26. Overcurrent coordination (IDMT grading)

This chapter specifies how GridSim grades inverse-time overcurrent (ANSI 51) relays against one another. It covers the time-current-curve (TCC) library for the IEC 60255-151 and IEEE C37.112 families and for definite time, the grading algorithm that compares a primary (downstream) relay with its backup (upstream) relay at a fault current, the gridsim grade verb that exposes it, and how gridsim protection-check --cascade --alarms sits beside it. The code is src/GridSim.Core/Protection/Coordination/OvercurrentCoordination.cs. Every function in it is a pure closed form with no state and no solver, so a given set of relay settings and a given current always produce the same verdict and, for a given runtime, the same operating times (the times use Math.Pow, and no test compares their bits across CPU modes).

The 51 element inside the protection assessment (ch. 17) answers a different question: whether one relay, set to one fixed curve, picks up on a solved operating state. Grading answers whether two relays that see the same fault trip in the right order with enough margin between them. The asset-level protection stages are in ch. 15. The fault currents that feed a grading study are produced by ch. 25.

Model

Elements

A relay is an OvercurrentElement: a curve family (OvercurrentCurve), a pickup current Is, and a setting. The pickup and every fault current are in the same unit, amps or per unit; the library only ever uses their ratio

M = I / Is

For an inverse-time curve the setting is the time dial (TimeDial, default 1.0): the IEC time-multiplier setting TMS or the IEEE time dial TD. For a definite-time element the setting is the fixed delay (DefiniteTimeSeconds, default 0.0 s) and the time dial is not read.

Operating time

OvercurrentCoordination.OperateTimeSeconds(element, current) returns the operating time in seconds. As implemented:

M = current / Is
definite time:   t = DefiniteTimeSeconds   if M > 1,  else t = +infinity
inverse time:    t = +infinity             if M <= 1   (no operation at or below pickup)
IEC family:      t = TMS * k / (M^alpha - 1)
IEEE family:     t = TD * ( A / (M^p - 1) + B )

M^alpha is Math.Pow(m, alpha). The pickup test is strict: a current exactly equal to Is never operates, and a current of exactly zero gives M = 0 and never operates. +infinity is double.PositiveInfinity, and the CLI prints it as never.

Because M^alpha - 1 tends to zero as M tends to 1 from above, the IEC time tends to infinity at pickup. The IEEE form has the same pole in its A term and adds the constant offset B that the time dial multiplies, so an IEEE curve flattens to TD * B at very high current while an IEC curve tends to zero.

Curve constants

IEC 60255-151 (OvercurrentCoordination.IecConstants, returns (K, Alpha)):

Curve OvercurrentCurve CLI name k alpha
Standard inverse IecStandardInverse iec-si 0.14 0.02
Very inverse IecVeryInverse iec-vi 13.5 1.0
Extremely inverse IecExtremelyInverse iec-ei 80.0 2.0
Long-time inverse IecLongTimeInverse iec-lti 120.0 1.0

IEEE C37.112 (OvercurrentCoordination.IeeeConstants, returns (A, B, P)):

Curve OvercurrentCurve CLI name A B p
Moderately inverse IeeeModeratelyInverse ieee-mi 0.0515 0.1140 0.02
Very inverse IeeeVeryInverse ieee-vi 19.61 0.491 2.0
Extremely inverse IeeeExtremelyInverse ieee-ei 28.2 0.1217 2.0

Definite time is DefiniteTime, CLI name dt, with the delay in place of a time dial.

Asking IecConstants for an IEEE curve, or IeeeConstants for an IEC curve, throws ArgumentOutOfRangeException. The IEC pairs, (alpha, k) in the ABB table and (k, alpha) in the returned tuple, are the four pairs printed in Table 8.2.1 of the ABB Distribution Automation Handbook, section 8.2; the IEEE constants are the C37.112 values and no document in docs/reference prints them.

The 51 element of the protection assessment reads its standard-inverse constants from IecConstants, and uses the same expression tms * k / (Math.Pow(bigM, alpha) - 1.0), so the relay and this library use one table and one formula.

Input validation

OperateTimeSeconds refuses meaningless inputs with ArgumentOutOfRangeException rather than returning a number that looks plausible:

  • the pickup must be finite and greater than 0;
  • the current must be finite and at least 0 (NaN, a negative value and +infinity are refused; zero is allowed and never operates);
  • an inverse-time time dial must be finite and greater than 0;
  • a definite-time delay must be finite and at least 0 s.

Algorithm

Grading a pair

Grade(primary, backup, faultCurrent, requiredMarginSeconds) evaluates both elements at the same current:

tP     = OperateTimeSeconds(primary, faultCurrent)
tB     = OperateTimeSeconds(backup,  faultCurrent)
margin = tB - tP
coordinated = (tP is finite) AND (tB is finite) AND (margin >= requiredMarginSeconds)

It returns a GradingResult carrying PrimaryTimeSeconds, BackupTimeSeconds, MarginSeconds, RequiredMarginSeconds and Coordinated. The comparison is >=, so a margin exactly equal to the required interval passes. The required interval must be finite and at least 0 s, or Grade throws ArgumentOutOfRangeException.

The required margin is the coordination time interval (CTI). Its default is OvercurrentCoordination.DefaultCoordinationTimeIntervalS, 0.40 s. National Grid PS(T)010 Issue 1 (July 2017), Appendix A.5, sets 400 ms as the minimum acceptable margin at National Grid/DNO interfaces (larger when its formula gives more), and 0.4 s is the typical margin with electromechanical relays and oil circuit breakers in Electricity North West EPD350 Issue 6 (March 2023), section 4.3. EPD350 allows 0.2 s where modern electronic relays and vacuum breakers are used on both sides; a generic study cannot assume that, so the 0.2 s value is not the default and a caller who has those relays passes a smaller interval. The CLI default CliDefaults.GradeCtiS (src/GridSim.Cli/CliDefaults.cs) is that same constant, not a second number.

Three consequences follow directly from the two lines above.

  • Identical relays have zero margin, so they never coordinate against a positive CTI.
  • A primary that does not operate at the fault current (a fault below its pickup) has tP = +infinity and cannot coordinate, whatever the backup does.
  • A backup that does not operate while the primary does gives margin = +infinity, but tB is not finite, so the pair is not coordinated: nothing would back the primary up. The margin is still reported as inf, and the CLI verdict is NOT COORDINATED (backup does not operate).

If both elements are at or below pickup, margin = infinity - infinity = NaN, Coordinated is false because the primary is infinite, and the CLI prints the margin as -.

Chains

GradeChain(downstreamToUpstream, faultCurrent, requiredMarginSeconds) takes a list ordered from the relay nearest the fault to the relay furthest from it. It grades each consecutive pair (i, i+1) with Grade at the one fault current and returns the pairwise results in order. A chain of n elements gives n - 1 results; a chain of one or none gives an empty list. The chain is coordinated when every result is. Non-adjacent pairs are not graded: R1 against R3 is not checked, because on a radial feeder R2 operates between them.

A radial feeder carries the whole fault current through every relay between the source and the fault, so one common current is correct for the chain. For a meshed network the per-branch currents differ; obtain them from Iec60909.BranchFaultCurrents (ch. 25) and grade each pair at the current its own branch carries with Grade.

How settings are chosen

GridSim does not choose or optimise relay settings. Every pickup, time dial and delay is supplied by the caller, and the library only evaluates and checks them. A study therefore runs by trying settings and reading the margins: the grade verb takes several fault currents in one run so that the margin can be seen across the range from the minimum to the maximum fault level, and the smallest margin in the output is the one that limits the dial.

Failure modes

Condition Result
Primary at or below pickup Coordinated false, tP = +infinity; CLI verdict NOT COORDINATED (primary does not operate)
Margin below the CTI, primary operates Coordinated false; CLI verdict NOT COORDINATED (margin below CTI)
Margin negative (backup faster than primary) Same as the line above: the margin is below the CTI
Backup at or below pickup, primary operates Coordinated false, margin inf; CLI verdict NOT COORDINATED (backup does not operate)
NaN, negative or infinite current; non-positive pickup or time dial; negative delay; negative or non-finite CTI ArgumentOutOfRangeException from the library, exit 2 from the CLI
Malformed relay spec FormatException naming the spec, exit 2 from the CLI

The grade verb

gridsim grade --chain CURVE:PICKUP:TD,... --current I[,I...] [--cti S]

The verb's flags, defaults and exit codes are also listed in the grade section of 0019 CLI reference.md. The behaviour that matters for this chapter is below.

  • --chain is required: two or more relay specs separated by commas, downstream first. A spec is CURVE:PICKUP:TIMEDIAL, or dt:PICKUP:DELAY_S for definite time. CURVE is one of the CLI names in the constants tables, case-insensitive. The three fields are split on : with no extra or missing field, numbers are read in invariant culture, and whitespace around fields is ignored. OvercurrentCoordination.ParseElement does the parsing and throws FormatException naming the spec and the field.
  • A decimal comma cannot be used on the command line: --chain and --current are split on commas first, so --current 2000,5 grades at 2000 and at 5, and --chain iec-si:4,00:0.1,... fails with a field-count error for iec-si:4. --cti 0,4 is refused as not a finite number.
  • --current is required: one or more fault currents, comma-separated, each finite and at least 0, in the same unit as the pickups. The chain is graded at every current in turn.
  • --cti is the required coordination time interval in seconds. The default is 0.4. It must be finite and at least 0.
  • --json, --csv and --out write the result to a file. The pairs table has one row per pair per current (fault_current, pair, primary_s, backup_s, margin_s, required_margin_s, coordinated); a time that never operates is Infinity and an undefined margin is NaN there. The relays table lists each relay's curve, pickup, time dial and definite-time delay, and the summary carries relays, cti_s, all_coordinated and binding_margin_s (null when any pair is not coordinated; a coordinated pair always has a finite margin).

Output is a header with the relay count and the CTI, one line per relay, then for each current a table of pairs (R1->R2 is relay 1 as primary and relay 2 as backup) with times and margin to four decimals and a verdict, then a final line. Times print as F4; the file output carries full precision. The times are computed from the settings, not measured; the printed four-decimal values are stable.

Exit codes:

Code Meaning
0 Every pair is coordinated at every current. The last line is GRADED: with the binding margin.
3 At least one pair is not coordinated at some current. The last line is NOT GRADED:.
2 Usage error: a missing --chain or --current, a malformed spec, fewer than two relays, a bad current or CTI.

The binding margin on the GRADED: line is the smallest margin among the coordinated pairs across all currents; both times of a coordinated pair are finite, so it is always a number. The NOT GRADED: line prints no binding margin.

A captured run

Three relays on the IEC standard-inverse curve, all with pickup 400, time dials 0.1, 0.3 and 0.6, graded at 2000 and 4000 (the same unit as the pickup):

$ gridsim grade --chain iec-si:400:0.1,iec-si:400:0.3,iec-si:400:0.6 --current 2000,4000
Overcurrent grading  -  3 relays (downstream first), CTI 0.4 s
  R1: IecStandardInverse, pickup 400, time dial 0.1
  R2: IecStandardInverse, pickup 400, time dial 0.3
  R3: IecStandardInverse, pickup 400, time dial 0.6

  fault current 2000
  | pair | primary s | backup s | margin s | verdict |
  |------|-----------|----------|----------|---------|
  | R1->R2 | 0.4280 | 1.2839 | 0.8559 | OK |
  | R2->R3 | 1.2839 | 2.5678 | 1.2839 | OK |

  fault current 4000
  | pair | primary s | backup s | margin s | verdict |
  |------|-----------|----------|----------|---------|
  | R1->R2 | 0.2971 | 0.8912 | 0.5941 | OK |
  | R2->R3 | 0.8912 | 1.7824 | 0.8912 | OK |

GRADED: every pair coordinated at every current; binding margin 0.5941 s (CTI 0.4 s).
[exit 0]

(Capture docs/_captures/overcurrent-coordination/grade-chain.txt.) A primary below its pickup:

$ gridsim grade --chain iec-si:1000:0.1,iec-si:400:0.5 --current 500
Overcurrent grading  -  2 relays (downstream first), CTI 0.4 s
  R1: IecStandardInverse, pickup 1000, time dial 0.1
  R2: IecStandardInverse, pickup 400, time dial 0.5

  fault current 500
  | pair | primary s | backup s | margin s | verdict |
  |------|-----------|----------|----------|---------|
  | R1->R2 | never | 15.6500 | -inf | NOT COORDINATED (primary does not operate) |

NOT GRADED: at least one pair is not coordinated (see above).
[exit 3]

The margin is 15.65 - infinity, printed with its sign as -inf.

A usage error and a bad spec both exit 2:

$ gridsim grade --chain iec-si:400:0.1 --current 2000
error: --chain needs at least two relays (a primary and its backup), downstream first.
[exit 2]
$ gridsim grade --chain iec-xx:400:0.1,iec-si:400:0.3 --current 2000
error: --chain: Relay 'iec-xx:400:0.1': unknown curve 'iec-xx' (iec-si, iec-vi, iec-ei, iec-lti, ieee-mi, ieee-vi, ieee-ei or dt).
[exit 2]

protection-check --alarms

gridsim protection-check <case> --cascade --alarms <soe.csv> is not a grading feature. Its --alarms step (AlarmLogCsv, SequenceOfEvents in Protection/) does not call OvercurrentCoordination; the cascade's 51 element reads its standard-inverse constants from IecConstants. The cascade trips branch relays in the order of their assessed operating times, re-solves, and repeats (ch. 17); --alarms then compares that predicted order with a real sequence-of-events log. The comparison is by branch and order, not by wall-clock time, because the cascade ranks trips by relay operating time and has no real clock.

The log is CSV with the exact header at_s,device,from,to,description. AlarmLogCsv (src/GridSim.Core/Protection/AlarmLogCsv.cs) reads it strictly: at_s is a finite number of seconds from the event start, device is non-empty, from and to are non-negative integer bus ids that are either both non-zero (a branch alarm) or both 0 (a non-branch alarm such as a bus voltage alarm, which is counted but not matched), and the description is everything after the fourth comma. Blank lines and lines starting with # are skipped. Any other malformed line throws InvalidDataException naming the line, so an alarm is never silently dropped.

SequenceOfEvents.CrossReference (src/GridSim.Core/Protection/SequenceOfEvents.cs) matches each predicted step, in predicted order, to the earliest unmatched alarm on the same branch; a branch is identified by its unordered pair of bus ids, so 6-8 and 8-6 are the same branch. The matches are classed as Agreement, PredictedNotObserved, ObservedNotPredicted or OrderMismatch (an observed time earlier than the previous matched step's, with a tolerance of 1e-9 s). The result is fully consistent when the last three counts are all zero.

Exit codes: 0 when the prediction reproduces the log; 3 when it diverges; 2 when --alarms is given without --cascade; 1 when the file is missing or malformed.

An agreeing log (docs/_captures/overcurrent-coordination/soe-agree.csv), showing the tail of the output:

...
Cascade propagation (2 trip(s)):
  1. relay 50 (Instantaneous overcurrent) opens branch 6-8 in inst  ->  2 branch(es) then overloaded
  2. relay 50 (Instantaneous overcurrent) opens branch 8-28 in inst  ->  re-solve did NOT converge
  stop: non-convergent after opening 8-28 - the network has split / collapsed (blackout).

Sequence of events vs prediction (3 alarm(s), 1 non-branch not matched): 2 agree, 0 predicted not observed, 0 observed not predicted, 0 out of order
  Agreement: predicted and observed on branch 6-8 (predicted #1, observed at 0.1 s)
  Agreement: predicted and observed on branch 8-28 (predicted #2, observed at 0.35 s)
SOE: FULLY CONSISTENT - the predicted cascade reproduces the alarm log.
[exit 0]

The command was gridsim protection-check case30 --cascade --oc 1.0 --alarms docs/_captures/overcurrent-coordination/soe-agree.csv. A diverging log (soe-diverge.csv) on the same case:

...
Sequence of events vs prediction (2 alarm(s), 0 non-branch not matched): 1 agree, 1 predicted not observed, 1 observed not predicted, 0 out of order
  PredictedNotObserved: predicted 50 trip on branch 8-28 not seen in the alarm log
  ObservedNotPredicted: observed 51 trip on branch 2-6 was not predicted
  Agreement: predicted and observed on branch 6-8 (predicted #1, observed at 0.1 s)
SOE: DIVERGES - the predicted cascade does not reproduce the alarm log.
[exit 3]

--alarms without --cascade is refused:

$ gridsim protection-check case30 --alarms docs/_captures/overcurrent-coordination/soe-agree.csv
error: --alarms cross-references the predicted cascade; add --cascade.
[exit 2]

Parameters and defaults

Name Value Unit Meaning Source symbol
Default CTI 0.40 s Required margin between primary and backup OvercurrentCoordination.DefaultCoordinationTimeIntervalS (src/GridSim.Core/Protection/Coordination/OvercurrentCoordination.cs)
CLI default CTI 0.40 s --cti default; the Core constant CliDefaults.GradeCtiS (src/GridSim.Cli/CliDefaults.cs)
Time dial default 1.0 - TMS or TD when not given to the record OvercurrentElement.TimeDial
Definite delay default 0.0 s Fixed delay of a DefiniteTime element OvercurrentElement.DefiniteTimeSeconds
k, alpha table above s, - IEC 60255-151 constants IecConstants
A, B, p table above s, s, - IEEE C37.112 constants IeeeConstants
Pickup caller A or pu Is, same unit as the current OvercurrentElement.PickupCurrent
Time dial caller - TMS (IEC) or TD (IEEE), greater than 0 OvercurrentElement.TimeDial
Order tolerance 1e-9 s Out-of-order test in the SOE match SequenceOfEvents.CrossReference
Alarm log header at_s,device,from,to,description - Required first non-comment line AlarmLogCsv.Header

Invariants

Each invariant is pinned by a test in tests/GridSim.Tests. The curve tests assert to 12 decimal places (Assert.Equal(expected, actual, 12)), which is the closed-form check. The four IEC pairs are asserted exactly; the IEEE constants are checked only through a closed form that repeats them.

Invariant Test
IEC standard inverse equals TMS * 0.14 / (M^0.02 - 1), the form the 51 relay uses OvercurrentCoordinationTests.Iec_standard_inverse_matches_the_closed_form
The other three IEC families equal their (k, alpha) closed forms OvercurrentCoordinationTests.Iec_families_use_their_tabulated_constants
The IEEE families equal TD * (A / (M^p - 1) + B) OvercurrentCoordinationTests.Ieee_families_match_the_c37_112_closed_form
At or below pickup the time is +infinity; doubling the dial doubles the time; time falls as current rises OvercurrentCoordinationTests.Below_pickup_is_infinite_and_the_dial_scales_time_linearly
Definite time is the fixed delay above pickup at any level, +infinity below OvercurrentCoordinationTests.Definite_time_is_a_fixed_delay_above_pickup
MarginSeconds = backup - primary; identical relays give margin 0 and are not coordinated OvercurrentCoordinationTests.Grading_margin_is_backup_minus_primary
A primary below pickup is never coordinated OvercurrentCoordinationTests.A_non_operating_primary_is_not_coordinated
A chain grades each consecutive pair, and each result equals the standalone Grade OvercurrentCoordinationTests.Chain_grades_each_consecutive_pair
The four IEC pairs equal the ABB handbook table exactly; the anti-drift test pins the standard-inverse pair S3ProtectionGroundingTests.Iec_curve_constants_match_the_ABB_handbook_table, Ws13CoreConstantsAntiDriftTests
The default CTI is 0.40 s, Grade and GradeChain report it as RequiredMarginSeconds, and 0.35 s fails it S3ProtectionGroundingTests.Default_coordination_time_interval_is_400_ms, Grade_without_a_cti_uses_the_400_ms_default
The CLI default is the Core constant and the usage text says 0.4 S3ProtectionGroundingTests.The_cli_grade_default_is_the_core_constant_not_its_own_number
Each valid spec parses to the exact element, and each bad spec fails naming the spec GradeAndSoeCliTests.Idmt_specs_parse_to_the_exact_element, A_definite_time_spec_carries_its_delay, Bad_specs_fail_loud_naming_the_spec
A NaN, negative or infinite current, a bad time dial, a bad delay, an infinite pickup and a bad CTI are refused; zero current never operates GradeAndSoeCliTests.A_meaningless_fault_current_is_refused, Zero_current_never_operates_rather_than_failing, A_meaningless_time_dial_is_refused, A_meaningless_definite_time_delay_is_refused, An_infinite_pickup_and_a_meaningless_cti_are_refused
A network fault current from BranchFaultCurrents feeds GradeChain end to end Iec60909Tests.Branch_fault_current_feeds_the_coordination_grading
The alarm log parses each row exactly and refuses each malformed row with its line number; an empty file and a bad header are refused naming the problem GradeAndSoeCliTests.A_well_formed_log_parses_every_row_exactly, A_malformed_log_is_refused_with_its_line_never_dropped, A_missing_file_fails_loud
A parsed log cross-references a cascade by unordered branch GradeAndSoeCliTests.A_parsed_log_cross_references_a_cascade
The CLI source contains the wiring strings: the flags, the GradeChain call, the exit-code assignments for grade and the diverging log, and the message for --alarms without --cascade (a source-text check that runs nothing) GradeAndSoeCliTests.Cli_grade_and_alarms_are_wired_with_their_exit_codes
grade without its flags exits 2 with the usage line; the result writer handles the verb name. No test runs grade --chain ... --json CliProcessSmokeTests, CliResultWriterTests

Worked example

The first captured run above, recomputed by hand. The relays are R1 iec-si:400:0.1 and R2 iec-si:400:0.3; the fault current is 2000. All three relays share the pickup Is = 400 and the IEC standard-inverse constants k = 0.14, alpha = 0.02.

Operating time of R1 at 2000:

M     = 2000 / 400                      = 5
ln 5                                    = 1.6094379124341003
M^0.02 = exp(0.02 * 1.6094379124341003) = exp(0.032188758248682) = 1.032712419896443
M^0.02 - 1                              = 0.032712419896443
t(R1) = TMS * k / (M^0.02 - 1)
      = 0.1 * 0.14 / 0.032712419896443
      = 0.014 / 0.032712419896443       = 0.4279720070945375 s

The capture prints 0.4280, which is that value rounded to four decimals.

The CTI check for the pair R1->R2 uses the same M and the same denominator, so t(R2) = 0.3 * 0.14 / 0.032712419896443:

t(R2)  = 0.042 / 0.032712419896443      = 1.2839160212836123 s
margin = t(R2) - t(R1)
       = 1.2839160212836123 - 0.4279720070945375
       = 0.8559440141890748 s
CTI    = 0.4 s (the default, printed in the capture header)
margin >= CTI  ->  0.8559 >= 0.4  ->  coordinated, verdict OK

The capture prints 1.2839 and 0.8559. With the same pickup and curve the margin is (0.3 - 0.1) * 0.14 / (M^0.02 - 1), so it is proportional to the dial difference and falls as the current rises. At 4000, M = 10, M^0.02 - 1 = 0.0471285... and the margin is 0.5941 s; it is the smaller of the two currents' margins, which is why it is the binding margin on the GRADED: line.

A failing check recomputed the same way, from docs/_captures/overcurrent-coordination/grade-families.txt: gridsim grade --chain ieee-vi:200:0.5,iec-ei:200:0.3,dt:200:1.5 --current 1600 --cti 0.2. The fault current is 1600 and Is = 200, so M = 8 for all three relays.

R1 (IEEE very inverse, TD 0.5):  t = 0.5 * (19.61 / (8^2 - 1) + 0.491)
                                   = 0.5 * (19.61 / 63 + 0.491)
                                   = 0.5 * (0.31126984126984125 + 0.491)
                                   = 0.4011349206349206 s
R2 (IEC extremely inverse, TMS 0.3): t = 0.3 * 80.0 / (8^2 - 1)
                                   = 24 / 63
                                   = 0.38095238095238093 s
margin R1->R2 = 0.38095238095238093 - 0.4011349206349206 = -0.020182539682539... s
CTI = 0.2 s;  -0.0202 < 0.2  ->  NOT COORDINATED (margin below CTI)

The capture prints 0.4011, 0.3810 and -0.0202 with the verdict NOT COORDINATED (margin below CTI); the backup R2 is faster than its primary at this current, so the margin is negative. The second pair is definite time: R3 is a fixed 1.5000 s and 1.5 - 0.38095238095238093 = 1.1190 s, above the 0.2 s CTI, so R2->R3 is OK. The overall exit is 3. An extremely inverse backup behind a very inverse primary is a mismatch of curve shapes. With these settings the two curves cross where 9.805/(M^2 - 1) + 0.2455 = 24/(M^2 - 1), at M = 7.67, a fault current of about 1534; above it the extremely inverse R2 is the faster relay, so at 1600 the order is inverted. The fix is a larger dial on R2 or a different family, which the user chooses because GridSim does not select settings.

The printed times are computed from the supplied settings; the four-decimal values are stable.

Source map

File Type Responsibility
src/GridSim.Core/Protection/Coordination/OvercurrentCoordination.cs OvercurrentCurve, OvercurrentElement, GradingResult, OvercurrentCoordination Curve constants, operating time, Grade, GradeChain, ParseElement, default CTI
src/GridSim.Cli/Program.cs (RunGrade) CLI verb grade: flag parsing, per-current tables, verdict, exit codes, result file
src/GridSim.Cli/CliDefaults.cs CliDefaults.GradeCtiS CLI default CTI, bound to the Core constant
src/GridSim.Cli/Program.cs (RunProtectionCheck) CLI verb protection-check --cascade --alarms: reads the log before the solve, prints the cross-reference, exit codes
src/GridSim.Core/Protection/AlarmLogCsv.cs AlarmLogCsv Strict reader for the alarm log CSV
src/GridSim.Core/Protection/SequenceOfEvents.cs AlarmEvent, SoeCrossReference, SequenceOfEvents Match predicted cascade steps against observed alarms
src/GridSim.Core/Protection/ProtectionRelays.cs TimeOvercurrentRelay The 51 element, which reads IecConstants
src/GridSim.Core/Protection/ShortCircuit/Iec60909.cs Iec60909.BranchFaultCurrents Per-branch fault current used as the grading input
tests/GridSim.Tests/OvercurrentCoordinationTests.cs tests Curves, definite time, grading, chains
tests/GridSim.Tests/GradeAndSoeCliTests.cs tests Spec parser, input checks, alarm CSV, SOE, CLI wiring
tests/GridSim.Tests/S3ProtectionGroundingTests.cs tests Default CTI, ABB constants

Limits

  • A backup that does not pick up at the fault current is graded not coordinated, whatever the primary does; the grade does not say whether some other device further upstream would clear the fault.
  • GradeChain grades one fault current for the whole chain; a meshed network needs Grade called per pair with each branch's own current from Iec60909.BranchFaultCurrents.
  • Only the IEC and IEEE curves above and definite time exist; fuse and recloser curves, instantaneous (50) elements in a grade, and fuse-recloser coordination are not modelled.
  • Relay reset time, breaker clearing time and overshoot are not modelled separately; the CTI is one number the user supplies.
  • GridSim does not choose or optimise relay settings; every pickup, time dial and delay is an input.
  • --alarms matches by branch and order only; it does not compare times, and non-branch alarms are counted but never matched.