine itself adds no damping, because machines carry no resistance; resistive damping comes from the series R of the branches, the bus conductance Gs and the load conductance.

Compliance

HarmonicCompliance.AssessIeee519(model, penetration, fundamentalVm) gives, for each bus, ThdPct, the worst single order WorstIhdPct and its order, the two limits, and Compliant, which holds only when the voltage level is known and both ThdPct <= ThdLimitPct and WorstIhdPct <= IhdLimitPct. The limit tier comes from the bus's BaseKv (upper bounds inclusive).

IEEE 519-2014 bus-voltage limits (HarmonicCompliance.Ieee519VoltageLimits):

Nominal voltage THD limit Single-harmonic limit
BaseKv <= 1 8.0 % 5.0 %
1 < BaseKv <= 69 5.0 % 3.0 %
69 < BaseKv <= 161 2.5 % 1.5 %
BaseKv > 161 1.5 % 1.0 %

GB headline THD planning levels (G55ThdPlanningLevelPct), from ENA Engineering Recommendation G5 Issue 5 (2020), section 5.2, Table 1 "THDV planning levels at supply system PCC nominal operating voltage", p.21 (docs/reference S139):

Nominal voltage THD planning level
BaseKv <= 0.4 5.0 %
0.4 < BaseKv <= 25 4.5 %
25 < BaseKv <= 66 3.7 %
66 < BaseKv <= 230 3.0 %
BaseKv > 230 3.0 %

G55Verdict(bus) returns the planning level and whether the bus is within it. The per-order G5 tables (Tables 2 to 6) are not encoded.

A bus whose BaseKv is missing, zero, negative or non-finite has VoltageLevelKnown = false. It is judged at the strictest tier (IEEE 519 1.5 % and 1.0 %, G5 3.0 %) and is never certified, whatever its distortion. The CLI prints a warning with the count.

Source library

HarmonicSourceLibrary supplies assumed-typical spectra, each tagged CuratedPlaceholder and marked [VERIFY] in the source comments. Magnitudes are percent of the fundamental current.

Type Orders and magnitudes (%)
6-pulse 100/h at 5, 7, 11, 13, 17, 19, 23, 25 (20, 14.286, 9.091, 7.692, 5.882, 5.263, 4.348, 4.000)
12-pulse 100/h at 11, 13, 23, 25, 35, 37
pv-inverter 3: 2.0; 5: 4.0; 7: 3.0; 11: 2.0; 13: 1.5
ev-charger 3: 12.0; 5: 8.0; 7: 5.0; 9: 3.0; 11: 2.0
heat-pump-inverter 3: 12.0; 5: 9.0; 7: 6.0; 9: 4.0; 11: 3.0; 13: 2.0
arc-furnace 2: 5.0; 3: 8.0; 4: 3.0; 5: 6.0; 7: 4.0
saturated-transformer 2: 15.0; 3: 8.0; 4: 4.0; 5: 3.0
6-pulse-g5 5: 31.4; 7: 10.9; 11: 7.0; 13: 3.9; 17: 2.7; 19: 1.9; 23: 1.0; 25: 1.0; 29: 0.6; 31: 0.7; 35: 0.6; 37: 0.5; 41: 0.4; 43: 0.4; 47: 0.3; 49: 0.2
12-pulse-g5 5: 0.4; 7: 0.2; 11: 4.8; 13: 3.2; 17: 0.1; 23: 1.0; 25: 0.8; 35: 0.4; 37: 0.4; 47: 0.2
afe-g5 2: 0.4; 3: 0.5; 4: 0.2; 5: 3.4; 6: 0.2; 7: 1.5; 8, 9, 10: 0.1; 11: 0.4; 12: 0.1; 13: 0.4; 15, 17: 0.1; 19: 0.2; 21, 22: 0.1; 23, 25: 0.2; 26, 27, 28, 29, 31, 35, 37: 0.1
ideal the same spectrum as 6-pulse

The three -g5 profiles are G5 Issue 5 Annex B, Table B.3 "Harmonic current emission assumptions for three-phase equipment types", pp.99-100: Ih / I1 for orders 2 to 50 as percent, orders printed as 0.000 omitted. Their THDI reproduce the printed 0.3441 (six-pulse) and 0.0596 (twelve-pulse); the active-front-end entries give 0.0386 against the printed 0.0381, the difference being the rounding of the many 0.001 entries. They are typical profiles, not a measured converter, so they carry CuratedPlaceholder like the rest of the library.

HarmonicSourceLibrary.Make(type, bus, fundamentalCurrentPu) builds a source (an unknown type throws). The default synthetic source, used by the CLI harmonics verb without --spectra or --converter-sources, by experimental harmonic-kcl, by the cycle's harmonics job and by the web HARMONICS tab, is Make(HarmonicSourceLibrary.DefaultSyntheticSourceType, largest-Pd bus, 0.5), the 6-pulse-g5 profile; harmonics --synth-spectrum ideal uses the 1/h spectrum instead (--synth-spectrum g5 names the default), and the flag is refused with --spectra or --converter-sources. Spectra with a triplen entry (pv-inverter, ev-charger, heat-pump-inverter, arc-furnace, saturated-transformer, afe-g5) are refused by the balanced study model, and even orders are not in the default order set.

Per-converter sources (--converter-sources)

ConverterHarmonicSources.FromModel(model, level, operatingPoint) (src/GridSim.Core/Harmonics/ConverterHarmonicSources.cs) turns every in-service converter-interfaced generator (Generator.IsConverterInterfaced) into one harmonic current source, except power-flow-only devices. Synchronous machines are harmonic sinks, not sources.

  • Profile. A self-commutated converter (battery, PV, full-converter wind, VSC HVDC) takes afe-g5 (SelfCommutatedProfile); a unit with ConverterFaultCurrentPu exactly 0, the model's encoding of a line-commutated HVDC link, takes 12-pulse-g5 (LineCommutatedProfile; that such a station is twelve-pulse is [VERIFY]).
  • Level (ConverterHarmonicLevel). Rated (the default, the G5 Stage 1C / 2A assessment basis): I1 = MBase / BaseMva pu. Dispatched: I1 = sqrt(P^2 + Q^2) / BaseMva pu, with P and Q the unit's solved output from the fundamental power flow (SolvedGeneration.UnitOutput); a unit at zero output injects nothing and is listed as not modelled. Part-load profiles are [VERIFY]: no document on disk gives them.
  • Components. Each component is the profile's Ih / I1 times I1, at phase 0, so units add linearly, the G5 Issue 5 s.6.3.3 rule when no diversity is declared.
  • Orders. The study runs over orders 2 to 50 (ConverterHarmonicSources.StudyOrders, StudyOptions = HarmonicModelOptions.Study with those orders). The balanced study cannot carry the triplen (zero-sequence) orders of afe-g5; they are left out and each is named in ConverterHarmonicSourceSet.OmittedComponents.
  • Fail loud. A non-finite or non-positive base, a converter rating that is not finite and positive (Rated), or a non-finite Pg / Qg (Dispatched) throws ArgumentException. The CLI exits 1 on a case with no converter that injects, 3 when dispatched needs a fundamental solve that did not converge, and 2 when --converter-sources is combined with --spectra or --synth-sources or given another value than rated or dispatched.

With --afe-reactance X [--afe-resistance R] (HarmonicModelOptions.ActiveFrontEndReactancePu, ActiveFrontEndResistancePu, pu on each unit's rating) every active-front-end unit is stamped as a Norton equivalent, R + j h X to ground in parallel with its source (G5 Issue 5 s.3.29: such converters may be resonant plant); line-commutated units are unchanged. No value exists on disk, so there is no default; without the flag the converter is an ideal current source. The export then carries a harmonicModel.activeFrontEnd block listing each stamped unit and its impedance on the system base.

Source set file: gridsim-harmonics/1

HarmonicSourceSet.Load(path) reads camelCase JSON, property names case-insensitive, enums by name, with fields schema, case, baseMva (default 100), takenUtc, note and sources. It rejects a schema other than gridsim-harmonics/1 and, when takenUtc is present, calls ForwardInferenceGuard.RejectFuture: a stamp newer than utcNow - 169 h (ForwardInferenceGuard.HorizonHours) throws ForwardInferenceException (ch. 8, Provenance and invariants). Validate(model) collects every offender into one InvalidDataException: a baseMva that differs from the model's by more than 1e-9 (checked when both are above 0), a source bus absent from the model, a non-finite fundamental current, a component order below 1, a non-finite magnitude or phase. The authoritative schema for GDA-written files is NetworkModel/HarmonicDataSchema.json in the GDA repository.

Export: gridsim-harmonic-export/1

HarmonicExport.WriteJson writes one document with the blocks schema, meta, provenance, model, orders, harmonicModel, sources, voltage (non-zero phasors only: order, bus, vmPu, vaDeg), indices, resonance, resonanceSweep and compliance; the fields are listed in ch. 17. The harmonicModel block records every input beyond the case network that Y(h) used (the machine xSystemPu values and the load pdMw, qdMvar), so tools/crossval/crossval_harmonics.py can rebuild Y(h) and the voltages with NumPy alone and diff them. The export alone is not enough: it holds no branch R, X, B, taps or bus shunts. The script also needs --case, a case directory (system.json, buses.json, transmission.json, optionally transformer.json; a built-in case name is not accepted), and --sources, a gridsim-harmonics/1 file (written from the export's sources block after a default run).

Solver wiring in the production callers

  • CLI harmonics: HarmonicModelOptions.Study (with --converter-sources, ConverterHarmonicSources.StudyOptions, orders 2 to 50); HarmonicPenetration.ComponentsOutsideOrders (refuses, exit 1, any non-zero source component at an order outside Orders; a Core caller uses HarmonicPenetration.RefuseComponentsOutsideOrders, and every HarmonicPenetrationResult carries ComponentsOutsideOrders); HarmonicPenetration, HarmonicIndices.FromPenetration normalised by HarmonicIndices.SolvedFundamentalVm over the case's own solve (the --once solve; exit 3 when it does not converge), HarmonicCompliance.AssessIeee519 with the same voltages, HarmonicImpedanceScan and HarmonicFrequencySweep at the scan bus. A triplen source (ArgumentException) exits 1 and an unknown --bus exits 2.
  • Web HARMONICS tab (SimSession.StudyHarmonics): the same default source and Study model; THD is normalised by the live frame's solved fundamental through the same HarmonicIndices.SolvedFundamentalVm (a non-converged frame is a Failure verdict); it adds the G5 planning-level verdict; it skips a case above 1,500 buses (PresentationLimits.HeavyModelBusLimit).
  • Scheduled harmonics job (AnalysisJobLibrary.Harmonics): penetration only, on the same source and model, gated at CycleOptions.HarmonicsBusLimit = 1500 buses.
  • gridsim experimental harmonic-kcl audits Y(h) V(h) = I(h) on the study penetration (physics law 12); gridsim experimental passivity checks the driving-point impedance is positive-real over 5 to 2500 Hz in 5 Hz steps.

Parameters and defaults

Name Value Unit Meaning Source symbol
Order set 3, 5, ... 49 (24 orders) order Orders solved by penetration and the scan. HarmonicModelOptions.DefaultOrders (HarmonicModelOptions.cs)
Skin coefficient, overhead and unknown 0 none k in rFactor; 0 means no skin effect. HarmonicModelOptions.SkinCoefficient
Skin coefficient, cable 0 (falls back to OHL value when 0) none k for Equipment == "cable". HarmonicModelOptions.CableSkinCoefficient
Long-line correction off flag Hyperbolic correction per branch with B != 0. HarmonicModelOptions.LongLineCorrection
Load shunts off (on in Study) flag Loads as damping shunts. HarmonicModelOptions.IncludeLoadShunts
Machine sources off (on in Study) flag Synchronous machines as 1/(j h X) to ground. HarmonicModelOptions.IncludeGeneratorSources
Balanced sequences off (on in Study) flag Sequence-correct phase shift; triplens refused. HarmonicModelOptions.BalancedHarmonicSequences
Fallback machine X''d 0.20 pu on MBase Used when a machine carries no X''d. HarmonicModelOptions.GeneratorFallbackXdPu (FaultAnalysis.DefaultSubtransientXdPu)
Sweep lowest order 1.5 order First grid point (75 Hz at 50 Hz). FrequencySweepOptions.MinOrder
Sweep highest order 50.0 order Last grid point (2.5 kHz at 50 Hz). FrequencySweepOptions.MaxOrder
Sweep step 0.1 order Grid spacing (5 Hz at 50 Hz). FrequencySweepOptions.Step
Refinement tolerance 1e-6 order Final golden-section bracket width. FrequencySweepOptions.RefineTolerance
Grid cap 100,000 points Largest accepted sweep grid. FrequencySweepOptions.MaxGridPoints
CLI source current 0.5 pu Fundamental current of the default synthetic source (6-pulse-g5). CliDefaults.DefaultHarmonicSourcePu (GridSim.Cli/CliDefaults.cs)
Coupled tolerance 1e-10 pu Largest voltage change that stops the fixed point. CoupledHarmonicPowerFlow.Solve parameter tol
Coupled iteration cap 50 passes Passes before Converged = false. CoupledHarmonicPowerFlow.Solve parameter maxIter
Norton conductance 0.05 pu Default converter shunt conductance. NortonCouplingModel constructor
Estimator sigma 1e-3 pu Default measurement standard deviation. HarmonicVoltageMeasurement.Sigma
Dense pivot floor 1e-12 times max |A_ij| relative Singular threshold of the dense oracle. NumericTolerances.RelativePivotFloor
BiCGSTAB tolerance 1e-12 relative Complex BiCGSTAB residual tolerance. NumericTolerances.DefaultComplexKrylovTolerance
Forward-inference horizon 169 hours Newest permitted takenUtc lag. ForwardInferenceGuard.HorizonHours
Heavy-model gate 1500 buses Web tab and scheduled job skip larger cases. PresentationLimits.HeavyModelBusLimit, CycleOptions.HarmonicsBusLimit

Determinism

Harmonic results are bit-identical across runs and across execution order:

  • Orders run in parallel only when the default solver is in use, each worker has its own solver, and every result is written by order index. No reduction crosses threads.
  • The scan reduces its peak after the parallel solves finish, sequentially, with a first-maximum tie-break.
  • Sweep grid points are MinOrder + p * Step, computed from the index and never accumulated. Each point is independent and written by index; the grid peak tie-break is the lowest point; the refinement is sequential with a fixed step count.
  • The cached RCM ordering is a pure function of the matrix pattern, so reusing it across orders gives the same bits as a fresh ordering. Factoring once and back-substituting per right-hand side gives the same bits as one solve per right-hand side.
  • A singular order is reported for the lowest singular order, whatever order the workers finished in.
  • THD, IHD and Compliant are sums and comparisons over a fixed index order.

What the tests pin is the same process: HarmonicFrequencySweepTests.Repeated_sweeps_are_bit_identical repeats a sweep, and the ComplexSolverReusePinTests compare cached and fresh solves. Across CPU types the mechanism is that the harmonic path (RealExpandedComplexSolver over SparseLu, System.Numerics.Complex arithmetic) uses scalar double operations with no SimdKernels call and no explicit fused multiply-add. No automated test runs the harmonic path on different CPU types or compares the dense and real-expanded complex solvers bit for bit (ComplexSolverCrossValidationTests uses tolerances of 1e-9 and 1e-8).

Invariants

Invariant Test
At h = 1 with default options Y(1) is the fundamental YBus, cell for cell. FrequencyDependentYBusTests.Y_of_order_one_reduces_to_the_fundamental_ybus, ComplexCsrBuilderPinTests.Fundamental_Y_h_build_is_unchanged_by_the_sort_port
Series reactance and line charging scale with h. FrequencyDependentYBusTests.Series_reactance_and_charging_scale_with_the_harmonic_order
Cable and overhead branches get different skin factors and different Y(h); the long-line correction is the identity on a short line and bites on a long one. HarmonicNetworkDataTests.Cable_and_ohl_get_different_skin_factors_and_different_Yh, HarmonicNetworkDataTests.Long_line_correction_is_identity_for_a_short_line_and_bites_for_a_long_one
A machine adds exactly -1/(h X) to its bus susceptance; X is X2 plus the unit transformer on the system base; converter and power-flow-only units are not stamped; a zero reactance fails loud naming the unit. HarmonicSourceImpedanceTests.Machine_stamp_adds_exactly_minus_one_over_h_x_to_the_bus_susceptance, Machine_source_reactance_is_x2_plus_unit_transformer_on_the_system_base, Converter_and_power_flow_only_units_are_not_stamped, A_zero_source_reactance_fails_loudly_naming_the_unit
The study preset turns on machines and loads and nothing else; default options add no machine terms. HarmonicSourceImpedanceTests.Study_preset_turns_on_machines_and_loads_and_nothing_else, Default_options_add_no_machine_terms, HarmonicBalancedSequenceTests.Study_preset_is_balanced
A net-exporting bus adds no conductance; a leading load is a capacitor whose susceptance grows with h; a lagging load is a reactor that falls as 1/h. HarmonicBalancedSequenceTests.A_net_exporting_bus_adds_no_conductance, A_leading_load_is_a_capacitor_whose_susceptance_grows_with_order, A_lagging_load_is_unchanged_a_reactor_whose_susceptance_falls_with_order
A negative-sequence order sees the phase shift reversed; a positive-sequence order keeps it. HarmonicBalancedSequenceTests.A_negative_sequence_order_sees_the_phase_shift_reversed, A_positive_sequence_order_keeps_the_phase_shift
A triplen Y(h) cannot be built in balanced mode; a non-integer or non-positive order is refused; penetration and the coupled flow refuse a triplen source naming it; triplen orders carry exactly zero voltage; the scan skips them. HarmonicBalancedSequenceTests.A_triplen_Y_h_cannot_be_built_in_balanced_mode, A_non_integer_or_non_positive_order_is_refused_in_balanced_mode, Penetration_refuses_a_triplen_source_in_balanced_mode_naming_it, Coupled_flow_refuses_a_triplen_source_in_balanced_mode, Study_penetration_with_a_six_pulse_source_gives_exact_zero_at_triplen_orders, Study_scan_skips_triplen_orders
Orders rotate positive, negative, zero by h mod 3. HarmonicAnalysisTests.Balanced_orders_rotate_positive_negative_zero
Penetration satisfies Y(h) V(h) = I(h); KCL balances; the scan equals the response to a unit injection. HarmonicAnalysisTests.Penetration_solves_the_network_equations_Yh_V_equals_I, Impedance_scan_equals_the_penetration_response_to_a_unit_injection, HarmonicPhysicsTests.Harmonic_kcl_holds_for_a_solved_penetration
The scan finds a parallel resonance above the fundamental. HarmonicAnalysisTests.The_scan_finds_a_parallel_resonance_above_the_fundamental
The sweep finds a resonance between integer orders at its analytic frequency and the refined magnitude matches the exact value. HarmonicFrequencySweepTests.Finds_a_resonance_between_integer_orders_at_its_analytic_frequency, Refined_peak_magnitude_matches_the_exact_single_bus_value
Sweeps are bit-identical run to run; grid points are min + k*step. HarmonicFrequencySweepTests.Repeated_sweeps_are_bit_identical, Grid_points_are_min_plus_k_step_never_accumulated
A phase shifter makes the sweep cover the negative-sequence network. HarmonicFrequencySweepTests.A_phase_shifter_sweeps_the_negative_sequence_network_too
Invalid sweep settings and an unknown bus are refused; an ungrounded network fails loud at the lowest frequency. HarmonicFrequencySweepTests.Invalid_sweep_settings_are_refused, Unknown_bus_is_refused, An_ungrounded_network_fails_loud_at_the_lowest_frequency
Every harmonic study fails loud on a singular Y(h), naming the lowest order, on the parallel and the sequential path. HarmonicSourceImpedanceTests.Penetration_on_an_ungrounded_radial_feeder_throws_naming_the_lowest_order, Penetration_singular_order_is_deterministic_on_the_sequential_path_too, Impedance_scan_on_an_ungrounded_radial_feeder_throws, Coupled_harmonic_flow_on_an_ungrounded_radial_feeder_throws, WebHarmonicsStudyFailureTests.Ungrounded_network_study_is_a_visible_failure_with_the_engine_message
The study model solves a radial feeder with real distortion. HarmonicSourceImpedanceTests.Study_model_solves_the_radial_feeder_with_real_distortion
The three complex solvers agree and satisfy A x = b; all return null on a singular system. ComplexSolverCrossValidationTests.All_three_complex_solvers_agree_and_satisfy_Ax_equals_b, ComplexSolverSingularContractTests.All_three_solvers_return_null_on_a_singular_system
A cached ordering and factor-once reuse are bit-identical to fresh solves; penetration and scan are unchanged end to end. ComplexSolverReusePinTests.Cached_ordering_across_same_pattern_orders_matches_a_fresh_solver_bit_for_bit, Factor_once_multi_rhs_matches_solve_per_rhs_bit_for_bit, Penetration_is_unchanged_end_to_end, Impedance_scan_is_unchanged_end_to_end
THD is the root-sum-square of harmonic voltages over the fundamental; the 6-pulse K-factor is in the 7 to 10 band and a pure fundamental is 1; sharpness is high for a tall resonance. HarmonicIndicesTests.Voltage_thd_is_the_rms_of_the_harmonic_voltages_over_the_fundamental, Six_pulse_load_has_a_transformer_k_factor_near_nine, Damping_sharpness_is_high_for_a_tall_resonance
IEEE 519 limits tighten with voltage level; the same distortion passes at LV and fails at EHV. HarmonicIndicesTests.Ieee519_voltage_limits_tighten_with_voltage_level, Compliance_passes_at_lv_and_fails_the_same_distortion_at_ehv
An unknown voltage level is judged at the strictest tier and never certified, for IEEE 519 and G5, and the export flags it. HarmonicComplianceUnknownKvTests.An_unknown_voltage_level_is_judged_at_the_strictest_tier_and_never_certified, Even_negligible_distortion_cannot_be_certified_without_a_voltage_level, A_known_voltage_level_is_unchanged, G55_verdict_follows_the_same_rule, Export_flags_the_unknown_voltage_level
The coupled flow with no coupling equals linear penetration; a damping coupling reduces the resonant voltage and converges; the coupling model is tagged as assumed. HarmonicCoupledTests.With_no_coupling_it_matches_linear_penetration, A_damping_coupling_model_reduces_the_resonant_voltage_and_converges, The_coupling_model_is_honestly_tagged_as_assumed
The estimator recovers one and two known injections, rejects an under-determined problem, refuses indistinguishable sources and never fits against a zero impedance column. HarmonicStateEstimatorTests.Recovers_a_single_known_injection_to_machine_precision, Recovers_two_simultaneous_sources, Rejects_an_under_determined_problem, HarmonicStateEstimatorFailLoudTests.Indistinguishable_candidate_sources_are_refused_not_zeroed, The_estimator_no_longer_substitutes_a_zero_impedance_column
A balanced triplen is pure zero sequence and a balanced fifth pure negative sequence; an unbalanced injection yields all three sequences. ThreePhaseHarmonicsTests.A_balanced_triplen_is_pure_zero_sequence, A_balanced_fifth_is_pure_negative_sequence, An_unbalanced_injection_produces_all_three_sequences, A_balanced_diagonal_feeder_keeps_the_three_phase_magnitudes_equal
A source set round-trips; a wrong schema and a fresh timestamp are refused; a source on an absent bus is flagged. HarmonicSourceSetTests.Round_trips_through_json, Rejects_a_wrong_schema_version, A_fresh_timestamp_is_refused_but_a_historical_one_is_accepted, Validate_flags_a_source_on_a_bus_the_model_lacks
The G5 planning levels follow G5 Issue 5 Table 1; the three -g5 profiles reproduce the printed THDI (the active-front-end one within rounding); the default synthetic source is 6-pulse-g5 and ideal is the 1/h spectrum. S3HarmonicAndEventGroundingTests.G55_planning_level_follows_G5_Issue_5_Table_1, G5_six_pulse_profile_reproduces_the_printed_THDI, G5_twelve_pulse_profile_reproduces_the_printed_THDI, G5_active_front_end_profile_is_within_the_rounding_of_the_printed_THDI; R1DefaultsTests.N131_the_default_synthetic_source_is_the_g5_six_pulse_profile_and_ideal_is_the_1_over_h
Per-converter sources: each component is the G5 table value times I1 at phase 0; the CLI names the sources and the omitted triplens, exits 1 on a case with no converter and 2 on a usage error N036N075ConverterHarmonicSourcesTests.Each_component_is_the_g5_table_value_times_i1_at_phase_zero, Cli_converter_sources_on_the_uk_case_names_the_sources_and_the_omissions, Cli_converter_sources_on_a_case_with_no_converter_exits_1, Cli_converter_sources_usage_errors_exit_2
The 6-pulse library spectrum injects 1/h; the heat-pump spectrum is low-order odd and scales with the fundamental. HarmonicSourceSetTests.The_six_pulse_library_spectrum_injects_one_over_h, The_heat_pump_inverter_spectrum_is_low_order_odd_and_scales_with_the_fundamental
The export contract is locked, records the machine reactances and loads, and carries the refined sweep peak. HarmonicExportContractTests.Export_locks_the_harmonic_export_contract, HarmonicSourceImpedanceTests.Export_records_the_machine_reactances_and_loads_the_study_used, HarmonicFrequencySweepTests.Export_records_the_refined_sweep_peak
The --bus flag is read through the fail-loud integer parser FlagInt. The test checks the source text of Program.cs for that call; it does not run the CLI. CliFailLoudFlagContractTests.Harmonics_bus_flag_is_parsed_fail_loud

Worked example

The run is gridsim harmonics case9 --enableExport=docs/_captures/harmonics/case9-export.json, captured in docs/_captures/harmonics/case9-export.json and case9-export.txt. The default synthetic source is the G5 profile 6-pulse-g5 (5th 31.4 %, 7th 10.9 %, odd non-triplen orders up to 49): one 6-pulse source of 0.5 pu at bus 9, the largest-demand bus (125 MW). The export block harmonicModel records what Y(h) used beyond the case: three machines with xSystemPu 0.08080808080808081 (bus 1), 0.10416666666666667 (bus 2) and 0.15625 (bus 3), and loads at buses 5, 7 and 9 of 90 + j30, 100 + j35 and 125 + j50 (MW, MVAr). Every bus is 345 kV.

Bus 9 at order 7. The diagonal terms the study model adds at bus 9 at h = 7 are, from the export numbers and the formulas above:

load  g = 125 / 100 = 1.25 pu             b = -(50 / 7) / 100 = -0.0714286 pu

and the machine at bus 1 contributes b = -1 / (7 * 0.08080808080808081) = -1.7678571 pu to bus 1. The injected current at order 7 is I7 = 0.5 * 10.9 / 100 = 0.0545 pu (the exported spectrum entry is magnitudePercent 10.9). The exported voltage at bus 9, order 7 is

    {
      "order": 7,
      "bus": 9,
      "vmPu": 0.035837397144042,
      "vaDeg": 4.0772958508525905
    },

Because bus 9 is the only injection point, the voltage there is the driving-point impedance times the current:

|Z_99(7)| = |V9(7)| / |I7| = 0.035837397144042 / 0.0545 = 0.6575669

The exported resonance block gives zMag 0.6575669200741651 for the whole-number scan at bus 9, which peaks at order 7. The quotient is 0.6575669200741652, so the two agree to 15 significant digits and differ by 1e-16: the scan solve Y(7) x = e_9 and the penetration solve Y(7) V = I are the same linear system scaled by I7.

THD at bus 9. The exported voltage entries for bus 9 (the G5 profile injects all 16 non-triplen orders from 5 to 49; orders that are multiples of 3 are exactly zero and are not exported):

Order h vmPu (pu) vmPu^2
5 0.04860883648700535 2.362819e-03
7 0.035837397144042 1.284319e-03
11 0.015562805056876931 2.422009e-04
13 0.005086517066291241 2.587266e-05
17 0.004864959318851337 2.366783e-05
19 0.0026758684535858356 7.160272e-06
23 0.0010449408875055702 1.091901e-06
25 0.0009351290269347221 8.744663e-07
29 0.0004670035952596365 2.180924e-07
31 0.0005037319283338796 2.537459e-07
35 0.0003759888281140457 1.413676e-07
37 0.00029453345914916843 8.674996e-08
41 0.00021059058577289037 4.434839e-08
43 0.00020003715091016292 4.001486e-08
47 0.00013642671826800105 1.861225e-08
49 8.702365238770053e-05 7.573116e-09
sum of vmPu^2        = 3.948816549e-03       (from the unrounded vmPu values)
sqrt(sum)            = 0.06283960971
V_1(bus 9)           = 0.9956308580 pu       (the solved fundamental voltage of bus 9)
THD_V(bus 9)         = 0.06283960971 / 0.9956308580 * 100 = 6.311536972 %

The exported indices block gives worstThdPct 6.311536972429553 at worstBusId 9, and the console prints 6.31%. The two agree.

Compliance at bus 9. The largest single harmonic is the 5th: IHD = 0.04860883648700535 / 0.9956308580 * 100 = 4.8822 %. The bus is 345 kV, above 161 kV, so the limits are 1.5 % THD and 1.0 % single harmonic. The export entry is

    {
      "bus": 9,
      "baseKv": 345,
      "thdPct": 6.311536972429553,
      "thdLimitPct": 1.5,
      "worstIhdPct": 4.882214737929257,
      "worstIhdOrder": 5,
      "ihdLimitPct": 1,
      "compliant": false,
      "voltageLevelKnown": true
    }

Both tests fail (6.3115 > 1.5 and 4.8822 > 1.0). The console count is 0/9 buses compliant.

Sweep. The sweep grid has floor((50 - 1.5)/0.1 + 1e-9) + 1 = 486 points, matching gridPoints. The grid peak is bracketed by its two neighbours, 0.2 orders wide, and the golden-section search narrows it to 1e-6 order. It lands at peakOrder 7.47497016807171 (peakHz 448.4982100843026, which is 7.47497016807171 * 60, the case's 60 Hz) with zMag 0.687623565377445, above the whole-number peak 0.6575669 at order 7, as the refinement guarantees.

Sharpness. The whole-number scan covers the 16 non-triplen orders; sharpness 3.83763679770113 is 0.6575669 / median(|Z|), so the median of the 16 magnitudes is 0.6575669 / 3.83763679770113 = 0.171347.

The captured sources are in docs/_captures/harmonics/; gb-full.txt shows the same lines on the 3539-bus model, where the sweep peak at h=4.9818 (157.445 pu) is 40.5 % above the whole-number peak at order 5 (112.064 pu).

Source map

File Type Responsibility
src/GridSim.Core/Harmonics/HarmonicModelOptions.cs HarmonicModelOptions Order set, skin, long-line, load-shunt, machine-source and balanced-sequence switches; the Study preset; SkinFactor.
src/GridSim.Core/Harmonics/FrequencyDependentYBus.cs FrequencyDependentYBus Y(h) assembly: branch, shunt, load, machine and long-line terms; BuildSequence; BalancedShiftSign; machine reactance.
src/GridSim.Core/PowerFlow/AdmittanceStamp.cs AdmittanceStamp The shared pi-model stamp with tap, phase shift, h and rFactor.
src/GridSim.Core/Harmonics/HarmonicSource.cs HarmonicSource, HarmonicComponent, HarmonicSourceLibrary Source spectra, InjectionAt, and the assumed-typical library.
src/GridSim.Core/Harmonics/HarmonicSequence.cs HarmonicSequence, HarmonicSequenceKind Positive, negative and zero sequence by h mod 3.
src/GridSim.Core/Harmonics/HarmonicPenetration.cs HarmonicPenetration, HarmonicPenetrationResult Linear penetration solve and the triplen refusal.
src/GridSim.Core/Harmonics/HarmonicImpedanceScan.cs HarmonicImpedanceScan, ImpedanceScanResult Driving-point impedance scan at whole orders.
src/GridSim.Core/Harmonics/HarmonicFrequencySweep.cs HarmonicFrequencySweep, FrequencySweepOptions, FrequencySweepResult Fine sweep and golden-section refinement.
src/GridSim.Core/Harmonics/HarmonicIndices.cs HarmonicIndices THD, IHD, K-factor, damping sharpness.
src/GridSim.Core/Harmonics/HarmonicCompliance.cs HarmonicCompliance, BusComplianceResult IEEE 519 limits and the G5 Issue 5 planning levels and verdicts.
src/GridSim.Core/Harmonics/CoupledHarmonicPowerFlow.cs CoupledHarmonicPowerFlow, IHarmonicCouplingModel, NortonCouplingModel Coupled iterative harmonic flow.
src/GridSim.Core/Harmonics/ThreePhaseHarmonics.cs ThreePhaseHarmonicPenetration, ThreePhaseHarmonicSource Three-phase penetration and the sequence view.
src/GridSim.Core/Harmonics/HarmonicStateEstimator.cs HarmonicStateEstimator Complex weighted least-squares source estimation.
src/GridSim.Core/Harmonics/SingularHarmonicNetworkException.cs SingularHarmonicNetworkException The fail-loud error for a singular Y(h).
src/GridSim.Core/Abstractions/IComplexLinearSolver.cs IComplexLinearSolver, IComplexLinearFactorization The complex-solver seam.
src/GridSim.Core/Numerics/ComplexLinearSolvers.cs DenseComplexLuSolver, RealExpandedComplexSolver, SparseComplexBiCgStabSolver The three solver implementations.
src/GridSim.Core/IO/HarmonicSourceSet.cs HarmonicSourceSet gridsim-harmonics/1 load, validation and the forward-inference guard.
src/GridSim.Core/IO/HarmonicExport.cs HarmonicExport gridsim-harmonic-export/1 writer.
src/GridSim.Cli/Program.cs RunHarmonics The harmonics verb.
src/GridSim.Cli/CliDefaults.cs CliDefaults.DefaultHarmonicSourcePu The default source current.
src/GridSim.Core/Scheduling/AnalysisJobLibrary.cs AnalysisJobLibrary.Harmonics The scheduled penetration job.
src/GridSim.Web/Sessions/SimSession.cs StudyHarmonics The Web HARMONICS tab study.
tools/crossval/crossval_harmonics.py script Independent NumPy rebuild of Y(h) and the voltages from an export plus a case directory and a source file.

Limits

  • The harmonics verb is positive-sequence and balanced, and a source with a non-zero triplen component is refused. The three-phase penetration runs as dist3ph <feeder> harmonics, with one balanced library source.
  • The three-phase penetration has no transformer, load or machine term (laterals, regulators and transformers are refused; loads are left out of Y(h)), and its sequence content is not validated against an independent three-phase reference.
  • The coupled harmonic flow has one coupling model, the placeholder NortonCouplingModel, no CLI verb and no independent coupled-solver validation.
  • The harmonic state estimator has no input format for dated harmonic voltage measurements, no CLI verb and no independent reference.
  • A source spectrum component at an order outside HarmonicModelOptions.Orders (for example 2, 4, 53 or 55) is not injected by HarmonicPenetration.Solve; the result lists it in ComponentsOutsideOrders, and the CLI and RefuseComponentsOutsideOrders refuse it.
  • No test pins the IEEE 519 tier boundaries at 1, 69 and 161 kV. No CLI test covers the harmonics: FAILED - path.
  • No machine resistance is modelled, so resonance peaks are sharper than a machine with resistance would give.
  • Only the headline G5 Issue 5 THD planning levels (Table 1) are encoded, not the per-order tables.
  • The per-converter sources use full-load G5 profiles at every level, and the active-front-end internal impedance has no sourced value.
  • The supraharmonic band (2 to 150 kHz) is not modelled; the sweep ends at h = 50 (2.5 kHz at 50 Hz).