Design: EMT time-domain solver (Dommel companion model)

Status (verified 1.95.091): Implemented: the single-phase companion engine with ideal switches, faults and critical damping adjustment, Bergeron lines, constant-impedance loads, off-nominal taps and series-capacitor arms, and the three-phase (abc) engine with mutual coupling and average-value grid-following and grid-forming converters (ThreePhaseConverter). Not implemented: converter and machine models in the single-phase scalar engine, a public real-valued factorisation seam, and a three-phase build from GridModel. Implemented in: src/GridSim.Core/Dynamics/Emt/EmtEngine.cs (EmtEngine), EmtNetwork.cs (EmtNetwork, FromGridModel), EmtElement.cs (SeriesBranch, SeriesCapacitorBranch, ShuntElement, VoltageSource, CurrentSource, SwitchElement, BergeronLine), Companion.cs (EmtCompanionStamp), EmtEvent.cs, EmtUnits.cs, EmtTypes.cs, ThreePhaseEmt.cs (ThreePhaseEmtEngine, ThreePhaseNetwork, ThreePhaseBranch, ThreePhaseFault, ThreePhaseConverter); CLI verb emt. Design-to-code name map:

Design name Implemented as
IRealLinearFactorization (future public seam) not implemented; EmtEngine calls the internal Numerics/SparseLu.Factor and SparseLuFactorization.Solve directly
converter and machine models behind the CurrentSource seam (scalar engine) not implemented there; average-value converters exist only in ThreePhaseEmtEngine (ThreePhaseConverter)
EmtCompanionStamp in Companion.cs
EmtLineTests, EmtRlcAnalyticTests, EmtSteadyStateTests, EmtSwitchingTests present under those names in tests/GridSim.Tests/

This is a design record. The current behaviour is documented in the technical manual chapter 21. Electromagnetic transient.

Governing constraint

An EMT run is Solving, not inference, under UnderstandingRestrictions.md: it integrates the network's governing differential equations forward in time about the model, and its output is a model trajectory - never a claim about the real grid's present or future. It therefore:

  • sits in the Dynamics/ seam beside the swing/harmonic forward-simulation tools (ch. 5, ch. 19), not in Estimation/;
  • does not engage the RestrictionReview gate (Diagnostics/RestrictionReview), which fires only when a Dynamics/ process model is fused into the estimator's predict step. An EMT solver never touches the estimator, so it is unconditionally permitted as forward simulation;
  • seeds only from guard-permitted data if any dated input is used (the 169 h ForwardInferenceGuard, ch. 8), and labels every output a model trajectory;
  • carries ProvenanceTag.CuratedPlaceholder + the literal [VERIFY] token on any assumed parameter. The passive R/L/C/source/switch elements implemented here are grounded in the model's per-unit data; future converter/machine control internals (vendor-proprietary, absent from the lake) will be placeholders.

Method

The network is solved by Dommel's nodal companion-model method. Each reactive element is discretised with the trapezoidal rule into an equivalent conductance G_eq in parallel with a history current source I_hist. Assembling these gives a real nodal system

G * v(t) = i_history(t) + i_sources(t)

which is solved for the instantaneous node voltages every fixed timestep dt. G is constant between switching events, so it is factored once and back-substituted each step - the amortization that makes microsecond stepping affordable.

Companion models (per-unit; omega0 = 2*pi*FrequencyHz, L = X/omega0, C = B/omega0)

All fold to the single form I_hist = HistCoeffV*v_prev + HistCoeffI*i_prev (see Companion):

Element Trapezoidal Backward Euler (CDA half-step)
Series R-L G = 1/(R+2L/dt), I_hist = G*v_prev + alpha*i_prev, alpha = (2L/dt-R)/(2L/dt+R) G = 1/(R+L/dt), I_hist = i_prev/(1+R*dt/L)
Capacitor G = 2C/dt, I_hist = -G*v_prev - i_prev G = C/dt, I_hist = -G*v_prev
Resistor / switch G = 1/R, no history same

A voltage source is stamped as its Norton equivalent when Thevenin (G = 1/Rs, injection e(t)/Rs) or as a Dirichlet node when ideal (eliminated from the unknown set, like the slack bus - never a penalty conductance). A switch/fault is a conductance toggling between 1/Ron and 1/Roff; it stays permanently in the matrix pattern (open = a tiny conductance), so the fill-reducing ordering is computed once and only a numeric re-factor is needed on an event.

Rest initialisation

A source already on at t=0 requires the history to reflect the rest state (i_L=0, v_C=0) or the source appears to ramp 0->V over the first step (half the initial di/dt - the standard trapezoidal step-from-rest artefact). EmtEngine.InitializeRest performs an IC solve (capacitors hold their nodes at 0, inductors open, sources at emf(0), resistors carry the resulting DC) and seeds each reactive branch's history from it.

Critical Damping Adjustment (CDA)

Trapezoidal integration is only marginally stable (poles on the j*omega axis), so a switching discontinuity excites a spurious 2*dt (Nyquist) oscillation - most visibly a capacitor's current alternating +/- after a voltage step. On the event step the engine takes two backward-Euler dt/2 half-steps (BE is L-stable; alpha = 0), annihilating the mode, then resumes trapezoidal. A whole-run backward-Euler fallback (--rule be, O(dt) accuracy) is available if CDA is undesirable.

Numerics & reuse

  • Companion assembly mirrors PowerFlow/AdmittanceStamp and Harmonics/FrequencyDependentYBus (a per-parameter matrix rebuild): EmtCompanionStamp produces the companion; Numerics/Sparse.CsrMatrix.Builder assembles G.
  • Factor-once/solve-many uses the internal Numerics/SparseLu.Factor -> SparseLuFactorization.Solve (RCM ordering, Gilbert-Peierls LU). EmtEngine lives in GridSim.Core, so it calls these directly. A future public IRealLinearFactorization seam (mirroring IComplexLinearFactorization) would let the GPU backend drop in and decouple external callers - deferred, not needed for the current cut.
  • The batch loop runs under Simulation/GcScope.LowLatency with per-step buffers pre-allocated.

Files

src/GridSim.Core/Dynamics/Emt/: EmtUnits, Companion (EmtCompanionStamp), EmtElement (SeriesBranch/ShuntElement/VoltageSource/CurrentSource/SwitchElement), EmtEvent (SwitchEvent), EmtNetwork (+FromGridModel, EmtCase, EmtBuildOptions), EmtTypes (EmtPoint/EmtResult/EmtRunStats/ IntegrationRule/EmtProbe/EmtOptions), EmtEngine. CLI: the emt verb in GridSim.Cli/Program.cs.

Travelling-wave (Bergeron) lines

A lossless distributed line is a surge-impedance conductance Yc = 1/Zc to ground at each end plus a history current source carrying the wave that left the other end N = round(tau/dt) steps ago - the ends couple only through the delay buffers, so the stamp is diagonal-only. From a branch's per-unit X, B: Zc = sqrt(X/B), tau = sqrt(X*B)/omega0 (EmtUnits.SurgeParams). BergeronLine in EmtEngine; per-line ring buffers advance one slot per full step (frozen during a CDA half-step). FromGridModel(UseTravellingWaveLines: true) builds charged non-transformer branches as lines (lossless - series R dropped in that mode).

Constant-impedance loads

FromGridModel(IncludeLoads: true, default) models each bus's Pd/Qd as a constant-impedance shunt at 1 pu: Y = (Pd - jQd)/BaseMva -> a conductance plus an inductor (Qd>0) or capacitor (Qd<0). This damps the otherwise near-lossless network to a physical settling.

Three-phase (abc) with mutual coupling - ThreePhaseEmtEngine

Each bus is three phase nodes (3*bus + p). A ThreePhaseBranch (symmetric self/mutual R,L) stamps the 3x3 companion of its matrices - Y = (R + (2/dt)L)^-1, alpha = Y*((2/dt)L - R), history I_hist = Y*v_prev + alpha*i_prev per phase - so inter-phase mutual coupling is exact (the difference from three independent circuits). Ideal three-phase sources (120 deg-apart Dirichlet nodes), per-phase shunts/loads, and shunt faults (ThreePhaseFault, e.g. single-line-to-ground) are supported; faults toggle a conductance in a fixed pattern. Reuses the same nodal reduction + SparseLu factor-once path as the scalar engine.

Validation (acceptance gates)

  • EmtRlcAnalyticTests - closed-form series-RLC step response (over-, critically-, under-damped) to < 1e-5 against an independent oracle; error is O(dt^2); byte-deterministic.
  • EmtSteadyStateTests - a DC-energised RL network relaxes to the resistive DC solution.
  • EmtSwitchingTests - closing onto an L-C branch gives a TRV peak about 2 x V; CDA cuts the post-event numerical roughness by > 2x on a capacitor-switching case.
  • EmtLineTests - a matched Bergeron line absorbs its wave with no reflection; an open-ended line doubles the far-end voltage at tau and the reflection returns at 2tau.
  • ThreePhaseEmtTests - a balanced coupled line matches the analytic positive-sequence phasor to < 5e-3 with zero-sequence approx. 0 (mutual coupling handled); a single-line-to-ground fault collapses the faulted phase, leaves the healthy phases energised, recovers on clearing, and creates a zero-sequence voltage.

Limitations / remaining future phase

  • Converters/machines slot in behind the CurrentSource/Norton seam with a dq interface and CuratedPlaceholder [VERIFY] parameters - the one substantial phase not yet built.
  • Off-nominal taps are modelled as an ideal From-side transformer and X < 0 as a series R-C arm (R078, see technical chapter 21.7); a phase-shifting transformer is refused by name (it needs a three-phase build). Bergeron lines are lossless (series R dropped); a lossy line lumps R at the ends. FromGridModel three-phase needs per-phase sequence data (absent from the lake -> would be [VERIFY]), so the three-phase engine is driven directly for now, not from FromGridModel.