17. Protection assessment (a passive relay overlay)

This chapter specifies the passive protection overlay: a library of relay elements that read a solved state and report which of them would operate and why, without altering the solve. It covers the registry of relay functions and the equation and settings of each, the operating quantities every relay reads, the balanced and unbalanced fault studies that give the overlay a real fault to judge, the cascade simulation that follows a trip through the network, the sequence-of-events cross-reference against a real alarm log, and the protection-check and fault verbs that expose them.

The overlay is read-only. It never calls the power-flow solver on the caller's model, never mutates the model or the result, and is a pure function of its inputs, so the same state and settings give the same verdicts on every run. The operating quantities (voltages, currents, loadings, apparent impedances, busbar residuals) always come from the solved state. The pickups they are compared against are generic standard-practice values, each graded (ProtectionConfidence):

Grade Meaning Elements
Grounded A statutory or grid-code GB value. 81U, 81O, 81R
Generic A standard-practice default that a real scheme would grade per site. 27, 59, 32, 37, 49, 50, 51, 21, 78, 87, 50N, 51N, 21N, 46
NotCheckable The element needs data the state does not carry; the verdict says so and never operates. 81R and 78 without a trajectory; the earth and negative-sequence group without an unbalanced study

This is a screening tool, not a certified protection study: relay settings are site-specific and are not public. The scope boundary with neighbouring chapters is fixed. The protection stages of an asset that act during a simulation and change the trajectory (infeed trip, load shed, branch opening) are ch. 15, Protections. The IEC 60909 short-circuit duty (Ik'', ip, Ib, Ith, the breaker adequacy check) is ch. 25, Short-circuit IEC 60909. The grading of inverse-time relay chains (gridsim grade, the curve table, the coordination time interval) is ch. 26, Overcurrent coordination. This chapter uses their results and does not repeat them.

Model

Assessment entry points

ProtectionAssessment (src/GridSim.Core/Protection/ProtectionAssessment.cs) has three entry points.

Entry point What it does
Assess(model, result, settings?, trajectory?, faultCurrentPuByBus?, sequence?) Requires a converged result, builds one ProtectionContext, runs every relay in ProtectionRegistry.All over it and returns a ProtectionReport.
AssessThreePhaseFault(model, prefault, faultBusId, faultReactancePu = 0, settings?) Requires a converged prefault state, runs FaultAnalysis.ThreePhase, then Assess on the faulted state with the fault current passed to the busbar differential. Returns the FaultResult and the report.
AssessUnbalancedFault(model, prefault, faultBusId, type, faultReactancePu = 0, settings?) The same for FaultAnalysis.Unbalanced: Assess runs on the faulted positive-sequence state with the UnbalancedFaultResult as the sequence argument, and the busbar differential sees the largest phase fault current at the faulted bus.

Every entry point starts with ConvergenceContract.RequireConverged (src/GridSim.Core/PowerFlow/ConvergenceContract.cs), which throws NonConvergedStateException naming the study (Protection assessment, Protection assessment (fault), Fault analysis, Protection cascade), the status, the mismatch and the iteration count. A non-converged state never gets a verdict.

ProtectionReport holds Verdicts (every relay's output), Settings (the settings used), HadTrajectory, and three views: Operating (the verdicts with Operate = true: timed elements first, fastest first; then the untimed ones, largest margin relative to the pickup (ProtectionReport.RelativeMargin, the margin over |Pickup|, or the raw margin when the pickup is zero or not finite) first; ties keep the verdict row order), AnyOperate and OperatingByFunction (a count per function name). PrimaryClearance is the element that clears the fault first: an operating busbar differential (87) when there is one, otherwise the first operating branch element with an operating time (49, 50, 51, the 21 zones, 50N, 51N, the 21N zones, 46), and null when neither operates.

RelayVerdict

Every relay returns RelayVerdict records:

Field Meaning
Device ANSI device number as shown, for example 27, 51, 21-Z2, 21N-Z3.
Function Human name, for example Undervoltage.
LocationKind, LocationId, LocationName Bus (bus id), Branch (branch index in Model.Branches, equal to the LineFlow index), Generator (generator index) or System (-1, system).
Operate Whether the element picks up.
Quantity, Unit The operating quantity and its unit (pu, xRateA, xIn, MW, Hz, Hz/s, deg, and - for the not-checkable ground verdict, whose quantity and pickup are NaN).
Pickup The setting the quantity is compared against.
Margin Signed distance past pickup in the quantity's own unit; positive once operated.
TimeToTripS Operating time in seconds where the element has a curve or a definite time; 0.0 for instantaneous; null where there is none.
Basis The plain-language sentence, for example Vm 0.000 pu at bus 7 is below the 0.80 pu undervoltage pickup.
Confidence The grade above.

A relay that scans many locations (every bus, every branch) emits every operating verdict plus the single closest non-operating one (VerdictCollector: the non-operating verdict with the largest, least negative, margin), so a report can say both where an element fires and how near the next location is to firing. 81U, 81O, 81R and 78 are system elements and return one System verdict each. The ground group returns one System verdict when there is no sequence study, and the collector pattern per branch when there is one; each of these has one System verdict.

The operating quantities

ProtectionContext (src/GridSim.Core/Protection/ProtectionContext.cs) computes each quantity once from the result and the model. All are positive-sequence phasor values in per unit on GridModel.BaseMva.

Vm[i]            = result.Vm[i]                                         per bus
S_from, S_to     = sqrt(P^2 + Q^2) at each end, from LineFlow, MVA
IFromPu[l]       = (S_from / BaseMva) / Vm_from      (0 if Vm_from <= 1e-9)
IToPu[l]         = (S_to   / BaseMva) / Vm_to        (0 if Vm_to   <= 1e-9)
IRatedPu[l]      = RatingMva / BaseMva               (0 if RatingMva <= 0)
LoadingFraction  = max(S_from, S_to) / RatingMva     (0 if unrated)
ZAppFrom[l]      = Vm_from^2 / conj(P_from + jQ_from)   in pu on BaseMva
ZAppTo[l]        = Vm_to^2   / conj(P_to   + jQ_to)
                   (infinite if |S| <= 1e-12 pu: no measurable flow)
ZLine[l]         = R + jX of the branch (series impedance, pu)

LineFlow records the power flowing into the branch at each end, so each ZApp is what the relay at that end sees looking into the line. The thermal loading is taken on the heavier end, the same max(|S_from|, |S_to|) / RateA that LineFlow.LoadingPercent carries on solver results and on the faulted state FaultAnalysis.FaultedFlows returns (the context forms its own loading from both ends in any case), so no verdict depends on which way round a branch is stored. A line flow that matches no branch of the model (a result solved on a different model) throws InvalidOperationException naming the flow; the context never borrows the impedance of another branch.

The busbar differential quantity is the Kirchhoff current residual at each bus, with the bus shunt netted off so a capacitor bank does not read as a fault:

netP[i] = PInj[i]/BaseMva - Gs[i]/BaseMva * Vm[i]^2
netQ[i] = QInj[i]/BaseMva + Bs[i]/BaseMva * Vm[i]^2
for each LineFlow: netP[from] -= P_from/BaseMva;  netQ[from] -= Q_from/BaseMva
                   netP[to]   -= P_to/BaseMva;    netQ[to]   -= Q_to/BaseMva
DiffCurrentPu[i] = sqrt(netP^2 + netQ^2) / Vm[i]       (no division if Vm <= 1e-9)

On a converged solve this is rounding error. When a fault study supplies faultCurrentPuByBus, the faulted bus takes max(DiffCurrentPu[i], If), because a fault inside a bus zone is a current path the relay sees as the sum of its circuit currents and that the nodal balance does not contain.

The per-branch settings are resolved through ProtectionContext.SettingsFor(branchIndex): the record in ProtectionSettings.PerAsset whose key is the branch's LineFlow.Name, else the generic settings. A branch with an empty name always gets the generic settings. Elements 49, 50, 51, 21, 50N, 51N, 46 and 21N read the branch's own settings; 27, 59, 32, 37, 81x, 78 and 87 read the generic ones.

The registry

ProtectionRegistry.All (src/GridSim.Core/Protection/ProtectionRelays.cs) runs the relays in this order. The order is the order of verdicts in ProtectionReport.Verdicts.

# Class Device Function Location Operating quantity Operates when
1 UnderVoltageRelay 27 Undervoltage each bus lowest phase voltage VmPhaseMinPu (equal to Vm without a sequence study), pu vm < UnderVoltagePu
2 OverVoltageRelay 59 Overvoltage each bus highest phase voltage VmPhaseMaxPu, pu vm > OverVoltagePu
3 DirectionalPowerRelay 32 Reverse power each generator the generator's scheduled Pg, MW Pg < -ReversePowerMw
4 UnderCurrentRelay 37 Undercurrent each branch max(IFromPu, IToPu), pu i < UnderCurrentFloorPu
5 ThermalOverloadRelay 49 Thermal overload each rated branch LoadingFraction, xRateA L > ThermalPickupFraction
6 InstantaneousOvercurrentRelay 50 Instantaneous overcurrent each rated branch max(IFromPu, IToPu) / IRatedPu, xIn m > InstantaneousOcMultiple
7 TimeOvercurrentRelay 51 Time overcurrent each rated branch max(IFromPu, IToPu) / IRatedPu, xIn m / TimeOcMultiple > 1
8 DistanceRelay 21, 21-Z1 to 21-Z3 Distance each line ZApp at each end, pu ZApp inside a forward zone
9 UnderFrequencyRelay 81U Underfrequency system run minimum frequency, else Model.FrequencyHz, Hz f < UnderFrequencyHz
10 OverFrequencyRelay 81O Overfrequency system run maximum frequency, else Model.FrequencyHz, Hz f > OverFrequencyHz
11 RocofRelay 81R RoCoF system trajectory peak |df/dt|, Hz/s r > RocofTripHzPerS
12 VectorShiftLomRelay 78 Vector shift / LoM system trajectory peak vector shift, deg vs > VectorShiftTripDeg
13 DifferentialRelay 87 Differential each bus DiffCurrentPu, pu d > DifferentialPickupPu
14 GroundFaultRelay 50N, 51N, 21N, 46 Ground / negative-sequence see below needs Sequence see below

The registry is not in ascending device-number order (the source comment says so and gives the grouping); the table is the order the code runs.

Rated branches are those with RatingMva > 0; 49, 50 and 51 skip an unrated branch. 21 skips a line whose series impedance magnitude is at or below DistanceRelay.MinLineImpedancePu (1e-9 pu), a bus coupler with no usable reach. 32 reads Generator.Pg of the model, the scheduled output, not a solved output.

Relay equations

27 and 59. Margin is pickup - vm for 27 and vm - pickup for 59.

32. Margin is -Pg - ReversePowerMw. The reported pickup is -ReversePowerMw.

37. The floor is an absolute current in per unit, not a fraction of rating. It detects a branch that carries essentially no current (an open-ended or de-energised circuit). It skips an out-of-service branch (which keeps a zero-flow entry) with no verdict, so a switched-out circuit does not operate it; a lightly loaded line carries a small real current and does not operate it. Margin is floor - i.

49 thermal overload. With L = LoadingFraction, P = ThermalPickupFraction, tau = ThermalTimeConstantS:

operate:  L > P
t = tau * ln(L^2 / (L^2 - P^2))          first-order thermal replica, cold start

TimeToTripS is t. The loading is the loading before the trip with no preload history: the replica starts cold.

50 instantaneous overcurrent.

m = max(IFromPu, IToPu) / IRatedPu
operate:  m > InstantaneousOcMultiple        TimeToTripS = 0.0 (printed "inst")

51 time overcurrent. The IEC 60255 standard-inverse curve with its argument M the current as a multiple of the pickup setting, not of the rated current:

m = max(IFromPu, IToPu) / IRatedPu
M = m / TimeOcMultiple
operate:  M > 1
t = TimeOcTms * 0.14 / (M^0.02 - 1)

The constants k = 0.14 and alpha = 0.02 come from the shared curve table OvercurrentCoordination.IecConstants(OvercurrentCurve.IecStandardInverse) (src/GridSim.Core/Protection/Coordination/), the table ch. 26 owns. Margin is m - TimeOcMultiple. The time tends to infinity as M tends to 1.

21 distance. Each line carries a relay at both ends. For one end:

angle test:  |angle(ZApp) - angle(ZLine)| <= DistanceAngleWindowDeg          (forward)
zone:        forward and |ZApp| <= DistanceZone1Reach * |ZLine|   -> Zone 1, t = DistanceZone1TimeS
             else           |ZApp| <= DistanceZone2Reach * |ZLine|   -> Zone 2, t = DistanceZone2TimeS
             else           |ZApp| <= DistanceZone3Reach * |ZLine|   -> Zone 3, t = DistanceZone3TimeS
margin:      (DistanceZone3Reach * |ZLine| - |ZApp|) / |ZLine|   if forward, else -infinity

A reverse element never operates and never wins the "closest to firing" pick. One verdict is reported per line, from the end that decides: an end that operates beats one that does not, a lower zone beats a higher zone, between two non-operating ends the larger margin wins, and a tie keeps the From end. A verdict from the To end says so in its basis (relay at the to end, bus N). The device reads 21-Z1, 21-Z2 or 21-Z3 when it operates and 21 otherwise. The reported pickup is the reach of the zone that operated, else the outer reach. Load encroachment shows as a heavily loaded line whose apparent impedance shrinks into Zone 3; the element has no load blinder.

81U, 81O. The frequency is the trajectory's minimum (81U) or maximum (81O) when a ProtectionTrajectory is supplied, else the model's nominal FrequencyHz. A steady state therefore operates 81U or 81O only if the setting is moved across the nominal frequency.

81R, 78. Without a trajectory each reports NotCheckable with margin minus infinity and never operates: a steady snapshot has no df/dt and no voltage-angle transient. With a trajectory the quantity is MaxAbsRocofHzPerS (81R) or MaxAbsVectorShiftDeg (78), compared with RocofTripHzPerS and VectorShiftTripDeg. ProtectionTrajectory(MaxAbsRocofHzPerS, MinFrequencyHz, MaxFrequencyHz, MaxAbsVectorShiftDeg = 0) is the caller-supplied summary of a dynamic run.

87 busbar differential. Margin is d - DifferentialPickupPu. On a healthy converged state the residual is rounding error and the element is secure; it operates once a fault current is injected at a bus.

The ground group (50N, 51N, 21N, 46). Over a positive-sequence state (a power flow, or the balanced fault) there is no zero- or negative-sequence quantity to measure, and the group returns one System verdict, NotCheckable, with the reason in its basis. When an UnbalancedFaultResult is supplied it evaluates four elements on the study's sequence currents. Residual current is |3 I0|, negative-sequence current is |I2|, each taken as the larger of the branch's two ends and expressed in xIn on IRatedPu:

50N  m = Ires / rated;   operate m > EarthFaultInstantaneousMultiple;  t = 0
51N  M = (Ires / rated) / EarthFaultTimeMultiple;  operate M > 1;
     t = EarthFaultTms * 0.14 / (M^0.02 - 1)                  same IEC curve as 51
46   m = max(|I2_from|, |I2_to|) / rated;  operate m > NegativeSequenceMultiple;
     t = NegativeSequenceTimeS                                definite time
21N  lines only, in service, |Z1L| > 1e-9:
       k0 = (Z0L - Z1L) / (3 Z1L)
       for each end, each phase p in {a, b, c}:  Z = V_p / (I_p + 3 k0 I0)
       zones, angle window and times as 21; the end and phase in the fastest zone decide

Z0L is the branch's R0 + jX0 when either is non-zero, else LineZeroSeqRatio * Z1L (3.0). 21N skips transformers. 50N, 51N and 46 skip unrated branches.

Unbalanced studies on the phase elements

When a sequence study is supplied the phase elements measure phase quantities, not the positive sequence alone. The phase phasors come from the sequence phasors with a = e^(j 120 deg):

Ia = I0 + I1 + I2
Ib = I0 + a^2 I1 + a I2
Ic = I0 + a I1 + a^2 I2            (voltages the same way from V0, V1, V2)

Per branch end the current is the largest of |Ia|, |Ib|, |Ic| (BranchSequenceCurrents.MaxPhaseFromPu, MaxPhaseToPu), so 37, 50 and 51 read it and 49's loading is the larger end's phase current over IRatedPu. The context also computes a from-end power Re(V1 conj(I1) + V2 conj(I2) + V0 conj(I0)) * BaseMva (ProtectionContext.PFromMw), but no shipped relay reads it; 32 reads the generator's Pg. 27 and 59 read each bus's lowest and highest phase-voltage magnitude. 21 measures the three phase-to-phase loops at each end,

Z = (Vx - Vy) / (Ix - Iy)        loops a-b, b-c, c-a      (infinite if |Ix - Iy| <= 1e-12)

and the loop in the fastest zone decides, named in the verdict ([b-c loop]). A power flow and a balanced fault are assessed with the positive-sequence quantities, unchanged. The study and the state must have been solved on the same model: a branch-count or endpoint mismatch throws InvalidOperationException.

Algorithm

The passive overlay on a solved state

Assess(model, result, settings, trajectory, faultCurrentPuByBus, sequence):
    result.RequireConverged("Protection assessment")
    s   = settings or ProtectionSettings defaults
    ctx = ProtectionContext(model, result, s, trajectory, faultCurrentPuByBus, sequence)
    verdicts = []
    for relay in ProtectionRegistry.All (order above):
        verdicts += relay.Evaluate(ctx)
    return ProtectionReport(verdicts, s, trajectory is not null)

No relay calls a solver. The assessment is a deterministic function of its arguments; it does not change them.

Fault injection: balanced three-phase

FaultAnalysis.ThreePhase(model, prefault, faultBusId, faultReactancePu = 0) (src/GridSim.Core/Protection/FaultAnalysis.cs) is the Thevenin bus-impedance superposition on the converged prefault state. It throws ArgumentException for a bus that is not in the model, and NonConvergedStateException for a non-converged prefault.

  1. Prefault voltages. V0[i] = Vm[i] e^(j VaDeg[i] pi/180), keyed to the model bus order.
  2. Fault-study admittance. The network Ybus (branch pi-models with tap and phase shift, and bus shunts) plus diagonal stamps added in this order:
  3. Each bus with Pd or Qd non-zero: a constant-impedance load, Y = conj(Sload) / max(|V0|^2, 1e-6) with Sload = (Pd + jQd) / BaseMva. The nominal load is used, not the solved voltage-dependent load.
  4. Each synchronous generator that is not PowerFlowOnly and not converter-interfaced: its source reactance, Y = 1 / (j Xsys) with Xsys = Generator.FaultSourceReactancePu(0.20) * BaseMva / MBase (MBase at or below zero means BaseMva). FaultSourceReactancePu is the machine's SubtransientXdPu when it is above zero, else the synthesised default FaultAnalysis.DefaultSubtransientXdPu (0.20 pu), plus max(0, UnitTransformerXPu). A source with Xsys at or below zero is not stamped. A PowerFlowOnly device is not a fault source.
  5. One Zbus column. FaultNetworkSystem.ForModel factors the matrix once; Zcol = Y^-1 e_k for the fault bus k. Zth = Zcol[k].
  6. Superposition, with Zf = j * faultReactancePu (a pure reactance):
If        = V0_k / (Zth_kk + Zf)
V_faulted = V0 - Zcol * If
  1. Faulted flows. Branch flows are formed from V_faulted with the same pi-model as YBus (S = V conj(Y V) * BaseMva at each end); an out-of-service branch keeps a zero-flow entry so LineFlows stays aligned with Branches. Nodal injections are Ynet * V_faulted over the unstamped network admittance, summed per row in ascending column order from the sparse cells, which is bit-for-bit the dense row sum (FaultInjectionWalkPinTests).
  2. Result. FaultResult: the faulted PowerFlowResult (Converged = true, Iterations = 0, MaxMismatch = 0, justified because the prefault was required to converge and the faulted state is a direct linear solve), FaultCurrentPu = |If|, FaultCurrentKa = |If| * BaseMva / (sqrt(3) * BaseKv) when the fault bus has BaseKv > 0 and 0 otherwise, TheveninZPu = |Zth|, DifferentialCurrentPuByBus = { k: |If| }, and the converter infeeds.

The fault admittance is factored by the sparse LU on the real 2n expansion (FaultNetworkSystem) at every size, so a 9-bus case and gb-full run the same arithmetic; the dense complex LU is a test oracle only. A singular fault network (an island with no source or earth path) fails loud with the fault-network admittance matrix is singular (an island with no source or earth path?).

Converter-interfaced units

A converter-interfaced unit (Generator.IsConverterInterfaced: an explicit ConverterInterfaced flag, else the unit's Type) has no EMF behind a reactance. It is left open in the fault admittance and enters as a current-limited injection on the grid-code fast-fault-current characteristic. Per unit, with ir = MBase / BaseMva, imax = k * ir where k is ConverterFaultCurrentPu or the default Generator.DefaultConverterFaultCurrentPu (1.2), and the prefault active and reactive currents ip0 = Pg / BaseMva / |V0|, iq0 = Qg / BaseMva / |V0|:

dip   = |V0| - |V|
q     = clamp(iq0 + K * dip * ir, -imax, imax)          K = DefaultConverterReactiveGain = 2
pRoom = sqrt(max(0, imax^2 - q^2))                       reactive priority
p     = sign(ip0) * min(|ip0|, pRoom)
I     = (p - j q) * e^(j theta)       theta = angle(V) if |V| > 1e-3, else the prefault angle

The network and the converter currents are solved as an adaptively damped fixed point on the one factorisation:

dI = I_now - I_prefault   at each converter bus
x  = Y^-1 dI
If = (V0_k + x_k) / (Zth_kk + Zf)
V  = V0 + x - Zcol * If
update:  I_now += damping * (target - I_now)       damping starts at 0.5, halves (floor 0.02) when the change grows
stop:    max change < 1e-9, or 1000 iterations

FaultResult.ConvertersConverged records the outcome, and FaultResult.Converters lists each unit's terminal voltage, current (pu and as a multiple of its rating), active and reactive split and whether it sits on its limit. A converter with k = 0 feeds no fault current.

Fault injection: unbalanced

FaultAnalysis.Unbalanced(model, prefault, faultBusId, type, faultReactancePu = 0, subtransientXdPu = 0.20, lineZeroSeqRatio = 3.0) solves the fault on three sequence networks superposed on the prefault state. FaultType.ThreePhase is refused with ArgumentException; it belongs to ThreePhase.

  • Positive sequence: the balanced study's network.
  • Negative sequence: the same passive network and loads, each unit as Generator.FaultSourceNegativeSeqReactancePu (its NegativeSeqXPu, default its X''d, plus the unit transformer), and every branch phase shift reversed.
  • Zero sequence: the IEC 60909 zero-sequence network (ShortCircuit.Iec60909.BuildZeroSequenceNetwork, specified in ch. 25): winding connections and neutral reactances, line R0/X0 or lineZeroSeqRatio * Z1, loads neglected, no line charging. Only the part of the network connected to the fault bus through zero-sequence paths carries zero-sequence current. FaultBusGrounded is true when that component reaches an earthed neutral.

With V = V0_k, driving-point impedances Z1, Z2, Z0 at the fault bus and Zf = j * faultReactancePu:

SLG  (phase a)  : I1 = I2 = I0 = V / (Z1 + Z2 + Z0 + 3 Zf)
LL   (b-c)      : I1 = -I2 = V / (Z1 + Z2 + Zf),   I0 = 0
DLG  (b-c-earth): Zg = Z0 + 3 Zf
                  I1 = V / (Z1 + Z2 Zg / (Z2 + Zg))
                  I2 = -I1 Zg / (Z2 + Zg)
                  I0 = -I1 Z2 / (Z2 + Zg)
bus voltages    : V1 = V0 - Z1col I1,   V2 = -Z2col I2,   V0seq = -Z0col I0

With no earth path in the zero sequence at the fault bus, SLG gives zero current and DLG is solved as LL. UnbalancedFaultResult carries the sequence currents, the phase-current magnitudes PhaseAPu, PhaseBPu, PhaseCPu, the earth current |3 I0|, the three driving-point impedances (Z0 infinite when ungrounded), the per-bus sequence voltages, the per-branch sequence currents (BranchSequenceCurrents) and the faulted positive-sequence state, which is what the overlay's flow quantities read. Converter-interfaced units add no fault current in this study: no negative- or zero-sequence fault behaviour is defined for them, so they keep their prefault current in all three networks, and ConvertersWithoutFaultInfeed names them. The CLI prints a note: line with their count and rated MVA whenever the case has any.

The fault verb

gridsim fault <case|case.m|case-dir> --bus <id> [--zf pu] [--type 3ph|slg|ll|dlg] solves the prefault flow (MaxIterations = 100, Q limits on), runs the fault study and assesses the faulted state with the default ProtectionSettings. It prints:

  • the fault current in pu, and in kA when the bus has a base voltage;
  • the Thevenin impedance and the faulted-bus voltage (3ph), or for an unbalanced type the phase currents, the earth current, the sequence currents, the faulted bus's phase voltages and the driving-point Z1, Z2, Z0;
  • the converter-interfaced fleet line (count, K, total infeed, units at their limit) when the case has any;
  • the relays operating on the faulted state, in the table device | function | location | quantity | pickup | time | basis, in Operating order, with inst for a zero time and - for none;
  • the closing line PROTECTION SIMULATION: a three-phase fault at bus N would drive M relay operation(s) - primary clearance by D (Function) on LOCATION, T. (an unbalanced study names the type, for example a line to line (phases b-c) fault at bus 7). The element named is ProtectionReport.PrimaryClearance, and T is its operating time to two decimals in seconds, or instantaneously for a zero time. When relays operate but no branch element with an operating time picks up, the line ends - no branch element with an operating time picks up (no circuit is cleared by the elements above).; with no operation it ends operation(s)..

--zf is a reactance in per unit (Zf = j zf). fault and protection-check refuse a negative or non-finite --zf (exit 2).

protection-check

gridsim protection-check <case|case.m|case-dir> [--uv pu] [--ov pu] [--uf Hz] [--of Hz] [--oc xIn] [--thermal frac] [--rocof Hz/s] [--cascade [--alarms <soe.csv>] | --fault-bus ID [--zf pu] [--fault-type 3ph|slg|ll|dlg]] solves the case (MaxIterations = 100, Q limits on) and assesses it. The flags set UnderVoltagePu, OverVoltagePu, UnderFrequencyHz, OverFrequencyHz, InstantaneousOcMultiple, ThermalPickupFraction and RocofTripHzPerS; every other setting is at its default on the command line. The verb prints the header, the operating-elements table, one not evaluated line listing the NotCheckable verdicts (not evaluated on a steady snapshot: ... on a power flow, not evaluated without a trajectory or the needed sequence data: ... on a fault study), and the closing line:

  • PROTECTION SIMULATION: no relay would operate on this state (within the generic settings)., or
  • PROTECTION SIMULATION suggests N protection event(s) would occur. e.g. on LOCATION, relay D (Function) would likely operate: BASIS. where the example is the first row of Operating, or
  • with --fault-bus and no operation, no relay would operate on the three-phase fault at bus N (or on the slg fault at bus N for the other types).

With --fault-bus the same settings are assessed on the faulted state, and the fault current and Thevenin impedance print first. The full flag set is in 0019 CLI reference.md and the fault verb.

End of a plain solve

The detailed solve report (gridsim <case> --once) ends with one line from the same overlay. On a converged state it reads either Protection simulation: no relay would operate on this state (generic settings). or Protection simulation: N event(s) suggested - e.g. on LOCATION, relay D (Function) would likely operate (BASIS). Runprotection-checkfor the full list. On a state that did not converge it reads Protection simulation: skipped - the power flow did not converge, so there is no state to assess. The solve above the line is untouched.

Cascade simulation

ProtectionCascade.Simulate(model, prefault, settings = null, maxSteps = 12) (src/GridSim.Core/Protection/ProtectionCascade.cs) follows one overload through the network. It requires a converged prefault, never touches the caller's solve, and works on copies of the model.

state = prefault;  current = model
for step = 1 .. maxSteps:
    report = Assess(current, state, settings)
    next   = the operating branch verdict whose device is 49, 50, 51 or starts with 21,
             ordered by (TimeToTripS or 0) ascending, then row index (position in report.Verdicts);
             first one (N277: equal times were broken by Margin descending before)
    if none:  stop  ("stable - no branch relay would operate" if no step ran, else "settled - no further branch trips")
    open that branch (InService = false) in a copy of the model
    resolved = Newton solve of the copy (SolverSelector.CreateNewton, MaxIterations 100, Q limits on)
    record CascadeStep(step, device, function, branch, from, to, TripTimeS, basis,
                       resolved.Converged, branches then overloaded)
    if resolved did not converge (or threw): stop, state split or collapsed
    current = copy;  state = resolved
stop at the cap: "reached the 12-step cap (still cascading)"

The branch to open is the verdict's LocationId, the exact branch index, so a parallel circuit that shares a display name is not confused with its twin. Branches then overloaded is the count of rated branches in the re-solved state loaded above ThermalPickupFraction * 100 percent by LineFlow.LoadingPercent. The elements that act are the branch elements 49, 50, 51 and 21; voltage, frequency, reverse-power and differential elements shed or trip infeed or are fault-only, and are left to the active layer (ch. 15). CascadeResult carries the steps, FinalConverged and StopReason; Cascaded is true when at least one step ran. The stop reasons are exactly:

StopReason Meaning
stable - no branch relay would operate The prefault state trips nothing.
settled - no further branch trips After at least one trip, the re-solved state trips nothing more.
non-convergent after opening NAME - the network has split / collapsed (blackout) The re-solve after a trip did not converge. This is the terminal state. NAME is the branch name when set, else F-T.
reached the N-step cap (still cascading) The cap was reached with the cascade still running; N is the caller's maxSteps, 12 by default (ProtectionCascade.DefaultMaxSteps).
internal: could not resolve the tripped branch The verdict names no in-service branch; not reachable from the shipped relays.

gridsim protection-check <case> --cascade prints the ordered sequence below the assessment. --cascade follows the steady solved state and does not combine with --fault-bus.

Sequence of events

SequenceOfEvents.CrossReference(predicted, observed) reconciles a predicted CascadeResult against a real timestamped alarm log. gridsim protection-check <case> --cascade --alarms <soe.csv> reads the log and prints the comparison. The match is by branch identity and relative order, not by wall-clock time: the cascade orders trips by relay operating-time rank, and at_s is used only to order the observed alarms and to detect an out-of-order arrival.

Log format (AlarmLogCsv, UTF-8): the exact header at_s,device,from,to,description, then one alarm per line. at_s is seconds from the event start (a finite number, invariant culture; map a real UTC stamp to it first). device is the ANSI id as logged and is non-empty. from and to are the branch end-bus ids, both 0 for a non-branch alarm. description is everything after the fourth comma. The description and device are trimmed. Blank lines and lines starting with # are skipped, including before the header, and the header is compared on the trimmed line. A line with exactly one of from and to equal to 0, or with a negative or non-integer bus id, is refused.

Algorithm:

  1. Take the observed alarms with from != 0 and to != 0, ordered by at_s. A branch is identified by its unordered bus pair.
  2. For each predicted step in predicted order, match the earliest unmatched alarm on the same branch. No alarm gives PredictedNotObserved (the model over-predicted).
  3. Over the matched pairs in predicted order, a pair whose observed time is earlier than the previous matched pair's (by more than 1e-9 s) is OrderMismatch; otherwise Agreement.
  4. Each unmatched branch alarm is ObservedNotPredicted: the model is missing something there.

SoeCrossReference.FullyConsistent is true when there is no PredictedNotObserved, ObservedNotPredicted or OrderMismatch entry. Divergences lists the rest. The device column of the log is carried through but not compared with the predicted device.

Parameters and defaults

ProtectionSettings (src/GridSim.Core/Protection/ProtectionTypes.cs), an immutable record. Override with new ProtectionSettings() with { TimeOcTms = 0.05 }.

Name Value Unit Meaning Source symbol Grade
27 pickup 0.80 pu Undervoltage. ENA EREC G99 Issue 2 Table 10.1, U/V, V - 20 % (2.5 s delay in the table, not modelled) UnderVoltagePu Generic
59 pickup 1.10 pu Overvoltage. G99 Issue 2 Table 10.1, O/V stage 1, V + 10 % (1.0 s delay in the table, not modelled) OverVoltagePu Generic
81U pickup 47.5 Hz Underfrequency. G99 Issue 2 Table 10.1, U/F stage 1 (20 s delay in the table, not modelled) UnderFrequencyHz Grounded
81O pickup 52.0 Hz Overfrequency. G99 Issue 2 Table 10.1 (0.5 s delay in the table, not modelled) OverFrequencyHz Grounded
81R pickup 1.0 Hz/s RoCoF. G99 Issue 2 Table 10.1, loss of mains RocofTripHzPerS Grounded
78 pickup 12.0 deg Vector shift. The legacy G59 high-impedance upper end (K1 = 2.0 times 6 degrees); not an acceptable loss-of-mains technique under G99 Issue 2 VectorShiftTripDeg Generic
50 pickup 2.50 x rated Instantaneous overcurrent InstantaneousOcMultiple Generic
51 pickup 1.20 x rated Time overcurrent pickup Is TimeOcMultiple Generic
51 TMS 0.10 - Time multiplier of the IEC standard-inverse curve TimeOcTms Generic
37 floor 0.001 pu Absolute undercurrent floor UnderCurrentFloorPu Generic
49 pickup 1.00 x RateA Thermal pickup ThermalPickupFraction Generic
49 tau 900.0 s Thermal time constant ThermalTimeConstantS Generic
21 Zone 1 reach 0.80 x line Z DistanceZone1Reach Generic
21 Zone 2 reach 1.25 x line Z DistanceZone2Reach Generic
21 Zone 3 reach 2.00 x line Z DistanceZone3Reach Generic
21 Zone 1 time 0.0 s DistanceZone1TimeS Generic
21 Zone 2 time 0.3 s DistanceZone2TimeS Generic
21 Zone 3 time 0.8 s DistanceZone3TimeS Generic
21 angle window 75.0 deg Half-width of the forward sector about the line angle DistanceAngleWindowDeg Generic
32 pickup 5.0 MW Reverse power magnitude ReversePowerMw Generic
87 pickup 0.10 pu Differential operate current DifferentialPickupPu Generic
50N pickup 1.00 x rated Residual instantaneous EarthFaultInstantaneousMultiple Generic
51N pickup 0.20 x rated Residual time-overcurrent pickup EarthFaultTimeMultiple Generic
51N TMS 0.10 - EarthFaultTms Generic
46 pickup 0.20 x rated Negative-sequence current NegativeSequenceMultiple Generic
46 time 1.0 s Definite time NegativeSequenceTimeS Generic
per-asset overrides null - Full settings per branch name for 49, 50, 51, 21, 50N, 51N, 46, 21N PerAsset -

The 50N, 51N and 46 values are marked [VERIFY] in the source: no published setting policy states them as multiples of a circuit's rated current.

Constants and defaults of the studies:

Name Value Meaning Source symbol
Default X''d 0.20 pu Subtransient reactance of a machine that carries none, on its MBase FaultAnalysis.DefaultSubtransientXdPu
Converter gain K 2.0 Reactive current per unit voltage dip, on the unit's rating FaultAnalysis.DefaultConverterReactiveGain
Converter fault multiple 1.2 k = I_skPF / I_rG where a unit carries none Generator.DefaultConverterFaultCurrentPu
Line Z0 ratio 3.0 Z0 = 3 Z1 where a line carries no R0/X0 UnbalancedFaultResult.LineZeroSeqRatio
Collapsed-voltage floor 1e-9 pu Below it no current is derived as S/V ProtectionContext.MinVoltageForCurrentPu
No-flow floor 1e-12 pu At or below it the apparent impedance is infinite ProtectionContext.MinApparentPowerPu
Minimum line impedance 1e-9 pu Below it the distance element skips the line DistanceRelay.MinLineImpedancePu
Cascade step cap 12 ProtectionCascade.DefaultMaxSteps
Cascade re-solve iterations 100 Newton cap of each post-trip solve ProtectionCascade.ResolveMaxIterations

Exit codes

protection-check:

Exit Cause
0 The assessment ran, whether or not any element operates. A cascade or fault verdict list is a result, not a failure.
1 The case failed to load; the fault study failed (InvalidOperationException or ArgumentException, for example a singular fault network); the --alarms file is missing or malformed (the message names the line).
2 No case; a bad flag value (error: --NAME expected ... but got '...'); --fault-bus for a bus not in the case; --fault-type or --zf without --fault-bus; --zf negative; --fault-bus with --cascade; --alarms without --cascade.
3 The prefault power flow did not converge; the converter iteration of the fault study did not converge (the verdicts still print); an slg or dlg study on a model with no transformer winding connection anywhere (the verdicts still print); --alarms was given and the prediction does not reproduce the log (SOE: DIVERGES).

fault: 0 on success; 1 for a load error or a fault-analysis error (including a bus not in the model); 2 for no case, no --bus, or a --type other than 3ph, slg, ll, dlg; 3 when the prefault flow did not converge, or for an slg or dlg study on a model with no transformer winding connection (the result prints, the reason goes to standard error). Like protection-check, fault exits 3 when the converter iteration does not converge (D-DOC-013), and refuses a negative or non-finite --zf (exit 2).

No test runs either verb's exit codes: the CLI tests cited below check the text of Program.cs, and the codes in this section were confirmed by running the Release binary.

No bundled case carries transformer winding connections (MATPOWER and JSON v1 cannot hold them), so slg and dlg exit 3 on every bundled case, and ll is the unbalanced type that runs without them. All three unbalanced types run without error from the API on a model built with windings, and from a JSON v2 case that gives them (N234, October 2026: phase P5 opened for fault sequence data; ch. 28).

--json, --csv and --out write the result to a file. protection-check writes the settings, the fault study, an operating table, the not-evaluated text, a cascade table and an soe table; fault writes the study at full precision and a relays table, a converters table (3ph) or a branches table (unbalanced).

Invariants

Invariant Test
The assessment never mutates the solved result. ProtectionAssessmentTests.Assessment_does_not_mutate_the_solved_result
A healthy converged case raises no voltage or differential operation; the shunt is netted off the residual. ProtectionAssessmentTests.Healthy_case_in_band_has_no_voltage_or_differential_operations
An inverted band (27 pickup 1.06 pu above 59 pickup 0.94 pu) puts every bus out of band, so 27 and 59 both operate. ProtectionAssessmentTests.Undervoltage_and_overvoltage_pick_up_when_the_band_is_tightened_around_the_state
A branch rated below its flow fires 49, 50 and 51. ProtectionAssessmentTests.Thermal_and_overcurrent_operate_on_a_branch_rated_below_its_flow
More current trips 51 sooner; the curve argument is the pickup multiple, not the rated multiple. ProtectionAssessmentTests.Time_overcurrent_is_faster_at_higher_current, Time_overcurrent_uses_pickup_multiple_not_rated_multiple
81R and 78 are NotCheckable and never operate without a trajectory; a trajectory at 47.0 Hz, 2.0 Hz/s and a 15 degree vector shift fires 81U, 81R and 78. ProtectionAssessmentTests.Frequency_and_rocof_relays_need_a_trajectory_and_then_operate
A generator absorbing power past the pickup fires 32. ProtectionAssessmentTests.Reverse_power_flags_a_motoring_generator
The ground group is NotCheckable on a power flow and operates on an unbalanced study. ProtectionAssessmentTests.Earth_and_negative_sequence_are_reported_not_checkable, EarthFaultAndIec60909CompletionTests.The_earth_fault_elements_operate_on_an_earth_fault_and_stay_not_checkable_on_a_power_flow
Distance verdicts do not depend on the orientation a branch is stored in; thermal loading uses the heavier end. ProtectionWs6Tests.Distance_verdicts_do_not_depend_on_branch_orientation, Thermal_loading_uses_the_heavier_end
A site-specific override changes only the named asset; a null map equals the generics. SiteSpecificRelayTests.A_site_specific_override_suppresses_only_the_named_asset, A_null_override_map_is_identical_to_the_generics
The 27, 59, 81U, 81O, 81R and 78 defaults equal the cited G99 and G59 values; the zone times, the 1e-9 and 1e-12 floors, the 12 and 100 step limits and the IEC standard-inverse pair equal their literals. The other defaults (50, 51, TMS, 37, 49, the zone reaches, the angle window, 32, 87, 50N, 51N, 46) are pinned by no test. S3ProtectionGroundingTests, Ws13CoreConstantsAntiDriftTests.Protection_constants_equal_the_literals_they_replaced
A bolted fault collapses the bus and draws a large current; a fault impedance lowers the current and leaves voltage on the bus. FaultAndCascadeTests.A_bolted_three_phase_fault_collapses_the_bus_and_draws_a_large_current, A_higher_fault_impedance_limits_the_fault_current
The faulted state operates 87, 21 and 27. FaultAndCascadeTests.The_faulted_state_operates_the_differential_and_distance_and_undervoltage_elements
Operating is fastest first and the primary clearance is a timed branch element (87 first); within one device the untimed order is by relative margin; equal times keep row order. Doc4ProtectionIec60909Tests.D158_operating_list_is_fastest_first_and_primary_clearance_is_a_timed_branch_element, D158_within_one_device_the_order_is_the_old_margin_order
The sparse injection walk equals the dense row sum bit for bit. FaultInjectionWalkPinTests.Sparse_cell_injection_walk_is_bit_for_bit_the_dense_loop
SLG, LL and DLG match their closed forms; with no earth path SLG is zero and DLG is LL; a 3ph type is refused by the unbalanced entry point. EarthFaultAndIec60909CompletionTests.Single_line_to_ground_matches_the_series_connection_closed_form, Line_to_line_and_double_line_to_ground_match_their_closed_forms, Without_an_earth_path_there_is_no_earth_current_and_dlg_is_line_to_line, A_three_phase_type_is_refused_by_the_unbalanced_entry_point
The phase elements read phase currents and loop impedances in an unbalanced study; a power flow and a balanced fault are unchanged; converters add no unbalanced infeed and are named. EarthFaultPhaseElementsTests
A converter holds its current limit with reactive priority and contributes far less than an X''d machine; the unit transformer is in series with the machine; a power-flow-only unit is no source. ConverterFaultContributionTests
An unstressed case does not cascade; an overloaded branch is opened first. FaultAndCascadeTests.An_unstressed_case_does_not_cascade, A_branch_rated_below_its_flow_starts_a_cascade_that_opens_that_branch_first
A non-converged state is refused by the assessment, the fault study and the cascade. ConvergenceContractTests.Fault_analysis_refuses_a_non_converged_prefault, Protection_cascade_and_assessment_refuse_a_non_converged_state
Prediction against log: agreement, a missed trip, an unpredicted trip and an order error are each classed; non-branch alarms are ignored. SequenceOfEventsTests
The log parser accepts the format exactly and refuses a malformed line, naming it; the CLI source contains the --alarms wiring (a source-text check that runs nothing). GradeAndSoeCliTests
The fault assessment uses the given settings and a fault impedance lowers the current (API tests); the CLI source contains the --fault-bus flags and exit messages (a source-text check). ProtectionCheckFaultCliTests

Worked example

Timings do not appear below; the trip times are computed from the state and are the same on every machine. All outputs are pasted from docs/_captures/protection-assess/.

A clean state, and one setting moved

case9 on the generic settings trips nothing. The three elements the snapshot cannot evaluate are listed:

$ gridsim protection-check case9
Protection assessment  -  case9  (9 buses, converged=True)  [passive; solve unchanged]
  operating elements: 0
  not evaluated on a steady snapshot: 81U (Underfrequency); 81O (Overfrequency); 81R (RoCoF); 78 (Vector shift / LoM); 50N/51N/21N/46 (Ground / negative-sequence)

PROTECTION SIMULATION: no relay would operate on this state (within the generic settings).
[exit 0]

Raising the undervoltage pickup to 1.00 pu asks what a tighter relay would do (check-case9-uv.txt). The lowest bus voltage is 0.996 pu, so 27 picks up on bus 9 and nothing else does:

  | 27 | Undervoltage | bus 9 | 0.996 pu | 1.000 | - | Vm 0.996 pu at bus 9 is below the 1.00 pu undervoltage pickup |

Moving an 81 setting across the nominal frequency operates it on a steady state, because the quantity is the model's nominal 50 Hz (check-case9-uf.txt, --uf 50.5):

  | 81U | Underfrequency | system | 50.000 Hz | 50.500 | - | operating frequency 50.000 Hz is below the 50.5 Hz underfrequency pickup |

The end of a plain solve

gridsim case30 --once ends with the overlay line (solve-case30.txt, elided):

Voltage range: 0.961 - 1.000 p.u. (in band)
Total losses: 2.44 MW, -6.79 MVAr
Protection simulation: 2 event(s) suggested  -  e.g. on branch 6-8, relay 49 (Thermal overload) would likely operate (branch 6-8 loaded to 109% of RateA (32 MVA); thermal replica trips in 1674 s). Run `protection-check` for the full list.

Cascade on case30

case30 has branch 6-8 loaded to 1.088 of its 32 MVA rating (cascade-case30.txt). The cascade opens it, re-solves, and finds the next trip:

$ gridsim protection-check case30 --cascade
Protection assessment  -  case30  (30 buses, converged=True)  [passive; solve unchanged]
  operating elements: 2
  | device | function | location | quantity | pickup | time | basis |
  |--------|----------|----------|----------|--------|------|-------|
  | 49 | Thermal overload | branch 6-8 | 1.088 xRateA | 1.000 | 1673.68s | branch 6-8 loaded to 109% of RateA (32 MVA); thermal replica trips in 1674 s |
  | 37 | Undercurrent | branch 9-11 | 0.000 pu | 0.001 | - | branch 9-11 carrying 0.00E+000 pu current (effectively de-energized, below the 1.0E-003 pu undercurrent floor) |
  not evaluated on a steady snapshot: 81R (RoCoF); 78 (Vector shift / LoM); 50N/51N/21N/46 (Ground / negative-sequence)

PROTECTION SIMULATION suggests 2 protection event(s) would occur. e.g. on branch 6-8, relay 49 (Thermal overload) would likely operate: branch 6-8 loaded to 109% of RateA (32 MVA); thermal replica trips in 1674 s.

Cascade propagation (2 trip(s)):
  1. relay 49 (Thermal overload) opens branch 6-8 in 1673.68s  ->  2 branch(es) then overloaded
  2. relay 51 (Time overcurrent) opens branch 8-28 in 2.84s  ->  re-solve did NOT converge
  stop: non-convergent after opening 8-28 - the network has split / collapsed (blackout).
[exit 0]

The thermal replica reproduces the time: L = 1.088, t = 900 ln(1.088^2 / (1.088^2 - 1)) is 1,677 s from the rounded loading, 1,673.68 s from the unrounded one. The 37 verdict on branch 9-11 is a real dead stub (zero current, both ends at the same voltage) and is not a branch-trip element, so the cascade ignores it. Step 1 opens 6-8 and the re-solve converges with two branches then overloaded. Step 2 opens 8-28 by its 51 element in 2.84 s and the re-solve does not converge, so the cascade stops at the terminal state.

Sequence of events against a log

The log docs/_captures/protection-assess/case30-alarms.csv records both predicted trips and one bus alarm:

# Alarm log for the case30 cascade, seconds from the fault start.
at_s,device,from,to,description
12.4,49,6,8,Thermal alarm on 6-8
15.1,51,8,28,Overcurrent trip on 8-28
15.3,27,0,0,Bus 28 undervoltage (not a branch alarm, not matched)

gridsim protection-check case30 --cascade --alarms docs/_captures/protection-assess/case30-alarms.csv prints the cascade above, then (cascade-case30-alarms.txt):

Sequence of events vs prediction (3 alarm(s), 1 non-branch not matched): 2 agree, 0 predicted not observed, 0 observed not predicted, 0 out of order
  Agreement: predicted and observed on branch 6-8 (predicted #1, observed at 12.4 s)
  Agreement: predicted and observed on branch 8-28 (predicted #2, observed at 15.1 s)
SOE: FULLY CONSISTENT - the predicted cascade reproduces the alarm log.
[exit 0]

Drop the second branch row from the log and the verb reports PredictedNotObserved, prints SOE: DIVERGES and exits 3.

A bolted fault on case9

gridsim protection-check case9 --fault-bus 7 superposes a bolted three-phase fault on the converged state (check-case9-fault7.txt, elided):

$ gridsim protection-check case9 --fault-bus 7
Protection assessment  -  case9  (9 buses)  three-phase fault at bus 7, Zf=j0.000 pu  [passive; prefault solve unchanged]
  fault current: 9.26 pu (1.55 kA)   Thevenin Z: 0.1098 pu
  (generator subtransient reactance synthesised at 0.20 pu; positive-sequence, so three-phase only)
  operating elements: 17
  | device | function | location | quantity | pickup | time | basis |
  |--------|----------|----------|----------|--------|------|-------|
  | 50 | Instantaneous overcurrent | branch 6-7 | 2.655 xIn | 2.500 | inst | branch 6-7 current 2.65x rated exceeds the 2.50x instantaneous pickup (trips instantly) |
  | 87 | Differential | bus 7 | 9.256 pu | 0.100 | inst | busbar differential 9.26E+000 pu at bus 7 exceeds the 0.10 pu bias pickup (internal fault) |
  | 21-Z2 | Distance | branch 6-7 | 0.103 pu | 0.127 | 0.30s | branch 6-7 apparent Z 0.103 pu is inside Zone 2 (reach 0.127 pu, line Z 0.102); operates in 0.3 s |
  | 21-Z2 | Distance | branch 7-8 | 0.073 pu | 0.091 | 0.30s | branch 7-8 apparent Z 0.073 pu is inside Zone 2 (reach 0.091 pu, line Z 0.072); operates in 0.3 s (relay at the to end, bus 8) |
  | 51 | Time overcurrent | branch 6-7 | 2.655 xIn | 1.200 | 0.87s | branch 6-7 current 2.65x rated over the 1.20x pickup; IEC standard-inverse trips in 0.9 s |
...
  | 49 | Thermal overload | branch 6-7 | 1.084 xRateA | 1.000 | 1711.28s | branch 6-7 loaded to 108% of RateA (150 MVA); thermal replica trips in 1711 s |
...
  | 27 | Undervoltage | bus 7 | 0.000 pu | 0.800 | - | Vm 0.000 pu at bus 7 is below the 0.80 pu undervoltage pickup |
...
  not evaluated without a trajectory or the needed sequence data: 81U (Underfrequency); 81O (Overfrequency); 81R (RoCoF); 78 (Vector shift / LoM); 50N/51N/21N/46 (Ground / negative-sequence)

PROTECTION SIMULATION suggests 17 protection event(s) would occur. e.g. on branch 6-7, relay 50 (Instantaneous overcurrent) would likely operate: branch 6-7 current 2.65x rated exceeds the 2.50x instantaneous pickup (trips instantly).
[exit 0]

Reading the numbers. The Thevenin impedance at bus 7 is 0.1098 pu, so V0_7 = If * |Zth| = 9.256 * 0.1098 = 1.016 pu is the prefault voltage, and the 87 quantity is the fault current itself (9.256 pu; 1.55 kA on the 345 kV bus: 9.256 * 100 / (sqrt(3) * 345)). Branch 6-7 is rated 150 MVA, so its rated current is 1.5 pu and the 51 quantity m = 2.655 is 3.98 pu; M = 2.655 / 1.2 = 2.2125 and t = 0.1 * 0.14 / (2.2125^0.02 - 1) = 0.87 s. The distance element on 6-7 sees Z = 0.103 pu against a line impedance of 0.102 pu: the fault is at the far end of the line, so the apparent impedance equals the line impedance, which is inside Zone 2 (1.25 x 0.102 = 0.127 pu reach) and outside Zone 1 (0.8 x 0.102 = 0.082 pu), and operates at the Zone 2 time of 0.3 s. On 7-8 the deciding end is the To end, at bus 8, as the basis says.

A fault impedance of --zf 0.5 (check-case9-fault7-zf.txt) limits the current to If = V0_7 / |Zth + j 0.5|, which is 1.67 pu, and only the differential operates, because every phase element's current and every bus voltage stays inside its setting:

$ gridsim protection-check case9 --fault-bus 7 --zf 0.5
Protection assessment  -  case9  (9 buses)  three-phase fault at bus 7, Zf=j0.500 pu  [passive; prefault solve unchanged]
  fault current: 1.67 pu (0.28 kA)   Thevenin Z: 0.1098 pu
  (generator subtransient reactance synthesised at 0.20 pu; positive-sequence, so three-phase only)
  operating elements: 1
  | device | function | location | quantity | pickup | time | basis |
  |--------|----------|----------|----------|--------|------|-------|
  | 87 | Differential | bus 7 | 1.671 pu | 0.100 | inst | busbar differential 1.67E+000 pu at bus 7 exceeds the 0.10 pu bias pickup (internal fault) |
  not evaluated without a trajectory or the needed sequence data: 81U (Underfrequency); 81O (Overfrequency); 81R (RoCoF); 78 (Vector shift / LoM); 50N/51N/21N/46 (Ground / negative-sequence)

PROTECTION SIMULATION suggests 1 protection event(s) would occur. e.g. on bus 7, relay 87 (Differential) would likely operate: busbar differential 1.67E+000 pu at bus 7 exceeds the 0.10 pu bias pickup (internal fault).
[exit 0]

The fault verb on case14

gridsim fault case14 --bus 4 (fault-case14-bus4.txt, elided) collapses the bus to 0.000 pu, draws 12.41 pu, and operates 23 elements. 87 on bus 4 operates at the fault current, 21 operates in Zone 2 on the five lines at bus 4 (from the far end where that is the deciding end) and in Zone 3 on three remote lines, and 27 operates across the depressed network:

$ gridsim fault case14 --bus 4
Balanced three-phase fault  -  case14  bus 4  Zf=j0.000 pu
  fault current: 12.41 pu   Thevenin Z: 0.0820 pu   faulted bus voltage: 0.000 pu
  (generator subtransient reactance synthesised at 0.20 pu; positive-sequence, so three-phase only)
  relays operating on the faulted state: 23
  | device | function | location | quantity | pickup | time | basis |
  |--------|----------|----------|----------|--------|------|-------|
  | 87 | Differential | bus 4 | 12.415 pu | 0.100 | inst | busbar differential 1.24E+001 pu at bus 4 exceeds the 0.10 pu bias pickup (internal fault) |
...
  | 21-Z2 | Distance | branch 4-7 | 0.209 pu | 0.261 | 0.30s | branch 4-7 apparent Z 0.209 pu is inside Zone 2 (reach 0.261 pu, line Z 0.209); operates in 0.3 s (relay at the to end, bus 7) |
...
  | 21-Z3 | Distance | branch 1-5 | 0.353 pu | 0.459 | 0.80s | branch 1-5 apparent Z 0.353 pu is inside Zone 3 (reach 0.459 pu, line Z 0.229); operates in 0.8 s |
...

PROTECTION SIMULATION: a three-phase fault at bus 4 would drive 23 relay operation(s) - primary clearance by 87 (Differential) on bus 4, instantaneously.
[exit 0]

Bus 4 has no base kV in case14, so no kA figure prints.

An unbalanced fault

A line-to-line fault at bus 7 of case9 runs without winding data (fault-case9-bus7-ll.txt, elided):

$ gridsim fault case9 --bus 7 --type ll
Line to line (phases b-c) fault  -  case9  bus 7  Zf=j0.000 pu
  phase currents: Ia 0.000 pu (0.000 kA)  Ib 8.016 pu (1.341 kA)  Ic 8.016 pu (1.341 kA)
  earth current |3I0|: 0.000 pu (0.000 kA)   sequence |I1| 4.628  |I2| 4.628  |I0| 0.000 pu
  faulted bus phase voltages: Va 1.016  Vb 0.508  Vc 0.508 pu
  driving-point Z1 0.0225+j0.1074  Z2 0.0225+j0.1074  Z0 infinite (no earth path in the zero sequence)
...
  | 21-Z1 | Distance | branch 6-7 | 0.000 pu | 0.081 | inst | branch 6-7 apparent Z 0.000 pu is inside Zone 1 (reach 0.081 pu, line Z 0.102); operates in 0.0 s (relay at the to end, bus 7) [b-c loop] |
  | 21-Z1 | Distance | branch 7-8 | 0.000 pu | 0.058 | inst | branch 7-8 apparent Z 0.000 pu is inside Zone 1 (reach 0.058 pu, line Z 0.072); operates in 0.0 s [b-c loop] |
  | 87 | Differential | bus 7 | 8.016 pu | 0.100 | inst | busbar differential 8.02E+000 pu at bus 7 exceeds the 0.10 pu bias pickup (internal fault) |
...
  | 46 | Negative sequence | branch 6-7 | 1.308 xIn | 0.200 | 1.00s | branch 6-7 negative-sequence current 1.31x rated exceeds the 0.20x pickup; definite time 1.00 s |
...

The closed form checks: I1 = V / (Z1 + Z2) = 1.016 / (2 * 0.1097) = 4.63 pu, I2 = -I1, and the faulted phases carry |Ib| = |Ic| = sqrt(3) * I1 = 8.02 pu. The phase-to-phase loop b-c is named in the distance verdict. An slg request on the same case reports the missing earthing data and exits 3 (check-case9-slg.txt):

$ gridsim protection-check case9 --fault-bus 7 --fault-type slg
Protection assessment  -  case9  (9 buses)  slg fault at bus 7, Zf=j0.000 pu  [passive; prefault solve unchanged]
  phase currents Ia 0.00  Ib 0.00  Ic 0.00 pu   earth current |3I0| 0.00 pu   (no earth path in the zero sequence at the fault bus)
  (phase elements on the phase currents and voltages; 50N/51N/21N/46 on the sequence currents; generic pickups)
  operating elements: 0
  not evaluated without a trajectory or the needed sequence data: 81U (Underfrequency); 81O (Overfrequency); 81R (RoCoF); 78 (Vector shift / LoM)

PROTECTION SIMULATION: no relay would operate on the slg fault at bus 7 (within the generic settings).
protection-check: the model carries no transformer winding connections at all, so it has no earthed neutral; the earth-fault verdicts below reflect missing data. Exit 3.
[exit 3]

Converter-interfaced units

gridsim fault data/gb-synthetic --bus 100 solves the fault with 50 converter-interfaced units (fault-gbsynthetic-bus100.txt, elided):

$ gridsim fault data/gb-synthetic --bus 100
Balanced three-phase fault  -  data/gb-synthetic  bus 100  Zf=j0.000 pu
  fault current: 3.54 pu (18.60 kA)   Thevenin Z: 0.3113 pu   faulted bus voltage: 0.000 pu
  (generator subtransient reactance synthesised at 0.20 pu; positive-sequence, so three-phase only)
  converter-interfaced units: 50 (current-limited, K=2.0 reactive priority)  total infeed 133.33 pu, 3 at current limit
  relays operating on the faulted state: 41
...

The fleet line is the converter fixed point above: 50 units, each at the grid-code characteristic with reactive priority, three of them on their current limit. A WARNING: converter current iteration did not converge is appended to that line when ConvertersConverged is false; the faulted state is then marked not converged, Assess refuses it, and fault and protection-check --fault-bus print the study without a relay table and exit 3.

Source map

File Type Responsibility
src/GridSim.Core/Protection/ProtectionTypes.cs ProtectionLocation, ProtectionConfidence, RelayVerdict, ProtectionTrajectory, ProtectionSettings, ProtectionReport The records: verdicts, grades, settings and defaults, the report views.
src/GridSim.Core/Protection/ProtectionContext.cs ProtectionContext The operating quantities computed once; per-branch settings; the phase quantities of an unbalanced study.
src/GridSim.Core/Protection/ProtectionRelays.cs IProtectionRelay, ProtectionRegistry, VerdictCollector, the 14 relay classes Each relay's equation; the registry order.
src/GridSim.Core/Protection/ProtectionAssessment.cs ProtectionAssessment Assess, AssessThreePhaseFault, AssessUnbalancedFault.
src/GridSim.Core/Protection/FaultAnalysis.cs FaultAnalysis, FaultType, FaultResult, UnbalancedFaultResult, BranchSequenceCurrents, ConverterFaultInfeed The balanced Thevenin study, the unbalanced sequence-network study, the converter fixed point.
src/GridSim.Core/Protection/FaultNetworkSystem.cs FaultNetworkSystem The factored fault admittance: the sparse LU at every size (dense LU as a test oracle only); singular fails loud.
src/GridSim.Core/Protection/ProtectionCascade.cs ProtectionCascade, CascadeStep, CascadeResult The trip, re-solve, re-assess chain.
src/GridSim.Core/Protection/SequenceOfEvents.cs SequenceOfEvents, AlarmEvent, SoeEntry, SoeCrossReference Prediction against alarm log.
src/GridSim.Core/Protection/AlarmLogCsv.cs AlarmLogCsv The alarm-log CSV reader.
src/GridSim.Core/PowerFlow/ConvergenceContract.cs ConvergenceContract, NonConvergedStateException The converged-state gate.
src/GridSim.Core/Protection/Coordination/ OvercurrentCoordination The IEC curve constants 51 and 51N use (ch. 26).
src/GridSim.Core/Protection/ShortCircuit/ Iec60909 The zero-sequence network the unbalanced study uses (ch. 25).
src/GridSim.Cli/Program.cs RunProtectionCheck, RunFault, RunUnbalancedFault, PrintDetailed The verbs, their flags and exit codes, the end-of-solve line.

Limits

  • Every pickup is a generic standard-practice value; real relay settings are site-specific and not public, so a verdict is a screen and not a certified protection study.
  • protection-check exposes seven settings as flags; the distance zones, the time multipliers, the 37 floor, the 87 pickup and PerAsset are reachable only through the API.
  • No verb supplies a ProtectionTrajectory, so 81R and 78 report NotCheckable on every command-line run, and 81U and 81O read the model's nominal frequency.
  • PerAsset overrides are keyed by branch name, and MATPOWER branches carry none, so no override applies to a MATPOWER case.
  • fault and protection-check both refuse a negative or non-finite --zf (exit 2) and both exit 3 when the converter iteration does not converge.
  • The from-end power on the context is computed but read by no relay.
  • 32 reads each generator's scheduled Pg from the model, not its solved output, so a slack machine that absorbs power in the solution is not seen.
  • 49 starts the thermal replica cold and carries no preload history.
  • 21 has no load blinder and no mutual-coupling or infeed compensation; it is the positive-sequence impedance screen described above.
  • --zf and faultReactancePu are a pure reactance, Zf = j zf; a resistive fault impedance cannot be entered.
  • The balanced fault stamps each load as a constant impedance at its nominal demand and each synchronous machine as X''d plus its unit transformer; a machine with no X''d takes 0.20 pu, so fault currents on cases without machine data are a synthesised screen.
  • The unbalanced study gives converter-interfaced units no fault infeed, because the model defines no negative- or zero-sequence behaviour for them, and it neglects loads and line charging in the zero sequence.
  • No bundled case carries transformer winding connections, so slg and dlg exit 3 on every bundled case.
  • The cascade opens one branch per step with no breaker timing, and treats any non-convergent re-solve as a split or collapse without distinguishing islanding from voltage collapse.
  • ProtectionReport.Operating ranks untimed elements by margin relative to their pickup, which makes different units comparable but is not a severity measure.
  • The sequence-of-events match compares branch identity and order, not the predicted and observed times, and does not compare the device.

See also