Every verb and flag the gridsim command line tool accepts, checked against the argument parsing in src/GridSim.Cli/Program.cs, VerbHelp.cs, VerbFlags.cs, LicenceCli.cs and StorageCli.cs (the project is GridSim.Cli; the binary it builds is gridsim). gridsim means the installed binary; from a checkout it is dotnet run --project src/GridSim.Cli -c Release -- (ch. 1).

This chapter is compiled into the binary. gridsim <verb> --help prints the verb's section, and the flags a section names are the flags the verb accepts (see Parsing rules), so a flag the code reads always has a row here.

Verb index

Verb names are case-insensitive (licence excepted, which must be lower case). Every verb dispatched in Program.cs has a section below.

Group Verbs
Software licence licence
Help help (and gridsim <verb> --help)
Running a case no verb
Contingency and analysis trip, screen, nminus1, nminus2, n-1-1, nminus1-sweep, stress, chain, cycle
Network analysis pf, ptdf, lodf, dcpf, dcopf, acopf, acopf-full, scuc, scopf, qsts, hosting, cpf, taps, restore, losses, dist3ph (experimental)
Physics and protection physics-check, conformance, protection-check, grade, fault, iec60909, experimental
Frequency and dynamics freq, replay, transient, domains, stability, modal, fit-frequency, inertia-placement
Harmonics, impedance and EMT harmonics, impedance-stability, emt
Evidence replay-event, scenario, h0-study, fleet, evidence
Data gda, gda-replay, synth, export, convert, validate, zonal, pmu-ingest (experimental), pmu-estimate, estimate, estimate-noise-floor, crossval
Real-time and telemetry serve, interpose
Benchmarking and preflight bench, bench --estimate, bench --perf, gpucheck, simdcheck, batchsolve, audit, compliance
Electrical references ref

gridsim --help (or -h, or gridsim help) prints the verb list, then exits 0. gridsim <verb> --help, gridsim <verb> -h and gridsim help <verb> print that verb's section of this chapter (see help).

Parsing rules and exit codes

  • Unknown flag names fail loud. Every --flag is checked against the set of flags the CLI knows. A misspelling prints error: unknown flag '<flag>' (misspelled?) and exits 2. The message names gridsim <verb> --help when the first word is a verb (gridsim --help otherwise) and this chapter, docs/manual/0019 CLI reference.md.
  • A flag of another verb fails loud too. Each verb takes the flags its own section below names (the text gridsim <verb> --help prints), its group's shared notes, the global switches and, on the result-file verbs, --json, --csv and --out. Any other flag prints error: <verb> does not take <flag> (it is not one of <verb>'s flags, so it would be silently ignored) and exits 2, so trip --top 5 stops instead of running without --top. The no-verb run (gridsim case14 --once) takes its one case and the global switches only: any other flag, a second case or an extra word prints error: the case run (no verb) takes one case and the global switches only, so '<token>' would be silently ignored and exits 2 (GR-202).
  • Each value flag once. A value flag given twice (--top 5 ... --top 10) prints error: <flag> given more than once and exits 2; it used to take the first and drop the second without a word (GR-670). The repeatable flags (--event, --bess) say so in their rows.
  • Flags have two dashes. A single-dash word (-bus 5) prints error: unknown option '-bus': flags start with two dashes and exits 2 (GR-683). A negative number (-5, -0.25) is a value, and -h (help) and -d (--dir) are the two short forms.
  • --name=value works for every flag and is treated exactly like --name value.
  • Numeric flags fail loud. A flag present with an unparseable value (--ticks 5O) prints error: <flag> expected <kind> but got '<value>' and exits 2. Numbers parse in the invariant culture (. is the decimal point). NaN and Infinity are refused.
  • A value flag present with no value fails loud. If a numeric or string flag (--minutes, --out, --catalog, ...) is the last token, or is followed by another --flag, the CLI prints error: <flag> expected <kind> but got '' and exits 2. Only an absent flag takes its default, so a shell variable that expanded to nothing is caught.
  • Enum flags fail loud. --rule, --converter, --criterion, --solver, --method and --gpu=<vendor> accept only the values listed for them; anything else exits 2.
  • Boolean flags are presence-only and may appear anywhere on the line.
  • Positional arguments (a case name, an event id) are the first free token that is neither a flag nor a flag's value. A verb that takes one case refuses a second (exit 2) rather than ignoring it (GR-676).
  • Usage banners go to stderr. A verb run without a required argument prints its usage lines on stderr and exits 2; stdout stays empty (GR-687).

Captured refusals (the text is the program's own):

$ gridsim nminus1 case14 --no-such-flag
error: unknown flag '--no-such-flag' (misspelled?). Run 'gridsim nminus1 --help' for the flags nminus1 takes, or see docs/manual/0019 CLI reference.md.
[exit 2]
$ gridsim trip --top 5
error: trip does not take --top (it is not one of trip's flags, so it would be silently ignored). Run 'gridsim trip --help' for the flags trip takes, or see docs/manual/0019 CLI reference.md.
[exit 2]
Exit code Meaning
0 Success.
1 Input error: a missing or unloadable file or case folder, invalid data in a case (for example a generator whose Pmin is above its Pmax, refused by dcopf and acopf), an invalid measurement set or window file (serve skips it and exits 1 at the end), a case that fails to load inside a batch run (bench, nminus1-sweep, stress, transient --cases), a requested result file that cannot be written. Also a failed check: the physics-law gate (physics-check, conformance), a right-half-plane eigenvalue (modal), a missed High tier (cycle), a batched result off the CPU reference (batchsolve), a singular harmonic network (harmonics), a violated experimental law, a bus the iec60909 --all-buses sweep cannot study.
2 Usage error: an unknown flag, a flag of another verb, a bad flag value, an unknown verb, an unknown case name (one rule on every verb), a bus id that is not in the case (stability --fault-bus, fault --bus, protection-check --fault-bus, iec60909 --bus, a --bess site), a licence refusal (a network above the tier's bus limit, or a key licence import rejects), a forward-inference rejection (REJECTED (forward inference), on every verb that reads dated data).
3 A verdict or convergence failure: a baseline that is not Reproduced, an estimate that is not converged or not observable, a crossval mismatch, non-converged steps (gda-replay, transient, chain), an EMT numerical failure, an infeasible dispatch (dcopf, acopf), a contingency verdict that is not secure (nminus1, nminus2, n-1-1, nminus1-sweep: the base case or any screened outage violates a limit, islands or does not solve; screen: any loss breaches a frequency limit), and a power flow that did not converge on the verbs that report it: the default solve report, --enableExport, a --ticks run with any tick that did not converge, pf, losses, taps, cpf (the base load does not converge), gda --solve and --all-gsps, serve with failed windows, fault and protection-check (including a converter current iteration that does not converge), the stability and modal verbs, impedance-stability, the experimental models and conformance (a case that stops converging or cannot be run). Also a failed probe or solve in gpucheck, bench and bench --estimate.
77 crossval only: the environment cannot run the check (no Python, or no pandapower).

A verb's own section lists its exceptions. physics-check exits 1, not 3, on a converged state that fails the hard-law gate (a physically impossible state); a power flow that did not converge exits 3.

Default output location. A verb that writes files writes its default output under results/ in the current directory (results/<verb>-<case> folders, results/stress.md, results/gridviz.json, results/exports/..., as each section's --out default says) and creates the folder when needed. An explicit --out <path> (or --enableExport=<path>, --json, --csv) is used exactly as given. The desktop and web apps find run folders in a results/ folder up to seven levels above themselves, so runs started from the repository root are discovered. synth follows the same rule: with no --out it writes results/synth/gb-synthetic (N256; it used to write the bundled data/gb-synthetic beside the executable, replacing the shipped case).

MATPOWER parse notes. Every verb that loads a MATPOWER .m file (a path, a bundled .m name, or a built-in name backed by one such as gb-reduced-29) prints the parser's notes on stderr, one note: <file>: <text> line each, before its own output: the nominal frequency it assumed (MATPOWER files carry none), DC lines read but not modelled (with a warning: line as well), isolated buses dropped, out-of-service generators kept, reference buses with no in-service unit, PV buses solved as PQ and similar. stdout is not affected. The built-in IEEE names (case14, ...) are parsed inside the program from embedded copies and print no notes; their nominal frequency is the assumed 50 Hz, except case9 / ieee9: the WSCC 9-bus system is a 60 Hz system and carries 60 Hz (October 2026, N017). A .m file's frequency can be declared with the global --frequency-hz <Hz> switch (N187, below); with it the "nominal frequency not given" note is not printed.

Result files

The verbs listed below can write their result to a file as well as print it. The console output does not change: every message about the files goes to stderr, so stdout is the same with or without these flags.

Flag Default Meaning
--json <file.json> - The whole result as one JSON document.
--csv <file.csv> - The result as CSV files (layout below).
--out <file.json\|file.csv> - The same, with the format chosen by the extension.

The verbs: dcopf, acopf, acopf-full, scuc, scopf, qsts, hosting, cpf, taps, restore, ptdf, lodf, dcpf, iec60909, fault, protection-check, grade, nminus1, nminus2, n-1-1, cycle, freq, domains, inertia-placement, dist3ph, losses, physics-check, experimental, convert (--json and --csv only: its second argument is already its output), validate, zonal, pf, pmu-ingest and pmu-estimate. serve does not take them: it is a resident stream that reports each measurement window as it arrives and may run without end, so one document written when it stops does not fit it. On every other verb --json and --csv exit 2 (modal's own --json and screen's own --csv excepted: screen --csv <file> writes its screening table, and modal --json prints JSON on the console and takes no file, modal --export <file.json> being its file output).

  • What is written. The verb's summary values and its tables, from the same values it prints, but complete: where the console lists the top N rows (dispatch, distribution factors, outages, branch losses, traced loads), the file has every row, and no number is rounded to the console's display precision.
  • JSON. One document: {"schema": "gridsim-cli-result/1", "tool": "gridsim <version>+<commit>", "verb", "args", "exitCode", "summary": {key: value}, "tables": {name: [{column: value}, ...]}}. Keys and column names are snake_case.
  • CSV. The verb's main table goes to the named file, every other table beside it as <stem>-<table>.csv, and the summary as <stem>-summary.csv (key,value, starting with the rows verb and exit_code). A verb with no table writes only the summary, to the named file. Invariant culture (. decimal point); a field holding a comma, a quote or a line break is quoted; booleans are true / false; an empty field is a value that does not apply.
  • Numbers are written in round-trip form, so reading the file back gives exactly the bits GridSim computed. JSON has no NaN or infinity, so those are written as the strings "NaN", "Infinity" and "-Infinity" (in CSV, the same words).
  • When. The files are written once the verb has finished its result, including a result whose verdict fails (NOT SECURE, GATE: FAIL, INFEASIBLE, NOT GRADED, a failed round trip): the exit code is inside, so a script can read why. A run that stops before it has a result (a usage error, a case that does not load, a solve that does not converge) writes nothing. When the verb itself ends without a result it says so on stderr ([<verb>] no result file written: ...); a refusal that ends the run at once (a usage error or an unknown case, exit 2) prints only its own error line. A file of the same name is replaced; a missing folder is created. The rules of Output files apply.
  • Errors. A flag with no value, a name with the wrong extension, the same flag twice, or two flags naming one file exit 2 before anything runs. A file that cannot be written exits 1.

Python

python/gridsim is a pure-Python package (standard library only) that runs these verbs and reads their result document, so scripts get the CLI's numbers bit for bit without scraping the console. It runs gridsim <verb> <args...> --json <temporary file> and returns a Result with verb, args, tool, exit_code, summary (a dict), tables (table name to a list of row dicts), stdout and stderr; the strings "NaN", "Infinity" and "-Infinity" come back as floats. A run that writes no result raises GridSimError with its exit code and its last stderr line.

import sys; sys.path.insert(0, "python")   # or put python/ on PYTHONPATH
import gridsim
gs = gridsim.GridSim()          # the CLI: cli=..., GRIDSIM_CLI, gridsim on the PATH, or this checkout's build
r = gs.pf("case14")             # gs.run("pf", "case14"); every result-file verb has a method (n_1_1, physics_check, ...)
r.summary["loss_mw"], r.table("buses")[0]["vm_pu"]

It wraps exactly the verbs listed above (a test keeps its list equal to the CLI's) and refuses --json, --csv and --out, which it gives itself. The other verbs write their own folders or reports, or run without end, so they are run with subprocess and their files read. Its tests: python -m unittest discover -s python/tests (the ones that run the real CLI skip when none is found). See python/README.md.

Output files

Every file and folder the CLI writes follows one rule (src/GridSim.Cli/CliFiles.cs), whether its path is a default under results/ or one you named with --out, --export, --csv, --json, --pv-out, --out-store, --dump-catalog or --enableExport:

  • The folder is created. A missing parent folder is created, so --export results/new/x.json works.
  • An existing output is replaced. A re-run replaces its own outputs, default or named: naming a file asks for it.
  • An input is never replaced. The CLI refuses, with exit 2 and error: refusing to write the <what> to '<path>': <why>, before anything is written to that path, any output that is a file the command line names as an input (any existing file named by an argument that is not the value of one of the output flags above), an existing file inside a case folder the command line names (a folder holding system.json), an existing file of the bundled data/ folder next to the executable, or an existing folder.

Three writers keep stricter rules of their own. interpose never replaces a captured window: a clash is kept under a -dupN name. convert and the JSON case writer never write over an existing case (exit 1). synth regenerates its case folder (by default results/synth/gb-synthetic); the bundled data/gb-synthetic is rewritten only when --out names it.

A run that writes a report FILE (bench, nminus1-sweep, stress, chain) writes its metadata beside the report as <report>.run-metadata.json (results/bench.md gets results/bench.run-metadata.json), so reports that share a folder keep their own metadata. A run that writes a run FOLDER writes run-metadata.json inside it.

Case arguments

Verbs that take a <case> resolve it through one loader: the built-in names case9/ieee9, case14, case30, case57, case118, case300, case145, case24/rts, cigre; uk/gb/gb-reduced (data/uk); gb-full (data/gb-full); gb-synthetic/synthetic (data/gb-synthetic, with its asset and protection bundle, exactly as --dir data/gb-synthetic, for every verb; N316, October 2026: the name used to build the network in memory, a different branch order, an unbalanced dispatch and no bundle, for every verb but trip); the published GB reference networks under data/matpower/gb (provenance and licences in its README.md): gb-reduced-29 (Strathclyde GBreducednetwork.m, 29 buses), gb-network-2224 (Edinburgh GBnetwork.m, 2,224 buses), pypsa-gb-reduced (PyPSA-GB's own 29-bus network from its CSV files, with GBreducednetwork.m's demand and generation; its import notes are printed on stderr) and pypsa-gb-zonal (a transport model: every solving verb refuses it with exit 1, see zonal); a JSON case folder (any folder with a system.json); a MATPOWER .m file; or a JSON v2 case manifest (.json).

A .m argument is taken as a path first, then as a path under data/matpower/ (for example pegase/case1354pegase.m), then, for a bare file name such as case33bw.m, searched for through the data/matpower/ subfolders in sorted order. A bare name that matches two files exits 2 and lists them.

JSON v2 cases. A <case> argument ending in .json is a JSON v2 case manifest ("schema": "gridsim-case/2", technical ch. 28). The manifest, the network files it lists (relative to the manifest, inside its folder) and the library files it imports (relative to the shipped data folder) are validated exactly as validate validates them, then the case is built by the same model builder as a v1 case folder, so a v2 case and its v1 equivalent give the same model and the same numbers bit for bit. Any problem refuses the load with every problem listed (exit 1): a schema error (for example a bus without baseKv, required in v2), a template reference that does not resolve, a placeholder template bound to an element, an override of an unknown parameter, and v2 content the model does not carry (generator subtransientXdPu / negativeSeqXPu, line and transformer type, transformer zero-sequence data, an out-of-service line or transformer, a grid-code or solver profile). Notes, such as the revision an unpinned import resolved to, are printed on stderr as note: <file>: ....

How each verb takes its case.

Form Verbs
Positional <case> or --dir <folder>. Both together exit 2 unless they name the same folder (uk --dir data/uk). A --dir folder that does not exist exits 1 with error: <verb>: case folder not found: '<folder>' (full path ...) before any report file is opened; a --dir with no value exits 2. At most one positional case (a second exits 2). trip, screen, nminus1, nminus2, n-1-1, domains, export, nminus1-sweep, stress, chain, cycle, emt, harmonics, impedance-stability, stability, modal
A positional case only; --dir exits 2 as a flag of another verb. pf, ptdf, lodf, dcpf, dcopf, acopf, cpf, taps, restore, losses, physics-check, protection-check, fault, iec60909, experimental, estimate, crossval, serve, convert (first argument)
A named option instead of a positional. gda-replay (--case), h0-study (--dir, default data/gb-synthetic), transient (a positional .m resolved as every .m argument is, or --cases), dist3ph (a feeder file, a radial .m or a case folder)

An unknown case name: one rule on every verb. A case argument that names no case at all (not a built-in name, not an existing folder, and not a .m or .json path) is a usage error: exit 2, naming the case and listing the built-in names. This holds on every verb that takes a case (chain, emt, physics-check, protection-check, fault, iec60909, ptdf, lodf, dcpf, pf, dcopf, acopf, cpf, taps, restore, experimental, estimate, crossval, serve, gda-replay, convert and the rest), and on the no-verb run (error: unknown command or case). trip reads an unmatched word as a generator name and exits 2 listing the generators; export reads it as an output path and exits 2. In a batch run over several cases (nminus1-sweep --all, stress --all, transient --cases, bench), a case that does not load is a LOAD FAIL row and the run exits 1 at the end; one named case that is unknown (stress nosuchcase, transient nosuchcase) exits 2 before the run starts. The verbs whose argument is a file or folder rather than a case name (dist3ph, zonal, validate, pmu-ingest) report one that is missing as an input error (exit 1).

A case file or folder that is named but missing or cannot be loaded (a .m path that does not exist, a folder with no buses.json, a malformed .m) exits 1 on every verb, stability and modal included. An existing folder that is not a built-in name is always read as a case folder, even with no system.json: gridsim pf docs exits 1 naming the file the folder lacks (D-DOC-151; the network analysis verbs, dcopf, ptdf / lodf, experimental, physics-check, protection-check, fault and crossval used to answer unknown case 'docs', exit 2).

$ gridsim screen nosuchcase
error: screen: unknown case 'nosuchcase' (built-in names: case118, case14, case145, case24, case30, case300, case57, case9, cigre, gb, gb-full, gb-network-2224, gb-reduced, gb-reduced-29, gb-synthetic, ieee9, pypsa-gb-reduced, pypsa-gb-zonal, rts, synthetic, uk; or a case folder, or a MATPOWER .m file, or a JSON v2 case manifest .json)
[exit 2]

Licence limit. A user network above the tier's bus limit is refused with exit 2 when it is loaded (licence). Built-in cases and the bundled networks are never counted.

Solver selection

Where a verb picks the Newton-Raphson engine itself it uses the shared rule in SolverSelector (src/GridSim.Core/PowerFlow/SolverSelector.cs, reached through SolverBackend.Solver, NewtonSolver and Pick). On the CPU every Newton power flow runs on the sparse engine (SolverSelector.DefaultSparseThreshold is 0). Sites that route through SolverBackend.Solver send a strictly radial network to the backward/forward sweep first. On the CPU the dense and sparse engines are bit-identical, so the rule changes speed and memory, not numbers. The dense engine stays available by explicit choice: gda --solve --dense, the bench verbs, and the web and desktop solver pickers.

The exceptions:

  • On a GPU backend (--gpu) the routing uses the crossover SolverSelector.DenseSparseCrossoverBuses (200 buses): dense up to it, sparse above, because the dense engine there is the device's dense LU, which is outside the bit-identity contract.
  • A solve export (--enableExport, and the solve crossval exports) keeps that crossover on every backend, because only the dense engine records the Jacobian in the trace.
  • The live per-tick loop in LiveSim (transient, the cycle base solve) switches to sparse above 1,500 buses; there the engine also picks the solve options.
  • bench --estimate forces each estimator backend explicitly, and the state estimator keeps its own 200-bus dense / sparse switch.
  • gda --solve --dense or --sparse forces the engine.

Contingency options. nminus1, nminus2, n-1-1, nminus1-sweep, stress, chain and cpf all solve with one option set (ContingencyAnalysis.StudyOptions): 100 iterations, generator reactive limits enforced, tolerance 1e-8 pu, and the on-load tap changer loop around the engine, so each post-outage or scaled state is the tap-regulated steady state that the default case solve reports. NETS SQSS v2.10 section 6.2 judges post-fault voltages after the Grid Supply Point tap changers have acted. On a case with no tap changers the loop is skipped and the numbers are the engine's own, bit for bit.

Global switches

Parsed before the verb and usable with any command. --cpu and --gpu may also come before the verb (gridsim --cpu dcopf case9 --prices): they are taken off the argument list before any verb-specific flag check, so a verb's own flags are checked against the verb (before October 2026 that run was refused, because the --prices check read --cpu as the verb).

Flag Default Meaning
--cpu on CPU linear-solver backends: dense LU, and a direct sparse LU (CpuSparseLuSolver, reverse Cuthill-McKee ordering, partial pivoting) for the sparse engine. ILU0-BiCGSTAB runs only if the LU reports the step singular.
--gpu off Auto-select a GPU backend, AMD-first: ROCm, then OpenCL, then CUDA, else fall back to CPU with a warning. A GPU sparse solve that gives up is retried on the exact CPU LU before the ILU0-BiCGSTAB fallback. GPU arithmetic is outside the bit-identity contract.
--gpu=rocm / --gpu=opencl / --gpu=cuda off Force a vendor; an absent device (or an OpenCL device without FP64) exits 2 rather than falling back to the CPU (bench and gpucheck report it instead). --gpu=auto and --gpu=cpu are also accepted; any other vendor name exits 2.
--inertia-model lumped\|distributed lumped Frequency-dynamics inertia model (lumped-scalar and scalar are aliases of lumped; any other value exits 2). Only trip integrates the distributed model; transient reports the domain split but integrates lumped; evidence, scenario, h0-study, fleet and replay-event warn and run lumped.
--asset-dynamics[=on\|off] off Opt into the authored per-asset dynamics fleet (inverter FFR, Loss-of-Mains trips, placed protection devices). A bare flag means on. Honoured by trip and transient. A case with no asset bundle (no asset-classes.json / asset-bindings.json and no protections.json) has nothing to enable: exit 1. trip refuses it together with --inertia-model distributed (exit 2).
--forming none\|vsm\|droop none Grid-forming frequency formation. Honoured by trip, transient, scenario and fleet. vsm requires --forming-inertia above 0 (exit 2 otherwise). With --inertia-model distributed it warns and runs the lumped forming integrator.
--forming-inertia <GVA.s> 0 Virtual former inertia Ev. vsm only: with --forming droop it is refused (exit 2), a droop former carrying no virtual inertia (N311).
--forming-damping <MW/Hz> 0 Virtual former damping Dv.
--frequency-hz <Hz> 50 (assumed) The nominal frequency of every MATPOWER .m file the run loads (a path, a bundled .m name, or a built-in name backed by a file such as gb-reduced-29). A .m file carries no system frequency, so without the flag it is assumed to be 50 Hz and a parse note says so; the IEEE, WSCC and most MATPOWER library cases are 60 Hz systems (gridsim modal data/matpower/lib/case9.m --frequency-hz 60). It sets the f0 of every dynamic study of that model: the small-signal state matrix (modal), the swing equation of stability (single study and CCT), trip's RoCoF, EMT branch inductances (emt), impedance scans and IEC 60909's frequency terms. It changes no power-flow, OPF or state-estimation number: the frequency enters none of those equations. Like --cpu it may stand anywhere on the line. The value must be a finite number above 0 Hz, given once (otherwise exit 2). For a PSS/E .raw file it is the base frequency when the file's BASFRQ is 0 or missing (otherwise 60 Hz, PSS/E's default, is assumed and noted); a file that states a different BASFRQ is refused (exit 1). It does not apply to a JSON case folder (its system.json carries frequencyHz) or to a built-in case name (each carries its own frequency); when the run loads no .m file at all, warning: --frequency-hz <Hz> had no effect ... is printed on stderr at the end and the exit code is unchanged. (N187, October 2026.)
--psse-revision <n> from the file The revision a PSS/E .raw file is read as when its first line does not say (no REV field and no PSS/E-NN comment, as in the UKGDS cases: gridsim ehv2.raw --psse-revision 30 --frequency-hz 50). One of 30, 33, 34, 35, given once (otherwise exit 2). A file that states a different revision is refused (exit 1). When the run loads no .raw file, warning: --psse-revision had no effect: this run loaded no PSS/E .raw file. is printed on stderr at the end. See ch. 2.
--seq-data <file.seq> none A PSS/E sequence data file (revision 30 layout) applied to every .raw case the run loads, so fault and iec60909 use its machine reactances (X''d, X2), line and transformer zero-sequence impedances and transformer winding connections. The name must end in .seq and be given once (otherwise exit 2). Its notes are printed on stderr as note: <file>.seq: ..., ending with the counts applied. Machine zero-sequence impedances and mutual coupling between whole lines are applied. Sequence data GridSim's networks have no element for (sequence shunt loads, mutual coupling over part of a line, zero-sequence switched shunts) refuses the load (exit 1) unless --allow-unmodelled is given. When the run loads no .raw file, warning: --seq-data had no effect: this run loaded no PSS/E .raw file. is printed on stderr at the end. See ch. 2.
--tap-control off Apply a PSS/E .raw file's automatic voltage control by tap (COD 1): each controlled winding becomes an on-load tap changer (band VMI..VMA, limits RMI..RMA, step (RMA - RMI) / (NTP - 1)) that the solve steps from the file's ratios, each winding regulating its own reactive power flow (COD 2, by tap) or active power flow (COD 3, by phase shift angle) is stepped the same way until the flow into it is in VMI..VMA, and a case that does not converge from the file's taps is solved from a ramp start (10 %, 20 %, ... of its demand and generation first; the report says so on a Ramp start: line). Without it the taps stay at the file's ratios. Given once (otherwise exit 2). When the run loads no .raw file, warning: --tap-control had no effect: this run loaded no PSS/E .raw file. is printed on stderr at the end. See ch. 2.
--shunt-control off Switch a PSS/E .raw file's switched shunts that have discrete local voltage control (MODSW 1, one block size, BINIT a whole number of blocks) in whole blocks to hold their bus in VSWLO..VSWHI: in the case solve (inside the tap loop; the report adds a Switched shunts: line) and in pf (as a --switched-shunts file's banks; giving both exits 2). Those with continuous local voltage control (MODSW 2) become static var compensators solved with the power flow (the report prints a Static var compensator line for each). Every other switched shunt stays fixed at BINIT, noted. Given once (otherwise exit 2). When the run loads no .raw file, warning: --shunt-control had no effect: this run loaded no PSS/E .raw file. is printed on stderr at the end. See ch. 2.
--allow-unmodelled off Read a PSS/E .raw file that holds in-service devices GridSim does not model (capacitor-commutated two-terminal DC links, VSC converters regulating a remote bus, multi-terminal DC converters on two DC buses, FACTS devices in modes 4 to 8 or regulating a remote bus, or induction machines with a standard design code, a double cage or saturation). Without it such a file is refused (exit 1), the message naming each kind and the line of its first record. With it those devices are read past, each kind counted in a note: line on stderr, and the power flow differs from the file's. GNE devices are refused either way. With --seq-data it also lets sequence data GridSim's fault networks do not model be read past, each kind counted in a note; for a UCTE-DEF .uct file it reads transformers that have special tables (##TT), using their own impedances. Like --cpu it may stand anywhere on the line; given twice it exits 2. When the run loads no .raw file, warning: --allow-unmodelled had no effect: this run loaded no PSS/E .raw file. is printed on stderr at the end and the exit code is unchanged. See ch. 2.
--bfs off Bare/case/dir forms: route the solve through the radial backward/forward-sweep solver (auto-selected for radial models anyway). The sweep declines a meshed or disconnected network (nothing is solved), so --bfs on a meshed case does not converge: exit 3 with --once, --enableExport or --ticks.
--enableExport[=path] off Bare/case/dir forms: dump the full math trace of one solve to JSON (results/exports/<case>-solve.json by default, where <case> is the built-in name, or for a path the file or folder name without .m: data/matpower/lib/case14.m writes case14-solve.json; D-DOC-154, it used to be data_matpower_lib_case14.m-solve.json; the export's meta still records the argument as given). The path is given only in the = form (--enableExport=out.json); on the bare run the space form (--enableExport out.json) exits 2 saying so, instead of writing the default file (GR-688). A solve that does not converge still writes the export, says so on stderr and exits 3; when the sweep declined, the solver is named BackwardForwardSweep (declined: ...). harmonics and impedance-stability use it to write their own exports.
--export-jacobian off Force the (large) Jacobian past the size gate into the export.
--export-tight off With --enableExport on a case (N251, October 2026): export GridSim's tightest converged state instead of the state at the everyday 1e-8 pu stopping test, which carries that convergence residual (up to about 1e-9 pu in voltage magnitude) and so can never meet a machine-epsilon comparison on its own. After the ordinary solve converges, the case is solved afresh with the same engine and options at 1e-9, 1e-10, ... 1e-15 pu and the tightest rung that converges is exported (the crossval verb's own rule, N243); the export's solve.tightenedTolerancePu names it, meta.elapsedMs is that rung's solve time, and a line [export] tightened: solve tolerance ... pu (... final mismatch ... pu) is printed. When no rung below 1e-8 converges the ordinary state is exported, without the field, and a line says so. Without the switch nothing changes (same solve, same bytes). Without --enableExport, or with harmonics or impedance-stability (their exports are not solve exports), it exits 2.
--audit-log <file> off Record the run in a tamper-evident audit log (gridsim-audit/1, technical ch. 31). Accepted with estimate, crossval, interpose and serve only; with any other verb, or given twice, it exits 2. The log is opened and verified before the verb does any work, against its anchor file (below): a tampered, truncated, restored or locked log, a damaged anchor file, or a missing directory, exits 1 and nothing runs. One entry is written when the run ends, however it ends once the log is open (including a refused flag or a failure; the few global checks that run before the log is opened, the unknown-flag gate, --importLicence and --frequency-hz, end a refused run with no entry), holding who ran it, the verb, each input's SHA-256 (a bundled case name is recorded as case-id, the hash of the name; a folder such as serve's --measurements-dir by a hash of every file's name and bytes), exit=<code> and the verb's one-line result; interpose also writes a started entry when it begins listening. After each entry the anchor (entry count and head hash) is written to the anchor file, one line gridsim-audit-anchor/1 count=N head=H, and printed to stderr as audit: <file> entries=N head=H. The next run opens the log against that anchor, so a log that lost entries since (tail truncation), was replaced by an older copy, or was rewritten with recomputed hashes is refused. A log that has entries but no anchor file is accepted with a warning on stderr, and that run's entry ends audit-anchor=missing; the anchor is written from then on. Keep the printed anchor elsewhere too and pass it to gridsim audit verify.
--audit-anchor <file> <log>.anchor The anchor file of --audit-log (needs --audit-log; alone, or given twice, it exits 2). The default sits beside the log, which catches accidental truncation and a restored copy; keep it somewhere the log's writer cannot change (another account's share, write-once media) to catch a deliberate edit of both. Its folder must exist (exit 1 otherwise).
--audit-forward <file> off Also append every audit entry, as one JSON line, to <file> (a SIEM collector's input or a write-once copy). Needs --audit-log. A failed forward never stops the run; it is reported at the end and the run exits 1.
--incident-log <file> off Raise security events as incidents (one per significant event, one per burst of routine ones) and append them to <file> as JSON lines, each naming the audit entry that evidences it. Needs --audit-log. A failed write is reported at the end and the run exits 1.
--audit-sign-key <private.pem> off ECDSA P-256 private key (PEM): sign the anchor after every entry, into <log>.anchor.sig. Needs --audit-log; a key that is not a P-256 private key exits 1.
--audit-verify-key <public.pem> off ECDSA P-256 public key (PEM): before the run starts, the anchor's signature must exist and verify, or exit 1. Needs --audit-log.

The audited verbs (estimate, crossval, interpose, serve) also write one action=security entry per security event at the point of detection, besides the run's own entry: an input refused by the horizon guard, an infeasible estimate, a suspected false-data injection, an output-guard refusal, a quarantined live window and a breached service-level objective. The audit: line at the end counts them (security-events=N). | --once | off | Bare/case/dir forms: solve once, print, exit. | | --ticks N | interactive | Bare/case/dir forms: run N headless live ticks then exit. N is at least 1: leave the flag out for the interactive loop; --ticks 0 or a negative count exits 2. Every tick is run and printed; when any tick did not converge (DIV) the run ends with error: <n> of <N> tick(s) did not converge (DIV) and exit 3. interpose uses it as a frame cap. | | --importLicence <file.gridsim> | - | Install a software licence from a .gridsim file, then exit (see the licence verb and ch. 4). Fully offline. The value must be a file path: an empty value (--importLicence=), a following flag (--importLicence --once) or no value at all exits 2 with error: --importLicence expected a licence file path (<file.gridsim>) but got '...'. Distinct from the DNO --licence distribution-area selector of gda. | | --version | - | Print gridsim <version>+<commit> (the release number and the full git commit the binary was built from) and exit 0. Answered before anything else, so it needs no licence and works alongside any other token. |

An unexpected internal error (a defect, not bad input) prints gridsim: internal error ... and the path of a crash log on stderr, then the process ends with the runtime's crash exit code (not 0, 1, 2 or 3). The crash log goes to %LOCALAPPDATA%\GridSim\crash (Linux ~/.local/share/GridSim/crash, macOS ~/Library/Application Support/GridSim/crash), or to the folder named by the GRIDSIM_CRASH_DIR environment variable when it is set. It holds the build, runtime, OS, arguments and the full exception; attach it to a bug report.

help

gridsim help [<verb> [<mode>]], gridsim <verb> --help, gridsim <verb> -h

With a verb, prints that verb's section of this chapter as plain text: its usage line, every flag with its default, its exit codes and the notes its group shares, then the general exit-code rule, and exits 0. Because the chapter is compiled into the binary, the help is this text. Aliases work (gridsim n-1 --help prints the nminus1 section), and a verb with modes takes the mode (gridsim bench --estimate --help). gridsim help with no verb is gridsim --help (the verb list). gridsim help <word> for a word that is not a verb exits 2; gridsim <word> --help for a word that is not a verb prints the verb list. Help needs no licence and is answered before the unknown-flag check.

licence

Inspect and install the software licence (ch. 4). Fully offline.

Form Does
licence / licence status Print the active tier, holder, bus limit, expiry, and the licence-file path.
licence import <file.gridsim> Validate a .gridsim key file and install it to %LOCALAPPDATA%\GridSim\licence.gridsim.
licence path Print the licence-file path.

The global --importLicence <file.gridsim> switch is shorthand for licence import. A key can also be supplied for a single run through the GRIDSIM_LICENCE environment variable. With no licence installed, GridSim runs at the free Personal tier: 1,500 buses on user networks. The built-in cases and every network loaded from the bundled folders data/matpower, data/uk, data/gb-synthetic, data/gb-full, data/intl and data/dist3ph are Bundled Networks and are never counted (BundledNetworks, src/GridSim.Core/Licensing/BundledNetworks.cs). Bundled means the shipped files themselves, by content (N229, October 2026): the folder must be the program's own data/ folder (N216), and every file loaded must match the shipped-content manifest data/bundled.sha256 (SHA-256 of each shipped file). A file added to a bundled folder, or a shipped file edited, is a user network and is counted. A user network over the limit is refused with exit 2. A GRIDSIM_LICENCE or installed key that fails verification leaves the run at the Personal tier, and licence status shows the reason. A key is bound to the major version it was issued for: licence status shows it (for GridSim 1.x), and a key for another major version is rejected like any other, naming both versions. licence import exits 2 on a rejected key; an unknown subcommand or bad usage also exits 2. The licence verb is matched in lower case only.

A key applies from its issue date to its expiry date, both inclusive (UTC). Outside that window the free Personal tier applies, exactly as with no key: a key dated in the future shows NOT YET VALID (starts <date>) and applies from that day (it used to apply at once), and an expired key shows EXPIRED <date>. In both cases, and for a key of another major version, the status line shows the limit that applies, 1,500 buses (the free tier applies), not the key's own limit (an expired unlimited key used to show unlimited buses).

Running a case (no verb)

Argument Loads
(none) UK reduced 10-zone model (data/uk), live loop.
case9/ieee9, case14, case30, case57, case118, case300, case145, case24/rts, cigre Embedded IEEE and CIGRE cases, each read from its MATPOWER file (case9 adds the published WSCC machine data, MBase and H, that no .m file carries). case9 without --enableExport prints a detailed solve and exits.
uk The UK reduced model.
<file>.m or --mpc <file>.m Any MATPOWER case (raw ohm/kW distribution files are unit-normalised, with a note: line on stderr saying so).
--dir <path> / -d <path> A JSON case directory.
(anything else) error: unknown command or case, exit 2. The other built-in names (gb, gb-full, gb-synthetic, ...) are for the verbs, not this form.

The detailed solve report (--once, and case9) says what the data does not give rather than printing a zero. A case whose generators carry no inertia constant (every MATPOWER case: the format has no H column) prints Inertia not in the data (no generator H), and a bus with no base voltage (MATPOWER baseKV 0, as in case14) shows - in the kV column, with a line under the table counting such buses. When the model has on-load tap changers and their loop did not finish, a line under the convergence line says so: Taps NOT SETTLED: N tap changer(s) at the end of their range with the controlled bus still outside its deadband: <names>, or that the loop stopped at its pass cap with taps still moving. That line is a report, not a failure: the power flow decides the exit code (3 when it did not converge). The live dashboard shows the same line, and the WPF and web shells mark the OLTC fleet NOT SETTLED. Without --once or --ticks the run is the interactive live loop, which stops on a key press. See ch. 5.

Contingency and analysis verbs

These verbs are used in ch. 11, Contingency analysis.

trip

gridsim trip [<case>] [<gen>] [--dir <path>] [--export <csv>] [--gb-services[=<scale>]] [--band[=<fraction>]] [--envelope <class>:<param>=<low>..<high>[,...]] [--dyn-data <file>]

Trip a generator and report the peak RoCoF (Peak RoCoF, the largest |df/dt| over the run), the nadir and the settling frequency, plus the same trip at half inertia. <gen> is a case-insensitive substring of a generator name; no match lists the available names and exits 2. With two free tokens the first is the case and the second the generator. A single free token is the case when it names one (built-in name, .m file, case folder) and the generator name otherwise; it is found wherever it sits, so trip --dir data/uk Torness trips Torness. More than two free tokens exit 2. Without <gen> the largest non-slack unit with inertia is tripped (exit 2 if there is none). trip is the only verb that integrates --inertia-model distributed; it also honours --asset-dynamics and --forming. The half-inertia comparison runs the lumped model. The run is integrated at the case's own nominal frequency (D2, October 2026): RoCoF = f0 * deltaP / (2E), so the 60 Hz case9 reports 1.2 times the RoCoF a 50 Hz run of the same loss and inertia would, and its trajectory starts at 60 Hz (before D2 every case ran at 50 Hz).

The system inertia on the System inertia: line is the rotating mass only (N314, October 2026; the N289 rule the lumped total, the distributed model and the asset fleet already use): a unit whose type is a known converter technology (wind, solar, storage, interconnector, ...) adds nothing whatever H its data carries, and the tripped unit takes out only what it put in. It used to sum H x MBase over every unit. No bundled case has a converter-typed unit with H above 0, so every bundled trip prints the same numbers.

With --inertia-model distributed the loss is placed at the tripped unit's bus (R060, October 2026): it lands on the speed domain whose machines remain at that bus, or, when the tripped unit was the only machine there, it is shared among the domains by their synchronising coupling to that bus (the distribution of a power impact). A Loss placed: line under Inertia model: states the rule that placed it. Before R060 every loss landed on the domain with the largest total MVA, whichever unit tripped; the per-domain nadirs and RoCoFs depend on the placement, the centre-of-inertia figures do not. When the inter-domain coupling cannot be derived from the network (no branch reactance, a failed reduction, or negligible coupling between the domains) the run uses the uniform 0.5 Hz target-mode stiffness and a Coupling: line says so and why (R025; this used to be silent). Buses that no machine is connected to, such as one isolated by a topology edit, are left out of the reduction instead of making it fail.

--asset-dynamics needs a case with an asset bundle: on one without (data/uk, the IEEE cases) it exits 1 instead of being ignored. The name gb-synthetic is the shipped data/gb-synthetic folder, with its asset bundle (N238 for trip, N316 for every verb, October 2026; it used to build the bundle-less network in memory). It cannot be combined with --inertia-model distributed (exit 2): the multi-domain model carries no asset fleet yet, so one of the two would be dropped. With asset dynamics on, the Asset dynamics: on line splits the infeed lost into inverter trips (Loss-of-Mains RoCoF or vector shift, or under-voltage ride-through) and protection-device operations; a note: line counts the assets whose voltage or loading stages this lumped run does not evaluate (it solves no network: they are neither operated nor held).

After the run, trip assesses the system frequency protection on the run's trajectory (ProtectionAssessment. AssessTrajectory, D-DOC-220): 81U against the run minimum, 81O against the run maximum and 81R against the peak |df/dt|, with the protection-check defaults (G99 Issue 2 Table 10.1: 47.5 Hz, 52.0 Hz, 1.0 Hz/s). Each line says holds, WOULD OPERATE or not evaluated; 78 (vector shift) is not evaluated, because the run is a centre-of-inertia frequency trajectory with no bus voltage angle. On a case whose nominal frequency is not 50 Hz (case9, 60 Hz) 81U and 81O are not evaluated too: the G99 pickups are settings for a 50 Hz system and do not apply (D2). The lines are informational: the exit code does not change.

Flag Default Meaning
<case> data/uk Case to load (Case arguments).
<gen> largest unit Generator-name substring to trip.
--dir data/uk JSON case directory.
--export - Write the frequency trajectory CSV (dtm,f), playable with gridsim replay <file>. A missing folder is created (Output files).
--gb-services[=<scale>] off Add the GB Dynamic Containment / Moderation / Regulation arrest layer at the EAC auction volumes (950 / 520 / 490 MW, GbResponseServices.Typical), times <scale> (default 1; a finite number above 0, else exit 2), on top of the generic governor. A Response: line states the volumes. --gb-services 0.5 also works.
--band[=<fraction>] off Add the nadir's uncertainty band over the swing constants that are literature-typical and not fitted to GB data (load damping, responsive fraction, governor time constant; FrequencySensitivitySweep, R079): each is moved by +/- <fraction> (default 0.20; strictly between 0 and 1, else exit 2) one at a time, most leverage first, and over every corner of the joint box. The band follows the half-inertia line; every line before it is unchanged. Lumped model only: with --asset-dynamics or --inertia-model distributed it exits 2. --band 0.3 also works.

With --band the output gains a block such as:

Uncertainty band (--band 0.2): the unfitted swing constants each +/- 20 % (literature-typical, not fitted to GB data):
  nadir over every corner:  <min> .. <max> Hz (width <w> Hz); peak RoCoF band <r> Hz/s (inertia and the loss set the RoCoF, not these constants)
  one at a time, most leverage first:
    load damping (%/Hz)              0.8 -> 1.2       nadir <a> -> <b> Hz  (swing <s> Hz)
    ...

The sweep's nominal run is the trip run itself (checked bit for bit). The constants can be fitted to a measured trace with fit-frequency.

--envelope <class>:<param>=<low>..<high>[,...] (with --asset-dynamics, R095) sweeps control parameters of the case's asset classes (asset-classes.json) over their plausible ranges around this trip (AssetEnvelope.Sweep): every corner of the ranges (2^k runs for k parameters, at most 12), then a tornado (each parameter low and high with the others at their midpoints, most leverage first). It prints the nadir band (minimum, median, maximum), the peak RoCoF band, whether a cascade is possible (some corners trip infeed and others do not: the data cannot say which, and that is the finding) and the tornado, after the half-inertia line; every line before it is unchanged. The result is tagged UnvalidatedAtScale. Example: trip --dir data/gb-synthetic --asset-dynamics --envelope dg-alomcp:rocofTripHzPerS=0.5..2. The class must be in the case's library and the parameter one its kind is simulated with (the accepted keys of the asset-class loader); low below high, both finite; no item twice. Without --asset-dynamics it exits 2; on a case whose bundle holds protection devices only it exits 1; a bad item, or a swept value the asset-class checks refuse, exits 2 naming it.

Flag Default Meaning
--envelope off With --asset-dynamics: the asset-class parameters to sweep, <class>:<param>=<low>..<high>, comma-separated.
--dyn-data - A machine dynamic data file (gridsim-dynamics/2, the file stability --rms reads). The trip integrates the system frequency swing, whose only per-machine number is the inertia H, so each generator the file binds takes the file's H (the case's own H where the template gives none); every engine of the run (lumped, --inertia-model distributed, --asset-dynamics) and the choice of the unit to trip see that inertia. A Machine data: line under the title names the file, counts the generators and how many H values differ from the case, and says that the file's GENROU reactances, exciters and governors are not used by this swing. A file whose H values equal the case's gives the same trip, bit for bit. A missing file or one that fails the v2 schema, kind-spec or binding checks exits 1 with every problem listed, before any run.

screen

gridsim screen [<case>] [--dir <path>] [--top 12] [--csv <path>]

N-1 RoCoF screening: rank every credible single infeed loss against the GB limits (RoCoF 0.125 Hz/s, statutory 49.5 Hz, LFDD risk) and report the binding case's inertia floor and headroom.

Each loss is integrated at the case's own nominal frequency (N275, October 2026), as trip is: RoCoF = f0 * deltaP / (2E), so the 60 Hz case9 screens at 1.2 times the RoCoF a 50 Hz run of the same loss and inertia gives (before N275 the screen ran every case at 50 Hz). The nadir is graded against the GB bands about the case's nominal (N297, October 2026: the GB edges as hertz offsets, so 59.5 Hz statutory and 58.8 Hz LFDD for case9; before, a non-50 Hz case was graded against 49.5 / 48.8 Hz, which its nadirs never reach). On such a case the header's statutory figure and the <... Hz verdict show the moved edge, and a note: line under the header names both edges. A 50 Hz case prints exactly as before.

Flag Default Meaning
<case> / --dir data/uk Case to load, or a JSON case directory (Case arguments).
--top 12 Rows to print (all losses are still screened and counted).
--csv - Write the full screening table to CSV: name,lost_mw,remaining_inertia_gva_s,peak_rocof_hz_per_s,nadir_hz,rocof_breach,statutory_breach,lfdd_risk. The RoCoF column is the peak over the run.

The last line is the verdict. Exit 3 (Verdict: NOT SECURE, N of M single loss(es) breach a limit) when any loss is LFDD RISK, <49.5 Hz or >0.125 Hz/s; exit 0 (Verdict: SECURE) when every loss is ok. The CSV is written first either way.

A case with no inertia data (every in-service generator has H = 0, as in the IEEE MATPOWER cases) is refused before anything is printed or written: error: screen: case '<name>' carries no inertia data ..., exit 1. The screen floors the remaining inertia at 1 MWs to avoid a division by zero, so such a case used to report every loss at an absurd RoCoF (case14: -5810 Hz/s). The system inertia is the rotating-mass total, as trip uses: a unit whose type is a known converter technology (wind, solar, storage, interconnector and the like) counts no inertia whatever H its data carries, and its loss removes none (N321, October 2026; it used to count; no bundled case has such a unit with H above 0, so no bundled screen moves). A case whose only H sits on converter-type units is refused like one with no H. A loss that leaves less than 1 MWs on a case that has inertia is still screened (it breaches every limit) and named on stderr in a warning: screen: ... line, because its RoCoF and nadir are the floor's artefact.

nminus1

gridsim nminus1 [<case>] [--dir <path>] [--global-vlimits] [--outage-types branch,gen,bus] [--outage-dispatch reference|droop|inertia] [--post-fault-rating A|B|C] [--batched-lanes N] (alias n-1)

Sequential N-1 branch outage screening on one model: each branch out in turn, re-solved, classified secure / violations / islanded. Default model data/uk; a positional case or --dir selects another (Case arguments). An outage that does not solve prints ISLANDED when it splits the network (the post-outage network has more connected parts than the case) and NO SOLUTION when the network is still connected but the power flow found no solution (a voltage collapse, for example case14 branch 1-2), with its reason: islanded or no solution for a non-converged solve, or solver error: <type>: <message> when the solver threw. The count line says N islanded, and M not solved when there are any. Both fail the verdict (exit 3). The result file's islanded counts only the splits and not_solved counts the rest. nminus2 and n-1-1 label rows the same way.

The three branch screens share these rules:

  • Options. The contingency option set and the tap-changer loop (Solver selection).
  • Base case first. The intact network is solved with the same options and printed once: Base case: secure (...) or Base case: N pre-existing violation(s), reported once here and not counted against any outage: <list>. A base case that does not converge exits 3 with error: <verb>: the base case of <model> did not converge (...), before any outage is screened.
  • Netting. A violation counts against an outage only when its branch, boundary or bus was not already violating in the base case. Status VIOLATIONxN counts those new violations; base only marks a converged outage that adds none while the base case's own violations remain in its state (counted as secure, and noted under the footer); secure means no violation at all.
  • Verdict. The last line: exit 0 with Verdict: SECURE (exit 0). when the base case and every screened outage are secure; exit 3 with Verdict: NOT SECURE, ... (exit 3). when the base case has a violation or any outage violates, islands or does not solve (and, for nminus2 and n-1-1, when a single outage was left out of the pairing because it already fails).
  • Voltage limits. Each bus is judged against its own limits where the case gives them (MATPOWER bus columns 12 and 13, VMAX and VMIN; JSON vminPu and vmaxPu in buses.json), and against the one operational band (0.94-1.06 pu) on any side a bus leaves unset; a case with no per-bus limits is judged against the band throughout. --global-vlimits judges every bus against the band and ignores the per-bus data. --bus-vlimits is accepted and does nothing (per-bus limits are on by default); giving it with --global-vlimits exits 2. Both flags are accepted by nminus1, nminus2, n-1-1 and nminus1-sweep only; on any other verb they exit 2. Because every MATPOWER file carries VMAX and VMIN, the choice changes verdicts on bundled MATPOWER cases. The ranking of outages for nminus2 and n-1-1 candidates uses the band.
  • Post-fault rating. By default every state's branch loading is judged against rating A (RateA, MATPOWER column 6, JSON ratingMva). --post-fault-rating B or C judges each outage state against the branch's rating B (short-term: MATPOWER RATE_B, JSON ratingBMva) or C (emergency: RATE_C, ratingCMva), and a branch that has no B or C rating (0) against its rating A; the base case stays on rating A. This follows NETS SQSS v2.10 (docs/reference S036, 8 April 2025): no loading above the pre-fault rating before a fault (for example paragraph 2.9.1) and no "unacceptable overloading" after a secured event (paragraph 5.1.8), which the Definitions put at loading beyond the equipment's "specified time-related capability". The meaning of MATPOWER's rating columns (A long term, B short term, C emergency) is MATPOWER's caseformat convention [VERIFY: not in docs/reference]. A is the default and changes nothing. Accepted by nminus1, nminus2 and n-1-1 only; elsewhere, or with any other value, it exits 2. With it the header says which rating is used and the result file adds post_fault_rating.

--batched-lanes N (N349, nminus1 only): solve the branch outages with the batched contingency sweep, N lanes posting their Newton steps to one batched linear solve (0 = one lane per processor, at most 1024). Every number is bit-identical to the default sequential screen (the CPU batched backend is the same sparse LU on each system); only the speed differs, and a note: line on stderr says the batched sweep ran. Generator and bus outages (--outage-types) are screened as before. A value that is not a whole number from 0 to 1024 exits 2.

nminus1 alone also takes --outage-types: a comma list of branch, gen and bus (default branch, the screen above). gen takes each in-service generating unit out in turn (NETS SQSS v2.10 paragraph 5.1.2, a single generating unit): its scheduled output is lost and the reference bus picks it up in the re-solve. bus takes each bus out with every branch touching it, every unit on it and its load: the bus-branch model's stand-in for a section of busbar (paragraph 5.1.5). The load and generation an outage took are printed under its row (lost load ... MW, lost generation ... MW (picked up by the reference)), reported but not judged (the SQSS loss-of-supply limits of Table 5.1 are not modelled). When an outage takes the last unit of the reference bus, or the reference bus itself, the reference moves to the bus of the largest remaining unit by |Pg| in the same connected part of the network, and the row says reference moved from bus X to bus Y; with no unit left there the outage is ISLANDED. Rows are printed worst first (branch outages first among equals, then generators, then buses). With a non-default choice the header reads N-1 screening (<kinds> outages), and the result file adds an outage_details table (outage,kind,lost_load_mw,lost_generation_mw,note). --outage-types on another verb, or with an unknown kind, exits 2.

--outage-dispatch (N124, nminus1 with gen or bus outages only) chooses who picks up the real power such an outage takes away before the re-solve. reference (the default, also slack) is the screen above: the reference bus takes it all, as PSS/E AC contingency analysis does with its dispatch disabled and PowerFactory with "as dispatched". droop shares the net lost power (lost generation less lost load) among the remaining synchronous units in proportion to their MBase, the primary-response gain MBase / R with one droop R for every unit (the case carries no per-unit droop; PSS/E dispatch by governor droop, PowerFactory "according to primary control"); inertia shares it in proportion to H x MBase (PSS/E dispatch by inertia, PowerFactory "according to inertias"). Converter plant, power-flow-only units and units with no path to a reference bus take no share. Each unit stays within its Pmin and Pmax: a unit whose share exceeds its headroom is held at its limit and the rest goes to the others; what no unit can take is left to the reference. The reference then carries only its own share, the change in losses and any remainder. The detail line reads lost generation ... MW (shared by governor droop) (or by inertia) and the note says how many units shared it, how many met a limit and any MW left to the reference, for example lost 60.0 MW shared by governor droop over 2 unit(s). With --outage-dispatch on another verb, without gen or bus in --outage-types, or with another value, it exits 2.

Result files: --json <file.json>, --csv <file.csv> or --out <file.json|file.csv> write the result to a file (Result files).

nminus2

gridsim nminus2 [<case>] [--dir <path>] [--candidates N] [--exhaustive] [--top N] [--global-vlimits] (alias n-2)

N-2 branch screening: two elements lost at once. A full pairwise sweep is C(n,2), so by default it screens N-1 first, ranks the single outages that solve by how hard they stress the system, keeps the --candidates most-stressed, and pairs only those (fewer when fewer solve). The single outages that do not solve (islanded or no solution) are left out of the pairing and listed under the table (N single outage(s) left out of the pairing because they already fail at N-1). Results are printed worst first. Default model data/uk. Exit codes as for nminus1.

Flag Default Meaning
<case> / --dir data/uk Case to load, or a JSON case directory (Case arguments).
--candidates 20 How many of the most-stressed single outages to pair (ignored with --exhaustive).
--exhaustive off Enumerate every pair; use only on small cases.
--top 20 Rows to print (all pairs are still screened and counted).
--post-fault-rating A Judge the outage states against rating A, B or C (see nminus1).
--global-vlimits off Judge every bus against the operational band 0.94-1.06 pu, ignoring the case's per-bus limits (see nminus1). --bus-vlimits is accepted as a no-op alias of the default.

Result files: --json <file.json>, --csv <file.csv> or --out <file.json|file.csv> write the result to a file (Result files).

n-1-1

gridsim n-1-1 [<case>] [--dir <path>] [--candidates N] [--exhaustive] [--top N] [--global-vlimits] (alias nminus1minus1)

N-1-1 sequential screening: lose one element, let the operator take corrective action, then lose a second element from that corrected state. The corrective action acts only when the first outage leaves a rated line or a limited boundary over its limit in the DC model; it then moves the fewest MW of generation that bring every rated line and limited boundary back inside its limit, keeping each DC island's total generation (island by island). With nothing over its limit the dispatch is unchanged, and when no redispatch within the generator limits can relieve it the dispatch is also unchanged. Pairs are ordered (first => second), and results print worst first. The candidate set and the failing single outages are as for nminus2. Default model data/uk. Exit codes as for nminus1.

Flag Default Meaning
<case> / --dir data/uk Case to load, or a JSON case directory (Case arguments).
--candidates 20 How many of the most-stressed single outages to use as first and second outages (ignored with --exhaustive).
--exhaustive off Enumerate every ordered pair; small cases only.
--top 20 Rows to print (all pairs are still screened and counted).
--post-fault-rating A Judge the outage states against rating A, B or C (see nminus1).
--global-vlimits off Judge every bus against the operational band 0.94-1.06 pu, ignoring the case's per-bus limits (see nminus1). --bus-vlimits is accepted as a no-op alias of the default.

Result files: --json <file.json>, --csv <file.csv> or --out <file.json|file.csv> write the result to a file (Result files).

nminus1-sweep

gridsim nminus1-sweep <case|--dir <path>|--all> [--parallel N] [--sample N] [--losses] [--global-vlimits] [--out <path>]

Parallel N-1 branch sweep with throughput reporting, over one case or the whole case registry (--all is the embedded classics plus every .m under data/matpower/). Writes Markdown, CSV and <report>.run-metadata.json beside the report (Output files). Each case is screened with the contingency option set and the tap-changer loop on the shared dense / sparse rule (Solver selection). The base case is solved first; its violation count is the last column, Base viol (CSV base_violations, after commit), and those violations are netted out of every outage as for nminus1. Islanded counts the outages that split the network and Not solved the connected outages with no solution (CSV islanded and not_solved, the last column). A base case that does not converge gives a BASE FAIL row. Bus voltages are judged as nminus1 judges them: against each bus's own limits where the case gives them (the default), or against the operational band with --global-vlimits, so the sweep and nminus1 give the same verdicts on the same case (the header line records vlimits=per-bus or vlimits=global). Before October 2026 the sweep always judged the band, so on a case with per-bus limits it disagreed with nminus1. Exit 1 if no case loaded or after a partial load failure; otherwise exit 3 when any case is not N-1 secure (a base-case violation, an outage that violates, islands or does not solve, or a BASE FAIL), and 0 when every case is.

Flag Default Meaning
<case> / --dir case118 Case name, .m file or case folder, or a JSON case directory (Case arguments).
--all off Sweep the whole registry (exit 2 with a case or --dir).
--parallel 0 (all cores) Worker threads; a negative value is refused.
--sample 0 (full) Screen an evenly spaced sample of N branches (logged, flagged (sampled)).
--losses off Also run the loss-contingency sweep and append the 20 outages that raise network losses most.
--global-vlimits off Judge every bus against the operational band 0.94-1.06 pu, ignoring the case's per-bus limits (see nminus1). --bus-vlimits is accepted as a no-op alias of the default.
--out results/nminus1-sweep.md Report path (CSV alongside).

stress

gridsim stress <case|--dir <path>|--all> [--from F] [--to F] [--step F] [--parallel N] [--out <path>] [--pv-out <file.csv>]

Load-to-collapse: scale the operating point until the flow stops converging and report max loadability. Each load point solves with the contingency option set and the tap-changer loop (Solver selection); Q-limits are enforced so collapse is real reactive exhaustion. Writes Markdown, CSV and <report>.run-metadata.json beside the report (Output files). Exit 1 if no case loaded or after a partial load failure; exit 2 for a bad --step or --from above --to; exit 3 when any case has no converged load point at all (its row reads <none> and NO LOAD POINT CONVERGED), unless exit 1 already applies. A load point whose solve fails numerically (a singular or non-finite Jacobian, typically past the nose) counts as not converged and is counted in the Notes column and on stderr; any other exception stops the run.

Max loadability is the highest load factor that converged before the first one that did not. The rule is the shared loadability loop the cpf verb also runs (ContinuationPowerFlow.ScanGrid here, on this verb's fixed grid of factors, every point solved in parallel). The two verbs answer different questions on purpose: stress re-dispatches the generators at each load factor (GridScenario.AtLoad) and steps through a fixed grid, while cpf lets the slack absorb the extra load and bisects to the nose.

Flag Default Meaning
<case> / --dir case118 Case name, .m file or case folder, or a JSON case directory (--all sweeps the registry; exit 2 with a case or --dir).
--from / --to / --step 0.5 / 2.0 / 0.05 Load-multiplier sweep. --step must be positive and --from must not be above --to (exit 2 otherwise).
--parallel 0 (all cores) Load points solved in parallel; a negative value is refused.
--out results/stress.md Report path (CSV alongside).
--pv-out - Also write the PV curves: for each case, every bus voltage at each load factor from --from up to the reported max loadability (the converged factors before the first failure), as case,load_factor,bus_id,vm_pu. A name not ending in .csv exits 2.

chain

gridsim chain <case|--dir <path>> [--steps N] [--mode fixed|ramp|daily] [--ramp-pct F] [--out <path>] [--bess <site> ... storage flags]

Consecutive warm-started solves: each step feeds the previous solution in as the initial condition. fixed re-solves the same point (at most 1 iteration, no drift expected); ramp adds --ramp-pct % load per step; daily follows the 24 h demand curve. Step 0 solves from the case's own voltages, so the footer's warm-start maximum covers steps 1 onwards, and fixed mode prints Warm start converges in <=1 iter with no drift - as expected. when that maximum is 1 or below. Every step solves with the contingency option set and the tap-changer loop (Solver selection). Exit 1 if the case does not load, 2 for an unknown --mode, 3 if any step does not converge (the table still lists every step).

Flag Default Meaning
<case> / --dir case118 Case name, .m file or case folder, or a JSON case directory (Case arguments).
--steps 50 Number of consecutive solves; at least 1.
--mode fixed fixed, ramp or daily.
--ramp-pct 0.5 Percent load increase per step (ramp).
--out results/chain-<case>.md Report path (CSV and <report>.run-metadata.json alongside); <case> is the last path element without .m.

Storage time series. One or more --bess flags switch chain into the storage time series: each battery site carries state of charge, temperature and ageing from step to step under a dispatch policy (ch. 13). With storage the default --steps is 48 and the report goes to results/chain-storage-<case>.md (CSV alongside). Each step solves with the same contingency option set and tap-changer loop as plain chain. A step that does not converge prints - for its slack output and lowest voltage (the CSV leaves slack, voltages and losses empty): it has no solved state. Exit 3 if any step fails to converge, or if a storage schedule LP does not solve to an optimum; exit 2 on a malformed site or policy, a site on a bus the case does not have, --policy price without --prices, or --prices with no value; exit 1 for a price file that is missing, unreadable or holds a value that is not a number (the message names the file and the line). An unknown case name exits 2 and a case file or folder that is missing or cannot be loaded exits 1, as on plain chain. The storage flags below need at least one --bess: on plain chain each of them exits 2 rather than being ignored.

Flag Default Meaning
--bess chem:bus:MW:MWh[:soc] - A battery site; repeat for more. Chemistry lfp, nmc, lto, na-ion, vrfb, lead-acid; initial SoC 0.5. Four or five fields; MW and MWh must be numbers above 0 and the starting SoC a number from 0 to 1; anything else (a sixth field, 0 MW, a negative MW, SoC 1.5, an unknown chemistry, a bus that is not a number) exits 2 naming the spec and the field. Chemistry presets are CuratedPlaceholder [VERIFY].
--policy peak-shave, or lp when --prices is given idle, peak-shave, price, hold or lp. price and lp act on the price series, so each needs --prices (exit 2 without: --policy price needs --prices, --policy lp needs --prices). lp plans the whole run as one storage schedule LP over the prices (exit 3 if that LP has no optimum).
--prices synthetic\|<file> - The price series (GBP/MWh, one per step) for the price and lp policies, and for the revenue line of the summary. synthetic is the labelled synthetic GB-shaped day (SyntheticPrices.GbDay, sampled at the start of each step; not a market record, and every output says so). A file holds one price per line, or CSV lines whose last field is the price; blank lines and lines starting with # are skipped; values use . as the decimal point and may be negative. Fewer values than steps exits 1; more is allowed (the first --steps are used, and a note on stderr says how many were not). dcopf and acopf take --prices as a switch of their own (nodal prices); every other verb refuses it (exit 2).
--step-hours 24/steps (daily), else 0.5 Hours per step.
--shave-high / --shave-low 90 % / 70 % of peak demand Peak-shave discharge and recharge thresholds (MW).
--buy-below / --sell-above 40 / 90 price policy thresholds (GBP/MWh): charge at full rating at or below the first, discharge at full rating at or above the second, hold between.
--degradation-gbp-per-mwh 0 Degradation cost per MWh throughput in the lp schedule's objective.

cycle

gridsim cycle <case|--dir <path>> [--window-ms 1000] [--workers N] [--cycles K] [--shards N] [--jobs n-1,harmonics,rocof,physics,watch] [--hold-steady]

The real-time prioritised parallel analysis cycle: one single-core Newton-Raphson base solve per cycle, then a worker-pool fan-out of every downstream analysis (N-1 sweep, harmonics, RoCoF screening, physics conformance and the watch list) over the shared immutable solved frame. High-priority work (base solve, hot N-1, harmonics, watch list) completes every cycle; Low-priority work (rotating N-1 shards, RoCoF, physics) is admitted best-effort while the core-millisecond budget (workers x window-ms) lasts, and any Low work deferred in a cycle keeps its place at the front of the rotating pool for a later one (round-robin coverage, no starvation). Per cycle it prints base-solve ms, High-tier completion, Low done/admitted/deferred, utilisation %, backlog depth and N-1 shard coverage. It is the soak driver of the performance programme. Exit 1 if High is ever missed or the case file or folder is missing or unloadable; exit 2 for an unknown case name, a positional case that disagrees with --dir, --pipeline, or a --jobs list with an unknown job or no job at all (error: cycle --jobs: Unknown analysis job 'bogus'. Choose from: watch, n-1, nminus1, harmonics, rocof, physics, conformance.). An empty job set used to run every cycle with nothing to do and report HP met every cycle: YES with exit 0.

Flag Default Meaning
<case> / --dir data/uk Case name or JSON case directory to run the cycle on.
--window-ms 1000 Wall-clock deadline per cycle (ms), at least 1; the compute budget is workers x window-ms core-ms.
--workers cores - 1 Fan-out worker pool size, at least 1 (one core reserved for the single-threaded base solve). Results do not depend on the worker count; only throughput changes.
--cycles 10 Number of cycles to run; at least 1.
--shards 8 Rotating Low-priority N-1 shard count, at least 1 (full branch coverage is reached over this many cycles).
--jobs all Comma list of analyses to schedule: n-1 (alias nminus1), harmonics, rocof, physics (alias conformance), watch, ignoring case. An unknown key, or a list with none, exits 2. The tiers are fixed: watch, harmonics and the hot-branch N-1 job are High; the N-1 shards, rocof and physics are Low.
--hot-loading 80 Branch loading (%) at or above which a branch joins the High-priority hot N-1 set.
--hold-steady off Hold the operating point fixed across cycles rather than stepping the live sim (comparable cycle-to-cycle timing).
--pipeline - Not implemented: exits 2 (the pipelined backlog drain does not exist; every job runs on the current frame).

Result files: --json <file.json>, --csv <file.csv> or --out <file.json|file.csv> write the result to a file (Result files).

Network analysis verbs

These verbs take their case as a positional argument only (a built-in name, a .m file, a JSON case folder or, for dist3ph, a feeder file; see Case arguments). A missing case exits 2, a case that does not load exits 1. The verbs are used in ch. 5 (pf) and ch. 6 (dcpf, dcopf, acopf, cpf, taps, ptdf, lodf, losses); dist3ph is in ch. 7.

pf

gridsim pf <case> [--distributed-slack pmax|pg|equal] [--switched-shunts <file.json>] [--top 12]

One AC power flow on the engine the shared rule picks (radial sweep, dense or sparse Newton), 100 iterations with reactive limits on, printed: convergence, iterations, mismatch, losses, the voltage range and the --top lowest bus voltages. Two opt-in controls wrap the unchanged engine as outer loops (like the tap-changer loop), so the dense and sparse engines give the same bits with them too:

  • --distributed-slack pmax|pg|equal: the real-power balance (losses and any scheduling error) is shared among the in-service units by participation factors proportional to Pmax, to scheduled Pg, or equal, instead of all landing on the reference bus. Each pass allocates the imbalance K, solves, and adds the reference bus's excess over its own allocation to K, until that excess is at most 1e-4 MW; units are held within [Pmin, Pmax] (water filling). The output lists the passes, K and each unit's move (the --top largest). A model with several reference buses, one in each network island, shares one imbalance per island among that island's units; two reference buses in one connected network are refused, naming them (exit 1). Every unit at a limit with imbalance left, or no settling within 50 passes, is NOT CONVERGED (exit 3).
  • --switched-shunts <file.json>: discrete shunt banks switched in whole steps to keep their bus voltage in a band. After each converged solve a bank below its band switches one step more capacitive, above it one step less, within its step range; a bank that reverses direction is frozen (it hunts across a band narrower than one step). One step adds stepMvar (MVAr at 1 pu, positive capacitive) to the bus Bs. The file: { "format": "gridsim-switched-shunts/1", "shunts": [ { "bus": 5, "stepMvar": 10, "minSteps": 0, "maxSteps": 4, "initialSteps": 0, "vminPu": 0.97, "vmaxPu": 1.03, "name": "C5" } ] } (bus, stepMvar, maxSteps, vminPu, vmaxPu required; every key checked). The output lists each bank's steps and bus voltage. Not settled (a bank frozen outside its band, or 50 passes) exits 3.
Flag Default Meaning
--distributed-slack off pmax, pg or equal; any other value exits 2.
--switched-shunts - A gridsim-switched-shunts/1 file; a missing or invalid file exits 1.
--top 12 Lowest voltages and largest slack moves to list; 0 or more (a negative value exits 2).

Exit 0 converged (and shunts settled); 3 not converged or not settled; 1 on a load error or a bad file; 2 on a usage error (an unknown --distributed-slack rule, a flag of another verb).

Result files: --json <file.json>, --csv <file.csv> or --out <file.json|file.csv> write the result to a file (Result files): the summary (case, convergence, losses, voltage range, the slack and shunt outcome), a buses table (every bus: |V|, angle, net injection), and with the options a slack_units table (every participating unit) and a switched_shunts table. A solve that does not converge writes no file; unsettled shunts write the file with exit code 3 inside.

ptdf

gridsim ptdf <case> --bus <id> [--top 12]

Power transfer distribution factors: +1 MW injected at --bus and withdrawn at the slack, and the share that flows on each branch, largest first (factors below 1e-4 are not listed). In a case with several DC islands the injection is withdrawn at the reference bus of the injection bus's own island (its slack, otherwise its largest generator), and the header says how many islands there are. Exit 2 without --bus, or for a --bus the case does not have (error: ptdf --bus <id>: case '<name>' has no bus <id>.; it used to print an empty list and exit 0); exit 1 if the factors cannot be built.

Flag Default Meaning
--bus required Injection bus id.
--top 12 Branches to list.

Result files: --json <file.json>, --csv <file.csv> or --out <file.json|file.csv> write the result to a file (Result files).

lodf

gridsim lodf <case> --branch <idx> [--top 12]

Line-outage distribution factors: how the flow of the outaged branch redistributes onto the others, largest first. --branch is the 0-based branch index; out of range exits 2. A bridge outage that islands the system prints that the LODF is undefined and exits 0.

Flag Default Meaning
--branch required 0-based branch index to outage.
--top 12 Branches to list.

Result files: --json <file.json>, --csv <file.csv> or --out <file.json|file.csv> write the result to a file (Result files).

dcpf

gridsim dcpf <case> [--top 12] [--out <file.csv|file.json>] [--json <file.json>] [--csv <file.csv>]

DC power flow: bus angles and branch flows from the linearised network, through the same DC model the PTDF, LODF and DC-OPF use (DistributionFactors; Core DcPowerFlow). Only series reactance enters; resistance, line charging, shunts, tap ratios and phase shifts are ignored, voltage magnitudes are 1 pu and there are no losses, so each DC island's reference bus (its slack, else its largest generator) injects exactly the island's imbalance. Injections are the in-service generators' output minus the bus demand. Prints a line per island (reference bus, buses, demand, scheduled generation, what the reference injects), how many rated branches are above 100% of RateA, and the --top largest flows with their loading. Overloads are reported, not an error.

Flag Default Meaning
--top 12 Branches to list, largest flow first; 0 lists none, a negative value exits 2.
--out / --json / --csv - Write the result through the shared result writer. With a .csv name: every branch flow to that file (index,name,from,to,flow_mw,rate_mva,loading_pct) and every bus angle and net injection to <stem>-buses.csv beside it (bus_id,va_deg,p_inj_mw), plus <stem>-islands.csv and <stem>-summary.csv; with a .json name (or --json), the same tables as one document. Numbers in round-trip form. An --out name ending in neither .csv nor .json exits 2.

Exit 0 on a solve; 1 when the case does not load or its DC model cannot be formed (an in-service zero-reactance branch that is the only link between two islands, or a singular B'); 3 when an island carries load but has no generator (the island line says NO GENERATION: load cannot be supplied); 2 for a usage error or a flag another verb owns.

dcopf

gridsim dcopf <case> [--no-limits] [--top 12] [--costs case|<file.json>] [--prices]

DC optimal power flow: the cheapest dispatch that meets demand, with line limits enforced unless --no-limits. Prints total cost (GBP/h), the dispatch by output and any binding line limits. The dispatch is feasible only when generation can meet demand and, with limits on, the security-constrained LP finishes Optimal. An infeasible, unbounded or iteration-limited LP prints INFEASIBLE and exits 3 (a verdict failure). Exit 1 if the case does not load or the solve throws. On a connected case the INFEASIBLE line says why: no dispatch within the units' output limits keeps every rated line within its rating (security LP Infeasible) (--no-limits drops the line limits), the security LP stopped without proving an optimum (status <s>), or generation capability cannot meet demand (<x> MW of in-service capability for <y> MW of demand) when the merit order itself falls short.

Lines no dispatch can relieve. Before the LP runs, every rated line's DC flow is bounded over every unit anywhere in its output range (the balance row dropped, so a superset of every dispatch the LP could choose). A line whose whole range lies above its rating (or below minus its rating) by more than 1e-6 MW cannot be brought within its rating by any dispatch: it is left out of the LP, as the corrective redispatch leaves out what no generator can move. Each one is printed whatever the outcome, <n> rated line(s) cannot be brought within rating by any dispatch; left out of the security LP and still overloaded: with its rating and the range of flows any dispatch gives it, and the summary says secure for every rated line except the <n> listed above; they also appear among the binding lines with their flow over the rating. The result file gains an unrelievable_lines table and unrelievable_line_count only then. dcopf gb-synthetic leaves out 2 lines, the meshed supergrid transformers MID SGT 400/275 1 (rating 1,000 MW, any dispatch 1,409.0 .. 1,446.0 MW) and LDN SGT 400/275 1 (rating 1,000 MW, any dispatch 1,258.1 .. 1,757.7 MW), and dispatches the rest at 602,945 GBP/h (2.7 s wall time for the whole run on the reference machine).

A case with several DC islands (gb-full has two) is dispatched island by island: each island meets its own demand from its own generation, against its own reference bus. The output lists every island (reference bus, buses, demand, generation, verdict and LP status) before the dispatch. An island with no generator is listed as NO GENERATION: load cannot be supplied when it carries load, and the run is then INFEASIBLE. With --no-limits the islands are dispatched by merit order. dcopf gb-full dispatches the 3,536-bus main island (reference bus 194, 53,279.4 MW) and the 3-bus island (reference bus 6774, 5.6 MW), leaves out 3 lines (COPP C1-_COPP T1 132kV, rating 109 MW, any dispatch -164.4 .. -125.7 MW; the parallel pair ENW-ENW 132kV#23 and #24, rating 150 MW, 168.8 MW whatever the dispatch) and dispatches 53,285 MW at 312,021 GBP/h; the run took 2 min 29 s of wall time on the reference machine. With --no-limits the same case dispatches both islands by merit order at 53,560 GBP/h (4.9 s).

Flag Default Meaning
--no-limits off Ignore branch ratings (unconstrained merit order).
--top 12 Generators, binding lines, and (with --prices) buses to list.
--costs off Dispatch on each generator's own cost curve instead of the fuel-type merit order. case uses the case's MATPOWER mpc.gencost; any other value is a gridsim-costs/1 JSON cost file laid over the case (below). Every in-service unit must end up with a curve, else exit 1. The built-in IEEE names read their MATPOWER files and so carry the files' curves (dcopf case9 --costs case and dcopf case9.m --costs case give the same dispatch).
--prices off Also report the nodal prices (LMPs) and the binding lines' shadow prices, from the optimum's dual values. The dispatch is the same bits with or without it.

Cost curves (--costs). Polynomial curves up to quadratic (MATPOWER MODEL 2 with NCOST 1-3; a longer row is accepted only when the terms above the quadratic are exactly zero) and convex piecewise-linear curves (MODEL 1) are optimised exactly, as MATPOWER's own DC OPF accepts them; a cubic or higher term, a negative quadratic coefficient or a non-convex piecewise curve is refused (exit 1), naming the generator. Linear and piecewise-linear costs are solved by the same structured simplex as the fuel-type dispatch (a piecewise curve becomes one LP column per segment); any quadratic term is finished by an exact active-set quadratic program started at the simplex's vertex. The total cost is the sum of the curves at the dispatch (constant terms included, as MATPOWER reports its objective) and each unit's figure is its marginal cost there; the units are the case's own currency, printed as cost units (MATPOWER's cost figures are in $/h by convention). Outside a piecewise curve's points its first and last segments are extended in a straight line. Startup and shutdown costs are read and carried but play no part (one period, no commitment). The cost file:

{ "format": "gridsim-costs/1",
  "generators": [
    { "index": 1, "model": "polynomial", "coefficients": [0.11, 5, 150] },
    { "name": "G2", "model": "piecewiseLinear", "points": [[0, 0], [100, 2500], [200, 6000]], "startup": 0 } ] }

index is 1-based in the case's generator list in file order (out-of-service units included: the order of MATPOWER's mpc.gen rows or of generation.json); name must name exactly one unit; give one of the two. Coefficients are highest order first, as in MATPOWER. Every key is checked: an unknown key, a unit named twice, a bad curve or a missing format tag is refused (exit 1) naming the entry. A unit the file does not name keeps the case's own curve, if any.

Prices (--prices). With y0 the balance row's dual and y_r the dual of rated line r's thermal row, the price at bus k is LMP = y0 + sum_r y_r PTDF[r, k]: y0 is the energy component (the price at the island's reference bus) and the sum the congestion component; the DC model is lossless, so there is no loss component. A binding line's shadow price is the cost saved per MW of extra rating. Each island is priced on its own; a dead island's buses get no price. At a degenerate optimum the duals are not unique and those of the optimal basis found are reported. Degenerate dispatch (N240). When several dispatches are equally cheap (every MATPOWER case on the fuel-type merit order prices all its units at 50 GBP/MWh) the LP has many optimal vertices. The simplex breaks ties between entering columns whose reduced costs are equal to within 1e-10 (relative) by taking the lowest index, so the dispatch reported does not depend on the last bits of the PTDF sums (before October 2026, a change in summation order could move pglib case588's dispatch by up to 251.7 MW at the same cost). Every LP whose path meets no such near-tie gives the same bits as before. The console prints the price range, the --top dearest buses and every binding line's shadow price; prices: not available when the dispatch is infeasible. Validated against the published PJM 5-bus example (Li and Bo, 2010; data/matpower/nesta/pglib_opf_case5_pjm.m, whose header records the paper's dispatch 40 / 170 / 323.49 / 0 / 466.51 MW: matched to the printed 0.01 MW) and against the HiGHS solver on pglib case3_lmbd, case5_pjm, case30_as and MATPOWER case9 / case30 (dispatch, cost and every LMP within 1e-6). gridsim dcopf pglib_opf_case5_pjm.m --costs case --prices prints a total cost of 17,479.90, LMPs 16.9774 (bus 1), 26.3845 (bus 2), 30.0000 (bus 3), 39.9427 (bus 4, the reference: its LMP is the energy component) and 10.0000 (bus 5), and branch 5 (bus 4 - bus 5) binding at -240.0 MW with a shadow price of 62.3220 per MW of rating.

Result files: --json <file.json>, --csv <file.csv> or --out <file.json|file.csv> write the result to a file (Result files). Without --costs the money is GBP and the keys say so (total_cost_gbp_per_h, dispatch column cost_gbp_per_mwh). With --costs the money is the case's own cost units, so the keys carry no currency: total_cost_per_h and the dispatch column marginal_cost_per_mwh (each unit's marginal cost), and the summary adds cost_source and cost_units (cost units); before October 2026 the keys said GBP whatever the curves' currency. The same rule applies to acopf --costs. A branch with no name (every MATPOWER branch) is shown in the console as its end buses, from-to. With --prices two tables are added, prices (bus_id,lmp_per_mwh,energy_per_mwh,congestion_per_mwh) and shadow_prices (branch,name,flow_mw,rate_mw,shadow_price_per_mwh).

acopf

gridsim acopf <case> [--loss-tol 1e-3] [--max-iter 20] [--top 12] [--costs case|<file.json>] [--prices]

DC dispatch with an AC loss loop (AcOptimalPowerFlow): NOT a full AC optimal power flow. It runs the DC-OPF dispatch inside an outer loop that inflates demand by the AC losses, re-dispatches and re-solves the AC power flow until the losses change by less than --loss-tol MW, so the dispatch pays for its own losses. Bus voltages, reactive power and AC branch flows are neither optimised nor limited. The header says so: ACOPF (DC dispatch + AC loss loop) - <case> (<n> buses) [not a full AC-OPF: no voltage, reactive-power or AC branch-flow limits]. Prints the iterations, losses, cost and dispatch. Exit 3 if the run does not converge, exit 1 if the solve throws.

A run that does not converge says which of three causes stopped it: the AC power flow at the DC-OPF dispatch of loss pass <k> ... did not converge (with the solver status, iterations, largest mismatch and the lowest voltage where it stopped; the DC dispatch ignores voltages and reactive power, so it can be a point the network cannot carry within the units' reactive limits), the losses settled after <n> pass(es), but the DC-OPF dispatch of the final pass is infeasible (run dcopf to see why), or the losses did not settle within <n> pass(es). A run whose first DC dispatch is infeasible in a way the loss loop cannot repair stops there, before any AC solve, with the DC-OPF dispatch of loss pass 0 (passes count from 0) is infeasible ..., and no later pass can be feasible (exit 3). The loop only ever raises demand, so this is decided only where it is proved: demand above the units' total Pmax, an island with demand and no unit, or a security LP that is Infeasible while every unit may produce nothing (Pmin 0 or below), and only when no branch resistance or bus shunt conductance is negative. Demand below the units' total Pmin, an LP that stalled, or line limits with a unit whose Pmin is above 0 still run the full loop. When every unit is priced the same (a case with no fuel types, such as every MATPOWER file), the first message adds that the dispatch is one arbitrary optimum of a degenerate LP and that --costs case dispatches on the case's own cost curves. acopf case118 and acopf case300 stop at pass 0 (the flat 50 GBP/MWh dispatch puts 25 and 50 units at Pmax, and the AC solve with reactive limits stops with lowest voltages 0.7966 and 0.7806 pu); with --costs case acopf case118 converges in 4 passes (losses 132.504 MW). acopf gb-synthetic converges in 6 passes (losses 1,235.507 MW, 675,277 GBP/h; 4 passes and 1,385.085 MW before the N240 tie-break chose a different optimal vertex of its degenerate DC dispatch) and its final pass leaves out 5 rated lines that no dispatch can relieve (MID SGT 400/275 1 and 2, LDN SGT 400/275 1, YRK G8P4 132/33, MID G2P1S3 33/11). Since N316 (October 2026) the name is the shipped folder, whose branch order differs from the in-memory builder it used to run; the folder stops at the same vertex and prints the same figures (measured at 1.95.259; acopf data/gb-synthetic prints the same output byte for byte). When the final DC pass left out rated lines that no dispatch can relieve (see dcopf), the run names them first (the final DC pass left out <n> rated line(s) no dispatch can bring within rating (still overloaded; ...), up to --top of them).

Flag Default Meaning
--loss-tol 1e-3 Loss convergence tolerance (MW); must be above 0.
--max-iter 20 Outer-loop cap; at least 1.
--top 12 Generators to list.
--costs off Every DC pass dispatches on the generators' own cost curves, exactly as dcopf --costs; the reported cost is then the sum of the curves at the final dispatch, in the case's cost units.
--prices off Also print the nodal prices (LMPs, with their energy and congestion parts) and line shadow prices of the final DC pass, as dcopf --prices prints them. They are lossless DC prices at the loss-inflated demand that pass dispatched: the loss loop only scales demand, so there is no marginal-loss component, and voltage and reactive power do not enter them. The dispatch is the same with or without the flag. The result file gains the prices and shadow_prices tables and prices_source.

Result files: --json <file.json>, --csv <file.csv> or --out <file.json|file.csv> write the result to a file (Result files).

acopf-full

gridsim acopf-full <case> [--max-iter 150] [--top 12] [--cost-file <file.json>]

The full AC optimal power flow (AcOpfInteriorPoint): a primal-dual interior point method, MATPOWER's MIPS with its defaults, starting point and stopping conditions. It chooses every bus voltage (magnitude and angle) and every unit's active and reactive output to minimise the units' polynomial cost curves, subject to the AC power balance at every bus, each rated branch's MVA limit (RATE_A) at both ends, each bus's own voltage limits (else 0.94 .. 1.06 pu) and each unit's P and Q limits, with every slack angle fixed. Transformer taps and phase shifts stay at their case values. The costs are the case's own curves (a .m file's mpc.gencost), or --cost-file (the cost file format of dcopf --costs). Unlike acopf it optimises voltages and reactive power and enforces the AC limits.

Prints the iterations, the objective (in the case's cost units per hour), generation, load and losses, the largest units' P and Q, the highest nodal prices (the multipliers of the active and reactive power balance at each bus, cost units per MWh and per MVArh) with each bus's voltage, and the binding constraints with their shadow prices (Vmin/Vmax per pu, Pmin/Pmax/Qmin/Qmax per MW or MVAr, Sf/St per MVA of the branch's from or to end, each per hour). On case9, case14, case30, case57, case118, case300, case1354pegase and case2869pegase the objective rounds to the figure MATPOWER's runopf prints (5296.69, 8081.53, 576.89, 41737.79, 129660.70, 719725.11, 74069.35 and 133999.29).

Exit 0 converged. Exit 1 for a case the method refuses, with the reason: a unit with no cost curve (give --cost-file) or a piecewise-linear one, a dispatchable load (Pmin below 0 with Pmax 0), a voltage-dependent load, crossed or non-numeric limits, a zero-impedance branch, no slack bus, or more than one island. Exit 3 when it does not converge (not converged: no convergence within <n> iteration(s), or numerical failure: ... for a singular Newton system, a step below 1e-8 or a barrier parameter out of range); the iteration log is printed on stderr and no dispatch is shown, because the point it stopped at is not an optimum. Branch angle difference limits are not enforced (the MATPOWER reader notes them when a file has them).

Flag Default Meaning
--max-iter 150 Iteration cap (MIPS max_it); at least 1.
--top 12 Units, buses and binding constraints to list.
--cost-file the case's curves A cost file (JSON, as dcopf --costs <file.json>) giving every unit's curve.

Result files: --json <file.json>, --csv <file.csv> or --out <file.json|file.csv> write the result to a file (Result files): the summary (objective_per_h, total_generation_mw, total_load_mw, losses_mw, iterations, cost_source) and the tables buses (bus_id,vm_pu,va_deg,lmp_p_per_mwh,lmp_q_per_mvarh,mu_vmin,mu_vmax), generators (unit,bus,pg_mw,qg_mvar,mu_pmin,mu_pmax,mu_qmin,mu_qmax), branches (branch,from,to,pf_mw,qf_mvar,pt_mw,qt_mvar,rate_mva,mu_sf,mu_st), binding (kind,element,shadow_price) and iterations (the log). A run that does not converge writes no result file.

scuc

gridsim scuc <case> [--uc-data <file.json>] [--periods N] [--no-line-limits] [--node-cap 100000] [--gap 1e-6] [--top 12]

Security-constrained unit commitment (UnitCommitment): which units run in each period, and at what output, at least total cost. It is a mixed-integer linear program solved by MilpBranchAndBound, an LP-based branch-and-bound over the sparse interior point LP, both in GridSim's own numerics (no external solver). Per unit and period: on/off and start decisions (whole), output between Pmin and Pmax while on, minimum up and down times, ramp limits (a start may reach max(ramp, Pmin) in its first period), start-up and no-load costs; per period: the demand balance (the case's bus loads times the period's scale) and a spinning reserve requirement (the committed units' headroom Pmax - P); per rated branch and period: the DC flow (PTDF times generation plus the flow the loads drive, as dcpf solves it) within RATE_A; and for each listed outage, every rated branch's post-outage DC flow (by the line outage distribution factors) within RATE_A.

Costs: a unit's marginalCost from the data file, else the case's cost curve (a .m file's mpc.gencost: linear and piecewise-linear curves are used exactly; a quadratic curve is cut into 4 chords between Pmin and Pmax, exact at the break points and slightly above the curve between them, and a note says so), else the fuel-type cost of dcopf. A polynomial curve's constant term is paid in every period the unit is on. The start-up cost is the data file's, else the gencost STARTUP column, else 0. Without a data file every unit starts on (so nothing starts) and the run is one period of the case's own load.

The data file (gridsim-uc/1, every key checked, every top-level key but format optional):

{ "format": "gridsim-uc/1", "periods": 24, "periodHours": 1,
  "demandScale": [0.7, 0.65, ...], "reserveMw": [100, 100, ...],
  "units": [ { "unit": 0, "marginalCost": 12.5, "noLoadCost": 100, "startupCost": 500, "minUp": 3, "minDown": 2,
               "rampUpMw": 80, "rampDownMw": 80, "initiallyOn": false, "initialPeriods": 5, "initialMw": 0,
               "mustRun": false },
             { "name": "G2", "startupCost": 200 } ],
  "contingencies": [ 4, "Line 7-8" ] }

A unit is named by unit (its index among the in-service generators, from 0) or name (unique); a contingency by a branch index (from 0) or a unique branch name. initialPeriods is how long the unit has been in its initial state (a unit inside its initial minimum time is held there); initialMw ramp-limits the first period. A unit whose Pmin is below 0 (storage charging, an exporting link) is always on.

Prints the problem size, the total cost with its energy, no-load and start-up parts, each period's demand, generation, headroom, reserve, system price and units on, the largest units' schedules (1 on, * started, 0 off) and the binding branch limits (intact, or after an outage). The system price is the balance row's dual in the LP with the commitment fixed at the answer (the usual pricing of a commitment), per MWh.

Exit 0 optimal (within the gap). Exit 1 for input the commitment cannot build exactly, with the reason: a malformed data file, a committable unit with no finite Pmax, several DC islands, an outage that islands the network, per-period arrays of the wrong length, or more than 200,000 columns. Exit 3 when no optimum is proven: infeasible (no schedule meets the demand, reserve and limits), the node cap reached (the best schedule found so far is printed, labelled NOT PROVEN OPTIMAL, with the best bound), or a node relaxation that ended without an answer (the node is named).

Flag Default Meaning
--uc-data none The unit commitment data file (gridsim-uc/1).
--periods the file's, else 1 The number of periods (must agree with the file's per-period arrays).
--no-line-limits off Leave the branch ratings out (a copper plate); listed outages are still secured.
--node-cap 100000 Branch-and-bound nodes before stopping; at least 1.
--gap 1e-6 Relative optimality gap.
--top 12 Units and binding limits to list.

Result files: --json <file.json>, --csv <file.csv> or --out <file.json|file.csv> write the result to a file (Result files): the summary (status, optimal, total_cost, energy_cost, no_load_cost, startup_cost, bound, nodes, lp_iterations, rows, columns, integer_columns, line_limits, contingencies, uc_data) and the tables periods (period,demand_mw,generation_mw,headroom_mw,reserve_mw,system_price_per_mwh), schedule (unit,bus,name,period,on,started,output_mw) and binding (period,branch,name,contingency,flow_mw,rate_mw; contingency -1 is the intact network). A run with no schedule writes no result file.

scopf

gridsim scopf <case> [--contingencies all|<i,j,...>] [--post-rating A|B|C] [--linear-costs case|<file.json>] [--full-lp] [--max-rounds 50] [--top 12]

Preventive security-constrained DC optimal power flow (DcScopf): the cheapest dispatch that keeps every rated branch within RATE_A in the intact network and within its post-outage rating after each secured single-branch outage, with no action after the outage. It is a sparse linear program on bus angles (each bus's balance and each branch's DC flow), and each secured (outage, branch) pair adds the post-outage flow through the line outage distribution factors, solved by GridSim's own sparse two-phase simplex. By default the pairs enter the LP only once the dispatch breaks them (constraint generation; each round re-solves with the broken limits added, until none is broken by more than 1e-6 MW); --full-lp puts every pair in from the start and gives the same optimal cost. The DC model is that of dcopf, ptdf and lodf (series reactance only). See technical chapter 29 for the formulation and its validation.

Outages: all (the default) secures every in-service branch whose outage leaves the network connected; outages that would island it are listed and not secured. A comma list of branch indices (from 0) secures those; a listed outage that islands the network, an unknown or out-of-service branch, or a duplicate is refused (exit 1). Costs: the fuel-type cost of dcopf (GBP/MWh), or with --linear-costs each unit's own curve (case for a .m file's mpc.gencost, or a gridsim-costs/1 file), which must be linear: a quadratic or piecewise-linear curve is refused (exit 1), not approximated. A curve's constant term is added to the total cost.

Prints the outages secured and not secured, the LP size and solves, the total cost, the range of nodal prices (each bus's balance dual: the cost of one more MW of demand there), the largest units' dispatch and the binding limits (intact, or after the outage of a branch, against the rating used).

Exit 0 optimal. Exit 1 for input the SCOPF cannot build: several DC islands, a refused outage, a cost curve that is not linear, a unit with no cost curve under --linear-costs case, invalid generator limits. Exit 3 when there is no secure dispatch: the security set is infeasible, the round cap is reached, or an LP solve failed (the cause is printed); no dispatch is printed and no result file is written.

Flag Default Meaning
--contingencies all all, or a comma list of branch indices (from 0) to secure.
--post-rating A The rating after an outage: A, B (short-term) or C (emergency); A on a branch where B or C is not given. The intact network always uses A.
--linear-costs fuel-type costs case or a gridsim-costs/1 file: each unit's cost curve, which must be linear.
--full-lp off Every post-outage limit in the LP from the start (no constraint generation).
--max-rounds 50 The most LP solves constraint generation may take; at least 1.
--top 12 Units, binding limits and islanding outages to list.

Result files: --json <file.json>, --csv <file.csv> or --out <file.json|file.csv> write the result to a file (Result files): the summary (status, optimal, total_cost_per_h, cost_units, demand_mw, post_fault_rating, outages_secured, islanding_outages, rounds, post_outage_rows, rows, columns, lp_iterations, full_lp) and the tables dispatch (unit,bus,name,p_mw,marginal_cost_per_mwh), prices (bus_id,lmp_per_mwh), binding (branch,name,contingency,flow_mw,rate_mw; contingency -1 is the intact network) and islanding_outages (branch). A run with no secure dispatch writes no result file.

qsts

gridsim qsts <case> --study <file.json> [--top 10] [--allow-unsettled]

Quasi-static time series (QstsEngine): a sequence of power flows, one per step, over the load, generation, PV and storage profiles of a study file, warm-started from the previous step, with the controllers acting in time and their state (tap positions, bank steps, delay timers, inverter set points, storage energy) carried from step to step. The engine is the one the case solve picks: the backward/forward sweep for a radial feeder (or with --bfs), otherwise the shared Newton engine on the selected backend, with the default power-flow options. Step 0 is solved from the case as given, so a one-step study with nothing varying gives exactly the case's own power flow.

Two control modes ("mode" in the file):

  • timed (the default): the time-aware controllers below. Within a step: the timers and storage energy advance over the elapsed interval; the step is solved; then, repeatedly, inverters and storage settle to a fixed point, else every capacitor bank whose delay has run out switches one step, else every tap changer whose delay has run out moves one tap, re-solving after each round, until nothing acts (or maxControlIterations, default 25, discrete rounds; maxContinuousIterations, default 200, continuous ones; when the per-unit inverter iteration reaches that cap without settling, as with many coupled volt-var units, an accelerated iteration over all units takes over with a fresh cap of the same size, technical ch. 37).
  • steady: each step is solved by the existing steady-state loops (the tap loop of the case solve, around the switched-shunt loop of pf --switched-shunts when banks are given), so the controls settle instantly; taps and bank steps carry to the next step. Volt-var, volt-watt, peak shaving, line drop compensation and var/time bank control need timed and are refused here.

Controllers (timed mode):

  • Tap changers: the case's OLTC records (target, deadband, step, range), with timing from the file's oltc block: delaySeconds (initial delay), interTapSeconds (later steps of the same excursion under "sequence": "continuous"; "sequential" waits the full delay before every step), "characteristic": "inverse" (delay x half-band / |deviation|, not below minDelaySeconds), line drop compensation ldcRPu / ldcXPu (pu on the system base: the regulated voltage is |V - (R + jX) I| with I the transformer current into the regulated bus), and "coordination": "sequential" (only the first ready regulator by priority moves per round) or "independent". A delay counts from the first step at which the voltage is seen outside the band; with steps longer than the delay the regulator makes, at that step, every operation its timers allow (catch-up). An OLTC regulating a generator-held bus holds, as in the case solve.
  • Capacitor and reactor banks: equal steps of stepMvar (MVAr at 1 pu, negative for a reactor) between minSteps and maxSteps, with "control": voltage (in below onPu, out above offPu, at controlsBus or the bank's bus), var (in when the reactive power into branch at its From end exceeds onMvar, out below offMvar) or time (in from onTime to offTime, "HH:MM"); delaySeconds / offDelaySeconds; deadTimeSeconds (no switching back in until that long after switching out). A bank that reverses within a step is frozen for the rest of the step.
  • PV inverters: ratedMw at profile value 1, ratedMva, availability profile; control.function unity, pf (powerFactor, pfMode absorbing or injecting), volt-var, volt-watt or volt-var-volt-watt, with curves "voltVar": "1547-A" | "1547-B" | {v1,q1,...,v4,q4} (Q as a fraction of ratedMva, positive injecting; default IEEE 1547-2018 Category B) and "voltWatt": "1547" | {v1,p1,v2,p2} (default 1.06 / 1.10 pu); responseSeconds (open-loop response time: 90 % of a change after that long); priority var (P gives way) or watt (Q gives way) within ratedMva.
  • Storage: ratedMw, capacityMwh, initialSoc, socMin, socMax, chargeEfficiency, dischargeEfficiency, and dispatch.mode schedule (MW profile, discharge positive), peak-shave (keep the active power into branch at its From end between lowMw and highMw) or self-consumption (cover its bus's demand net of PV there). The power is held for the step; E(k+1) = E(k) + eta_c Pc dt - Pd / eta_d dt; the power is limited so the energy stays within the SOC limits.

The study file (gridsim-qsts/1; every key checked, unknown keys refused):

{
  "format": "gridsim-qsts/1",
  "stepSeconds": 900, "steps": 96, "mode": "timed", "startTime": "00:00",
  "profiles": {
    "res":   { "stepSeconds": 1800, "values": [0.62, 0.60, 0.58], "interpolation": "linear", "wrap": true },
    "solar": { "stepSeconds": 900, "csv": "solar.csv", "column": "pv" }
  },
  "loads": [ { "buses": "all", "profile": "res" } ],
  "generators": [ { "name": "G1", "profile": "wind", "absoluteMw": false } ],
  "loadAdditions": [ { "name": "EV7", "bus": 7, "mw": 0.5, "profile": "ev", "powerFactor": 0.98 } ],
  "pv": [ { "name": "PV5", "bus": 5, "ratedMw": 2, "ratedMva": 2.2, "profile": "solar",
            "control": { "function": "volt-var", "voltVar": "1547-B", "responseSeconds": 5 } } ],
  "storage": [ { "name": "B7", "bus": 7, "ratedMw": 1, "capacityMwh": 2, "initialSoc": 0.5, "socMin": 0.1, "socMax": 0.9,
                 "chargeEfficiency": 0.95, "dischargeEfficiency": 0.95,
                 "dispatch": { "mode": "peak-shave", "branch": "T1", "highMw": 5, "lowMw": 2 } } ],
  "oltc": { "coordination": "independent",
            "default": { "delaySeconds": 30, "interTapSeconds": 5, "sequence": "continuous", "characteristic": "definite" },
            "settings": [ { "transformer": "T1", "ldcRPu": 0.01, "ldcXPu": 0.02 } ] },
  "capacitors": [ { "name": "C9", "bus": 9, "stepMvar": 0.6, "maxSteps": 1, "control": "voltage",
                    "onPu": 0.97, "offPu": 1.04, "delaySeconds": 60, "deadTimeSeconds": 300 } ],
  "limits": { "vminPu": 0.94, "vmaxPu": 1.06, "loadingPercent": 100, "perBusVoltageLimits": false }
}

Required: format, stepSeconds (whole seconds, at least 1), steps. A profile gives one sample per its own stepSeconds from t = 0, inline (values) or from a CSV column (csv, a path relative to the study file, and column, a header name or an index from 0; a header row is recognised when the first cell is not a number); "interpolation" hold (default) or linear; "scale" multiplies every value; a study longer than a profile is refused unless the profile has "wrap": true. Load profiles multiply the bus demand (scaleP / scaleQ, default both; "buses": "all" means every bus with demand, and a bus takes one load profile); generator profiles multiply Pg (or give it in MW with absoluteMw), the generator named by name or by index among the in-service units (from 0). PV, storage and added loads enter their bus as a negative / positive load. A reactive function on a PV unit at a PV or slack bus is refused (the generator holds that voltage). "generationFollowsLoad": true scales every generator off the slack bus that has no profile of its own by the step's demand ratio (the profile value when one profile scales every bus) and re-balances the dispatch, as chain does, so a transmission case's slack does not absorb the whole demand swing; without it generation stays as in the case.

Prints the run size and speed, the energy totals, the voltage range and when it occurred, the tap and bank operation counts per device, each storage unit's final state of charge and the buses and branches outside their limits, with the time spent outside (h:mm:ss; each step stands for one step length) and the duration-weighted excess (pu.h above / below).

Exit 0 when every step converged and settled. Exit 1 when the study file is refused (every problem is listed). Exit 3 when a step does not converge (the run stops there, no result file is written) or, without --allow-unsettled, when a step's controls did not settle within the iteration caps (the result file is written, with exit 3 inside).

Flag Default Meaning
--study (required) The gridsim-qsts/1 study file.
--top 10 Buses and branches outside their limits to list.
--allow-unsettled off Exit 0 even when a step's controls did not settle within their caps.

Result files: --json <file.json>, --csv <file.csv> or --out <file.json|file.csv> write the result to a file (Result files): the summary (case, buses, engine, mode, step_seconds, steps, completed, unsettled_steps, tap_operations, capacitor_operations, vmin_pu, vmax_pu, load_mwh, loss_mwh, source_mwh, pv_available_mwh, pv_mwh, pv_curtailed_mwh, storage_charge_mwh, storage_discharge_mwh, buses_violating, branches_violating, digest: a SHA-256 over every number of the run, equal between two runs exactly when they agree to the bit) and the tables steps (step,time_s,settled,solves,iterations,vmin_pu,vmin_bus,vmax_pu,vmax_bus, max_loading_pct,max_loading_branch,loss_mw,loss_mvar,load_mw,source_mw,pv_available_mw,pv_mw,pv_mvar,storage_mw), devices (kind,name,operations), operations (the log: step,time_s,kind,device,from,to,sensed,control_iteration), bus_violations (bus_id,seconds_above,seconds_below,pu_seconds_above,pu_seconds_below,max_pu,min_pu), branch_violations (branch,name,seconds_over,percent_seconds_over,max_percent), taps (step,transformer,tap), banks (step,bank,steps), pv (step,unit,p_mw,q_mvar), storage (step,unit,p_mw,soc_start) and, unless the file sets "recordStates": false, voltages (step,bus_id,vm_pu) and loadings (step,branch,loading_pct, rated branches).

hosting

gridsim hosting <case> [--study <file.json>] [--method snapshot|qsts] [--resource pv|load] [--buses all|<ids>] [--max-mw X] [--tolerance-mw T] [--snapshots d:r,...] [--resource-profile NAME] [--pv-function unity|pf|volt-var|volt-watt] [--mva-per-mw 1] [--load-pf 1] [--reverse-branch auto|none|NAME] [--reverse-allowance-mw 0] [--allowed-violation-s 0] [--tap-increase-pct P] [--criteria list] [--threads N] [--top 20]

Hosting capacity (HostingCapacity): the largest PV (or, with --resource load, added demand such as electric vehicle charging or heat pumps) at each candidate bus before a limit is broken, found by bisection on the size in MW. Each candidate is studied on its own, with the resource added at that bus only.

Methods:

  • snapshot (the default): one regulated power flow per snapshot, each a demand multiplier (on every bus with demand) and a resource multiplier (PV availability or the added load's level). Default snapshots: for PV, minimum demand 0.3:1 and full demand 1:1; for load, 1:1. Tap changers and capacitor banks of the study (or the case's OLTCs) settle instantly (every delay is taken as zero).
  • qsts: the whole time series of --study (a gridsim-qsts/1 file, see qsts) with the resource added, driven by --resource-profile (a profile of the study; constant 1 when not given). A bus or branch may be outside its limits for --allowed-violation-s seconds before it counts, and --tap-increase-pct adds the tap-operation criterion: the run may make at most that percentage more tap operations than the base run.

Constraints (all by default; --criteria takes a comma list of overvoltage, undervoltage, thermal, reverse-power, tap-operations, non-convergence): a bus above or below the study's voltage limits (default 0.94 and 1.06 pu), a rated branch above the loading limit (default 100 % of RATE_A), active power flowing back through the --reverse-branch (the protection proxy: feeder protection and the source tap changer are set for forward flow; auto, the default, takes the first named branch leaving the slack bus; none turns it off), more tap operations than allowed, and a power flow that does not converge. A limit the base case (no added resource) already breaks counts only where the resource makes it strictly worse, so an existing problem does not mask the capacity and is not blamed on the resource; such limits are listed.

Search: --max-mw (default twice the case demand, at least 1 MW) is tried first; if it passes, the capacity is reported as above it. Otherwise the bracket [0, max] is halved (mid = lo + (hi - lo) / 2) until it is at most --tolerance-mw wide (default max / 1024). The reported capacity is the passing end, the "fails at" size the failing end, and the limiting constraints are those broken at the failing end; for a limit that grows steadily with the size, the true capacity lies between the two. The same sizes are evaluated in the same order on every run; --threads studies several candidates at once (each with its own engine) without changing any number.

Prints the method, search, limits and any base-case violations, then one row per candidate (lowest capacity first): the capacity, the failing size and the limiting constraint with where and how far.

Exit 0 when the study ran (a location limited within the range is a result). Exit 1 when the study is refused (every problem is listed) or the base case does not solve. Exit 2 for a usage error (--method qsts without --study, a bad flag value).

Flag Default Meaning
--study none The gridsim-qsts/1 study: the time series (qsts method), and the controls and limits (both methods).
--method snapshot snapshot or qsts.
--resource pv pv or load.
--buses all Candidate buses: all (every PQ bus) or a comma list of bus ids.
--max-mw 2 x demand Top of the search (MW).
--tolerance-mw max / 1024 Width of the final bracket (MW).
--snapshots see above Snapshot conditions as demand:resource pairs.
--resource-profile constant 1 The study profile driving the resource (qsts method only).
--pv-function unity The hosted PV's inverter function: unity, pf, volt-var (IEEE 1547-2018 Category B) or volt-watt.
--mva-per-mw 1 The hosted PV's apparent power rating per MW (at least 1).
--load-pf 1 The hosted load's power factor (lagging).
--reverse-branch auto The reverse-power branch: auto, none or a branch name.
--reverse-allowance-mw 0 Reverse power allowed before it counts (MW).
--allowed-violation-s 0 Time a bus or branch may spend outside its limits (qsts method, s).
--tap-increase-pct off Tap operations allowed above the base run (qsts method, %).
--criteria all The constraints judged (comma list).
--threads 1 Candidates studied at once.
--top 20 Rows to list.

Result files: --json <file.json>, --csv <file.csv> or --out <file.json|file.csv> write the result to a file (Result files): the summary (case, buses, engine, resource, method, max_mw, tolerance_mw, candidates, evaluations, min_hosting_mw, base_violations) and the tables locations (bus_id,hosting_mw, failing_mw,limited,limiting,detail,evaluations; failing_mw is Infinity where the maximum passed), limiting (bus_id,constraint,element,value,detail: every constraint broken at the failing size) and base_violations (constraint,element,value,detail).

cpf

gridsim cpf <case> [--step 0.25] [--min-step 1e-3] [--max-steps 200] [--pv-out <file.csv>]

Maximum loadability by stepping and bisection (ContinuationPowerFlow.MaxLoadability). Despite the verb's name it is not a predictor-corrector continuation power flow (no tangent predictor, no parameterised corrector, no tracing round the nose): it scales every bus's P and Q demand by a multiplier lambda, with the slack absorbing the extra generation, solves an ordinary power flow at each lambda, steps lambda up while it converges and, on a failure, backs off and halves the step. The answer is the largest lambda at which the Newton power flow still converges, a slightly conservative estimate of the voltage-collapse nose (Newton fails as the Jacobian becomes singular). Prints the largest converged lambda (round-trip precision) and the margin above base load. The line ends nose bracketed to <min-step> only when the walk ended because its step fell below --min-step. When --max-steps runs out first it says NOT bracketed: --max-steps <n> ran out first; the nose lies between this lambda and <the smallest lambda that failed> (or, when every solve converged, that lambda is only a lower bound), the run explains on stderr and exits 3; before October 2026 it printed nose bracketed either way and exited 0. Exit 3 when no lambda converges. A case whose base load (lambda 1) does not converge but whose lower loads do prints the lambda below 1 and the negative margin (how far the load must fall before the case solves), then says on stderr that the base case did not converge, and exits 3: the case as given has no loadability margin (cpf data/intl/france: lambda 0.986328125, margin -1.37%, exit 3). This answers a different question from stress, which re-dispatches generation at each load factor on a fixed grid of factors; the two definitions are deliberately distinct. What counts as a converged point is the same for both: every point is solved with the contingency option set and the tap-changer loop (Solver selection), on the selected backend. cpf case9 prints max loadability lambda = 2.373046875 and cpf uk 6.052734375.

Flag Default Meaning
--step 0.25 Initial lambda step; above 0.
--min-step 1e-3 Bisection stops below this step (the nose is bracketed to it); in (0, --step].
--max-steps 200 Cap on power-flow solves; at least 1. Running out before the nose is bracketed to --min-step exits 3 (the lambda printed is then a lower bound).
--pv-out - Also write the PV curves: every converged point's voltage at every bus, one row each, as case,lambda,bus_id,vm_pu, in the order solved (lambda rises strictly). The points come from the same loop, so the printed lambda is the same. A name not ending in .csv exits 2.

Result files: --json <file.json>, --csv <file.csv> or --out <file.json|file.csv> write the result to a file (Result files); the summary carries nose_bracketed, solves and lowest_failed_lambda (null when every solve converged).

taps

gridsim taps <case> [--target 1.0]

Coordinated tap schedule (TapOptimizer.Flatten): one set of tap ratios across every OLTC that minimises the sum of squared bus-voltage deviations from --target, rounded to each OLTC's step grid. Prints the objective before and after and each transformer's current and recommended tap.

Every OLTC record must name exactly one branch of the case and control a bus the case has; otherwise the run exits 1 before any solve, naming each bad record (an OLTC that matched no branch used to be dropped from the schedule without a word). The schedule minimises every bus's deviation from the one --target, so it can leave the bus an OLTC controls outside that OLTC's own target plus or minus its deadband, where its local regulator would move the tap away from the schedule: such OLTCs are listed after the schedule (<n> OLTC(s) would leave this schedule: ..., with the controlled bus, its voltage and the OLTC's own target and deadband); nothing is printed when every OLTC accepts the schedule. The tap search (downhill simplex, at most 2,000 iterations) must meet its convergence test: when it stops at the cap the schedule found is still printed, stderr says it is not a proven optimum, and the run exits 3 (it used to exit 0). Exit 1 when the case has no OLTCs or an OLTC record does not resolve, exit 3 when the base case does not converge or the search does not converge. The result file adds optimizer_converged, optimizer_iterations and a regulation table (transformer,controls_bus,vm_pu,target_pu,deadband_pu,within_deadband).

Flag Default Meaning
--target 1.0 Target bus voltage (pu); above 0.

Result files: --json <file.json>, --csv <file.csv> or --out <file.json|file.csv> write the result to a file (Result files).

restore

gridsim restore <case> --order <b1,b2,...> [--vmin 0.90] [--vmax 1.10] [--qtol 1.0]

Restoration (black-start) sequence check (RestorationSequencer.Evaluate). The branches named in --order start open, whatever their stored state, and are energised one per step in that order; every other branch keeps its state in the case. Each step re-solves the live (slack-connected) network with generator reactive limits enforced and the live on-load tap changers regulating, then reports the lowest and highest bus voltage, the buses outside [--vmin, --vmax], and the generator buses whose reactive output is within --qtol Mvar of a limit (the machine can absorb or supply no more, which is what makes an energisation step unsafe, for example a Ferranti over-voltage on a lightly loaded line). A step is feasible when it solves with no band breach and no generator at a limit.

A branch is named by its name in the case, or by #k, its 1-based row in the case's branch table (MATPOWER files carry no branch names). Exit 0 when every step is feasible; 3 when any step does not solve or is not feasible (the table is still printed, with the first unsafe step named); 1 for a branch that is not in the case, a branch named twice, a #k outside the table or one that is also another branch's name, or a load error; 2 without --order, for an empty entry in the list, or for a bad flag value.

Flag Default Meaning
--order - (required) The energisation order: branch names or #k rows, comma-separated, no empty entries.
--vmin / --vmax 0.90 / 1.10 The voltage band checked at each step (pu; the statutory band of VoltageLimits). --vmin above 0, --vmax above --vmin.
--qtol 1.0 A generator bus whose reactive output is within this many Mvar of its summed Qmin or Qmax counts as at its limit; 0 or more.

Result files: --json <file.json>, --csv <file.csv> or --out <file.json|file.csv> write the result to a file (Result files): one row per step, with null voltages for a step that did not solve.

losses

gridsim losses [<case>]

Loss allocation on the solved base case, under a header naming the case (Loss allocation - <case> (N buses, M branches)): total P and Q losses, the real power drawn by bus shunt conductances (Bus shunt conductance, only when the case has any: it is in the solver's injection total but in no branch), the reconciliation residual (rounding once the shunt draw is accounted for), losses by zone (when the case has zones) and the 20 lossiest branches. <case> defaults to case9 and is resolved like every other case argument (Case arguments): an unknown name exits 2 naming it, a missing or unloadable .m file or case folder exits 1, and a second case argument exits 2. Solves on the shared dense / sparse rule. Exit 3 if the base case does not converge. No flags.

Result files: --json <file.json>, --csv <file.csv> or --out <file.json|file.csv> write the result to a file (Result files).

dist3ph

gridsim dist3ph <feeder.json> [sweep] [--tol 1e-10] [--max-iter 200] gridsim dist3ph <feeder.json> fault --bus ID [--type all|3ph|slg|ll|llg] [--zf PU] gridsim dist3ph <feeder.json> estimate --measurements <m.json> [--method wls|wlav|branch-current] [--tol 1e-10] [--max-iter 50] [--robust-passes 8] [--robust-floor 0.001] gridsim dist3ph <feeder.json> harmonics --bus ID --spectrum TYPE --current PU [--afe feeder] gridsim dist3ph <feeder.json> to-v2 --to <out.json>

EXPERIMENTAL. The unbalanced three-phase distribution stack (GridSim.Core.Distribution) on a radial feeder read from a gridsim-dist3ph/1 JSON file, or (N339, October 2026) its JSON v2 form gridsim-dist3ph/2 (format in technical ch. 18; bundled examples under data/dist3ph/, including the IEEE 4-node and the IEEE 123-node test feeders; user guide in ch. 7). The mode word follows the file and defaults to sweep. Each mode accepts only its own flags; a flag from another mode is a usage error (exit 2), not silently ignored.

  • sweep: the three-phase backward/forward sweep (ThreePhaseSweep). Prints per bus and phase |V| (pu and line-to-neutral volts), angle and the voltage unbalance factor. A non-converged sweep prints its status and the final voltage change on stderr, reports no voltages, and exits 3. The sweep solves single- and two-phase laterals (a phase a bus does not have prints - and has no result row; the unbalance factor is printed for three-phase buses only), line charging, regulators on fixed taps, closed switches, capacitors, and constant-current, constant-impedance and delta loads; a feeder with any of these (closed switches alone included) prints one line counting them, and a named bus (such as RG1) is shown by its name.
  • to-v2 (N339): writes the feeder as a gridsim-dist3ph/2 document (schemas/v2/dist3ph.schema.json) at --to, then proves it: the written file is read back with the v2 reader and compared with the feeder bit for bit (every per-unit number by its 64 bits, ids, kinds, phases, transformer elements, order). The v2 form is the solver-authoritative per-unit model (closed unit vocabulary: pu@system, MVA, kV; nothing converted at load) with provenance: a document default and optional per-element entries. A feeder read from a v1 file (or lifted from a case) carries no provenance and is written with CuratedPlaceholder and a note naming the source and carrying [VERIFY] (GridSim invents no tag; set it before relying on the file); a v2 feeder keeps its own. Prints wrote <file> (gridsim-dist3ph/2); read back: the same feeder, bit for bit and the provenance tag. Exit 2 without --to or when the output exists (never overwritten); 1 when the feeder holds something the v2 form cannot (named, nothing written) or the file cannot be written; 3 when the written file does not read back to the same feeder (the difference named, the file kept). gridsim validate <file> checks a gridsim-dist3ph/2 file against the schema and then with the reader itself. Every mode reads a v2 feeder as it reads a v1 one; the v1 format is unchanged.
  • fault, estimate and harmonics model the elements above that they can define exactly and refuse the rest (exit 1, naming each refused kind), never leaving an element out silently. fault: shunt capacitors, line charging and loads of every kind are neglected (shunt elements, as the constant-power loads are; the fault current is that of the series path) and a closed switch is a zero impedance; a single- or two-phase branch or a regulator on the path to the faulted bus is refused, naming the branch (elsewhere in the feeder it does not enter the study). estimate (WLS and WLAV): loads and capacitors are accepted (its measurement model has no injection measurements); laterals, line charging, regulators and closed switches are refused. estimate --method branch-current: every element is modelled (a regulator and line charging are undone from the measured From-end current in the forward sweep, a lateral drops only on its phases, a closed switch has no drop); a regulator or a charged line must face away from the source, and a current on a phase the branch does not carry is refused. harmonics: shunt capacitors and line charging (G + j h B) and closed switches (their buses one node) are in Y(h), and the printed network line says so; laterals and regulators are refused.
  • The feeder may also be a radial positive-sequence case, a MATPOWER .m file or a JSON case folder: it is lifted into a balanced three-phase feeder (MultiPhaseGridModelAdapter: each branch's r + jx and charging on every phase, each bus load per phase, ZIP loads as constant-impedance, constant-current and constant-power parts, shunt capacitors, the slack as the source). A case the sweep cannot model is refused (exit 1): a voltage-controlled (PV) bus, an off-nominal tap or phase shift, a shunt conductance or reactor, a bus without a kV base, or a network that is not one radial tree. On such a lift the sweep agrees with the pf Newton solution.
  • fault: sequence-network fault currents at --bus (SequenceFaultStudy): three-phase, single-line-to-ground, line-to-line and double-line-to-ground (ground current), in pu and amps, from a 1.0 pu prefault voltage behind an infinite source. Each branch is reduced to its transposed-equivalent sequence impedances. A fault at the source bus is refused (exit 1): the infinite bus has zero impedance. Every fault type refuses a zero loop impedance (for example a bolted fault at a bus joined to the source only by closed switches) and a non-finite current, naming the type, rather than printing Infinity or NaN.
  • estimate: the three-phase node-voltage WLS estimator (ThreePhaseWlsEstimator, robust WLAV with --method wlav) on a gridsim-dist3ph-measurements/1 file (per-phase voltage magnitudes, per-phase branch current phasors, optional nominal-voltage pseudo-measurements for unmetered buses). Non-convergence (including an unobservable set) exits 3 with no estimate reported. A converged estimate prints the voltage table and then one residual row per measurement in the fit (| measurement | phase | measured pu | estimate pu | r/sigma |, magnitudes first, then currents as re+jim; a magnitude at the source bus is not in the fit and is not listed); the result file has the same rows as a residuals table. The estimator is dense (a 6n x 6n gain inverted every iteration), so a feeder with more than 416 non-source buses (2,500 states) is refused, exit 1. --method wlav re-weights the measurements by 1 / max(|r / sigma|, floor) for at most --robust-passes passes (default 8, at least 1) with the floor --robust-floor (default 0.001, above 0); both flags are refused (exit 2) with another method. When the last pass still moves a weight by 0.001 or more, the estimate prints WARNING: the robust re-weighting (IRLS) reached its cap of N pass(es) before the weights settled; ... (exit stays 0, as for the single-phase estimate; the result file has irls_cap_reached). With --method branch-current it is the branch-current estimator instead (BranchCurrentDsse): the current phasors are WLS-combined per branch and phase and one forward sweep from the source gives the voltages. It uses current phasors only, so a measurement file that also has voltage magnitudes or pseudo-measurements is refused (exit 1), as are --tol, --max-iter, --robust-passes and --robust-floor (exit 2). A current named against the reversed endpoints (from the To bus) is accepted as minus the From-end current, as wls and wlav accept it, except across a regulator or a charged line (exit 1, naming the branch). Every phase a tree branch carries needs a current phasor: a branch with no phasor, or with phasors on some of its phases only, leaves the estimate not converged (exit 3), and the message lists the unobservable branch phases (1-2 b).
  • harmonics: the three-phase harmonic penetration (ThreePhaseHarmonicPenetration) with one balanced harmonic current source at --bus: the --spectrum profile of the harmonic source library (the same names as the harmonics verb's sources, for example 6-pulse-g5; there is no default) at a fundamental current of --current pu, rotated by h x 120 degrees on phases b and c. The network is the feeder's series impedances with the reactance scaled by the order (with any shunt capacitors and line charging, and closed switches as one node), the source as the harmonic reference, and no loads. Prints, per order, the harmonic voltage at the source bus on each phase and in sequence components, and the bus with the largest harmonic voltage; then the root-sum-square harmonic voltage at the source bus per phase. Exit 1 for a bus not in the feeder, the source bus, or a singular network; 2 without one of the three flags or for an unknown spectrum.
Flag Default Meaning
--tol 1e-10 sweep: max per-phase voltage change (pu); estimate: max state update. Above 0.
--max-iter 200 (sweep), 50 (estimate) Iteration cap; at least 1.
--bus required (fault, harmonics) Fault or harmonic-source bus id; must be in the feeder and not the source.
--type all all, 3ph, slg, ll or llg.
--zf 0 Fault resistance (pu on the feeder base), at least 0: Zf = --zf + j0. The fault header prints it as Zf = ... pu (resistive). Note that fault and protection-check read --zf as a fault REACTANCE (Zf = j--zf, printed Zf=j...); the same flag name means a resistance here and a reactance there (D-DOC-166).
--measurements required (estimate) The measurement file.
--method wls wls, wlav (robust IRLS outer loop) or branch-current (the branch-current estimator).
--spectrum required (harmonics) A harmonic source library profile: 6-pulse, 12-pulse, pv-inverter, ev-charger, heat-pump-inverter, arc-furnace, saturated-transformer, 6-pulse-g5, 12-pulse-g5, afe-g5 or ideal (the idealised 1/h six-pulse spectrum, the same as 6-pulse).
--current required (harmonics) The source's fundamental current (pu on the feeder base), above 0.
--afe - N354, harmonics only: feeder stamps the feeder file's active-front-end converter units (its v1 converters section: id, bus, kva, xPercent, optional rPercent, the internal impedance in percent on the unit's own rating; no default value exists [VERIFY]) into Y(h), each phase R + j h X between the phase and the converter's floating star point (a three-wire shunt: positive and negative sequence, no zero sequence). A line names the units. A feeder with no converters section exits 1; any other value exits 2. Without the flag the units are not stamped and the study is unchanged. N360: the v2 form holds the units too (its converters section: id, bus, ratingMva, xOnRating, optional rOnRating, per unit on the unit's own rating, the same doubles the v1 file gives), so to-v2 writes them and reads them back bit for bit, and --afe feeder works on a v2 feeder.

Exit 0 on success; 1 on an input error (unreadable or invalid feeder or measurement file, every message naming the file and JSON path; a bus the feeder does not have; a study that refuses its input); 2 on a usage error; 3 when the sweep or the estimator does not converge.

Result files: --json <file.json>, --csv <file.csv> or --out <file.json|file.csv> write the result to a file (Result files).

Physics and protection verbs

These verbs take <case|case.m|case-dir> as a positional argument. Protection and short-circuit work is in ch. 12; the physics audit is in ch. 27.

physics-check

gridsim physics-check <case|case.m|case-dir> [--tol MVA]

Audit one solved state against the physical laws (energy balance, Ohm, Joule, KCL, complex power, and the rest of the registry) and print one row per law. The gate is the hard laws (1, 2, 3, 6, 8 in PhysicsCheckRegistry.HardGateLaws) AND a converged solve: GATE: PASS means the power flow converged and the state is physically admissible. The header prints converged=<true|false> and the tolerance. A solve that did not converge prints its laws for diagnosis, then GATE: FAIL - the power flow did not converge (status ..., max mismatch ... pu after N iterations) and exits 3. A converged state that fails the gate prints GATE: FAIL - physically-impossible state. Worst: law N <name>: residual R <unit> above the tolerance T <unit> (<detail>) and exits 1. Exit 1 also on a load error, 2 without a case or for a bad --tol.

The reactive balance (law 8) is checked at every bus the solve ended as PQ, including a PV bus pinned at a reactive limit (checked against that limit) and a PV bus with no generator. Law 9 (synchronism) reads NotApplicable with NOT SCORED in its detail: a power flow has no trajectory.

Flag Default Meaning
--tol BaseMva x 1e-8 Residual tolerance (MVA), one absolute line for every law. The default is the power-flow convergence tolerance (1e-8 pu) on the case's own base: 1e-6 MVA on a 100 MVA case, 1e-4 MVA on the 10,000 MVA uk. A negative value exits 2.

Result files: --json <file.json>, --csv <file.csv> or --out <file.json|file.csv> write the result to a file (Result files).

conformance

gridsim conformance [--tol MVA] [--out <dir>] [--no-allowances]

Run the physics-law audit over the whole case registry (embedded classics plus every .m under data/matpower/) and write conformance.md, conformance.csv and run-metadata.json. A case that did not converge is listed as such and not counted in the pass total; a case that fails to load is skipped with a stderr line.

Known failures. Three shipped PGLib optimisation cases never converge as power flows (pglib_opf_case3_lmbd, pglib_opf_case162_ieee_dtc, pglib_opf_case240_pserc, status MaxIterations: each stores an optimisation operating point, not a power-flow start). They are on an explicit allowance list (src/GridSim.Cli/ConformanceAllowances.cs), each with its reason: such a case shows allowed in the gate column and is listed with its reason under the table, and does not fail the run. An allowance covers only that case ending with that status; the same case ending NonFinite, any other unconverged case, and any case that cannot be loaded or run still fail. An allowed case that converges is audited like any other and a stderr note says the allowance was not needed. --no-allowances switches the list off.

Exit 0 when every converged case passes and every unconverged case is allowed (the shipped corpus); 1 if any converged case fails the hard-law gate; 3 if any case did not converge without an allowance or could not be run (when both happen the exit is 3); 2 for a bad --tol.

Flag Default Meaning
--tol BaseMva x 1e-8 per case Residual tolerance (MVA). The default is each case's power-flow convergence tolerance (1e-8 pu) on its own base; a value sets one absolute line for every case. A negative value exits 2.
--out results/conformance Output directory.
--no-allowances off Fail the run on every unconverged case, the known PGLib ones included.

protection-check

gridsim protection-check <case|case.m|case-dir> [--uv pu] [--ov pu] [--uf Hz] [--of Hz] [--oc xIn] [--thermal frac] [--rocof Hz/s] [--cascade [--alarms <soe.csv>] | --fault-bus ID [--zf pu] [--fault-type 3ph|slg|ll|dlg]]

Passive protection assessment of the solved state with generic relay settings: which elements would operate, with pickup, time and basis. The solve itself is unchanged. Elements that need a trajectory (frequency derivatives) are listed as not evaluated on a steady snapshot. The assessment requires a converged solve: a non-converged state never gets a verdict. The verb refuses it with protection-check: the power flow did not converge (...) and exit 3. Exit 2 without a case; exit 1 on a load error.

With --fault-bus ID the same settings are assessed on a balanced three-phase fault at that bus (ProtectionAssessment.AssessThreePhaseFault: the fault superposed on the converged prefault state, as the fault verb does), so the current, voltage, distance and busbar-differential elements see a real fault; the fault current and Thevenin impedance are printed first. Exit 0 with the verdict list; 2 for an unknown fault bus, a non-integer --fault-bus, --zf without --fault-bus, a negative or non-finite --zf, or --fault-bus with --cascade; 1 when the fault study itself fails; 3 when the prefault power flow does not converge, or when the converter current iteration of the fault study does not converge (the study is printed, the relays are reported not assessed: no verdict is computed from a state that did not converge).

The operating elements are listed fastest first (D-DOC-158): those with an operating time in ascending time (instantaneous first, the busbar differential 87 among them; equal times in row order, that is the relay registry order and then the bus / branch order of the case: N270, it used to be the margin, whose last bit decided between distance zones that have the same margin in exact arithmetic), then the rest (voltage, frequency, reverse power, undercurrent) by their margin relative to their own pickup. They used to be sorted by the raw margin, whose unit differs per element, so a reverse-power margin in MW headed a fault report; the e.g. line of the verdict names the first row. The undercurrent element 37 watches in-service branches only (D-DOC-091: it used to operate on every out-of-service branch, whose flow entry is zero). The earth-fault distance element 21N measures a branch end's earth loops only when the residual current there exceeds 10 % of the largest phase current (ProtectionSettings.EarthDistanceResidualReleaseFraction, generic; the 0.10 is the preset that the Siemens 7SA522 V4.3 manual recommends, address 1207A "3I0>/ Iphmax"; D-DOC-088: it used to operate on a line-to-line fault, which has no residual current).

Flag Default Meaning
--uv / --ov 0.80 / 1.10 Under- and over-voltage pickup (pu). The defaults are the G99 Issue 2 Table 10.1 HV settings (ProtectionSettings.UnderVoltagePu, OverVoltagePu).
--uf / --of 47.5 / 52.0 Under- and over-frequency pickup (Hz). The defaults are G99 settings for a 50 Hz system: on a case at another nominal frequency (case9, 60 Hz; a .m file declared with --frequency-hz) 81U and 81O are reported not checkable, naming both frequencies, instead of operating on the healthy steady state. Giving both --uf and --of supplies settings for the case, taken as written for its own nominal frequency (D2, October 2026).
--oc 2.50 Instantaneous overcurrent pickup (multiple of rating).
--thermal 1.00 Thermal pickup (fraction of rating).
--rocof 1.0 RoCoF trip setting (Hz/s).
--cascade off Follow the propagation: trip the first branch element, re-solve, repeat, and print each step and the stop reason.
--fault-bus ID - Assess the protection on a balanced three-phase fault at bus ID instead of the steady state. Not with --cascade.
--zf pu 0 With --fault-bus: the fault reactance (pu, Zf = j--zf, 0 is bolted; printed Zf=j...); a negative or non-finite value exits 2. dist3ph fault --zf is a resistance instead (D-DOC-166).
--fault-type 3ph With --fault-bus: slg, ll or dlg assess an unbalanced fault from the fault verb's sequence-network study: the earth-fault (50N, 51N, 21N) and negative-sequence (46) elements are evaluated on the sequence currents, the phase elements on the phase currents and voltages built from them. 3ph is the balanced study. Exit 2 without --fault-bus or for another value. On a model with no transformer winding connection anywhere (every MATPOWER and JSON v1 case) slg and dlg print the verdicts, then say on stderr that the earth-fault verdicts reflect missing data and exit 3.
--alarms <soe.csv> - With --cascade: cross-reference the predicted cascade against a real sequence-of-events log (SequenceOfEvents.CrossReference; matched by branch and order, not exact time). Prints agreements, predicted-not-observed, observed-not-predicted and out-of-order trips, divergences first. Exit 3 when the prediction does not reproduce the log; exit 2 without --cascade; exit 1 when the file is missing or malformed (named line).

The alarm log is CSV with the header at_s,device,from,to,description: seconds from the event start (finite), the ANSI device id as logged (non-empty), the branch's two end-bus ids (both 0 for a non-branch alarm such as a bus voltage or frequency alarm, which is listed but not matched), and free text (everything after the fourth comma). Blank lines and lines starting with # are skipped; any other malformed line is refused, never dropped.

Result files: --json <file.json>, --csv <file.csv> or --out <file.json|file.csv> write the result to a file (Result files).

grade

gridsim grade --chain CURVE:PICKUP:TD,... --current I[,I...] [--cti 0.4]

Inverse-time overcurrent grading (OvercurrentCoordination.GradeChain): a radial chain of relays, listed downstream first, graded pair by pair (primary then its backup) at each fault current. Each relay is CURVE:PICKUP:TIMEDIAL with CURVE one of iec-si, iec-vi, iec-ei, iec-lti (IEC 60255-151, TMS) or ieee-mi, ieee-vi, ieee-ei (IEEE C37.112, TD), or dt:PICKUP:DELAY_S for definite time. Pickup and current share one unit (amps or per unit); network fault currents per branch come from iec60909 (the current is an input here, which keeps the curves exact). A pair is coordinated when the primary operates, the backup operates too, and the backup lags the primary by at least the CTI (D-DOC-092: a backup that never operates at the current, below its pickup, reads an infinite margin and NOT COORDINATED (backup does not operate)). Prints each pair's times, margin and verdict (a time that never comes is never; an infinite margin prints inf or -inf with its sign, D-DOC-169), then the binding (smallest) margin. Exit 0 when every pair is coordinated at every current, 3 when any is not, 2 on a usage error (an unknown curve, a non-positive pickup or time dial, a negative delay, current or CTI, fewer than two relays, or a --current list that is not strictly ascending). See technical ch. 26.

Flag Default Meaning
--chain required The relays, comma-separated, downstream first.
--current required One or more fault currents, comma-separated, finite and at least 0, in strictly ascending order (D-DOC-174). The comma separates currents, so a decimal comma such as 2000,5 used to be graded as the two currents 2000 and 5; out of order or repeated it now exits 2 asking for a decimal point (2000.5). Each current is printed as its own fault current section, so what was graded is always visible.
--cti 0.40 Required coordination time interval (s), finite and at least 0 (OvercurrentCoordination.DefaultCoordinationTimeIntervalS).

Result files: --json <file.json>, --csv <file.csv> or --out <file.json|file.csv> write the result to a file (Result files).

fault

gridsim fault <case|case.m|case-dir> --bus <id> [--zf 0.0] [--type 3ph|slg|ll|dlg]

Balanced three-phase fault at --bus through fault reactance --zf (pu, Zf = j--zf, printed Zf=j...; D-DOC-166: dist3ph fault --zf is a resistance instead): fault current (pu, and kA when the bus has a base kV), Thevenin impedance, faulted-bus voltage, the converter-interfaced units' current-limited infeed, and the relays that operate on the faulted state. Generator subtransient reactance is synthesised at 0.20 pu where a unit carries none. The prefault solve must converge: a non-converged prefault state is refused with fault: the pre-fault power flow did not converge (...) and exit 3. Exit 2 without a case or --bus, for an unknown --type, or for a --bus that is not in the case (error: fault: fault bus <id> is not in case '<name>'., checked before any solve, the same rule as protection-check --fault-bus and iec60909 --bus); exit 1 on a load error or a fault-analysis error. When the converter current iteration of the three-phase study does not converge, the study is printed for diagnosis, the relays are not assessed (relays: not assessed (the faulted state did not converge, ...): a non-converged state is not a network state), stderr says the faulted state is not reliable, and the run exits 3. A negative or non-finite --zf exits 2 (error: --zf expected a finite fault reactance of 0 pu or more (Zf = j zf) ...), as protection-check --zf does (D-DOC-089: it used to be accepted with exit 0, fault case9 --bus 5 --zf -0.1 printing a faulted-bus voltage of 2.776 pu). The relays are listed fastest first (see protection-check), and the closing line names the primary clearance (ProtectionReport.PrimaryClearance), with its time: the faulted busbar's differential 87 when it operates (instantaneous unit protection; its time now prints inst), otherwise the fastest operating branch element with an operating time, or it says that no such element picks up (D-DOC-158: it used to name the first row of a list sorted by raw margin, which on fault uk --bus 1 was the Moyle reverse-power element). The faulted state's line loadings (LineFlow.LoadingPercent, read by the result's callers, not by the relays) are taken on the heavier end, as every power-flow engine takes them (D-DOC-090: they used the from end only).

--type slg|ll|dlg solves an unbalanced fault instead: single line (phase a) to ground, line to line (phases b-c), or double line (b-c) to ground, on the three sequence networks superposed on the prefault state. The positive sequence is the balanced study's network; the negative sequence the same with each unit's X2 (default X''d) and every phase shift reversed; the zero sequence is built from the transformer winding connections and neutral reactances (the network iec60909 uses; line Z0 = 3 x Z1 where a line carries no R0 / X0), with loads neglected and no line charging. With Zf = j--zf: SLG I1 = I2 = I0 = V/(Z1+Z2+Z0+3Zf); LL I1 = -I2 = V/(Z1+Z2+Zf); DLG I1 = V/(Z1 + Z2 (Z0+3Zf)/(Z2+Z0+3Zf)). It prints the phase currents (pu and kA), the earth current |3I0|, the sequence currents, the faulted bus's phase voltages and the driving-point Z1 / Z2 / Z0, then the relays that operate: the phase elements on the phase quantities built from the sequence study and the earth-fault and negative-sequence elements on the sequence currents (50N residual instantaneous at 1.0 x rated, 51N residual IEC standard inverse at 0.2 x rated and TMS 0.1, 46 negative sequence at 0.2 x rated with 1.0 s, 21N residual-compensated earth-loop distance on lines with the 21 zones; generic values, [VERIFY] against a cited setting policy). A fault bus with no earth path in the zero sequence carries no earth current: an SLG fault then gives zero current and a DLG fault is solved as LL (both said). A model with no transformer winding connection anywhere (every MATPOWER and JSON v1 case, so no bundled MATPOWER case) has no earthed neutral at all: --type slg and --type dlg print the study, then stderr says the result reflects missing data and the run exits 3. --type ll does not use the zero sequence and exits 0. A JSON v2 case can carry the data (N234, October 2026: phase P5 opened for fault sequence data): a transformer's windings, r0Pu / x0Pu and neutralXPu, and a generator's subtransientXdPu / negativeSeqXPu; a v2 case that gives windings runs slg and dlg with its own earth paths and exits 0 (see technical ch. 28).

Phase elements: 50 / 51 / 37 read the largest of each branch end's three phase currents, 49 that current over the rated current, 27 / 59 each bus's lowest / highest phase-voltage magnitude, and 21 each end's three phase-to-phase loops, Z = (Vx - Vy) / (Ix - Iy), with the loop in the fastest zone deciding (named in the verdict, for example [b-c loop]). A balanced fault and a power flow are assessed on the positive sequence alone. Converter- interfaced units add no fault current in the unbalanced study: the model defines no negative- or zero-sequence fault behaviour for them, so they stay at their prefault current in all three sequence networks. A note: line says how many and their rated MVA whenever the case has any, and the result file adds converters_without_fault_infeed and converters_without_fault_infeed_mva; the 3ph study models their positive-sequence fast fault current. The result file adds the phase, earth and sequence currents and a branches table (index,name,from,to,max_phase_from_pu, max_phase_to_pu,residual_from_pu,residual_to_pu,negative_sequence_from_pu,negative_sequence_to_pu).

Result files: --json <file.json>, --csv <file.csv> or --out <file.json|file.csv> write the result to a file (Result files).

iec60909

gridsim iec60909 <case|case.m|case-dir> (--bus <id> | --all-buses) [--type 3ph|ll|slg|dlg] [--objective max|min] [--tb 0.10] [--tk 1.0] [--breaker kV,making,breaking,withstand[,s[,asym]]] [--branches [--top N]] [--corrections --rated-pf <cos phi> [--no-unit-oltc]] [--peak-method b|c]

IEC 60909 short-circuit duty at --bus (Iec60909): initial symmetrical current Ik'', peak ip with its factor kappa and the fault-loop R/X, breaking Ib, steady Ik, thermal-equivalent Ith over --tk with its factor m, the DC component at --tb, the Thevenin impedance, and the converter share of Ik''. Values print at round-trip precision. Line charging and bus shunts are excluded from the positive and negative networks, as the standard directs. For 3ph, Ib carries each machine's near-to-generator factor mu at --tb through the IEC 60909-0:2016 multiple-fed formula, so it is below Ik'' whenever a machine feeds more than twice its rated current; ll and slg report Ib = Ik'' (no decay for unbalanced faults). Exit 2 without --bus (or --all-buses) or for an unknown bus; exit 1 on a load or study error. An earth fault (slg, dlg) on a model that carries no transformer winding connection anywhere (no MATPOWER or JSON v1 case can hold them, so no bundled MATPOWER case does) has no earthed neutral: the duty is printed, then stderr says it reflects missing data and the run exits 3. The --all-buses sweep, fault and protection-check with an earth-fault type refuse the same way. A JSON v2 case can hold winding connections (N234, October 2026), and one that does is not refused: its earth faults use its own earth paths and exit 0. See technical ch. 25.

--peak-method b|c (N134): how the three-phase peak factor kappa is found. b, the default, is IEC 60909-0 Method B (below; every result without the flag is unchanged). c is Method C, the equivalent frequency method that NESO uses for peak-make (ETYS Appendix D, docs/reference S242 p.4): the fault network's driving-point impedance is recomputed with every reactance at fc = 0.4 f (20 Hz on a 50 Hz system, 24 Hz on 60 Hz), R/X = (Rc / Xc) x 0.4, and kappa = 1.02 + 0.98 e^(-3 R/X) with no 1.15 safety factor and no cap. Method C also gives the DC component idc(tb): its R/X comes from the fault network at a second equivalent frequency set by f x tb (fc / f = 0.27 below 1 cycle, 0.15 below 2.5, 0.092 below 5, 0.055 below 10; Iec60909.MethodCDcFrequencyRatio, [VERIFY] the ratios), and a duty with f x tb at 10 cycles or more (for example --tb 0.2 at 50 Hz) is refused with exit 1, because the method gives no ratio there. Ik'', Ib, Ith, m and the printed R/X are the same as with b. The ip line then ends Method C: kappa(R/X_C), R/X_C <value> at fc = 0.4 f) and the result file adds peak_method and r_over_x_c. Every --type takes it (N353: ll, slg and dlg apply Method C on the fault's own sequence loop, Z1 + Z2, Z1 + Z2 + Z0 or Z1 + Z2 || Z0, with every reactance at fc; with --bus or --all-buses); any other value exits 2. Method C and fc / f = 0.4 are in IEC 60909-0:2016 subclause 8.1.2 (2001: 4.3.1.2 c)), read from the 2016 contents list; [VERIFY] the clause text, and the numbering of the new 2026 Edition 3.0.

October 2026 (D-DOC-096 / 097 / 098):

  • Only the fault bus's island is studied: the buses connected to it through in-service branches. A separate island with no generator has no earth path in the IEC 60909 networks (no loads, charging or shunts), which made the whole matrix singular on the sparse path (above 1,500 buses): iec60909 gb-full --bus 35 exited 1 at every bus while the dense path tolerated it. Every value of a connected case is unchanged; a fault bus whose own island has no source is refused by name (... the island of fault bus N (k bus(es) ...) has none., exit 1, or listed in the sweep).
  • In a MESHED fault network (a ring, a parallel circuit, or more than one source; one source on a radial network is not meshed) kappa is IEC 60909-0 Method B's 1.15 x kappa(R/X), capped at 2.0 (1.8 at 1 kV and below) but never below kappa(R/X), and the ip line says meshed network: 1.15 x kappa(R/X), Method B. It feeds ip only: the thermal factor m (and so Ith), idc and R/X keep the network's own R/X (with the cap binding, m would jump to its non-decaying limit of 2). The result file adds kappa_meshed. The clause is IEC 60909-0:2016 subclause 8.1.2 (2001: 4.3.1.2 b)), read from the 2016 contents list; [VERIFY] its text.
  • The Ik line says which rule the steady-state current follows (result file ik_basis): far from every generator nothing is added (Ik = Ik'' exactly); near a generator fed from several sources it is the standard's Ik = Ik''M (the initial current without motors; GridSim models none); near a generator that is the fault's only synchronous source it says UPPER BOUND, because the standard's Ik = lambda x IrG needs the machine's saturated reactance x_dsat, which no case carries (Ith with n = 1 is then an upper bound too); an unbalanced fault takes no decay (Ik = Ib = Ik'').
Flag Default Meaning
--bus required (or --all-buses) Fault bus id.
--type 3ph 3ph (three-phase), ll (line-to-line), slg (single-line-to-earth, on the zero-sequence network) or dlg (double-line-to-earth, the earth current |3 I0|).
--objective max max (voltage factor c = 1.10 HV / 1.05 LV, equipment rating) or min (c = 1.00 / 0.95, protection sensitivity).
--tb 0.10 Breaker minimum time delay (s) for Ib and the DC component; above 0.
--tk 1.0 Fault duration (s) for Ith; above 0.
--breaker - Check a switchgear rating against the duty (Iec60909.CheckBreaker): rated voltage kV, peak making kA, symmetrical breaking kA, short-time withstand kA, optionally its duration in s (default 1) and optionally the rated asymmetrical breaking kA (which adds the DC breaking check against sqrt(Ib^2 + idc^2)), comma-separated, every value above 0. The rated voltage must cover the highest system voltage Um of the bus (IEC 60038: 145 kV for 132 kV, 420 kV for 400 kV), not its nominal voltage; a double-line-to-earth duty is checked at its largest line-conductor current. Prints each check with its signed margin (rating minus demand; the withstand is referred to --tk on an equal-energy basis). An inadequate breaker exits 3.
--branches off List every in-service branch's from- and to-end current for the three-phase fault (Iec60909.BranchFaultCurrents, the current a relay on the branch sees; c_max source), every branch of the fault bus's island, largest first. Three-phase at one --bus only (else exit 2). The result file gets a branch_currents table. (D-DOC-168: the console list used to stop at 12 rows while its header counted every branch.)
--top N all With --branches: print only the N largest rows, and a closing line saying how many were left out (the result file still holds every branch). N at least 1; exit 2 without --branches.
--all-buses off The duty at every bus with a base kV instead of one --bus (not both, else exit 2). Prints one row per bus and the largest Ik''; the result file gets a buses table. A bus that cannot be studied (no base kV, no source) is listed with the reason and the run exits 1 after the table; with --breaker, an inadequate breaker at any bus (checked at the bus's own voltage) exits 3.
--corrections off Apply the IEC 60909-0 impedance-correction factors before the study (maximum objective only, else exit 2): K_G to a directly connected generator's X''d and X2, K_S (or K_SO with --no-unit-oltc) to a power-station unit (a unit with a unit transformer reactance) as a whole, K_T to each network transformer's impedance with x_T taken on its own rating from RateA (a transformer with no RateA, and any element on a bus with no base kV, is listed as not corrected). The model is per unit on nominal voltages, so the voltage ratios in the formulas are taken as 1. Needs --rated-pf. The factors applied are printed (range per factor) and written to a corrections table. [VERIFY]: the K_S / K_SO forms and the zero-sequence correction against the standard's text (IEC 60909-0 is not in docs/reference).
--rated-pf - With --corrections (required): the generators' rated power factor cos(phi_rG), in (0, 1]; GridSim carries none, so it is never assumed.
--no-unit-oltc off With --corrections: unit transformers without an on-load tap changer (K_SO at the main tap, p_G = 0, instead of K_S).

Result files: --json <file.json>, --csv <file.csv> or --out <file.json|file.csv> write the result to a file (Result files).

experimental

gridsim experimental [<subcommand> <case> [flags]]

Opt-in experimental models, tagged unvalidated-at-scale and kept off the validated solve and estimate paths. With no subcommand it lists them. <case> must come straight after the subcommand and accepts <case|case.m|case-dir>.

Subcommand Does
reciprocity <case> Physical-consistency law Y = Y^T (law 11).
wave <case> Continuum electromechanical-wave model: inter-area normal modes, dominant mode and its shape. Needs per-machine inertia: a case with no generators or a generator with no inertia constant (H not above 0, as MATPOWER data loads) is refused with exit 1 right after the power flow and before the classical reduction builds its network matrices (about 1.46 GB on gb-full). The dominant mode is the first mode after the rigid-body (zero) modes, one per island of machines (N282, October 2026; it was the first mode above 1e-6 Hz, which could pick the centre-of-inertia mode or an island's); an islanded case prints a rigid-body (island) modes line and its inter-area list starts after them. The modes are those of the symmetric part of the synchronising coupling (R035, October 2026: the transfer conductances make the coupling asymmetric, and the symmetric eigen-solver used to be handed the asymmetric matrix, which lifted the centre-of-inertia mode off zero); a coupling asymmetry set aside line gives the largest |k_ij - k_ji| in MW/rad, and the mean stiffness is now in MW/rad (it was the per-unit figure).
modal-consistency <case> Small-signal structural residuals (COI null mode, law 16, and the K_ext row sum).
harmonic-kcl <case> Harmonic KCL, Y(h) V(h) = I(h), on the study-model penetration with a synthetic six-pulse source at the largest-demand bus (law 12): the G5 Issue 5 Table B.3 six-pulse profile 6-pulse-g5, named in the header line. Exit 1 on a violation or a singular network.
passivity <case> [--bus ID] The grid driving-point impedance is positive-real over 5-2500 Hz in 5 Hz steps (law 14). --bus defaults to the largest generator's bus; exit 2 if there is no generator and no --bus, or the bus is not in the model; exit 1 on a violation.
trace <case> [--losses] [--top 5] Bialek proportional-sharing trace: where each generator's power went, or with --losses which generators cause the network losses.
carbon <case> [--top 8] Carbon tracing: the gCO2/kWh each load consumes, from traced generation.
boundaries <case> [--top 6] Which generators supply each ETYS boundary's transfer.

Exit 2 on a missing case or an unknown subcommand; exit 1 on a load error or a flow graph with a loop (trace, carbon); exit 3 on a non-converged solve.

Result files: --json <file.json>, --csv <file.csv> or --out <file.json|file.csv> write the result to a file (Result files).

Frequency and dynamics verbs

These verbs are used in ch. 14, Frequency studies (freq, replay, transient, domains) and ch. 15 (stability, modal).

freq

gridsim freq [csv]

NESO 1-second frequency statistics plus a GB limit-breach scan (RoCoF 0.125 Hz/s, operational 49.8 Hz, statutory 49.5 Hz, LFDD 48.8 Hz) and a 20 ms upsample demo. Default input: data/neso/frequency-sample.csv beside the executable. Exit 1 if the file is missing. A row newer than the 169 h forward-inference horizon is refused: REJECTED (forward inference): ... and exit 2. The first non-blank line may be a column header (dtm,f) and blank lines are skipped; any other line that is not timestamp,Hz with a finite frequency above 0 exits 1 naming the line number and the line, and a file with no data rows at all exits 1 (it used to print zero statistics and exit 0). A breach is reported, not an error: the exit is 0. The file may sit anywhere on the line, before or after the flags; a second file argument exits 2.

The high side of the same bands is scanned too (R081, October 2026): when any sample is above 50.2 Hz an over-frequency: line follows the limits line with the seconds above the operational 50.2 Hz and the statutory 50.5 Hz edges. A trace that stays at or below 50.2 Hz prints no such line (the output is as before). The result file carries seconds_above_operational and seconds_above_statutory beside the seconds_below_... keys.

Result files: --json <file.json>, --csv <file.csv> or --out <file.json|file.csv> write the result to a file (Result files).

replay

gridsim replay [csv] [--sps F] [--seconds N] [--frames N]

Play a recorded frequency trace in the terminal (gauge and RoCoF), upsampled to 20 ms. Keys: space play/pause, up/down speed, left/right step, Home restart, Q quit. Exit 1 if the file is missing or empty, or if a line in the loaded window is not a valid timestamp,Hz row (named in the message, as for freq); exit 2 with REJECTED (forward inference): ... for a row newer than the 169 h horizon. The file may sit anywhere on the line (replay --sps 100 run.csv plays run.csv); a second file argument exits 2.

Flag Default Meaning
[csv] data/neso/frequency-sample.csv Source trace.
--sps 50 Slices per second (50 is real time), 0.25 to 2000; outside that range exit 2.
--seconds 600 Seconds of source to load; at least 1.
--frames 0 Above 0 runs headless for N slices then exits.

transient

gridsim transient <case|--cases a,b,c|--cases suite> [flags]

Headless demanding time-domain run: a simulated duration at a fine slice, integrating swing-equation frequency each slice. Writes timeseries.csv, sampled solve-math exports (exports/slice-*.json), summary.md and run-metadata.json. --cases suite (or all) runs case9, case14, case30, case57, case118, case300 and pegase/case1354pegase.m. The global --forming (with --forming-inertia and --forming-damping) and --asset-dynamics switches are honoured: they reach the live frequency integrator, and the run metadata names them. --asset-dynamics on a case with no asset bundle exits 1 for that case. The frequency is integrated at the case's own nominal frequency (case9 and the two-area case at 60 Hz, every GB and MATPOWER-file case at 50 Hz unless --frequency-hz says otherwise), so a 60 Hz run's freq_hz column and nadir sit about 60 Hz. With --asset-dynamics, inverter Loss-of-Mains trips book the dispatch actually running, and both those trips and the protection devices' demand sheds are restored by secondary redispatch over about 5 minutes, as a --trip loss is.

Flag Default Meaning
<case> case9 Case name, or a .m file under data/matpower/.
--cases - Comma list, or suite / all.
--minutes (alias --duration) 60 Simulated duration in minutes; above 0.
--dt-ms 1.0 Slice length, milliseconds; above 0.
--log-every 1 Write every N-th slice to the CSV; at least 1.
--export-every 0 (off) Full solve-math export every N-th slice (slice 1 and the trip window always export).
--export-jac off Include the Jacobian in exports.
--trip 0 (none) Infeed MW to trip mid-run.
--trip-at 0 Trip time (seconds). Exit 2 if past the run end: the contingency would never fire, or without a --trip above 0 (nothing to time).
--trip-window 2.0 Seconds each side of the trip always logged and exported. Exit 2 without a --trip above 0.
--solver auto dense, sparse, bfs / sweep or auto (any other value exits 2). auto sends a radial network to the sweep, uses sparse above 1,500 buses (the LiveSim per-tick threshold) and dense otherwise.
--dyn-data - A machine dynamic data file (gridsim-dynamics/2, as for trip): each generator it binds takes the file's inertia H for the live swing (the only per-machine number it integrates); a stderr line says so, and the run metadata and summary header add dyn-data=<file> (inertia H only). One case only: with --cases it exits 2. A missing or invalid file exits 1, before the run.
--out results/transient-<case>-<stamp> Output directory (batch runs use results/transient-<stamp>/<case>).

Exit 1 if no case loaded at all, if some cases of a batch failed to load, for --asset-dynamics on a case with no asset bundle, or for a --dyn-data file that is missing or invalid; exit 2 for a bad --dt-ms, --minutes or --solver, a --trip-at past the run end, --trip-at or --trip-window without a --trip above 0, or --dyn-data with --cases; exit 3 if any slice failed to converge (frequency and RoCoF from unconverged states are not trusted).

domains

gridsim domains [<case>] [--dir <path>]

Report the speed domains of the distributed-inertia model: per-domain machine count, GVA.s and GVAd stiffness, and whether a dominant domain exists (deltaGVA at least 10 %). Default model data/uk; a positional case or --dir selects another (Case arguments). It is the diagnostic companion to --inertia-model distributed.

Result files: --json <file.json>, --csv <file.csv> or --out <file.json|file.csv> write the result to a file (Result files).

stability

gridsim stability [<case>] [--dir <path>] [--rms] [--avr none|sexs|ieeet1] [--pss] [--dyn-data <file>] [--screen] [--fault-bus N] [--clear ms] [--clear-by-trip K[,K...]] [--events <list> [--events-out <dir> [--events-every N]]] [--export <json>]

Classical multi-machine transient stability (constant E' behind X'd, Kron-reduced network, RK4 swing). Default case case9 (Anderson-Fouad X'd; any other case uses a synthetic 0.30 pu default and is flagged INDICATIVE). <case> is a case argument; --dir loads a JSON case directory instead. A positional case and --dir together exit 2 unless they name the same folder, and a second positional case exits 2.

Flag Default Meaning
--rms off Use the salient/subtransient RMS engine (six-state GENROU machines) instead of the classical swing. GENROU parameters are synthesised from X'd, so the result is INDICATIVE; the engine itself is validated (it reduces to the classical CCT). Works with --screen, --fault-bus and --clear; with --clear it also reports the converter fleet's fault ride-through.
--avr none With --rms: none (field held), sexs or ieeet1 exciters on every synchronous machine (typical, indicative settings); any other value exits 2.
--pss off With --rms and an AVR: add a PSS1A stabiliser to each exciter. Without an AVR it exits 2.
--dyn-data - A machine dynamic data file (gridsim-dynamics/2, see schemas/schemaNotes.md), or a PSS/E .dyr file when the case is a PSS/E .raw file (its records are mapped onto the case's machines, then checked and bound the same way; ch. 2; --allow-unmodelled leaves out what GridSim cannot represent; every --dyn-data verb takes a .dyr file this way). Classical engine (no --rms, single bus and --screen; N314, October 2026, it used to exit 2 there): the classical swing is built from X'd, H and the damping D, and each machine the file binds takes all three from it, exactly as modal does (X'd on the machine base; D per unit on the system base, the same quantity as the RMS study's; H the case's own where the template gives none); the other machines keep the X'd map (Anderson-Fouad on case9, else the synthetic 0.30 pu) and D = 0. The header says how many X'd values came from the file and adds a machine data: line with the loader's notes; the result stays INDICATIVE unless no X'd is synthetic and every value is tagged Recorded or DerivedFromRecorded. A file whose values equal the built-in ones gives the same clearing times. --export stays the undamped kernel check (the export records the file's H and X'd). With --rms (F23): Each machine it binds takes the file's GENROU reactances and time constants, inertia (the case's own H when the template gives none, said in a note: line), damping, saturation and leakage, and the exciter (SEXS, IEEET1, EXAC1, ESAC1A or ESST4B, with a PSS1A), and governor (TGOV1, IEEEG1, HYGOV or GAST) its template names; the other machines keep the synthesised data. A file exciter replaces --avr on its machine; --avr and --pss fill the rest. (modal, trip and transient take the same file for the part of it their models use.) The header says how many machines the file covers, which governors it brought and the provenance tags of its values. The INDICATIVE footer goes only when the file covers every machine and every value is tagged Recorded or DerivedFromRecorded. On either engine a missing file or one that fails the v2 schema, kind-spec or binding checks exits 1 with every problem listed.
--screen off Critical clearing time at every generator bus, worst first. It has no single fault bus and no fixed clearing time, so with --fault-bus or --clear it exits 2 before any work, naming the flag (N266, October 2026; both used to be accepted and silently ignored); with --export it exits 2. The header counts the integrated machines and the units held as constant injections (converter, power-flow-only and zero-inertia units), as the single-bus run does.
--fault-bus 7 (case9) / first non-generator bus Fault location.
--clear - Fixed clearing time in ms, giving a STABLE / UNSTABLE verdict; omit for the critical clearing time. Classical and --rms. Must be a finite number, 0 or more (0 is an instantaneous clear); a negative value, NaN or Infinity exits 2 (a negative value used to run a study with no fault in it and report STABLE). At most 1000 ms (N266, October 2026): above it exits 2. Why 1000 ms: the slowest clearance GB plant coordinates with is back-up protection within 800 ms in England and Wales (300 ms in Scotland), Grid Code CC.6.2.2.2.2; 1000 ms is the window both CCT searches use, so a fixed clearing time stays inside the range the CCT answers; and the RMS study runs a fixed 3 s, so a much later clear would end the run with the fault still on. Without the bound a large value also grew the run's time and memory without limit. Both engines (N246, October 2026; the --rms engine since CF2): under the verdict a law 9 (synchronism, scored from this run): HOLDS (or VIOLATED) line scores the physics law from the run's own rotor-angle trajectory with the out-of-step criterion of PSS/E and PowerFactory, any machine more than 180 degrees from the centre of inertia at any sample: largest rotor angle from the centre of inertia X deg (limit 180 deg, the out-of-step criterion); peak speed deviation Y Hz, reported, not scored (no frequency band in a fault study). The verdict itself is unchanged (the integrator's pole-slip test, 360 degrees from the centre of inertia); when a machine passes 180 but not 360 degrees a note: line says the two criteria differ. On --rms the centre of inertia and the maximum cover the machines the RMS verdict judges (island reference machines are left out of both, as the verdict leaves them out). The steady-state law 9 row of physics-check names this verb as the one that scores it.
--clear-by-trip - N351, --rms only: the fault at --fault-bus is cleared by also tripping these branches (comma list of 0-based indices into the case's branch list), as a line fault is cleared by its breakers. Without --clear it is the critical clearing time search with those trips at every trial's clearing instant (the same step grid, window and first-loss rule as below); with --clear a STABLE / UNSTABLE verdict for that clearing time. Not with --screen or --events (exit 2).
--events - N351, --rms only: one scheduled RMS event study. A comma list of kind:arguments@seconds items: fault:BUS@t (bolted fault), clear:BUS@t (its clearance), trip:K@t (branch K trips, 0-based), reclose:K@t (it closes again: auto-reclose), load:BUS:P:Q@t (a load step of P MW and Q Mvar, negative to shed) and gentrip:G@t (generator G trips, 0-based). For example --events "fault:7@0.1,clear:7@0.183,trip:5@0.183,reclose:5@0.683". Prints the events and a STABLE / UNSTABLE verdict over the connected machines. The run lasts 3 s, or 3 s past the last event. It owns the whole disturbance: with --screen, --fault-bus, --clear or --clear-by-trip it exits 2; a malformed list exits 2 naming the item; an event the study refuses (a bus not in the case, a reclose of a branch that is not tripped, a time after the end) exits 2 with the reason.
--events-out - N363, with --rms --events only (otherwise exit 2): writes the event study's export to the folder (created if missing): rms-events-machines.csv (every machine trace at every integration step: t_s,trace,bus,delta_rad,speed_pu,eqp_pu,edp_pu,eqpp_pu,eddp_pu, each number in its shortest round-trip form), rms-events-converters.csv when the fleet has converter plant (t_s,converter,name,bus,v_pu,p_pu,q_pu,ip_pu,iq_pu,in_dip_mode), rms-events.json (schema gridsim-rms-events-export/1: case, nominal frequency, step, duration, the events in time order, the verdict, converter-iteration failures, the machine list with island references marked, provenance Synthetic and whether the result is INDICATIVE) and run-metadata.json. Both CSVs start with the run header and a # provenance: line (Synthetic, a model trajectory, not a record; INDICATIVE when the GENROU data is synthesised). A file that cannot be written exits 1. The run and its verdict are unchanged.
--events-every 1 With --events-out only (otherwise exit 2): write every N-th integration step to the export CSVs (steps 0, N, 2N, ...; a whole number from 1 to 1000000, anything else exits 2). The default 1 writes every step, so an export without the flag is the full-resolution one. rms-events.json records everySteps and samplesWritten; the run itself is unchanged.
--export - Write a gridsim-classical-export/1 trajectory for the scipy cross-check (tools/crossval/crossval_classical.py). Classical single-bus run only: with --rms or --screen it exits 2 before any work (error: stability: --export writes the classical single-bus trajectory and is not available with --rms (no file would be written).); it used to be accepted with no file written. A missing folder is created (Output files).

With --rms the critical clearing time is step-quantised: the fault is switched only on whole 2 ms integration steps, so the reported CCT is the longest clearing time on that step grid that keeps synchronism, and clearing one step (2 ms) later loses it. The output says so, and a single-bus run prints the two ends of the bracket. Digits below the step carry no information and are not reported.

The classical critical clearing time (no --rms) is step-quantised in the same way: the longest clearing time on the 2 ms step grid that keeps synchronism, with one step (2 ms) more losing it. Both the single-bus run and --screen say so, and a single-bus run prints the bracket (for example "clearing at 550 ms holds synchronism, at 552 ms it is lost" for case9 bus 7). 0 ms means even an instantaneous clear loses synchronism; 1000 ms means nothing in the 1000 ms search window loses it.

Both CCTs (classical and --rms) are the first loss of synchronism from below. Stability is not always monotone in the clearing time: after the bisection, the 16 step counts (32 ms) below the reported CCT are checked to hold and as many above the first loss are probed. A later clearing time that holds again (a stable pocket) is flagged: --screen adds NON-MONOTONE: holds again at N ms to that bus's row, and a single-bus run prints a warning line. On case9 (classical) bus 2 reports 312 ms with a pocket at 320 ms, and bus 1 reports 498 ms with a pocket at 502 ms:

$ gridsim stability case9 --screen
GridSim  -  TRANSIENT STABILITY SCREEN (classical multi-machine)  *  WSCC-9
==================================================================
3 machines (0 converter / power-flow-only / zero-inertia units held)  *  3 generator-bus faults  *  X'd = Anderson-Fouad

 Rank  Fault bus   CCT (ms)
    1          3        302   <- most critical
    2          2        312   NON-MONOTONE: holds again at 320 ms
    3          1        498   NON-MONOTONE: holds again at 502 ms

Self-clearing 3-phase fault at each generator bus; lower critical clearing time = less margin.
CCT = longest clearing time on the 2 ms integration-step grid that keeps synchronism (clearing one step, 2 ms, later loses it); resolution 2 ms.
A CCT of 0 ms means even an instantaneous clear loses synchronism; 1000 ms means no clearing time in the 1000 ms search window loses it.
It is the first loss from below: the 16 steps (32 ms) below it are checked to hold and as many above it are probed; NON-MONOTONE marks a later clearing time that holds again (a stable pocket).
Each trial is judged over the 5 s after the fault clears (the documented default window: first-swing stability, the range in which the classical constant-E' model holds); an undamped system can lose synchronism on a later swing, so a longer window can give a shorter CCT.
[exit 0]

The checks cost up to 32 extra trial runs per bus (3.5 times the bisection alone on case9). With --rms the verb runs one search per bus as well; its stable end is the CCT and the same search gives the flag.

The criterion and the window (N341 / N343, October 2026). The CCT is the first loss: the largest clearing time below which every trial holds synchronism, which is what PSS/E and PowerFactory report; a stable pocket above it is printed as a note (NON-MONOTONE), never as the CCT. Each trial (classical and --rms) is judged over a fixed window after the fault clears, 5 s by default (ClassicalInit.CctPostClearWindowSeconds, RmsTransientStability.PostClearWindowSeconds): first-swing stability, the range in which the classical constant-E' model is valid. Every CCT explanation ends with a line saying so: Each trial is judged over the 5 s after the fault clears (the documented default window: first-swing stability, ...); an undamped system can lose synchronism on a later swing, so a longer window can give a shorter CCT. The undamped classical swing keeps every swing it starts, so the number depends on the window: WSCC-9 bus 7 at 60 Hz is 550 ms with the 5 s window and 436 ms with a 20 s window (the Core API takes the window as an optional argument; the CLI uses the default). The stable pockets case9 shows at 60 Hz (buses 1, 2, 5, 7 and 9) are the same multi-swing effect.

Exit 3 on a non-converged base solve; exit 2 on a zero-inertia case, an unknown case name, a --fault-bus that is not in the case (error: stability: fault bus <id> is not in case '<name>'., checked before any solve), a negative or non-finite --clear or one above 1000 ms, --export with --rms or --screen, --fault-bus or --clear with --screen, a positional case that disagrees with --dir, or an RMS study error (including a governor or exciter whose limits cannot hold the solved operating point); exit 1 for a case file or --dir folder that is missing or cannot be loaded, and for a --dyn-data file that is missing or invalid. A STABLE or UNSTABLE verdict does not change the exit code.

gridsim modal [<case>] [--dir <path>] [--damping D] [--enable-inverters] [--include-soc] [--json] [--export <json>] [--dyn-data <file>]

Small-signal (modal) stability of the linearised multi-machine swing: eigenvalues, frequency and damping ratio of every mode, the least-damped oscillatory mode, right-half-plane count, the dominant participating states per mode and an ASCII s-plane. Default case case9; the X'd map is the same as stability (Anderson-Fouad for case9, else a synthetic 0.30 pu, flagged INDICATIVE).

Flag Default Meaning
<case> / --dir case9 Case argument or JSON case directory; both together exit 2 unless they name the same folder.
--damping 0 (undamped) Machine damping D applied to every machine (MW per rad/s).
--enable-inverters off Add the inverter states of the case's bound converter classes (a documented archetype). A grid-following class's frequency estimator takes the class's pllBandwidthHz / pllDampingRatio when authored; otherwise its detection latency as a critically damped delay stand-in (every bundled class); otherwise the one PLL default, 20 Hz at 0.707 (R138, October 2026; it was 5 Hz, critically damped).
--include-soc - Not implemented: exits 2 (a state-of-charge integrator is a decoupled origin pole, left out of the stability matrix by design).
--json off Print the model and modes as JSON on the console instead of the tables. Takes no value: unlike the shared writer's --json <file.json> (Result files), it writes no file; --export <file.json> does. --json <name>.json exits 2 and points at --export.
--export - Write the small-signal model and modes to a JSON file (gridsim-smallsignal/1). The file also carries participationAvailable (false when the state matrix is defective: the participation rows are then all-zero placeholders, not participation), participationUnavailableReason (only when false) and exitCode (the exit code the run ends with: 1 for a right-half-plane eigenvalue, else 0). --json prints the same fields.
--dyn-data - A machine dynamic data file (gridsim-dynamics/2, the file stability --rms reads). The classical small-signal model is built from three numbers per machine, X'd, H and the damping D, and each machine the file binds takes all three from it (X'd on the machine base, as the built-in map; D per unit on the system base, the same quantity as the RMS study's; H the case's own where the template gives none); --damping and the X'd map fill the other machines. The header says how many X'd values came from the file and adds a machine data: line (the file's subtransient data, exciters and governors are not part of this model) with the loader's notes; the result stays INDICATIVE unless every machine is bound and every value is tagged Recorded or DerivedFromRecorded. A file can give a MATPOWER case the inertia it lacks. A missing or invalid file exits 1, before any solve.

Exit 1 if any eigenvalue lies in the right half-plane (small-signal unstable), for a case file or --dir folder that is missing or cannot be loaded, or for a --dyn-data file that is missing or invalid; exit 3 on a non-converged base solve; exit 2 on an unknown case name, a positional case that disagrees with --dir, or a model that cannot be assembled. An unstable result is still a complete analysis, so the export is written and says exitCode: 1. When the state matrix is defective (for example data/gb-synthetic --enable-inverters) the eigenvalues are reported but participation factors are undefined: stderr says why, the participation table prints unavailable, and the export says participationAvailable: false.

A MATPOWER case (the GB ones gb-reduced-29, gb-network-2224, pypsa-gb-reduced, and the IEEE cases other than case9 / ieee9) exits 2: a .m file carries no inertia data, so every unit loads with H = 0 and the swing model has no rotor. The parser's "nominal frequency not given ... assumed 50 Hz" note printed above it is a separate assumption (right for GB) and not the cause; the error message says so. Use a JSON case with inertiaH per machine (gb, gb-reduced, gb-synthetic, uk, gb-full). gb-full (952 machines, 1,902 reduced states) is far beyond the dense eigenvector path's size: participation needs one complex dense LU per eigenvalue (1,902 of them), so a participation run takes hours.

fit-frequency

gridsim fit-frequency <trace.csv> --inertia <GVA.s> --demand <MW> --loss <MW> [--loss-at <s>] [--fit damping,responsive,governor] [--max-iter N] [--nominal-hz <Hz>]

Fit the lumped swing model's nadir and recovery constants to one measured loss-of-infeed trace (R079, October 2026): load self-damping (DampingPctPerHz, % of demand per Hz), the responsive headroom fraction and the governor time constant, by least squares between the trace and the model's trajectory for the given loss, inertia and demand (FrequencyConstantsFitter, Nelder-Mead). The report shows each constant's seed (the shipped default), its result and whether it was fitted or held, then the RMS error over the samples, the nadir error (simulated minus measured) and the number of model evaluations. It is a calibration check: the shipped defaults are not changed, and adopting a fitted value is a separate, deliberate step. The initial RoCoF depends only on the inertia and the loss, so it carries no information about these constants; the nadir depth and the recovery shape do.

The trace is a CSV of two numeric columns, seconds,Hz: the time in seconds on the model's clock (0 s is the start of the window) and the measured frequency. The first non-blank line may be a header; blank lines are skipped. Every other line must have exactly two fields, a finite time of 0 s or more that increases on the row before, and a finite frequency less than 5 Hz from the trace's nominal frequency; at least 3 rows. A bad row exits 1 naming the line number and the line. The time is not a timestamp: give the loss instant on the same clock with --loss-at.

The nominal frequency (N314, October 2026): the swing model runs at the trace's own nominal. Without --nominal-hz the trace names it: its first sample must lie less than 5 Hz from 50 Hz or from 60 Hz (the two standard system frequencies, 10 Hz apart, so never both), and that nominal is used for every row; a first sample near neither exits 1 and asks for --nominal-hz. With --nominal-hz <Hz> (finite, above 5 Hz) that nominal is used instead, for a system on another frequency. The Event: line prints the nominal used. A 50 Hz trace is fitted exactly as before.

The model starts at the trace's pre-event frequency: the last sample before --loss-at, in equilibrium there (the replay's rule; services respond to the absolute frequency). A trace with no sample before the loss starts at the nominal. The Start: line says which.

Flag Default Meaning
<trace.csv> - The measured trace (required).
--inertia - System inertia at the event, GVA.s, above 0 (required).
--demand - System demand at the event, MW, above 0 (required).
--loss - Infeed lost, MW, above 0 (required).
--loss-at 1.0 The loss instant on the trace's clock, seconds, 0 or more, before the last sample.
--fit damping Which constants to fit: a comma list of damping, responsive, governor, each at most once. Damping alone is well identified from one trace; fitting all three from one trace is weakly identified (they trade off), and a Note: line says so.
--max-iter 2000 The optimiser's iteration cap, at least 1.
--nominal-hz from the trace (50 or 60) The trace's nominal frequency, Hz, finite and above 5 Hz. Every sample must lie less than 5 Hz from it.

Exit 0 for a converged fit; exit 1 for a trace file that is missing or invalid (including a first sample near neither 50 nor 60 Hz without --nominal-hz); exit 2 for a missing required flag, a value that is not a number above 0, a --nominal-hz that is not finite and above 5 Hz, a negative --loss-at or one at or after the last sample, an unknown or repeated --fit word, no trace argument or a second one, and the global --forming, --asset-dynamics and --inertia-model distributed switches (the fitter runs the plain lumped swing, so they would be ignored); exit 3 when the optimiser does not converge within --max-iter (the last point is printed for diagnosis, with a NOT CONVERGED line on stderr, and is not a fit).

inertia-placement

gridsim inertia-placement [<case>] [--placements fleet,demand,spine-t,south,optimised] [--budgets 120,180,240,360,480,700,900,1200] [--losses sizewell,hinkley,kent,scotland] [--residual 0.25] [--condenser-h 8] [--rocof-limits 0.125,0.25,0.5,1] [--post-event 6] [--avr none|sexs|ieeet1] [--optimise-budget 240] [--optimise-passes 1]

The inertia placement study: with a network's synchronous inertia in better places, can it run on less of it? Default case gb-full. Today's synchronous fleet keeps --residual of its inertia (each machine's H scaled; dispatch and locations unchanged); the rest of each budget is synchronous condensers of inertia constant --condenser-h, at no power and no reactive power at the solved state (so the power flow is the case's), placed by each placement:

  • fleet: where today's synchronous inertia is, in proportion to it;
  • demand: in proportion to demand, each bus's demand gathered to its nearest 275/400 kV bus;
  • spine-t: equal shares at eleven sites forming an inverted T / ladder (Inverness, the central belt, the Borders, the east and west England corridors, the Midlands, Cornwall, the South West, the Thames, Kent and East Anglia), each on its nearest 275/400 kV bus;
  • south: everything at the Thames site, a deliberately concentrated contrast;
  • optimised: the same sites with weights from a coordinate search at --optimise-budget (each pass tries each site's weight doubled and halved and keeps the change that lowers the worst bus RoCoF over every loss most; up to --optimise-passes passes, stopping early when a pass changes nothing). A local search, not a proven optimum.

Each loss is a 1.8 GW step (the SQSS infeed loss; constant admittance at the bus's solved voltage, the RMS engine's load step) at the 275/400 kV bus nearest Sizewell, Hinkley Point, Sellindge (the Kent interconnectors) or Torness (Scotland over B6), at t = 1 s, run on the RMS engine (stability --rms's synthetic GENROU machines with --avr exciters on every machine and condenser, mechanical power held: no frequency response) for --post-event seconds after it on a 5 ms step. Every bus at 132 kV and above is measured: its frequency from its voltage angle over one nominal cycle, its RoCoF over a 500 ms window (the GB loss-of-mains window) with the voltage angle jump at the loss taken out and reported on its own.

Prints, for each run, the centre-of-inertia RoCoF and the worst bus RoCoF of the RMS run and K, their ratio (the spatial penalty); the loss the machines felt (2 E RoCoF / f0: not exactly 1.8 GW, because the RMS loads are constant admittances and the converter plant holds its current, so both change their power as the voltage moves); the full-loss worst bus RoCoF (K times the swing-equation figure f0 x 1.8 GW / 2E); the worst angle jump; the north-south inter-area oscillation (damping ratio and frequency, fitted over every half-cycle of the difference of the north and south machines' mean speeds, smoothed over 0.4 s to average out local swings; NaN with fewer than four half-cycles); and the time the RMS run's centre-of-inertia frequency took to fall to 49.8 Hz. Then, per placement, the smallest scanned budget meeting criterion A (the full-loss worst bus RoCoF at or below each of --rocof-limits) and criterion B (at least 3 s and 5 s to 49.8 Hz for the full loss with no response, from the swing equation, so the same for every placement), with the linear estimate between the budget that fails and the one that passes; and the time to 49.8 Hz with the case's frequency response from the lumped model (the default GB response, which placement does not change). Each run is a full RMS run of the network (about 10 s each on gb-full), so the default study takes a long time; it prints one line per run as it goes.

The results of the study on gb-full, with its method, sensitivity runs and limits, are in docs/validation/studies/inertia-placement.md.

Flag Default Meaning
--placements all five A comma list of fleet, demand, spine-t, south, optimised, each at most once.
--budgets 120,180,240,360,480,700,900,1200 The total synchronous inertia budgets (GVA.s), ascending; each must exceed the residual.
--losses all four A comma list of sizewell, hinkley, kent, scotland, each at most once.
--residual 0.25 The share of today's fleet inertia kept on the fleet, above 0 and at most 1.
--condenser-h 8 The added condensers' inertia constant (s, on their own rating), above 0.
--rocof-limits 0.125,0.25,0.5,1 Criterion A's limits on the worst bus RoCoF (Hz/s), each above 0; one minimum per limit.
--post-event 6 Simulated seconds after the loss, 1 to 60.
--avr ieeet1 The exciter on every synchronous machine and condenser: ieeet1, sexs or none (field held); the typical, indicative settings of stability --rms --avr.
--optimise-budget 240 The budget (GVA.s) the optimised placement's weights are searched at.
--optimise-passes 1 Passes of the coordinate search, at least 1.

Exit 0 when the study ran; exit 1 for a case it cannot study (no 275/400 kV bus with a map position, a budget at or below the residual, a power flow that does not converge; the reason is printed); exit 2 for a malformed flag.

Result files: --json <file.json>, --csv <file.csv> or --out <file.json|file.csv> write the result to a file (Result files): the summary and the tables runs (one row per placement, budget and loss), minimums, lumped, sites and placements (every bus share).

Harmonics, impedance and EMT verbs

These verbs are used in ch. 17 (harmonics), ch. 15 (impedance-stability) and ch. 16 (emt).

harmonics

gridsim harmonics [<case>] [--dir <path>] [--spectra <file.json> | --synth-sources | --converter-sources rated|dispatched] [--synth-spectrum g5|ideal] [--afe-reactance <pu> [--afe-resistance <pu>]] [--bus <id>] [--enableExport[=path]]

Frequency-domain harmonic study on the study model (network, machine source impedance, loads as damping shunts): penetration (Y(h) V = I), the driving-point resonance scan, a fine frequency sweep for the true peak between integer orders, voltage-THD indices (relative to each bus's solved fundamental voltage, from the same solve as --once; the Web HARMONICS tab uses the same normalisation) and an IEEE-519 compliance verdict. A bus with no base kV is judged at the strictest tier, never certified compliant, and counted in a printed warning. See ch. 17, Harmonic studies.

Flag Default Meaning
<case> / --dir case9 Case argument or JSON case directory (-d is a short alias of --dir).
--spectra - A gridsim-harmonics/1 source set. A non-zero component at an order outside the analysed odd orders 3 to 49 is refused (exit 1, each named); a triplen source is refused (exit 1). A set holding any measured source (provenance Recorded or DerivedFromRecorded) must carry takenUtc; an undated one, or any set dated inside the 169 h horizon, is refused with REJECTED (forward inference): ... and exit 2. An all-assumed library set (equipment spectra) may be undated.
--synth-sources - Select the synthetic default explicitly: one six-pulse source (0.5 pu fundamental) at the largest-demand bus (also the default without --spectra). Given together with --spectra, exits 2.
--synth-spectrum g5 The spectrum of that synthetic source: g5, the cited ENA EREC G5 Issue 5 Table B.3 six-pulse profile (6-pulse-g5: 5th 31.4 %, 7th 10.9 %, 11th 7.0 %, ... to the 49th, THDI 34.4 %), or ideal, the idealised 1/h six-pulse spectrum (orders 5 to 25, 5th 20 %, 7th 14.3 %, THDI 29.0 %). The output names the spectrum used (synthetic source : ...). Any other value exits 2; with --spectra or --converter-sources (which bring their own spectra) it exits 2.
--converter-sources - rated or dispatched: one source per in-service converter-interfaced unit (battery, PV, wind, tidal, HVDC / interconnector; not a power-flow-only device), with the ENA EREC G5 Issue 5 Table B.3 profile for its technology: active front end (afe-g5) for a self-commutated converter, twelve-pulse (12-pulse-g5, [VERIFY]) for a unit marked as feeding no fault current (a line-commutated HVDC link). rated scales each profile by the unit's rated current (MBase / BaseMva pu, the G5 Stage 1C / 2A basis); dispatched by its output at the solved operating point, sqrt(P^2 + Q^2) / BaseMva (the fundamental power flow is solved first, so the slack's P and every PV unit's Q are the solved values, not the case's Pg / Qg; a fundamental that does not converge exits 3; a unit at zero output is listed as not modelled). Sources add linearly (G5 s.6.3.3: no declared diversity). The study then analyses orders 2 to 50 (Table B.3's range); the triplen components (zero sequence) are left out of the balanced study, and their count and the first one are printed. Any other value exits 2; with --spectra or --synth-sources, exits 2; a case with no converter unit that injects, or a unit with a non-positive rating (rated) or non-finite output (dispatched), exits 1.
--afe-reactance - N149: model every active-front-end converter (the self-commutated units, the afe-g5 class; line-commutated units are untouched) as resonant plant, ENA EREC G5 Issue 5 s.3.29 p.17 ("may be classified as resonant plant due to their internal impedance"): a shunt of R + jhX to ground at its bus, the reactance X given here in pu on the unit's own rating (MBase), converted to the system base. With a converter source (--converter-sources) the unit becomes a Norton equivalent, its source in parallel with this impedance; with the other source choices the units are resonant plant only. No value is given by any document on disk (the converter's own coupling reactor or filter, [VERIFY]), so there is no default: without the flag converters stay ideal current sources and the study is unchanged. The output adds an AFE impedance line (unit count and the impedance). Not finite or not above 0 exits 2; a case with no active-front-end unit, or such a unit with a non-positive rating, exits 1.
--afe-resistance 0 N149: the resistance R in series with --afe-reactance (pu on the unit's rating, frequency-independent); 0 is the conservative choice (no converter damping). Negative or not finite exits 2; without --afe-reactance, exits 2.
--bus worst-THD bus Bus for the resonance scan and fine sweep; a non-integer value or a bus not in the case exits 2.
--enableExport[=path] results/harmonic-export.json Write the gridsim-harmonic-export/1 document.

Exit 2 on an unknown case name, a missing or unreadable --spectra file, an unknown --bus, a bad or contradictory source choice, or a forward-inference rejection; exit 1 for a missing case file or folder, a spectra component at an unanalysed order, a triplen source, no injecting converter unit under --converter-sources, no active-front-end unit (or one with no usable rating) under --afe-reactance, or a singular Y(h) (no THD and no verdict are reported); exit 3 when the fundamental power flow does not converge.

impedance-stability

gridsim impedance-stability [<case>] [--dir <path>] [--bus <id>] [--converter gfl|gfm] [--criterion auto|siso|mimo] [--grid canonical|real] [flags]

Impedance-based (generalised Nyquist) inverter-grid stability screen: forms the loop gain of the grid impedance and the converter admittance over frequency (SISO: the positive- and negative-sequence loops in the converter's dq frame, with the grid read at f + f0 and f - f0; MIMO: the 2x2 dq matrices), counts encirclements of (-1, 0), reports gain and phase margins, and sweeps SCR for the weak-grid instability boundary. The converter operating point is the chosen unit's solved output (the bus's solved generation, split between co-located units by scheduled P and by reactive range), not its scheduled Pg / Qg, at the solved bus voltage. Cross-checks against the right-half-plane eigenvalue count of the case's small-signal model where one can be built: that swing model uses the WSCC-9 Anderson-Fouad X'd for case9 (as stability and modal do), else the synthetic 0.30 pu, and zero damping (no bundled case carries damping data); the cross-check line names its basis in brackets. The SCR boundary line reports what the sweep found: the critical SCR at an unstable-to-stable crossing; "stable across the swept SCR range" only when every swept SCR is stable; "UNSTABLE at every swept SCR" when none is; the count of unstable SCRs when the sweep has no crossing; and n/a with --grid real, where no sweep runs. The converter model comes from the case's bound asset class when there is one, otherwise from the flags (tagged CuratedPlaceholder [VERIFY]). See ch. 15.

Flag Default Meaning
<case> / --dir case9 Case argument or JSON case directory (-d is a short alias of --dir).
--bus largest generator's bus Generator bus to attach the converter model to.
--converter gfl gfl (grid-following) or gfm (grid-forming); any other value exits 2. The grid-forming model's power loop is per unit on the unit's rating (MBase): a bound class's damping D (MW/Hz) and synthetic inertia J (MW.s/Hz) give the droop S / (D f0) and the lag J / D (R140, October 2026; they used to be scaled as 0.01 D pu and 1e-4 J s whatever the unit's size). The flag-built grid-forming model (no damping, no synthetic inertia) is unchanged; its power-loop bandwidth is --pll-bw when given, else the grid-forming placeholder 5 Hz.
--criterion auto auto (MIMO for gfl, SISO for gfm and for --outer-loop-only), siso or mimo (the generalised criterion); any other value exits 2, and mimo with --outer-loop-only exits 2. The grid-following admittance couples the two sequences, which SISO drops, so its SISO verdict can be wrong; the grid-forming admittance does not, so SISO is exact there and keeps the margins. With the ideal PLL of --outer-loop-only the dq loop is improper and its MIMO winding misses a right-half-plane root.
--fmin / --fmax 0.1 / 250 Frequency range (Hz).
--ppd 50 Points per decade.
--grid canonical Grid impedance: canonical (the exact single-inverter-vs-Thevenin model, swept over SCR) or real (the network's own harmonic driving-point impedance at the converter bus; fails with exit 3 if that solve is singular). Any other value exits 2.
--scr 3.0 Short-circuit ratio of the Nyquist scan (--grid canonical only; with --grid real the SCR flags exit 2).
--scr-min / --scr-max / --scr-steps 1 / 10 / 37 SCR sweep for the boundary search.
--pll-bw 20 Hz PLL bandwidth (flag-built model, or an override of a grid-following asset class). The value must be a finite number above 0: 0, a negative value, NaN or Infinity exits 2 (N266, October 2026; it used to be floored silently by the flag-built model and crash a bound asset class). With a grid-forming asset class it exits 2 (the class sets its own power-loop bandwidth); with the flag-built grid-forming model it sets the power-loop bandwidth (default 5 Hz). The default is the one grid-following PLL default the EMT and small-signal models also use (R138, October 2026; it was 5 Hz here, 20 Hz in EMT): a faster PLL is the destabilising direction on a weak grid, so an unauthored device is screened on the conservative side. A grid-following asset class without pllBandwidthHz takes the same 20 Hz.
--pll-damping 0.707 PLL damping ratio of the grid-following model: the flag-built model's value, or an override of a bound grid-following asset class's authored damping (without the flag the class's own damping is used, and any override tags the model CuratedPlaceholder, not Recorded). The value must be a finite number above 0 (0 or below, NaN or Infinity exits 2; N266). With --converter gfm (bound class or not) it exits 2: the grid-forming model takes no PLL damping ratio.
--current-bw - (no default) Current-loop bandwidth (Hz); setting it adds the current loop to the model detail (PllCurrentOuter). There is no default value: without the flag the model has no current-loop bandwidth (the PllOuter level and its fast stand-in roll-off), and the flag without a value exits 2. The value must be a finite number above 0 (0 or below exits 2). Grid-following only; with --converter gfm it exits 2.
--outer-loop-only off The outer-loop-only detail level (ImpedanceModelDetail.OuterLoopOnly): the grid-following PLL is ideal (gain frozen at 1/Vd0) and the current loop is the fast stand-in roll-off, a first screen when no inner-loop data exist. With --pll-bw, --pll-damping or --current-bw (which it would ignore), or with --converter gfm (whose admittance does not use the detail level), it exits 2.
--enableExport[=path] results/impedance-stability-export.json Write the scan to JSON.

Exit 3 on a non-converged power flow; exit 2 on an unknown case name, a second case argument, a positional case and a different --dir, or no generator at the chosen bus; exit 1 for a missing or unloadable file or folder. A completed scan exits 0 whether the verdict is STABLE or UNSTABLE. The case may sit anywhere on the line and may be a built-in name, a .m file or a case folder.

emt

gridsim emt [<case>] [--dir <path>] [--dt-us 20] [--duration 0.1] [--source <bus>] [--amp 1.0] [--freq 0] [--probe <list>] [--event <spec> ...] [--rule trap|be] [--no-cda] [--lines] [--no-loads] [--allow-non-passive] [--out <dir>]

Electromagnetic-transient time-domain solve: a Dommel nodal companion-model engine steps the instantaneous network at a fixed microsecond timestep. The output is a forward model trajectory. Writes timeseries.csv, summary.md and run-metadata.json. See ch. 16, Electromagnetic transients.

Flag Default Meaning
<case> / --dir data/uk Case argument or JSON case directory.
--dt-us 20 Timestep (microseconds); must be positive (exit 2).
--duration 0.1 Simulated time (s). Must be positive and at least half of one --dt-us step (the run takes round(duration / dt) steps, at least one); anything else exits 2.
--source first generator's bus Source bus.
--amp 1.0 Source amplitude (pu).
--freq 0 Source frequency (Hz); 0 is DC. A negative value exits 2.
--probe source-bus voltage + first series branch current Comma list of v:<bus> and i:<from>-<to> (or i:<from>-><to>, in the case's from -> to direction). Every token must name a bus or an in-service series branch of the case; a token that does not (an unknown bus, a non-numeric bus, no such branch, or neither v: nor i:) exits 2 and nothing runs. Where several in-service series branches join the same two buses (parallel circuits, such as 49-54 in case118), i:<from>-<to> is ambiguous and exits 2 naming how many there are; i:<from>-<to>#<k> picks the k-th of them in case order (N241; it used to read the first without a word). The default branch probe is labelled #1 when its branch has a parallel twin.
--event - Repeatable: fault:<bus>@<t>:<Rpu>, clear:<bus>@<t>, switch:<id>@<t>:close\|open. See the event rules below.
--rule trap trap (trapezoidal) or be (backward Euler); any other value exits 2.
--no-cda off Disable Critical Damping Adjustment (backward-Euler half-steps at switching events that remove the trapezoidal rule's spurious oscillation). CDA runs only under --rule trap; under --rule be it is off whatever this flag says.
--lines off Model charged, non-transformer branches as lossless Bergeron travelling-wave lines.
--no-loads off Leave out the constant-impedance load shunts (by default each bus's demand is one).
--allow-non-passive off Run a network that contains a non-passive element: a branch with a negative series resistance or a bus shunt with a negative conductance. Network-reduction equivalents carry these on purpose (IEEE 145 has 232, pglib case588 has 5). They generate energy, so the run may grow without bound. Without the flag such a case exits 2, naming the first ten elements; with it, stderr gives a warning with the count.
--out results/emt-out Output directory.

Event rules. Each event time must be a number of seconds from 0 up to the end of the run. An event between 0 and one step is applied at the first step; a negative time, or a time after the last step, exits 2. A fault resistance must be a positive number of per-unit ohms: 0 and negative values exit 2 (a bolted fault is a small resistance, for example 1e-4). Each fault bus and resistance pair gets its own fault switch. A later fault: at a bus that is already faulted changes that bus's fault to the new resistance: the bus's other fault switches open at that instant and the new one closes. clear:<bus> opens every fault switch at the bus and needs a fault: at that bus somewhere on the command line. Two fault: events at one bus at the same instant exit 2. The switch: action must be close or open (any letter case); any other word exits 2. Every problem on the command line is listed before the command exits.

summary.md reports CDA: on, CDA: off (--no-cda) or CDA: off (not used under backward Euler). Its refactorizations count is 1, plus 2 for every event that changes a switch when CDA is on, or plus 1 when CDA is off. run-metadata.json holds the shared run fields and a parameters object. That object records the case, dt, the duration and step count, the source, the rule, whether CDA ran, the --no-cda, --lines, --no-loads and --allow-non-passive switches, every probe (name, kind and target), and every event. For each event it keeps the token as given and what it became: the bus, the time, the resistance and the fault switch id.

Exit 1 on a case file or folder that cannot be loaded; exit 2 on an unknown case name, a network that cannot be built (including a non-passive one without --allow-non-passive), a malformed or out-of-range --event, a probe that names nothing, or a --duration that gives no step; exit 3 on an engine failure or a non-finite value in the trajectory.

Evidence verbs

All five share the event catalogue (--catalog <f.json>, schema gridsim-event-catalog/1; built-in events gb-2019-08-09, gb-2023-12-22 and gb-largest-loss-1320) and the forward-inference guard: any event or trace timestamp newer than 169 h ago is rejected with exit 2. A catalogue whose schema is not exactly gridsim-event-catalog/1 exits 1. Every recorded action in a catalogue states its kind: DemandDisconnection (automatic LFDD, never replayed in a counterfactual) or OperatorInstruction (for example the balancing-mechanism recovery, kept in every counterfactual because it replaces the lost energy whatever the nadir); an action without one exits 1, naming the event and the action.

All five take --trace <neso.csv>, which attaches a 1-second NESO trace to the credibility gate they all run, so the gate scores the per-sample RMSE and the back-test (nadir within 0.05 Hz, RoCoF within 0.05 Hz/s on the trace's own 1 s basis, nadir time within 2.0 s) exactly as replay-event --trace does; an RMSE above 0.05 Hz or a failed back-test caps Reproduced at Marginal. A trace file that does not exist exits 2, a trace row newer than the horizon exits 2 (REJECTED (forward inference): ...), and a trace line that is not a valid timestamp,Hz row exits 1. See ch. 18 (replay-event) and ch. 20, Counterfactuals (scenario, h0-study, fleet, evidence). A missing event id prints the usage and the built-in event ids and exits 2; an event id the catalogue does not hold exits 1.

Each of the five accepts only the flags in its own section: a flag that belongs to another verb (for example fleet --device-ffr, evidence --corners, replay-event --device-ffr) exits 2 with error: <verb> does not use <flag> ... <verb> accepts: .... --asset-dynamics is refused by all five, and --forming, --forming-inertia and --forming-damping by all but scenario and fleet. scenario and evidence refuse --device together with --device-inertia or --device-ffr (exit 2).

replay-event

gridsim replay-event <id> [--catalog <f.json>] [--trace <neso.csv>] [--out <dir>] [--dump-catalog <path>]

The credibility gate: reproduce a recorded event's RoCoF and nadir with no device. Writes baseline-frequency.json, summary.md and run-metadata.json to results/replay-<id> by default. --trace attaches a real 1-second NESO CSV to enable the per-sample RMSE check, printed with the number of samples scored; a trace file that does not exist exits 2, and so does a trace with a row newer than the 169 h forward-inference horizon (REJECTED (forward inference): ..., before any output is written); a trace that ends before the scored window is scored only where it reaches, with a WARNING line, and a trace that does not contain the event instant gives n/a and a WARNING. With a trace that covers the window a back-test vs trace line gives the back-test (PASS or FAIL, the nadir error, the RoCoF on the trace's 1 s basis, the nadir times). The inferred inertia from recorded RoCoF line inverts the swing equation; for a windowed record (gb-2023-12-22's 1 s figure) the recorded RoCoF is first scaled to an instantaneous slope by the replay's own instantaneous / windowed ratio, stated on the next line. --dump-catalog writes the built-in catalogue to disk and exits. Exit 3 for any verdict short of Reproduced (a Marginal baseline unlocks nothing).

scenario

gridsim scenario --event <id> [flags]

The counterfactual sweep (inertia x device x corners) plus the inertia risk curve. Refuses to run (exit 3, GATE FAILED) unless the no-device baseline reproduces the record. Writes matrix.csv, risk-curve.csv, counterfactual-frequency.json, summary.md to results/scenario-<id>.

Flag Default Meaning
--event required Event id (exit 2 if missing).
--inertia 260,155,120,102,50 GVA.s levels to sweep (the GB trajectory).
--device <f.json> - Device from a JSON file.
--device-inertia / --device-ffr 30.0 GVA.s / 1.0 GW Build the device from flags instead (a [VERIFY] placeholder TSGB).
--corners best,worst Comma list of best, nominal, worst.
--trace - 1-second NESO trace for the gate (see the notes above).
--catalog / --out built-ins / results/scenario-<id> Catalogue file / output directory.

The global --forming, --forming-inertia and --forming-damping switches carry a virtual former into every cell, so a low-inertia counterfactual is formed rather than floored. A --device file that does not load exits 2.

h0-study

gridsim h0-study --event <id> [flags]

The H=0 counterfactual: scale the real synchronous inertia toward zero while making a growing fraction of the converter fleet grid-forming, per asset (fleet-routed). Gated like scenario (exit 3 unless the baseline reproduces). Prints a scale x GFM-fraction table per corner (HELD, LFDD, CASC for a Loss-of-Mains cascade, NaN for a forming-dependent cell with no grid-forming source); forming-dependent cells are data and the run still exits 0. Writes h0-study.json, matrix.csv, summary.md and run-metadata.json to results/h0-study-<id>.

The header line dP=<MW> MW (first 5 s; <MW> MW over the whole event) gives the loss that sets the initial RoCoF (the loss steps in the first 5 s, the same window the replay's inertia cross-check uses) and the whole staged total (R287, October 2026: dP and each cell's analytic bare_inertia_rocof used the whole total; gb-2019-08-09: 1,521 MW, not 2,768 MW). summary.md also gives the largest single loss step. Converter units are made grid-forming whole, largest first, so a fraction can be overshot by up to one unit's MW (R289): matrix.csv carries realised_gfm_fraction after gfm_fraction, h0-study.json carries realisedGfmFraction per cell (and system.totalExogenousLossMw, rocofSettingLossMw, rocofSettingWindowS, largestSingleLossMw; the old largestLossMw key keeps the total), and the console prints GFM fraction realised by whole units: <requested> -> <realised> when they differ.

Flag Default Meaning
--event required Event id (exit 2 if missing).
--dir data/gb-synthetic Case directory. It must ship asset-classes.json and asset-bindings.json (exit 1 otherwise).
--sync-inertia-scale 1,0.5,0.25,0 Synchronous-inertia scale factors.
--gfm-fraction 0,0.25,0.5,0.75,1 Fractions of the converter fleet made grid-forming.
--gfm-class / --gfl-class gfm-vsm-study-2024 / gfl-wind-2024 Asset classes for the grid-forming and grid-following units.
--corners best,worst Comma list of best, nominal, worst.
--trace - 1-second NESO trace for the gate (see the notes above).
--catalog / --out built-ins / results/h0-study-<id> Catalogue / output directory.

fleet

gridsim fleet --event <id> [flags]

Single-versus-fleet emergent behaviour: the same total device budget split across N staggered units. Intrinsic inertia is N-additive; FFR is not (fewer MW online at the nadir). Gated like scenario (exit 3 unless the baseline reproduces). Writes fleet.csv to results/fleet-<id>.

Flag Default Meaning
--event required Event id.
--units 1,100 Unit counts to compare.
--total-inertia 40.0 Total device inertia budget (GVA.s).
--total-ffr 1.5 Total device FFR budget (GW).
--stagger 10.0 Fleet onset spread (s).
--tau 0.5 Per-unit FFR time constant (s).
--deadband 0.015 Per-unit frequency deadband (Hz).
--inertia event pre-event inertia System inertia (GVA.s).
--trace - 1-second NESO trace for the gate (see the notes above).
--catalog / --out built-ins / results/fleet-<id> Catalogue / output directory.

The global --forming, --forming-inertia and --forming-damping switches (N291, October 2026; the fleet engines refused grid-forming before) run every row with the same aggregate virtual former: vsm is a virtual synchronous machine (virtual inertia plus damping), droop a P-f droop former; the units add real inertia and fast response on top. A grid-forming: line under the header names the former, and run-metadata.json records it; without the switches the output is unchanged.

The three lines under the table state what the first and last rows show, compared at the printed precision: whether the RoCoF is the same (when it differs, the inertia total is the same in both rows, so the difference is the timing of the fast response), whether the staggered fleet has fewer, the same or more MW online at the nadir, and whether its nadir is deeper, the same or shallower.

evidence

gridsim evidence --event <id> [flags]

The umbrella dossier (gridsim-evidence/1): recorded versus simulated versus counterfactual columns, risk curve, fleet comparison and avoided cost. The counterfactual sections are withheld (and the exit is 3) unless the baseline reproduces. Writes evidence.json and summary.md to results/evidence-<id>. The RoCoF in the simulated and counterfactual columns is on the recorded figure's measurement basis (the 1 s windowed figure for gb-2023-12-22), the same figure the gate scores. The fleet section's units carry the device's own response time constant and dead-band.

Flag Default Meaning
--event required Event id.
--device / --device-inertia / --device-ffr - / 30.0 / 1.0 Device file or flag-built placeholder.
--inertia 260,155,120,102,50 Risk-curve inertia levels (GVA.s).
--cf-inertia event pre-event inertia Inertia for the headline counterfactual column (GVA.s).
--units 100 Fleet size for the fleet section.
--stagger 10.0 Fleet onset spread (s).
--voll 6000.0 Value of lost load, GBP/MWh (a curated placeholder, labelled as such in the output).
--voll-source - The reference the --voll figure is taken from: S324 (Ofgem BSC P305 decision: 3000 or 6000 GBP/MWh), S322 (London Economics 2013: 16940) or S323 (DECC EMR annex C 2013: 16940), all in docs/reference/voll. Any other value, or a --voll the reference does not state, exits 2 naming what it does state. A valid source is printed (VoLL source: ...) but does not raise the VoLL tag, which stays CuratedPlaceholder (N359: a citation records where a policy figure is stated, it does not re-source it; before N359 it tagged the VoLL Recorded); the duration has no source and stays CuratedPlaceholder, and the avoided cost takes the weaker tag of the two (printed per input).
--duration 0.5 Assumed shed duration (h) for avoided cost (a CuratedPlaceholder).
--trace - 1-second NESO trace for the gate (see the notes above).
--catalog / --out built-ins / results/evidence-<id> Catalogue / output directory.

Data verbs

These verbs read, write and estimate from data. GDA verbs are in ch. 22 and ch. 24; estimate and estimate-noise-floor are in ch. 21; the file formats are in ch. 31.

gda

gridsim gda --root <path> [flags]

Read the read-only GDA data lake and materialise a GridSim replica (data stays out of the repo). Without --root the lake comes from the GDA_DATA_ROOT environment variable (the GDA estate's own name for it), else from GDA_ROOT; with none of the three, usage prints and the verb exits 2. A variable that is set but does not name an existing folder is refused with GDA root error: the environment variable <name> is set but does not name an existing folder ... and exit 1, naming the variable but never printing its value; a wrong GDA_DATA_ROOT is not replaced by GDA_ROOT.

Flag Default Meaning
--root $GDA_DATA_ROOT, else $GDA_ROOT Path to the /gda lake (the folder holding NationalGrid/, NESO/).
--dno nged Source reader: nged, ukpn or npg.
--licence - Restrict to one licence area (for example EMIDS).
--gsp - Restrict to one GSP group. The name is checked first (case, spacing and kV spelling do not matter); an unknown name exits 2 with the nearest names.
--all-gsps off Build and solve every GSP supply area in turn. Spellings of one group are built once; names that select no live element are listed separately and not counted. Exit 3 if any area that builds fails to build or converge, or if none builds.
--minkv 0 Build only the network at or above N kV; demand below the cut (and its embedded generation) is folded onto the nearest boundary bus and reported in the notes.
--base 100 System base MVA.
--neg-gen off Embedded generation as negative load.
--all-gen off Admit every embedded-generation register row whatever its connection status (planning what-if). By default only connected plant enters the model; accepted, offered and unknown-status rows are left out and reported with their MW.
--no-oltc off Do not create OLTC controllers.
--no-geo off Skip geolocating buses from the substation table.
--as-of <date> now - 169 h Register as-of date (the no-forward-inference horizon; override for a specific replay date). ISO yyyy-MM-dd[THH:mm[:ss]].
--out - Materialise the replica as a JSON case directory (lossless for every generator field a JSON v1 case carries; see synth for the rule).
--solve off Solve the built model (60 iterations, reactive limits off): the engine of the shared rule (Solver selection); --sparse / --dense force the backend.
--fleet off National NESO fleet report instead (inertia, largest loss, RoCoF screen, ETYS boundary limits).
--schema <path> - Print a CSV/Parquet dataset's columns and row count, then exit.

--dno ukpn reads each LTDS table (circuits, two-winding transformers, observed peak demand, generation) from its published CSV under UkPowerNetworks/RAWData. When that CSV is missing or has only its header line (the full GDA lake keeps the rows in its Parquet conversion), the table is read from the lake's Parquet copy under UkPowerNetworks/Parquet instead (the same file name ending .parquet), cell for cell with the CSV reader's meaning, and a note: line names each table read that way. A CSV that has rows always wins. A Parquet text column that the conversion turned into numbers is refused (exit 1), because the original text cannot be recovered; numbers with more than 15 significant digits are counted in a note: line, because the conversion's parser may differ from a CSV read in their last binary place. With neither rows in the CSV nor a Parquet copy with rows, the build is refused (exit 1) naming the tables and both places searched.

--fleet is checked before --schema, and --all-gsps replaces the single build. An unknown --dno or an unparseable --as-of exits 2; a root, load or build failure exits 1; a carve that keeps no live element (0 buses) exits 3 and writes nothing; --solve exits 3 when the solve does not converge.

gda-replay

gridsim gda-replay (--series <ts.json> | --synth) [flags]

The historical state estimator: replay a demand time series through the validated solver, reconstructing grid state at each past timestamp (horizon-guarded, never nowcasting). Writes state-estimate.csv, exports/state-*.json and run-metadata.json. Exit 3 if any step fails to converge; exit 2 with neither --series nor --synth or on a forward-inference rejection; exit 1 if the case or series does not load.

Flag Default Meaning
--series - A GDA time-series JSON (real per-timestamp demand is data-gated).
--synth - Synthetic daily load shape instead.
--start 2024-01-01 Synthetic series start instant, ISO 8601 (yyyy-MM-dd, yyyy-MM-ddTHH:mm[:ss[.f]], optional Z or offset), read as UTC whatever the machine's time zone. Any other text exits 2.
--steps 48 Synthetic timestamps.
--step-min 30.0 Minutes between synthetic timestamps.
--case case118 Network to replay on: a case name, a .m file, or a JSON case directory (a folder holding system.json, such as one written by gda --out).
--export-every 0 (off) Full solve export every N-th step (step 0 always exports when tracing).
--out results/gda-replay-<case> Output directory, relative to the current directory (for a case directory, <case> is its last folder name).
--bess chem:bus:MW:MWh[:soc] - Hypothetical storage on recorded history, repeatable (same site spec as chain, ch. 13). The result is tagged Counterfactual and also writes storage-counterfactual.csv. A malformed site, or a site on a bus the case does not have (storage site '...' is at unknown bus N., as chain says), exits 2.
--policy peak-shave Storage dispatch policy: idle, peak-shave or hold. gda-replay takes no price series, so price and lp exit 2 (--policy <p> needs a price series, and gda-replay takes none).
--shave-high / --shave-low 90 % / 70 % of peak demand Peak-shave discharge and recharge thresholds (MW), as for chain.
--passive-plant off Run the case's bound passive plant at each step (delayed on-load tap changer taps and line / transformer thermal derating, advanced from the previous converged step). Off: the replay is exactly as without it.

synth

gridsim synth [flags]

Build the synthetic GB-at-scale case (no data held under a licence), solve it, and materialise it as a JSON case directory. Exit 3 if the check solve does not converge (the folder is still written).

Flag Default Meaning
--seed 20260605 Build RNG seed.
--scale 1.0 Network size scale factor: multiplies the 11 kV secondaries under each 33 kV primary (at least 2 each). Below 1.0 the result is a smaller GB: each zone's demand, embedded plant and transmission fleet are multiplied by the zone's secondaries built over those it gets at 1.0, so the load per secondary transformer stays at its 1.0 level. Every scale up to 0.36 builds the same 1,082-bus network with 14.5 GW of demand; with seed 20260605 every scale tried from 0.02 to 2.0 converges (0.02: 4 Newton iterations, V 0.951-1.040 pu; 0.5: 1,309 buses, 19.9 GW). At 1.0 and above nothing is scaled: a larger scale spreads the same GB demand over more secondaries (2.0: 3,946 buses). Must be a finite number above 0 (else exit 2).
--iters 60 Max Newton iterations for the check solve.
--oltc 30 Max OLTC passes.
--qlimits off Enforce Q-limits in the check solve.
--worst off Print the ten worst spec-vs-solved buses even when converged.
--out results/synth/gb-synthetic Output case directory. N256: the default used to be the bundled data/gb-synthetic beside the executable; to regenerate the shipped case, name it (--out data/gb-synthetic). --out with no value exits 2.

The folder is written by the same writer as gda --out, and it is lossless for every generator field a JSON v1 case carries: pMinMw, pMaxMw (when not the capacity; an unlimited limit as "Infinity"), qOutputMvar, dynamicsClass, converterInterfaced, converterFaultCurrentPu, powerFlowOnly, unitTransformerXPu, gridForming and inService: false (out-of-service units are written too), each only when it differs from the loader's default. What JSON v1 cannot hold (a generator's X''d and X2, gencost curves) is not dropped silently: a note: line on stderr names how many generators carry it.

export

gridsim export [<case>] [out.json] [--dir <path>] [--frames 72]

Write a visualisation scene (buses, branches, animation frames) for external renderers. Default output results/gridviz.json, default model data/uk. A free token that names a case is the case; any other free token is the output path and must end in .json (exit 2 otherwise, so a mistyped case name is not used as a file name).

Flag Default Meaning
<case> / --dir data/uk Case argument or JSON case directory.
[out.json] results/gridviz.json Output path.
--frames 72 Animation frames.

convert

gridsim convert <input.m|input.raw|input.uct|case-dir|case> <output.m|output.raw|output.xml|output.json|output-dir> [--public [--provenance <manifest.json>]]

Convert a case between MATPOWER, PSS/E RAW, CGMES, a JSON case folder (v1) and a JSON v2 case. An output ending in .m is written as MATPOWER (version 2); an output ending in .raw is written as PSS/E RAW revision 33 (see below); an output ending in .xml is written as CGMES RDF/XML (see below); an output ending in .json is written as a JSON v2 case (N299, October 2026): the manifest at that path and its network file beside it (uk.case.json writes uk.network.json); any other output is a JSON case folder. The input is loaded as every verb loads it (a .m file through the unit normaliser, a PSS/E .raw file through the RAW reader (ch. 2), a UCTE-DEF .uct file through the UCTE reader (ch. 2), a JSON folder dispatched as usual, or a built-in name). The conversion is then proved: the written case is read back and both are solved with the contingency option set and the tap-changer loop, and every bus voltage, angle and injection, both loss totals and every line flow must be the same bits. The last line says so (round trip: the written case solves bit-identically (...)).

Everything a power flow reads is written exactly and in model order (buses, generators including out-of-service ones, branches), so a MATPOWER case converts both ways without changing a bit. What the target format cannot hold is printed as note: lines (and written into a .m file as comments): to MATPOWER, names, layout coordinates, ZIP loads, generator types, inertia and fault data, OLTCs, boundaries and the asset bundles; to JSON, MATPOWER cost curves (gencost, carried by the model but not by JSON v1) and DC lines. A JSON folder written by convert sets "dispatch": false in system.json (the written outputs are the operating point) and keeps transformers in transmission.json, in branch order (see ch. 2). A bus with no per-bus voltage limits is written to MATPOWER with VMAX / VMIN 1.06 / 0.94, the band GridSim's checks fall back to.

A PSS/E RAW output carries the devices the RAW reader models, each in its own section: two-terminal LCC, VSC and multi-terminal DC links, FACTS devices (a STATCOM, a UPFC, a constant series impedance with its series element), static var compensators (a continuous switched shunt whose BINIT the reader adds back to the bus shunt), induction machines (custom single-cage design), on-load tap changers (COD 1) and transformer flow controls (COD 2 and 3). It is read back with tap and shunt control applied. A tap changer or flow control is written only when the reader's formulas give back its numbers to the bit (target and deadband from VMA and VMI, step from RMA, RMI and a whole NTP); one that cannot be is left at its present tap and named in a note: line, so the proof then shows the difference. RAW keeps lines and transformers in separate sections, so the read-back lists the branches in that order (lines, then transformers, then FACTS series elements); the proof compares it with the input put in that order, and a second round trip: line says whether the input in its own order also gives the same bits (a different branch order can change the last bits of the admittance sums). Not written, with a note: generator dynamics and fault data, boundaries, the asset bundles, MATPOWER DC lines; a name holding a single quote is written in double quotes. Refused (exit 1): ZIP loads, zero-sequence data, an infinite generator limit, a transformer with line charging and a ratio or phase shift.

A CGMES output is one RDF/XML file holding the equipment, topology, steady-state hypothesis and state-variable content: buses as TopologicalNodes with their base voltage and their stored voltage as an SvVoltage (where a solve starts), one EnergyConsumer per bus with demand, one LinearShuntCompensator per bus with a fixed shunt, the in-service generators as SynchronousMachines (voltage control and target at slack and PV buses, the slack's machines with referencePriority 1, reactive and active limits, ratedS, inertia), in-service branches as ACLineSegments when they are plain lines on one base voltage and otherwise as two-winding PowerTransformers (ratio and phase shift as tap changers; a ratio the linear changer cannot give back exactly as a one-point ratio table), and rate A as a permanent ApparentPowerLimit. It is read back through GridSim's CIM reader with the starting voltages and the ratings, on the input's system base (CGMES carries none); the read-back numbers buses 1..n in model order and lists lines before transformers, so the proof compares it with the input put in that form, and a second round trip: line says whether the input in its own numbering and order gives the same bits. CGMES holds ohms, siemens and kV, and the per-unit conversion (a product or quotient by a base that is not a power of two) does not reach every double: about half the values of a typical MATPOWER case have no CGMES value that converts back to the same bits. Each such value is written as the nearest one (one ulp off after read-back), a note: counts them by kind and names the first, and the proof then fails (exit 3) naming the first difference; a model whose values are images of physical values (one read from CIM, or one already passed through CGMES once) converts exactly. Refused, every reason listed and nothing written (exit 1): devices GridSim's CIM reader does not rebuild into the model the power flow solves (on-load tap changers and flow controls, HVDC links, FACTS devices, static var compensators, induction machines), ZIP loads, a bus with no base voltage, a slack bus with no in-service generator, machines at one voltage-controlled bus with different set-points. Not written, with a note: out-of-service equipment, generator types outside the CGMES unit classes, converter flags, fault and sequence data, cost curves, rates B and C, per-bus voltage limits, layout, boundaries and the asset bundles.

--public writes a public export: only what a gridsim-provenance/1 manifest traces to published sources. The manifest (--provenance <file>; by default provenance.json in the case folder, or <file>.provenance.json beside a case file) lists its sources (id, title, publisher, URL, licence, and published true only for a source anyone can obtain from its publisher) and, for each element, the sources it comes from: buses by id, branches and generators by name, and optionally a bus's demand and fixed shunt by bus id and an on-load tap changer by its transformer's name. Any other key, a cited source the manifest does not list, or an element citing no source is refused naming it. A bus is kept when every source it cites is published; a branch, generator or tap changer when its name is unique, every source it cites is published and its buses are kept. Unsourced demand and shunts on a kept bus are zeroed, layout coordinates are zeroed, a PV bus left with no generator becomes PQ, and devices the manifest has no section for (HVDC links, FACTS devices, static var compensators, induction machines, flow controls, mutual couplings, boundaries, the asset bundles, MATPOWER DC lines) are stripped. Every strip is printed as a public: line (and in the result file's public_stripped table), and the public model is then written and proved as any other conversion. No manifest, a manifest for another case, or a public model with no slack bus or with a kept slack bus whose generators were stripped exits 1 with nothing written: a public export is never made without evidence, and the built-in IEEE cases (no case folder) need --provenance. --provenance without --public is a usage error (exit 2).

A JSON v2 output carries the fault sequence data JSON v1 cannot (N234: generator subtransientXdPu / negativeSeqXPu, transformer windings, r0Pu / x0Pu and neutralXPu), so a v2 case converts to v2 and back with its earth-fault data. Its manifest sets "dispatch": false; every branch is written in place as a line (a transformer with isTransformer), except the trailing run of branches from the first one with winding data, which are written as transformers elements (the v2 loader always builds those after the lines, so this keeps the branch order). Its proof also compares every generator's X''d and X2 and every branch's R0, X0, windings and neutral reactances bit for bit, and a second round trip: line says so. The files are byte-stable: the same model writes the same bytes on every OS ("\n" line ends). The asset-dynamics and protection bundles are written too (N321, October 2026; they used to be left out with a note): each asset class as a case-local template gridsim.local.<class name>@1 (kinds gridFollowingInverter, gridFormingInverter, oltc for a transformer class, lineType for a line class, protection), the binding rules as the manifest's bindings (match types in lower case), each element's class as its template, and the placed protective devices as the network file's protections, so the written case loads with the same classes, rules and devices. A bundle that cannot be written exactly (a class name that cannot be a template id, such as one taken from an imported template id@rev) is not written at all, and a note says why. Notes name what is not written: such a bundle and the element template references into it, cost curves, DC lines, out-of-service branches (v2 refuses them for now), winding data that would need the branches reordered, and the names given to unnamed generators (unit-<n>) and branches (branch-<n>), since v2 requires names. A bus without a base voltage above 0 kV cannot be written to v2 (exit 1). The v2 output needs the v2 schemas to be proved (found as validate finds them); without them nothing is written (exit 1). An existing manifest or network file is never overwritten (exit 2).

Exit 0 when the round trip is bit-identical; 3 when it is not (a ZIP load or OLTCs written to MATPOWER, or tap changers whose band RAW cannot give back exactly, or values CGMES cannot hold exactly, for example), naming the first difference and, where the buses match, the largest voltage difference (|dVm|, |dVa|) and how many buses differ (the output is kept); 1 when the input does not load or the output cannot be written (a NaN, or a value the format cannot hold, is refused naming it); 2 for a usage error or when the output already exists (an existing .m file or a non-empty folder is never overwritten).

What each writer carries, notes and refuses for the full GB case, with the counts and the size of the resulting difference: gb-full through every writer.

Result files: --json <file.json> or --csv <file.csv> write the result, including the round-trip verdict, to a file (Result files); convert does not take --out, because its second argument is already its output.

validate

gridsim validate <file.json|folder>... [--schemas <dir>]

Check GridSim JSON v2 documents with the Phase 1 validator, choosing the check by each document's "schema" tag: gridsim-case/2 against case.schema.json (and, when the manifest is valid, each network file it lists, read relative to it: a missing one is an error on the manifest, an existing one is checked as a network file); gridsim-network/2 against network.schema.json; gridsim-library/2 files all together (schema, kind specs, unique id@rev, controller references resolving within the set); gridsim-kind/2 against kind.schema.json; gridsim-dynamics/2 (F23, machine dynamic data for stability --rms --dyn-data) against dynamics.schema.json and then its templates as one library (the binding to a case's generators is checked when a study loads it); gridsim-dist3ph/2 (N339, the three-phase feeder in its v2 form) against dist3ph.schema.json and then with the feeder reader itself (ids, references, the branch kind rules, one radial tree, phases; its first refusal is reported). A folder is searched for *.json files. A document with no tag (a v1 case file, for example) or an unknown tag, and a file that is not JSON, are reported as invalid. Library imports in a manifest are not resolved (they name files relative to a data root a lone manifest does not know); pass the library files to check them. See technical ch. 28.

Each document prints OK <path> (<tag>) or FAIL <path> (<tag>): N error(s) followed by every error as <pointer>: <message>, then a summary line.

Flag Default Meaning
--schemas schemas/v2 beside the program, else the nearest above it or above the current folder The folder holding the v2 schemas (with the kind specs in kinds/).

Exit 0 when every document is valid; 3 when any is not; 1 when a path does not exist, no .json file is found or the schemas cannot be found or loaded; 2 for a usage error.

Result files: --json <file.json>, --csv <file.csv> or --out <file.json|file.csv> write the result to a file (Result files).

zonal

gridsim zonal <pypsa-gb-zonal|folder>

Show a PyPSA-GB zonal transport model: the bundled pypsa-gb-zonal (PyPSA-GB @ 8e084af, MIT, 20 zones and 37 links, under data/matpower/gb/pypsa-gb/zonal) or a folder holding the same two files, buses.csv (name,y,x,v_nom,carrier: zone name, latitude, longitude) and links.csv (name,bus0,bus1,carrier,p_nom,p_min_pu). The headers must be exactly these. Prints the zones, every link with its capacity each way (p_nom forwards, -p_min_pu x p_nom backwards; an interconnector to a foreign node is marked), and, when the folder has a boundaries.json, the transfer capacity across each boundary cut: the bundled cuts B4, B6, B7 and B8 were derived from NESO's ETYS boundary GIS lines (March 2025) by tools/gb-reference/derive_boundaries.py.

A zonal model has links with a MW capacity and no impedance, so it has no power flow. This verb only reports what the files hold, and every verb that solves a network refuses pypsa-gb-zonal as an input error (error: case 'pypsa-gb-zonal' cannot be solved: it is a zonal transport model ..., exit 1).

Exit 0 when the model is shown; 1 when the files are missing or malformed (the message names the file, line and column) or the argument is neither the bundled name nor a folder; 2 for a usage error.

Result files: --json <file.json>, --csv <file.csv> or --out <file.json|file.csv> write the zones, links and boundary capacities to a file (Result files).

pmu-ingest

gridsim pmu-ingest <capture.bin> [--channels <map.json> --measurements-dir <dir>]

gridsim pmu-ingest --live tcp://host:port|udp://[bind]:port --live-frames N [--live-seconds S] [--live-idcode ID] [--live-udp-source IP] [--live-quarantine <dir>] [--channels <map.json> --measurements-dir <dir>]

EXPERIMENTAL. Decode a recorded IEEE C37.118.2 synchrophasor stream: the frames as sent, back to back, a CONFIG-1 or CONFIG-2 frame followed by DATA frames (technical ch. 33). Every frame's CRC is checked; the CONFIG frame is parsed (TIME_BASE, each PMU's FORMAT, channel counts, PHUNIT and FNOM); every DATA frame is decoded with one block per PMU of that configuration, in its order (a phasor data concentrator's multi-PMU frame; integer fields scaled by FNOM and PHUNIT); and the usable samples are aligned on their reporting instants by the phasor data concentrator. Prints the frame counts, one line per PMU (phasors, samples, first and last time, frequency range, how many STAT words were non-zero, how many samples were dropped), the number of aligned instants with a PMU missing, and a quality: line counting the dropped samples by reason. HEADER, COMMAND and CONFIG-3 frames are counted and not decoded; if the CONFIG frame changes during the capture, the change is reported and later frames use the new one: the configuration line then reads last configuration: and says each DATA frame was decoded with the configuration in force when it arrived. The per-PMU table lists every PMU of every configuration in force (a PMU whose phasor count changed shows each count, 2/3), and an instant counts as having a PMU missing only when a PMU of the configuration in force at that instant did not report (N260; the table and the expected list used to follow the capture's last configuration only). Analogue and digital channels are sized, not decoded. The whole file is split into frames before any frame is decoded, so a capture that does not frame cleanly is refused without decoding any of it.

Time: each DATA frame's instant is SOC + FRACSEC / TIME_BASE, computed exactly in whole 100 ns ticks (a fraction finer than one tick is rounded down to the tick at or before it). A CONFIG frame with TIME_BASE 0 is refused by name (exit 1), and a DATA frame whose FRACSEC count is not below TIME_BASE (a second or more, not a fraction) is malformed: counted and not used (exit 3).

Horizon: every decoded DATA frame's time must be older than the 169 h horizon (real clock). A capture with any frame newer than that, or in the future, is refused whole before anything is printed: REJECTED (forward inference): ..., exit 2.

Sample quality (STAT and the FRACSEC time quality, IEEE C37.118.2-2011 [VERIFY]): a sample is dropped, never aligned or mapped, when its frame's FRACSEC message time quality code is above 0x5 (time error 100 us or more, an undefined code, or 0xF clock failure: every block of that frame); when its STAT data-error bits 15-14 are not 00 (PMU error, test mode, absent data); or when it is unsynchronised (STAT bit 13 set, a STAT time quality, bits 8-6, of 100 us or worse, or an unlocked time, bits 5-4, of 10 s or more). 10 us is the line because a 100 us time error turns a 50 Hz phasor by 1.8 degrees, three times the angle share of the 1 % total vector error budget. The other STAT bits (sorting, trigger, configuration change, data modified) and the leap-second bits do not decide.

Flag Default Meaning
--channels - A PMU channel map (gridsim-pmu-channels/1): schema, case, baseMva, the angle reference (pmu, phasor, anchorDeg, a mapped voltage channel) and per PMU (pmu) its voltages (phasor, bus, baseVolts, vmSigmaPu, vaSigmaDeg) and currents (phasor, from, to, optional circuit, baseAmps, iMagSigmaPu, iAngSigmaDeg). Bases and sigmas must be finite and above 0. Checked against every configuration in force for a decoded DATA frame (each CONFIG frame of the capture that decoded at least one DATA frame; the last one when none did): every PMU present, every phasor index inside its PMU's count, a voltage channel on a voltage phasor and a current channel on a current phasor (PHUNIT). When the configuration changed during the capture, each one the map does not fit is named by the frame it arrived in (against the configuration from CONFIG frame N (in force for K decoded DATA frame(s)): ...). Needs --measurements-dir.
--live off N340: read a LIVE IEEE C37.118.2 stream instead of a capture file (give no file with it). tcp://host:port connects to the PMU or PDC, sends COMMAND frames "send CONFIG-2" and "turn on transmission" to --live-idcode, frames the stream (a byte where SYNC 0xAA must start a frame, or a frame size below 16, stops the run: exit 1, no resynchronising) and sends "turn off transmission" when it stops. udp://[bind]:port listens (bind address default 0.0.0.0) for the device's stream, one frame per datagram; a datagram that is not exactly one frame is dropped and counted (exit 3). The received frames then go through exactly the recorded path above (CRC, CONFIG, decoding, quality, alignment, the channel map and the horizon: a device streaming the present is refused, REJECTED (forward inference), exit 2, like a fresh capture; a PDC replaying history is read). Prints a live: line with the frames received.
--live-frames - With --live (required): stop after this many DATA frames (1 or more).
--live-seconds 30 With --live: the longest the receive runs (above 0, at most 86400). Stopping on it before --live-frames DATA frames arrived exits 3 after the summary; no frame at all exits 3.
--live-idcode 1 With a tcp:// --live: the device IDCODE (0 to 65535) the COMMAND frames address. Refused with udp://.
--live-udp-source any sender GR-818: with a udp:// --live, read only datagrams whose source address is this IP address; datagrams from any other sender are dropped and counted on the live: line, never captured. Refused with tcp://.
--live-quarantine off N358: with --live only (refused alone, exit 2). A live device streams the present, which the forward-inference horizon (169 h) refuses: without this flag such a run is REJECTED whole, exit 2. With it, every decoded DATA frame newer than the horizon is held back and NOT ingested (no quality judgement, no alignment, no channel map, no measurement set, no report row): the received frames, except the decoded DATA frames already older than the horizon, are written byte for byte to <dir>/pmu-live-<received UTC>.quarantine.c37 with a sidecar <capture>.quarantine.json (schema gridsim-pmu-quarantine/1: SHA-256, frame counts, source, received time, horizon, oldest and newest frame time, sourceClass telemetry, evidential false, recorded false, provenance tag CuratedPlaceholder, never Recorded). A line quarantine: ... names the file; the JSON report gains quarantined_data_frames. Frames older than the horizon continue through the recorded pipeline as before. Never overwrites (a clash gets -dupN). A folder inside the GDA public lake (a DataSchema.json at or above it) is refused, exit 1. pmu-ingest <file> refuses a quarantine capture (named *.quarantine.c37 or with the sidecar beside it), exit 1, whatever its age: it becomes recorded data only by re-sourcing the same instants from an archive.
--measurements-dir - With --channels: write one gridsim-measurements/1 set per aligned instant here (pmu-<yyyyMMddTHHmmssfffffff>Z.json, never overwriting: a clash gets -dupN), each VmPu / VaDeg per voltage channel and IMagPu / IAngDeg per current channel, angles re-referenced to the reference channel, dated with the instant and passed through the horizon guard. An instant whose reference channel did not report usably gives no set (its angles cannot be referenced); an instant with no mapped PMU gives none either. Prints measurement sets: N written to <dir> (...). Needs --channels.

Exit 0 when every frame decoded and every sample was usable; 3 when any DATA frame failed its CRC, was malformed (its length does not match the configuration, or its FRACSEC is not below TIME_BASE), or came before any CONFIG frame, when any sample was dropped by the quality rule, or when an aligned instant had no usable reference channel (each counted and reported, the summary still printed); 2 for usage (including --channels or --measurements-dir alone) and for a capture with a frame newer than the horizon; 1 when the file cannot be read, cannot be split into frames (a byte where a SYNC 0xAA should start a frame, or a frame running past the end), holds no CONFIG frame with a good CRC, or holds a CONFIG frame that passes its CRC but cannot be parsed (truncated, or TIME_BASE 0), and when the channel map cannot be read, is malformed (every problem named) or does not fit a configuration of the capture. The IEEE C37.118.2-2011 text is not in docs/reference; the field layout follows the decoder's cited tables [VERIFY].

Result files: --json <file.json>, --csv <file.csv> or --out <file.json|file.csv> write every phasor of every decoded block (time, PMU, STAT, frequency, ROCOF, rectangular and polar values, and its quality verdict: Usable, InvalidData, Unsynchronised or UnreliableFrameTime) to a file, with the dropped counts in the header fields (Result files).

pmu-estimate

gridsim pmu-estimate <case> --measurements <set.json> [--json <file>] [--csv <file>] [--out <file.json|file.csv>]

The linear PMU state estimate (1.95.245). Reads a gridsim-measurements/1 set (for example one pmu-ingest --channels ... --measurements-dir wrote) against the case and pairs its polar phasor rows into rectangular phasors: a bus's VmPu and VaDeg rows make its voltage phasor, and a branch's IMagPu and IAngDeg rows metered at the From end make its current phasor. Each pair is weighted by its exact first-order error covariance (the magnitude sigma in pu and the angle sigma in degrees, carried through the polar to rectangular transform at the measured value). Because both phasor kinds are linear in the rectangular bus voltages, the estimate is one non-iterative weighted least-squares solve (no flat start, no iterations, no convergence test).

Prints the phasors used, every row not used with its reason (power and flow rows, and a magnitude or angle without its partner: listed, never dropped silently), the objective J = sum (r / sigma)^2 with its degrees of freedom, and each bus's |V| and angle. There is no bad-data test (use estimate for chi-square and bad-data handling). The result writer's tables are buses (bus_id, vm_pu, va_deg) and not_used (row), with the counts and J in the summary.

Refused: two rows of one kind at one place (which to pair is ambiguous), a current metered at the To end, and a phasor of magnitude 0 (exit 1); a set that fails validation against the case, or holds no phasor at all (exit 1); a set newer than the horizon (REJECTED (forward inference), exit 2).

Flag Default Meaning
--measurements <set.json> (required) The gridsim-measurements/1 set.
--json, --csv, --out - The shared result writer (Result files).

Exit codes: 0 estimated; 1 a case or set that cannot be read, fails validation or holds no phasor; 2 usage, or a set newer than the horizon; 3 not observable (the phasors do not determine every bus voltage: the gain matrix is singular).

estimate

gridsim estimate <case> (--measurements <m.json> | --synth) [flags]

The measurement-based WLS state estimator. <case> is a built-in name, a .m file under data/matpower/, or a JSON case directory (anything with a system.json, so gb-spine and gb-full materialisations estimate directly). See ch. 21, State estimation for the workflow.

Flag Default Meaning
--measurements - A gridsim-measurements/1 file. It must carry takenUtc, an instant older than the 169 h horizon: an undated set, or one newer than the horizon, is refused with REJECTED (forward inference): ... and exit 2.
--synth - Solve the case as ground truth, sample a deterministic noisy set, and score the estimate against it. With --measurements it exits 2.
--seed 20260713 Synthetic sampler seed.
--noise 1.0 Noise scale multiplier.
--coverage-vm / --coverage-inj / --coverage-flow 1.0 / 1.0 / 1.0 Fraction of each measurement class sampled.
--method wls wls, huber, lav (least absolute values solved exactly by successive linear programming, N331 / N356; dense, refused above 2,000 states; prints the LAV objective sum |r| / sigma and no chi-square verdict, with a NOTE saying why), lav-lp (alias of lav, identical output), lav-irls (least absolute values by IRLS, the pre-N356 lav: an approximation, its weights do not settle and every run prints a NOTE saying so), schweppe-gm (alias gm: Schweppe-Huber generalised M on the leverage-normalised residual), qr (orthogonal Householder QR; dense, refused above 3,000 buses), constrained or feasible (alias constrained-physics). Any other value exits 2.
--prior flat flat keeps the set's voltage-schedule rows; solve solves the measured-injection power flow, replaces the set's pseudo-voltage-schedule rows (if any; the line says how many) with the solved profile and warm-starts from it.
--warm-start off Warm-start from the case's own solved operating point (needed for real data).
--phaseangle - One or more space-separated BUS:ANGLE:UTC:FREQ per-bus voltage-angle observations (angle in degrees, UTC in ISO-8601 Z form, frequency in Hz), authored as VaDeg rows and merged before the prior. Genuine per-bus angle differences directly observe the estimator's weakest directions; a common-mode system angle cancels against the slack (used only as a reference frame).
--phaseangle-ref auto auto re-references to the slack via a datum bus and time-projects via frequency; referenced projects only (subtracts --phaseangle-from-gda's common-mode); raw injects as given.
--phaseangle-sigma 2.0 1-sigma of each authored angle row, degrees.
--phaseangle-at set instant Common instant the angles are projected to; defaults to the set's takenUtc. ISO 8601 only, read with the invariant culture: yyyy-MM-dd, yyyy-MM-ddTHH:mm, yyyy-MM-ddTHH:mm:ss or with one to seven fraction digits, each with Z, an offset +HH:mm, or nothing (UTC). Any other shape (01/02/2100, 2 Jan 2100, a space for T) exits 2. The UTC part of each --phaseangle tuple follows the same rule.
--phaseangle-from-gda - GDA v1 lake root: read PHASEANGLE_INFERED (the system COI angle and true frequency/RoCoF) at the target instant and use it as the absolute reference frame / common-mode de-rotation.
--tol 1e-8 Convergence tolerance on the state update.
--max-iter 30 Iteration cap.
--no-bad-data off Skip bad-data detection: no chi-square test and no removal. The consistency line reads not tested (chi-square not run: --no-bad-data; J = ...).
--hti off Use Hypothesis-Testing Identification as the bad-data method instead of sequential largest-normalised-residual (LNR) removal: when chi-square fails, every suspect (normalised residual above 3) has its gross error estimated jointly and is removed only if its test statistic exceeds 3; repeat until chi-square passes, nothing is identified, or 20 removals. Separates interacting errors that LNR can mis-attribute. Dense: refused above 2,000 states. Applies to wls, qr, constrained and feasible; refused (exit 2) with the robust methods (huber, lav, lav-lp, lav-irls, schweppe-gm, which down-weight or fit instead of removing), with --backfill-removals and with --no-bad-data. Removals are printed and written to hti-removals.csv (pass, measurement, estimated error, test statistic); the pass counts from 0 (pass 0 is the first estimate), as the LNR loop, the estimate trace and hti-corrections.csv count (N256; it used to count from 1). The estimated error is labelled with its unit per row: columns estimated_error (internal units) and estimated_error_unit (pu for voltage and current magnitudes, rad for angles, pu_base_mva for powers and flows), then estimated_error_measured and measured_unit (the same error in pu, deg, MW or Mvar); the console prints the internal unit and, for angles and powers, the measurement-unit value in brackets; the export's removed list (LNR removals) is empty under --hti. Under constrained and feasible a virtual-zero-injection row is a hard constraint and is never removed.
--hti-correct off With --hti: correct each identified measurement in place instead of removing it, z <- z - e^ (its jointly estimated gross error, converted to the measurement's own units), keeping the row so observability is preserved; then re-estimate and re-run chi-square. A row identified again after its correction (the correction did not clear it) is removed. Corrections and removals together are capped at 20. Corrections are printed and written to hti-corrections.csv (pass, measurement, original and corrected value, estimated error with the same four unit-labelled columns as hti-removals.csv, test statistic). Without --hti it is a usage error (exit 2). The design is robust-gm-leverage.md section 6.2; there the default action is to correct, here removal stays the default.
--fdia-screen off Screen the final estimate for a residual-cloaked false-data injection: chi-square PASSED yet the state is physically impossible or outside the operational envelope (voltage band, thermal rating, generator Q capability). A limit breach counts only when it exceeds three times the estimate's uncertainty for that quantity (the sigma of the meter that measures it); smaller breaches are listed as not counted. Prints the verdict (suspected, clear, chi-square-failed or no-verdict) and writes fdia-screen.json. A suspected or no-verdict result exits 3 (see below). Refused (exit 2) with --no-bad-data.
--backfill-removals off Replace each removed measurement with a loose prior-evaluated pseudo (observability restoration). Needs a prior: refused (exit 2) without --prior solve or --warm-start, whose absence would make the flat start the prior.
--lean off Skip residual-covariance solves when chi-square already passed (backfill throughput switch; normalised residuals become NaN).
--trace off Capture the per-iteration convergence path into the export.
--export-solve off Also project the estimate into a gridsim-solve-export/1 document (estimated-solve-export.json), the estimated-state lake feed.
--out results/estimate-<case> Output directory (estimate-export.json, residuals.csv, measurements.json when synthetic).

The summary header names the method (=== Huber M-estimator state estimate: case14 ===), and a robust method whose reweighting stopped at its cap prints a WARNING line (IrlsCapReached); the same flag is written to estimate-export.json as estimate.irlsCapReached (always present, false for the non-robust methods) and, only when it is true, to the --audit-log outcome as irls_cap_reached=true.

Exit 0 only when the estimate converged and the network is observable; 3 otherwise, and also when --hti cannot identify the bad data because the suspect block is singular; 1 for load errors, an invalid measurement set or a ground-truth solve that does not converge; 2 for usage and flag errors, forward-inference rejections and a dense method (qr, constrained, feasible) refused above 3,000 buses. A chi-square failure on its own does not change the exit code (bad data is reported, not a run failure). With --fdia-screen, a suspected verdict, or a screen that has no verdict (estimate not converged, or no redundancy so chi-square never ran), exits 3: the screen was asked for and the estimate failed it or could not be judged. clear and chi-square-failed leave the exit code as above.

estimate-noise-floor

gridsim estimate-noise-floor <estimate-export.json|dir> [<estimate-export.json|dir> ...] [flags]

The measurement noise-floor study. Reads the residual tables of one or many estimate-export.json files written by estimate (a directory is searched recursively for files of that name), pools the normalised residuals by (source tag, measurement kind) and reports, per class, the scale factor k = true noise / declared sigma (robust median-based and std-based), a shape check (bias), the suggested sigma rescaling and whether the class is miscalibrated. Run it over many timestamps: a single snapshot rarely has enough samples per class. Exports of non-converged estimates are skipped with a warning; NaN normalised residuals (critical measurements, --lean runs) are counted and skipped. Put the paths before any flags.

Flag Default Meaning
--miscal-tol 0.25 Flag a class whose robust k leaves [1 - tol, 1 + tol] or whose bias exceeds tol; above 0.
--min-samples 8 Classes with fewer finite samples are reported but never flagged; at least 1.
--out results/estimate-noise-floor Output directory (noise-floor.csv, run-metadata.json).

A study, not a gate: exit 0 whenever a report is produced, miscalibrated classes included (they are the finding). Exit 1 for an unreadable or wrong-schema file, a path with no export, or a corpus with no usable (finite, converged) residual; exit 2 for no path or a bad flag value.

crossval

gridsim crossval <case|case-dir|solve-export.json> [--tol F] [--out <dir>]

An existing solve-export.json is diffed as it is: one written by another verb at the everyday 1e-8 pu carries that solve's own residual and will not agree to machine epsilon for that reason alone (the sidecar says so when its final mismatch is above 1e-10 pu).

Solve a case (or take an existing export), then hand it to the pandapower sidecar (tools/crossval/crossval.py, shipped beside the executable in a build and in a release, found there first, then in the source tree the build came from; never in the current folder) for an independent re-solve and diff. Requires Python with pandapower. The interpreter is chosen in this order, and the verb prints the one it used ([crossval] Python: <path> (from <source>)): GRIDSIM_PYTHON when set (a full path, or a name looked up on PATH; if it names nothing the verb exits 1 and runs no other interpreter); else the active virtual environment's own interpreter (VIRTUAL_ENV); else the first python (then python3) found on PATH, folder by folder in PATH order; else the py launcher (Windows); else the bare names. Voltage-dependent (ZIP) loads in the export are given to pandapower as its own ZIP load model. See ch. 27, Validation tools.

The comparison is held to machine epsilon (N243, October 2026). After GridSim's ordinary solve (1e-8 pu) converges, the verb solves the same case afresh at 1e-9, 1e-10, ... 1e-15 pu with the same engine and options and exports the tightest one that converges; it prints [crossval] solve tolerance <T> pu (... final mismatch <M> pu). (Newton stops with a residual just under its tolerance, and the state carries about J^-1 times that residual: up to 1e-9 pu at 1e-8. That is a convergence setting, not an error.) The sidecar gives pandapower the same problem: generators aggregated per bus as GridSim holds them (summed P, Q and reactive limits, the last unit's voltage setpoint), transformer charging as bus shunts, transformers written high-voltage end first, pandapower's pi transformer model, Q limits on, no distributed slack, and pandapower's own tolerance ladder. It checks that the admittance matrix pandapower solved equals MATPOWER's makeYbus on the exported rows to 4096 machine epsilons of the largest entry, and stops with no verdict (sidecar exit 4, verb exit 3) when it does not. The summary prints both differences in full precision (|V| in pu, the angle in rad and deg), the tolerance applied and, when one applies, the case's documented allowance (gb-network-2224 only: a floating-point floor, see ch. 27).

Flag Default Meaning
--tol 4096 machine epsilons (9.09e-13) Agreement tolerance, applied to the voltage magnitude in pu and to the angle in radians. Without the flag the sidecar's default applies; a negative value exits 2.
--out results/crossval-<name> Output directory (solve-export.json, crossval-diff.json).
--tool pandapower The cross-validation sidecar. pandapower is the only one; any other value exits 2.

Exit 0 when the two solves agree; 3 on a mismatch or a sidecar validation failure; 77 when the environment cannot run the check (no Python, or no NumPy / pandapower in the interpreter used); 2 for a missing argument; 1 for a case that does not load, or a GRIDSIM_PYTHON that names nothing. The sidecar's own exit 1 means "out of tolerance", so a sidecar that crashes (a Python traceback, which also exits 1) is reported as a comparison failure, exit 3, with the sidecar's error text on stderr.

Real-time and telemetry verbs

Both verbs keep to the forward-inference horizon: a measurement window newer than 169 h before now is never estimated. See ch. 25, Interposing live telemetry.

serve

gridsim serve <case> --measurements-dir <dir> [--method wls|ekf|ukf|enkf] [--utc-now <iso8601>] [--max-windows N]

Run the real-time estimator as a resident stream over a directory of gridsim-measurements/1 files, taken in file-name order. Each window is loaded against the horizon (the clock, or --utc-now): a window inside the horizon is skipped, never estimated, and counted as rejected-fresh; an undated window (no takenUtc) stops the run with REJECTED (forward inference): ..., exit 2. Each estimated window prints its sequence, state time and status; a converged (wls) or finite (ekf, ukf, enkf) window line ends with its largest 1-sigma bound, max-sigma |V|=<pu> pu angle=<deg> deg (sigma=n/a when the WLS state covariance was not computed, above 2,000 states). Ends with a processed / converged / rejected-fresh / failed summary, then the state of the last converged or finite window, one row per bus: | bus | |V| pu | sigma |V| pu | angle deg | sigma angle deg | under a heading estimated state at window #N (<time>), wls: (filtered state ... for the recursive filters). <case> is a built-in name, a .m file or a JSON case directory, given positionally (Case arguments). With --audit-log the run is recorded (the case, the window folder's hash, the summary and the state time of the newest estimated window).

Flag Default Meaning
--measurements-dir required Directory of *.json measurement windows.
--method wls wls (static WLS per window), or a recursive tracking estimator: ekf (extended Kalman, information form), ukf (unscented Kalman, derivative-free sigma points) or enkf (ensemble Kalman, 80 members, fixed seed so runs repeat). Any other value exits 2. The recursive filters are dense: all three refuse a case above 2,500 states, and ukf and enkf also refuse a window with more than 2,500 measurements (they invert an m x m innovation covariance every window); each refusal exits 2 with the reason.
--utc-now the clock The now the horizon is measured from, for a reproducible run. It may only be EARLIER than the real clock (a stricter horizon): a later one would let recent data through and is refused with REJECTED (forward inference): --utc-now ... is later than the real clock ..., exit 2, before any window is read. ISO 8601 only, as for estimate --phaseangle-at (01/02/2100 and other shapes exit 2).
--max-windows all Process at most N windows (the first N by file name). N must be at least 1: 0 or a negative count exits 2 naming the flag.

Exit 2 on missing arguments, a bad --method, --utc-now (malformed, or later than the real clock) or --max-windows (below 1), a filter size refusal, or a forward-inference rejection (an undated window); exit 1 if the case does not load or the directory holds no *.json windows; exit 3 if any window failed, or if no window produced a usable estimate (none converged: every window unobservable or not converged, or every window inside the horizon), with the reason on stderr. A window file that cannot be loaded (not JSON, not a measurement set) is named on stderr and skipped, as the web feed does, and the other windows run; the run then ends with exit 1 (an input error, ahead of any exit 3). An estimate the output guard refuses as newer than the horizon gives REJECTED (output guard) and exit 2.

interpose

gridsim interpose [<case>] --protocol <name> (--listen host:port | --port N) --crosswalk <map.json> [flags] gridsim interpose --list-protocols

The RTU/SCADA interposer: receive live protocol frames, validate and correct each frame, decode it to typed points, map the points through the crosswalk, and emit gridsim-measurements/1 windows. Each window is judged against the 169 h horizon (real clock) when it is flushed. Only a window older than that (a replayed, recorded capture) is written to --measurements-dir. A window newer than that (live telemetry) is held: never written to --measurements-dir (the first one is named on stderr, the rest counted), and kept only as a quarantine capture when --out-store is given (its Note says so). Stops on a key press, after --ticks N frames (the global switch; N is at least 1), or after --live-seconds S of listening, whichever comes first. Ends with accepted / rejected / decode-error / map-error / point / window / duplicate-name / client-reset counts (after points, which counts every decoded point, step-positions and bitstrings count those two kinds among them, N346), the IEC 104 ASDU types received but not decoded (unsupported-type-ids), the held-fresh and quarantined window counts, and discarded-bytes (octets thrown away without being part of a frame: junk skipped while resynchronising, and a partial frame left when a client went away; N230). A client that closes or resets its connection is dropped and the next one accepted. A window file never overwrites another: a clash is kept as <name>-dupN.json.

A malformed frame (rejected by frame correction, or framed but undecodable) is named once on stderr when the first one arrives (WARNING: interpose: malformed ...); later ones are counted (rejected, decode-errors). Any malformed frame makes the run exit 1 at its end, unless --tolerate-malformed is given (N230).

For IEC 104 the interposer is the controlling station and drives the link (N230): on each connection it sends STARTDT act (and records STARTDT con), answers TESTFR act with TESTFR con, acknowledges received I-frames with an S-frame at the latest after w = 8 of them or t2 = 10 s after the first unacknowledged one, and sends TESTFR act after t3 = 20 s with no frame received (IEC 60870-5-104 clause 5 defaults [VERIFY]). A STARTDT act or TESTFR act not confirmed within t1 = 15 s, or an I-frame out of sequence (its N(S) is not V(R)), closes the connection; the next outstation connection starts afresh (GR-803, GR-823). k and STOPDT are not implemented. Modbus TCP is received passively, as before.

IEC 104 decodes the monitor types 1, 3, 5, 7, 9, 11, 13, 15, 30 to 37 (N337: step position 5 / 32 and bitstring 7 / 33 are decoded, no longer counted unsupported). A step position (a tap position, -64 to +63; a moving tap is flagged transient) and a 32-bit bitstring are points but not electrical measurements: they never enter a window, and a crosswalk that binds one of their addresses is refused as a map error.

Flag Default Meaning
--protocol required iec104 (default port 2404) or modbus (default port 502). --list-protocols prints the registry and exits. DNP3 and IEC 61850 GOOSE are not selectable: they exist only as link-framing scaffolding with no application layer, and the registry listing says so.
--listen 0.0.0.0:<default port> Endpoint host:port, [IPv6]:port or a bare port; the port is 0 to 65535 (exit 2 otherwise).
--port protocol default Port on all interfaces, when --listen is absent.
--crosswalk required Point map (.json) from protocol addresses to measurements.
<case> the crosswalk's case, else rtu Case label for the windows (the case is not loaded).
--measurements-dir - Write each window older than the horizon as a JSON file here. A window newer than the horizon is not written (held); a run that held any exits 2 (see below).
--out-store - Also write windows to the quarantine Parquet store (refuses to open inside the GDA public lake). Windows newer than the horizon go here only, as quarantine captures.
--source-id rtu_live Source id for the quarantine store.
--window-ms 1000 Window length (ms); at least 1.
--monitor off Decode to the console only; no windows written. Refused (exit 2) with --measurements-dir or --out-store.
--no-parquet off Accepted; reserved, no effect.
--tolerate-malformed off Exit 0 even when frames were rejected or undecodable (N230); the warning and the counts still report them.
--live-seconds no limit Stop after S seconds of listening (above 0, at most 86400; N230), whatever has arrived. With --ticks N, stopping on time with fewer than N frames is exit 1 (after the summary); without --ticks, a run that received no frame at all says so on stderr.

With neither --measurements-dir nor --out-store it decodes only. Exit 2 on a missing or unknown protocol, a missing --crosswalk, --monitor with a sink, or a bad --live-seconds; exit 1 if the crosswalk, the store or the transport cannot be opened (the crosswalk load also refuses a 32-bit binding on register 65535 or one whose second register is bound separately, and an address bound more than once, naming each such address), if any frame was malformed (without --tolerate-malformed), or if --live-seconds ran out short of --ticks; exit 3 if any window was discarded because a point did not fit its binding (map-errors; the listener keeps running and prints why); otherwise exit 2 with REJECTED (forward inference): N window(s) newer than the 169 h horizon were not written to --measurements-dir when --measurements-dir was given and any window was held (the listener still runs to the end and prints the summary first). A run without --measurements-dir (decode only, --monitor, or --out-store alone) holds live windows by design and does not set that exit code.

Benchmarking and preflight verbs

These verbs are used in ch. 28, Benchmarking and GPU; audit is in ch. 26.

bench

gridsim bench [--runs N] [--parallel N] [--out <path>] [--note "text"] [--cases a,b,c] [--gpu]

The solver x backend matrix over the whole case archive (embedded classics plus every .m under data/matpower/). Writes Markdown, CSV and <report>.run-metadata.json beside the report (results/benchmark-results.run-metadata.json by default), with the run's settings under parameters (Output files). GPU engines are opt-in through the global switch and skip cases above 3,000 buses: --gpu (or --gpu=auto) probes ROCm, OpenCL and CUDA, --gpu=rocm, --gpu=opencl or --gpu=cuda probes that vendor only, and --gpu=cpu adds none. A vendor asked for whose device does not answer gets a report line saying so. The CPU engines are cpu-dense (dense LU), cpu-sparse (direct sparse LU, ILU0-BiCGSTAB fallback) and bfs (radial cases only).

Each cell first runs one untimed warm-up solve of the same case on the same engine, so the mean excludes JIT compilation, GPU kernel compilation and first-touch allocation (bench --perf and bench --estimate warm up the same way). The cell's conv / iters / mismatch are those of the first timed run. A cell timed once (cases above 4,000 buses) therefore takes twice its solve time.

Every cell is run and reported whatever happens to the others; the exit code is the batch rule. Exit 1 when any case could not be loaded (a LOAD FAIL row); otherwise exit 3 when any solve did not converge (**NO**), ran out of memory or threw (OOM, ERR:); otherwise 0. n/a cells (the radial sweep on a meshed case) and GPU size skips are not failures. The failed cells are listed on stderr at the end.

Flag Default Meaning
--runs 10 Timing repeats per case (auto-reduced for big cases); at least 1.
--parallel 0 (all cores) Worker threads (GPU engines always run serially); a negative value is refused.
--out results/benchmark-results.md Report path (CSV alongside). Pass docs/developer/benchmarks/benchmark-results.md to refresh the committed copy.
--note - Free-text note stamped into the header.
--cases the whole archive Bench only these cases, a comma list of case arguments (built-in names, .m files, case folders), in the order given. A case that does not load is a LOAD FAIL row (exit 1 at the end).

bench --estimate

gridsim bench --estimate [--runs N] [--cases a,b,c] [<case-dir> ...]

Times the WLS estimator per case per step backend (dense versus sparse, forced through the sparse threshold) on a fixed-seed synthetic set; sampling and the truth solve sit outside the timed region. Extra positional JSON case directories are appended.

Flag Default Meaning
--runs 3 Timing repeats (reduced above 1,000 buses).
--cases case14,case30,case57,case118,case300 Case list.

Output: results/bench-estimate/bench-estimate.csv plus a console table. Dense is skipped above 1,500 buses. Exit 1 when a case could not be loaded ([skip]); otherwise exit 3 when a truth solve or an estimate did not converge; otherwise 0. The failures are listed on stderr at the end.

bench --perf

gridsim bench --perf [--runs N] [--out <path>] [--note "text"]

The focused before/after yardstick for the performance programme: single-threaded, warmed once, median of N runs, with managed allocations per run on the measuring thread. Rows: sparse Newton-Raphson end to end (case118, case300), the three-phase fault study (case300), the OLTC outer loop (case118) and the many-order harmonic scan (case118). Writes Markdown and CSV keyed by commit.

Flag Default Meaning
--runs 20 Timed repeats (minimum 1).
--out results/perf-baseline.md Report path (CSV alongside). Pass docs/developer/benchmarks/perf-baseline.md to refresh the committed copy.
--note - Free-text note stamped into the header.

gpucheck

gridsim gpucheck

Fail-fast GPU preflight: reports CPU, ROCm, OpenCL and CUDA availability and runs one tiny case9 solve (dense and sparse) on each present backend, flushing every step so a crash names the failing call. No flags. Exit 3 when any probe that ran failed (a FAIL line, or a solve that ran but did not converge), listed on stderr; a backend that is not present is skipped, not failed, so a machine with no GPU exits 0 (gpucheck: OK - every probe that ran passed). See ch. 27, Validation tools.

simdcheck

gridsim simdcheck [--expect <tier>]

Report the CPU's vector capabilities and the active tier (Avx512, Avx256, Sse128 or Scalar, with the number of doubles per vector step) that the dense-LU, normal-equations and covariance kernels dispatch to at run time. When the CPU supports AVX-512F but the active tier is narrower (the .NET default on Skylake-SP and Cascade Lake Xeons), it prints a warning naming the fix: set DOTNET_PreferredVectorBitWidth=512 before start-up.

Flag Default Meaning
--expect - Gate mode: exit 3 when the active tier is narrower than the given one (Avx512, Avx256, Sse128, Scalar; case-insensitive). Any other value exits 2. Use it in CI on a box that should run 8-wide.

audit

gridsim audit verify <file> [--anchor-count N --anchor-head HEX] [--pubkey <public.pem> [--anchor <file>] [--sig <file>]] gridsim audit show <file> [--anchor-count N --anchor-head HEX] gridsim audit sign <file> --key <private.pem> [--anchor <file>] [--sig <file>] gridsim audit keygen <private.pem> <public.pem>

Verify a tamper-evident audit log (gridsim-audit/1, technical ch. 31): recompute the hash chain line by line. Prints OK <file>: N entries, head H and exits 0 when it verifies; prints TAMPERED <file>: entry i: <reason> and exits 3 at the first edited, deleted, inserted, reordered or truncated entry; exits 1 when the file is missing or unreadable and 2 on a usage error. Tail truncation and a whole-log rewrite keep a self-consistent chain, so they are caught only against an anchor kept outside the log: pass the entry count and head hash from an earlier verify, from the audit: line a run printed, or from the log's anchor file (gridsim-audit-anchor/1 count=N head=H, see --audit-anchor). The audited verbs and the web host also check the anchor file themselves before they append.

show runs the same verification and, only when the whole log verifies, first prints every entry, one per line, as #<seq> run=<UTC> state=<UTC or -> provenance=<tag> hash=<hash> <summary> (the summary is the recorded actor=... action=... inputs=... outcome=... text), then the same OK line. A log that does not verify prints no entries at all, only the TAMPERED line, and exits 3: nothing after a broken link can be trusted. Exit codes are as for verify.

Flag Default Meaning
--anchor-count - The entry count of a trusted earlier state (with --anchor-head; one without the other exits 2, and a negative count exits 2).
--anchor-head - The head hash of that state (with --anchor-count).
--pubkey - verify only: an ECDSA P-256 public key (PEM). The signature file over the anchor file must exist and verify (TAMPERED, exit 3, otherwise), then the log is verified against that anchor. Does not combine with --anchor-count / --anchor-head (exit 2).
--anchor / --sig <log>.anchor / <log>.anchor.sig verify --pubkey and sign: the anchor file and its detached signature file.
--key - sign only: the ECDSA P-256 private key (PEM). sign verifies the log against its anchor first and signs nothing when it does not verify (exit 3).

keygen writes a fresh P-256 key pair (the private key for the signing station, the public key for the host) and refuses to overwrite an existing file (exit 1).

compliance

gridsim compliance verify

Print this build's compliance attestation and exit 0 when the build is compliant, 1 when it is not. The attestation binds the build identity (the release version, the git commit, and a deterministic build hash) to the compliance manifest (the inventory of controls the build provides, each tied to the test or artefact that evidences it), reports the SBOM hash a release build was produced against (unset on a local build), and states how many of the controls GridSim owns are Achieved. A release build is compliant only when every in-scope control is Achieved and its evidencing test is green, so a non-compliant build cannot truthfully attest compliance. Needs no licence and makes no network call, so a reviewer can always ask a binary to attest itself. show is an accepted alias of verify; any other subcommand exits 2. See technical ch. 31.

batchsolve

gridsim batchsolve [--count N] [--n M] [--runs K] [--gpu]

Solve N same-sized MxM dense systems in one batched dispatch on the selected backend (the GPU batched Gaussian-elimination kernel on a CUDA or OpenCL device, else a parallel CPU loop over the reference LU; ROCm uses the CPU loop), then verify the result against the CPU reference and report timing. A demonstrator and micro-benchmark for the batched dense solver seam that turns a contingency sweep of many same-sized outages into a handful of batched dispatches instead of hundreds of locked single solves. A singular system is isolated (its segment returns NaN) and never fails the whole batch.

Flag Default Meaning
--count 64 Number of independent systems in the batch (N); values below 1 are raised to 1.
--n 64 Dimension M of each dense MxM system; values below 1 are raised to 1.
--runs 5 Timing repeats (median reported); values below 1 are raised to 1.
--gpu off Select the GPU batched backend (the global --gpu); falls back to the CPU batched reference with no device.

Exit 1 if the batched result differs from the CPU reference by more than 1e-6 or disagrees on which systems are singular; exit 2 if count x n x n exceeds the single-dispatch limit.

Electrical references

ref

gridsim ref encode <value> [--words N] [--check] gridsim ref decode <reference> [--words N] [--check] gridsim ref scatter <number|reference> --seed S [--words N] [--check] gridsim ref from-id <id> [--words N] [--check]

Electrical references: a number written as electrical words that can be read aloud and typed back, one word per byte from a fixed list of 256 (units, pioneers, materials, physics, signals and more; no switching, safety, phase, colour, asset, fuel or alarm words), most significant byte first, joined by dots: gridsim ref encode 0x3C042C prints copper.tesla.kron. Three words give 16,777,216 references, four give 4,294,967,296.

  • encode writes a value (decimal, or hexadecimal after 0x) as words; a value too large for the word count is refused.
  • decode reads a reference back and prints its value in decimal and hexadecimal. It is strict: lower case only, dots between words and nowhere else, exactly the expected number of words. An unknown word is refused with the nearest valid words by edit distance.
  • scatter maps sequential asset numbers to unrelated-looking references with no two ever the same (a keyed permutation; the same seed gives the same references on every machine). Given a number it prints the reference; given a reference it prints the number back.
  • from-id prints the reference that follows from an existing id (the leading bytes of the SHA-256 of its UTF-8 text). Different ids can share a reference; the verb does not check, so compare references across a set of ids before relying on them.
Flag Default Meaning
--words 3 Data words (1 to 8; 2 to 4 for scatter).
--check off Append (on decode: expect and verify) a check word, the CRC-8/SAE-J1850 of the data bytes, which catches any single wrong word and any swap of two neighbouring words.
--seed none The key of the scatter arrangement (decimal, or hexadecimal after 0x); required by scatter.

Needs no case, no licence and no network. Exit 1 when a reference is refused (the reason is printed); exit 2 on a usage error (unknown subcommand or flag, missing or malformed value, value too large for the word count).

Limits

  • acopf solves the DC problem and adds a loss loop; it does not solve the full AC equations. It neither optimises nor limits bus voltages, reactive power or AC branch flows. acopf-full is the full AC optimal power flow.
  • acopf-full optimises polynomial costs only (a piecewise-linear cost is refused), keeps taps and phase shifts at their case values and does not enforce branch angle difference limits.
  • gda-replay takes no price series, so its --policy price and --policy lp exit 2.
  • cycle --pipeline and modal --include-soc are not implemented and exit 2.
  • interpose selects iec104 and modbus only; DNP3 and IEC 61850 GOOSE exist as link-framing scaffolding with no application layer (R089).
  • stability, modal and impedance-stability use the Anderson-Fouad X'd on case9 and a synthetic 0.30 pu on every other case, flagged INDICATIVE. modal refuses MATPOWER cases because they carry no inertia constants.
  • inertia-placement uses the synthetic GENROU machines with the field and the mechanical power held (no AVR, no governor) and models a loss as a constant-admittance load step; its answers are INDICATIVE in the same way.