18. Replaying recorded events

replay-event re-simulates a recorded grid disturbance and scores the result against what the record says happened. The simulation starts from the event's recorded operating point (inertia and demand), applies its recorded losses and operator actions, carries no device, and compares the simulated rate of change of frequency (RoCoF) and frequency nadir with the recorded ones. The score is a verdict, Reproduced, Marginal or Failed. The verdict is the credibility gate for every counterfactual in ch. 20: scenario, fleet and h0-study refuse an event whose baseline is not Reproduced, and evidence withholds every counterfactual section. A replay presents its output as a reproduction of history, so replay-event takes only an event sourced from a record (see Provenance of an event). You need this chapter to check an event before you build on it, to read why a counterfactual refused to run, and to add an event of your own.

Before you start

  • gridsim means dotnet run --project src/GridSim.Cli -c Release -- when GridSim is not installed (see ch. 1). Run every command in this chapter from the repository root, because the trace files and catalogue files are given as paths relative to it.
  • Without --out, the run directory is results/replay-<id> under the current directory. Every example here passes --out results/... to name it. results/ is not tracked by git.
  • Three events are built into the program. gridsim replay-event with no id prints them:
$ gridsim replay-event
usage: gridsim replay-event <id> [--catalog <file.json>] [--trace <neso.csv>] [--out <dir>]
Built-in events: gb-2019-08-09, gb-2023-12-22, gb-largest-loss-1320
Reproduces the RECORDED RoCoF/nadir with NO device. A counterfactual is only credible
once the baseline is 'Reproduced'. Placeholder catalog figures are [VERIFY] until sourced.
[exit 2]

Worked example

Replay the 9 August 2019 disturbance, the event GridSim treats as its credibility target:

gridsim replay-event gb-2019-08-09 --out results/replay-gb-2019-08-09
$ gridsim replay-event gb-2019-08-09 --out results/replay-gb-2019-08-09

=== Replay: GB 9 Aug 2019 disturbance (Hornsea + Little Barford) ===
  when (UTC):        2019-08-09T15:52:33.0000000Z   provenance: DerivedFromRecorded (event tagged Recorded; the weakest of its parts)
  pre-event inertia: 215.0 GVA.s   demand: 21.1 GW   total loss: 2768 MW
  inferred inertia from recorded RoCoF: 223.7 GVA.s (cross-check vs 215.0)

  RoCoF:  sim  -0.171   recorded  -0.170 Hz/s   (1 % error)
  Nadir:  sim   48.84   recorded   48.80 Hz   (0.04 Hz error)
  Nadir envelope (declared-uncertainty corners): [48.20, 49.17] Hz - recorded INSIDE (consistent within the model's own error bars)
  RMSE vs trace: n/a (no 1-sec NESO trace attached - data-gated)
  assessment: BELOW STATUTORY (49.5 Hz)

  VERDICT: REPRODUCED  - baseline reproduces the record; counterfactuals unlocked.

  -> results\replay-gb-2019-08-09
[exit 0]

The simulated RoCoF is 1 % away from the recorded one and the simulated nadir is 0.04 Hz away. Both sit inside the tolerances (15 % and 0.15 Hz), so the verdict is Reproduced, the exit code is 0, and the counterfactual verbs accept this event. The timestamps in the run metadata and in the file headers differ by machine and run.

Reading the output

The console report has the same layout for every event.

Header. === Replay: <title> === is the event's title from the catalogue.

when (UTC) and provenance. The event onset (whenUtc) and the event's effective provenance: the weakest tag of all its parts (the event itself, its outcome, every loss, recorded action, response service and demand effect). A figure computed from the event carries no more trust than its weakest input. When the effective tag differs from the event's own, the line adds (event tagged <tag>; the weakest of its parts); the built-in recorded events carry DerivedFromRecorded losses, so they replay as DerivedFromRecorded. The full set of tags is in the provenance chapter.

pre-event inertia, demand, total loss. The recorded operating point: stored kinetic energy in GVA.s and transmission-net demand in GW, then the sum of the magnitudes of every loss in the event, in MW. The 2019 event lists nine losses that sum to 2768 MW. Recorded actions, such as the 892 MW of load disconnection, are not part of the total.

inferred inertia from recorded RoCoF. The inertia that the recorded RoCoF implies, E = f0 * |dP| / (2 * |RoCoF|) with f0 = 50 Hz, set against the event's stated inertia in brackets. dP is the sum of the losses that occur within the first 5 s of the sequence (for 2019: 150 + 737 + 244 + 390 = 1521 MW), so that the later gas-turbine trips of a staged event do not distort the initial slope. When no loss falls inside 5 s, the total loss is used. This line is a cross-check on the operating point, not part of the verdict. In 2019 it reads 223.7 GVA.s against a stated 215.0 GVA.s, 4 % apart. When the recorded RoCoF is a windowed figure, it is scaled by the replay's own instantaneous / windowed ratio before the inversion, and an indented line under it says so: for 2023 the ratio is 1.266 and the line reads 193.6 GVA.s against 161.0 GVA.s.

RoCoF. The simulated and recorded RoCoF in Hz/s, and the relative error ||sim| - |rec|| / |rec|. The comparison is on magnitudes, so the sign is informational. The simulated figure is the largest absolute RoCoF over the whole simulated window, which for a staged sequence is the steepest step, not necessarily the first. Its measurement basis follows the event's rocofMeasurementWindowS:

  • 0, the default, declares an instrument figure. The simulation is scored on its 20 ms maximum.
  • A positive window w, as 1.0 for the 2023 event, declares a figure read off a logger that samples every w seconds. The simulation is sampled on the same grid. Its statistic is the median, over every sub-second phase of that grid, of the largest consecutive-sample slope. A logger's phase against the event is unknown, so the median over phases is the unbiased single figure. A continuous sliding-window maximum would always find the steepest window and read steeper than any real sampled trace.

Nadir. The simulated and recorded minimum frequency in Hz, and the absolute difference. The values print to two decimals, so the 2023 recorded 49.275 Hz prints as 49.27. Only the value is scored. When the record gives the time of its nadir (outcome.nadirSeconds, 75.9 s for 2019) and the simulated nadir falls more than 2.0 s from it (ReplayTolerance.NadirTimeToleranceS), the one-line summary in summary.md adds [nadir time NOT reproduced: simulated nadir at <s> s, recorded at <s> s, ...], so a verdict reached on the value alone is never presented as a reproduced trajectory.

Nadir envelope. The same baseline replayed at the model's Best and Worst corners, which scale the three constants the model has not fitted to a record (load damping, responsive fraction, governor time constant). The bracket is [worst, best]. INSIDE means the recorded nadir lies within the model's own error bars. OUTSIDE means that something the corners do not scale, such as the inertia basis, is off. The envelope is reporting only. The verdict always comes from the nominal run.

RMSE vs trace. The root-mean-square difference in Hz between the simulated trajectory and a recorded 1-second trace, with the number of simulated samples scored, or n/a (no 1-sec NESO trace attached - data-gated) when no trace is attached. A trace that ends before the scored window adds a WARNING: trace ends <s> s before the scored window: ... line, and the RMSE covers only the samples the trace reaches; a trace that does not contain the event instant prints n/a and a WARNING naming both. See Replaying against a recorded trace.

back-test vs trace. Printed only when a trace covering the window is attached: the acceptance gate of the back-test (AssetValidation.Compare) against the trace, PASS or FAIL, with the nadir error in Hz, the simulated and recorded RoCoF on the trace's own 1 s basis, and the simulated and recorded nadir times. The gate is 0.05 Hz on the nadir, 0.05 Hz/s on the RoCoF and 2.0 s on the nadir time. A FAIL caps the verdict at Marginal.

assessment. The GB frequency-limit classification of the simulated response, taken in this order: LFDD RISK - demand disconnection when the nadir is at or below 48.8 Hz; BELOW STATUTORY (49.5 Hz) when it is below 49.5 Hz; RoCoF OVER <limit> Hz/s when RoCoF exceeds the active limit of 1.0 Hz/s; RoCoF OVER legacy 0.125 Hz/s; below operational (49.8 Hz); otherwise within limits. It describes the simulated trajectory and does not feed the verdict. The 2019 sim bottoms at 48.84 Hz, four hundredths above the 48.8 Hz line, so it reads BELOW STATUTORY, while the record touched 48.8 Hz and shed load.

VERDICT. One of REPRODUCED, MARGINAL, FAILED, with a one-line consequence. The last line is the run directory.

The verdict ladder

Verdict Condition Exit code Counterfactual verbs
Reproduced RoCoF error <= 15 % and nadir error <= 0.15 Hz, and with a trace attached an RMSE at or below 0.05 Hz and a back-test PASS 0 run
Marginal not Reproduced, but RoCoF error <= 30 % and nadir error <= 0.30 Hz 3 refuse
Failed anything else 3 refuse

The comparisons are inclusive. Both errors must satisfy the same rung, so a RoCoF error of 10 % with a nadir error of 0.40 Hz is Failed. Marginal and Failed unlock exactly the same thing, which is nothing. The difference is diagnostic: Marginal says the model is close, Failed says it is not. The tolerances are ReplayTolerance.Default (RocofRelTol 0.15, NadirAbsToleranceHz 0.15, RmseWarnHz 0.05) and cannot be changed from the command line. There is no flag that lets a counterfactual run on a baseline short of Reproduced.

Run directory

results/replay-gb-2019-08-09/
|-- run-metadata.json         what ran: commit, backend, machine, runtime, the run description and verdict
|-- baseline-frequency.json   the full baseline swing export: inputs, config, recurrence, headline, trajectory
`-- summary.md                provenance, verdict, one-line summary, inferred inertia

run-metadata.json for the run above:

# results/replay-gb-2019-08-09/run-metadata.json
{
  "timestampUtc": "2026-10-19T17:38:38.5276498Z",
  "backend": "cpu",
  "gitCommit": "v1.95.294-168-g786a2162",
  "buildConfig": "Release",
  "coreVersion": "1.95.462.0",
  "runtime": ".NET 10.0.12",
  "arch": "X64",
  "serverGc": true,
  "simdTier": "Avx256",
  "simdLanes": 4,
  "simdFma": true,
  "machineName": "LAPTOP",
  "os": "Microsoft Windows 10.0.26300",
  "cpu": "Intel(R) Core(TM) i3-N305",
  "logicalCores": 8,
  "ramGb": 8.3,
  "run": "replay-event  id=gb-2019-08-09  provenance=DerivedFromRecorded  verdict=Reproduced"
}

The run field carries the verdict, so a collection of run directories can be sorted by outcome without opening the reports. summary.md holds the same facts as the console, as a short list:

# results/replay-gb-2019-08-09/summary.md
# Replay - GB 9 Aug 2019 disturbance (Hornsea + Little Barford)

    GridSim  -  2026-10-19 17:38:38 UTC
    code:    git v1.95.294-168-g786a2162  |  GridSim.Core v1.95.462.0  |  build Release
    runtime: .NET 10.0.12  X64  GC=Server
    machine: LAPTOP  Microsoft Windows 10.0.26300
    cpu:     Intel(R) Core(TM) i3-N305  -  8 logical cores  -  8 GB RAM
    simd:    Avx256  (4 doubles/step)  FMA=True
    backend: cpu
    run:     replay-event  id=gb-2019-08-09  provenance=DerivedFromRecorded  verdict=Reproduced

- provenance: **DerivedFromRecorded**  (Credibility-gate target event, sourced from the Ofgem investigation report. The curated operating point (215 GVA*s / 21.1 GW) mirrors the measured catalog data/events/gb-2019-08-09-estimated.json.)
- verdict: **Reproduced**
- Reproduced: RoCoF sim -0.171 vs rec -0.170 Hz/s (1 % err); nadir sim 48.84 vs rec 48.80 Hz (0.04 Hz err); RMSE n/a (no trace)
- inferred inertia from recorded RoCoF: 223.7 GVA.s
- baseline swing export: `baseline-frequency.json`

baseline-frequency.json (schema gridsim-frequency-export/1, described in ch. 31) is the file to open when you want to hand-check the arithmetic. It holds the event steps, the exact dynamics configuration the validator used (device terms zero, recorded response services applied, window extended), the discrete recurrence in plain text, a headline block and the full 20 ms trajectory. For the 2019 run the window is 120 s, the last event at 90 s plus the 30 s tail described below. The headline block reports the 20 ms RoCoF and the nadir with its time. For a windowed event such as 2023 the headline RoCoF (-0.155 Hz/s) is the 20 ms figure, and the verdict uses the 1-second figure on the console (-0.123 Hz/s).

Exit codes

Code Meaning
0 verdict Reproduced, or --dump-catalog wrote its file
1 the event id is not in the catalogue, the catalogue could not be read, or the event is not sourced from a record (its effective provenance is below DerivedFromRecorded)
2 no id given, a --trace file that does not exist, an unknown flag or a malformed flag value, or an event rejected by the horizon guard
3 verdict Marginal or Failed

A CI job that gates on replay-event therefore passes only on a Reproduced baseline. With a trace attached, a result that would be Reproduced but has an RMSE above 0.05 Hz or a back-test FAIL is Marginal (see Replaying against a recorded trace).

Variations

A marginal baseline

The 22 December 2023 event is measured end to end: losses from settlement metering, operating point from the recorded inertia and the estimated demand, response services from the auction record, balancing-mechanism recovery from the bid-offer record, and the outcome from NESO's public 1-second trace. The built-in event carries no trace path, so the gate does not read that trace unless you attach it with --trace (see Replaying against a recorded trace).

gridsim replay-event gb-2023-12-22 --out results/replay-gb-2023-12-22
$ gridsim replay-event gb-2023-12-22 --out results/replay-gb-2023-12-22

=== Replay: GB 22 Dec 2023 excursion (IFA + Cottam, settlement-measured) ===
  when (UTC):        2023-12-22T13:09:51.0000000Z   provenance: DerivedFromRecorded (event tagged Recorded; the weakest of its parts)
  pre-event inertia: 161.0 GVA.s   demand: 22.4 GW   total loss: 1345 MW
  inferred inertia from recorded RoCoF: 193.6 GVA.s (cross-check vs 161.0)
    (recorded RoCoF is a 1 s windowed figure; inverted after scaling by the replay's instantaneous / windowed ratio 1.266)

  RoCoF:  sim  -0.123   recorded  -0.102 Hz/s   (20 % error)
  Nadir:  sim   48.98   recorded   49.27 Hz   (0.30 Hz error)
  Nadir envelope (declared-uncertainty corners): [48.65, 49.20] Hz - recorded OUTSIDE (a constant the corners don't cover - e.g. the inertia basis - is off)
  RMSE vs trace: n/a (no 1-sec NESO trace attached - data-gated)
  assessment: BELOW STATUTORY (49.5 Hz)

  VERDICT: MARGINAL  - NOT reproduced; do not run counterfactuals until the baseline matches (check [VERIFY] figures / tolerances).

  -> results\replay-gb-2023-12-22
[exit 3]

RoCoF is 20 % out and the nadir 0.30 Hz out. Both are inside twice the tolerance, so the verdict is Marginal and the exit code is 3. The recorded nadir lies outside the Best/Worst envelope, so no setting inside the declared corners closes the gap, and the inferred inertia (193.6 GVA.s) is 20 % above the stated 161.0 GVA.s. The 2023 dossier infers that the published outturn figure understates the stored energy by 20 to 40 GVA.s and isolates the residual to the inertia measurement basis. GridSim does not test that inference and does not fit an inertia value to close the gate. The record carries the published figure, the gate reports Marginal against it, and every counterfactual on this event stays locked. That verdict is the gate working as designed.

Replaying against a recorded trace

--trace <file.csv> attaches a 1-second frequency recording to the replay. The file has two comma-separated columns, a timestamp and the frequency in Hz (dtm,f). Blank lines and a header line are skipped; any other line that is not a data row is refused with exit 1, naming the line. A timestamp without an offset is read as UTC. The bundled recordings are data/neso/gb-2019-08-09-frequency.csv and data/neso/gb-2023-12-22-frequency.csv. With a trace the validator also computes a per-sample RMSE. It aligns the simulation's first loss with the trace sample nearest whenUtc, then compares the 20 ms trajectory with the trace on every simulated sample from that instant to the end of the window.

An RMSE above 0.05 Hz, or a back-test FAIL, demotes Reproduced to Marginal. Headline metrics that match while the trajectory shape diverges are not a reproduction. The 2019 event shows it:

gridsim replay-event gb-2019-08-09 --trace data/neso/gb-2019-08-09-frequency.csv --out results/replay-gb-2019-08-09-trace
$ gridsim replay-event gb-2019-08-09 --trace data/neso/gb-2019-08-09-frequency.csv --out results/replay-gb-2019-08-09-trace

=== Replay: GB 9 Aug 2019 disturbance (Hornsea + Little Barford) ===
  when (UTC):        2019-08-09T15:52:33.0000000Z   provenance: DerivedFromRecorded (event tagged Recorded; the weakest of its parts)
  pre-event inertia: 215.0 GVA.s   demand: 21.1 GW   total loss: 2768 MW
  inferred inertia from recorded RoCoF: 223.7 GVA.s (cross-check vs 215.0)

  RoCoF:  sim  -0.171   recorded  -0.170 Hz/s   (1 % error)
  Nadir:  sim   48.84   recorded   48.80 Hz   (0.04 Hz error)
  Nadir envelope (declared-uncertainty corners): [48.20, 49.17] Hz - recorded INSIDE (consistent within the model's own error bars)
  RMSE vs trace: 0.099 Hz over 5996 sample(s)
  back-test vs trace (gate 0.05 Hz / 0.05 Hz/s / 2.0 s): FAIL  nadir 0.054 Hz, RoCoF sim -0.154 vs rec -0.151 Hz/s, nadir time sim 76.0 s vs rec 76.1 s (0.1 s)
  assessment: BELOW STATUTORY (49.5 Hz)

  VERDICT: MARGINAL  - NOT reproduced; do not run counterfactuals until the baseline matches (check [VERIFY] figures / tolerances).

  -> results\replay-gb-2019-08-09-trace
[exit 3]

RoCoF and nadir errors are unchanged at 1 % and 0.04 Hz, but the RMSE is 0.099 Hz and the back-test fails on the nadir (0.054 Hz against the 0.05 Hz gate), so the verdict drops to Marginal and the exit code to 3. A single-mass swing model driven by nine staged power steps reproduces the headline physics of the excursion and not its sample-by-sample shape. The built-in 2019 event carries no trace path, so its headline gate stays the operative one. The 2019 dossier discusses the shape gap.

A trace can only move a verdict downwards. On the 2023 event it adds the RMSE and back-test lines and leaves the verdict at Marginal:

$ gridsim replay-event gb-2023-12-22 --trace data/neso/gb-2023-12-22-frequency.csv --out results/replay-gb-2023-12-22-trace

=== Replay: GB 22 Dec 2023 excursion (IFA + Cottam, settlement-measured) ===
  when (UTC):        2023-12-22T13:09:51.0000000Z   provenance: DerivedFromRecorded (event tagged Recorded; the weakest of its parts)
  pre-event inertia: 161.0 GVA.s   demand: 22.4 GW   total loss: 1345 MW
  inferred inertia from recorded RoCoF: 193.6 GVA.s (cross-check vs 161.0)
    (recorded RoCoF is a 1 s windowed figure; inverted after scaling by the replay's instantaneous / windowed ratio 1.266)

  RoCoF:  sim  -0.123   recorded  -0.102 Hz/s   (20 % error)
  Nadir:  sim   48.98   recorded   49.27 Hz   (0.30 Hz error)
  Nadir envelope (declared-uncertainty corners): [48.65, 49.20] Hz - recorded OUTSIDE (a constant the corners don't cover - e.g. the inertia basis - is off)
  RMSE vs trace: 0.281 Hz over 7926 sample(s)
  back-test vs trace (gate 0.05 Hz / 0.05 Hz/s / 2.0 s): FAIL  nadir 0.295 Hz, RoCoF sim -0.123 vs rec -0.102 Hz/s, nadir time sim 49.0 s vs rec 20.5 s (28.5 s)
  assessment: BELOW STATUTORY (49.5 Hz)

  VERDICT: MARGINAL  - NOT reproduced; do not run counterfactuals until the baseline matches (check [VERIFY] figures / tolerances).
...

A catalogue event can carry its own trace path in outcome.nesoTraceCsvPath, and --trace overrides it.

The measured 2019 catalogue

data/events/gb-2019-08-09-estimated.json carries the same event with the operating point taken from the state estimator: demand 21,147 MW (the built-in rounds it to 21,100 MW) and onset 15:52:00 UTC. Load it with --catalog:

gridsim replay-event gb-2019-08-09 --catalog data/events/gb-2019-08-09-estimated.json --out results/replay-estimated
$ gridsim replay-event gb-2019-08-09 --catalog data/events/gb-2019-08-09-estimated.json --out results/replay-estimated

=== Replay: GB 9 Aug 2019 disturbance (Hornsea + Little Barford) - measured operating point ===
  when (UTC):        2019-08-09T15:52:00.0000000Z   provenance: DerivedFromRecorded
  pre-event inertia: 215.0 GVA.s   demand: 21.1 GW   total loss: 2768 MW
  inferred inertia from recorded RoCoF: 223.7 GVA.s (cross-check vs 215.0)

  RoCoF:  sim  -0.171   recorded  -0.170 Hz/s   (1 % error)
  Nadir:  sim   48.84   recorded   48.80 Hz   (0.04 Hz error)
  Nadir envelope (declared-uncertainty corners): [48.20, 49.17] Hz - recorded INSIDE (consistent within the model's own error bars)
  RMSE vs trace: n/a (no 1-sec NESO trace attached - data-gated)
  assessment: BELOW STATUTORY (49.5 Hz)

  VERDICT: REPRODUCED  - baseline reproduces the record; counterfactuals unlocked.
...

Both catalogues reproduce the record. The title, the onset and the provenance line differ (the measured catalogue is itself tagged DerivedFromRecorded); RoCoF, nadir and the declared envelope ([48.20, 49.17]) agree to the printed digits. The file data/events/gb-events.json is the built-in catalogue as replay-event --dump-catalog writes it: gb-2019-08-09, gb-2023-12-22 and gb-largest-loss-1320, field for field, so --catalog data/events/gb-events.json replays the same events as the built-ins.

A screening event

gb-largest-loss-1320 is a generic single 1,320 MW infeed trip on a nominal operating point, titled for the SQSS normal infeed loss risk. Every figure, the recorded outcome included, is a CuratedPlaceholder marked [VERIFY], so the event is effectively CuratedPlaceholder. replay-event gb-largest-loss-1320 refuses it with exit 1 and writes nothing: error: event 'gb-largest-loss-1320' (...) is effectively CuratedPlaceholder (its weakest part: the event itself (CuratedPlaceholder)): a replay presents its output as a reproduction of a recorded event, so only an event sourced from a record (Recorded or DerivedFromRecorded throughout) is replayed ....

The study verbs (scenario, fleet, evidence, h0-study) take it as a design-basis input. They run the same gate on it, which reports Reproduced because the model agrees with the placeholder outcome: a consistency check that grounds nothing. Their console output adds an input provenance: [CuratedPlaceholder] line, and every figure they write carries that tag. Use this event to explore a device, never to quote a result.

Provenance of an event

The effective provenance of an event is the weakest tag of its parts. replay-event runs only on an event whose effective provenance is Recorded or DerivedFromRecorded; anything weaker (CuratedPlaceholder, Synthetic, Interpolated, or a recorded event with one placeholder part) exits 1 naming the weakest part. A part tagged as an output (Counterfactual or UnvalidatedAtScale) is refused as an input by name on every event verb. The baseline export a replay writes is a simulation of the event, so it is tagged at best DerivedFromRecorded, and never above the event's effective tag.

The event catalogue

A catalogue is a JSON file with the schema tag gridsim-event-catalog/1 and a list of events. Every figure carries a provenance tag, and every figure not taken from a primary source stays CuratedPlaceholder with [VERIFY] in its text. An event holds these fields.

Field Meaning
id, title The id is the argument of replay-event and the --event of the counterfactual verbs, matched without regard to case. The title prints in every report.
whenUtc The onset, UTC. It must be at least 169 hours old (see The horizon rule).
preEventInertiaMwS Stored kinetic energy before the event, in MW.s (215,000 is 215 GVA.s).
preEventDemandMw Transmission-net demand before the event, in MW.
losses The generation losses. Each has atSeconds from the onset, deltaPMw (negative for a loss), a what that cites its source, and a provenance.
recordedActions Operator or protection actions the record shows, in the same form plus a required kind. A positive deltaPMw is load removed. DemandDisconnection (LFDD, a consequence of the frequency itself) is replayed in the baseline and left out of every counterfactual; OperatorInstruction (for example the balancing-mechanism recovery of 2023) is kept in every counterfactual too, because the lost energy is replaced with or without a device. A catalogue entry without a kind is refused.
outcome The headline figures the replay must reproduce: initialRocofHzPerS, nadirHz, settleHz, lfddMwShed, provenance, notes, an optional nesoTraceCsvPath, rocofMeasurementWindowS (0 for an instrument figure, 1.0 for a 1-second logger figure), and an optional nadirSeconds, the time of the recorded nadir on the event clock (reporting only).
provenance, notes The tag and the source citations for the event as a whole.
responseServices, responseServicesComplete The frequency-response services the system held, each with mw, deadbandHz, fullDeliveryDeviationHz, timeConstantS, what, provenance and an optional low-gain knee (kneeDeviationHz, kneeFraction). responseServicesComplete: true declares the list to be all the response the system held.
preEventFrequencyHz The frequency the trip landed on, read off the trace. When set, the replay starts in equilibrium there.
demandEffect Optional: the demand reduction the record gives per Hz of frequency fall, mwPerHz (above 0), what and provenance. When set, the swing model's load damping is set to this figure in MW per Hz in the baseline and in every counterfactual.

Response services. Recent GB events are arrested by procured sub-second response (Dynamic Containment, Dynamic Moderation, Dynamic Regulation), not by governor droop. An event can carry the service volumes the system held, taken from the auction record, each on its published delivery shape. The replay integrates each as a proportional responder. When responseServicesComplete is true, as it is for GB events after the November 2023 go-live of the enduring auction capability and for 9 August 2019 (whose ESO report lists the whole low-frequency response held), the generic governor term is switched off so that response the record already lists is not counted twice. Counterfactuals keep the services as well. A device is evaluated on top of what the real system held, never as a replacement for it.

Pre-event frequency. When an event records the frequency the trip landed on, the replay starts at that frequency with the services partly deployed on their published curves and the standing imbalance carried as the balancing mechanism was carrying it. Recorded balancing-mechanism dispatch enters as recorded actions, by the same route as LFDD.

The window. The simulated window always covers the whole recorded sequence: it runs to the time of the last event plus 30 s, and never shorter than the 30 s default. The 2019 event plays out over 90 s, so a clipped window would replay a different event than the record describes. scenario, fleet, evidence and h0-study use the same rule, so they agree with the baseline about what covers an event.

The built-in events

Id What it is Verdict
gb-2019-08-09 The 9 August 2019 disturbance (Hornsea 1 and Little Barford). Nine losses, the 892 MW LFDD action and the outcome come from the Ofgem investigation report (January 2020), paragraphs 2.4.1 to 2.4.16, and each loss cites its paragraph. Operating point: 215 GVA.s (NESO recorded outturn for the half-hour) and 21,100 MW. The response the system delivered comes from the ESO report's Table 3 (six services, 1,090 MW delivered, listed as complete), and its demand effect, 700 MW/Hz, from the same report. Outcome: -0.17 Hz/s (E3C interim trace; Ofgem records only more than 0.125 Hz/s), nadir 48.8 Hz at 75.9 s, 892 MW shed. Reproduced
gb-2023-12-22 The 22 December 2023 excursion (IFA and Cottam), measured end to end. IFA -1,000 MW and Cottam -345 MW from settlement metering; 161 GVA.s and 22,400 MW; 49.879 Hz pre-event; DCL 873, DML 150 and DRL 203 MW from EAC auction 70; balancing-mechanism recovery of +904 MW by +129 s as recorded actions. Outcome from NESO's public 1-second trace: -0.102 Hz/s as a 1-second figure, nadir 49.275 Hz, no LFDD. Marginal
gb-largest-loss-1320 The screening case described above. refused by replay-event; Reproduced against placeholders in the study verbs

The sourcing behind the first two is in the 2019 and 2023 dossiers.

Authoring an event

  1. Dump the built-in catalogue as a starting point:
gridsim replay-event --dump-catalog results/dump-events.json
$ gridsim replay-event --dump-catalog results/dump-events.json
wrote built-in catalog (3 events) -> results\dump-events.json
[exit 0]

The dump holds all three events. It also writes a totalLossMw field on each, which is computed on load and ignored.

  1. Cut the file down to your event and set its fields. This is a complete catalogue that holds one illustrative event, saved as results/my-events.json (the copy used here is docs/_captures/events/my-events.json). Every figure in it is a placeholder, and it describes no real event, so replay-event refuses it until its figures are sourced and tagged Recorded or DerivedFromRecorded (see Provenance of an event); the study verbs take it as it is:
{
  "schema": "gridsim-event-catalog/1",
  "events": [
    {
      "id": "example-1000",
      "title": "Illustrative 1000 MW infeed loss [VERIFY]",
      "whenUtc": "2022-03-15T12:00:00Z",
      "preEventInertiaMwS": 180000,
      "preEventDemandMw": 30000,
      "losses": [
        {
          "atSeconds": 1,
          "deltaPMw": -1000,
          "what": "single infeed trip [VERIFY]",
          "provenance": "CuratedPlaceholder"
        }
      ],
      "recordedActions": [],
      "outcome": {
        "initialRocofHzPerS": -0.139,
        "nadirHz": 49.4,
        "settleHz": 49.8,
        "lfddMwShed": 0,
        "provenance": "CuratedPlaceholder",
        "notes": "Illustrative figures, not a real event [VERIFY].",
        "rocofMeasurementWindowS": 0
      },
      "provenance": "CuratedPlaceholder",
      "notes": "Illustrative example for the manual. Every figure is a placeholder [VERIFY].",
      "responseServicesComplete": false
    }
  ]
}
  1. Check it against the gate. While its figures are placeholders, replay-event example-1000 --catalog results/my-events.json refuses it with exit 1, naming the weakest part. scenario runs the same gate on it as a design-basis input:
gridsim scenario --event example-1000 --catalog results/my-events.json --out results/scenario-example-1000

The report opens with the input provenance: [CuratedPlaceholder] line and baseline gate: Reproduced, and every figure it writes carries the placeholder tag.

A verdict on placeholder figures says nothing about the world: here it is Reproduced only because the recorded outcome was written to be consistent with the model. The gate measures the model against the outcome you wrote, so the outcome must come from a source. Replace each CuratedPlaceholder with a sourced figure and tag it Recorded or DerivedFromRecorded; replay-event then replays it. If the verdict then falls short, the finding is about the model or the operating point, as the 2023 event shows. Do not edit the recorded outcome to make the verdict turn green. Marginal and Failed are the correct output when a record and the model disagree.

A failed baseline

Copy my-events.json to results/off-event.json, change the id to example-off, and set the recorded initialRocofHzPerS to -0.2 and nadirHz to 49.0. The model cannot produce those figures from 180 GVA.s and a 1,000 MW loss, and the ladder drops to Failed (the file used here is docs/_captures/events/off-event.json):

gridsim scenario --event example-off --catalog results/off-event.json --out results/scenario-example-off

The study refuses to run counterfactuals and exits 3. Standard error carries GATE FAILED: Refusing to run counterfactuals: the no-device baseline is 'Failed', not 'Reproduced'. Reproduce reality first. followed by the replay summary (RoCoF and nadir, simulated against recorded, with their errors). The recorded RoCoF alone already implies E = 50 x 1000 / (2 x 0.2) = 125.0 GVA.s against the stated 180.0, so the recorded RoCoF and the stated inertia disagree before any dynamics are involved.

The horizon rule

GridSim replays history only. Every timestamp it reads is checked against the forward-inference horizon, and a timestamp newer than 169 hours (7 days and 1 hour) before the present is rejected. The check sits at the point where data enters: an event's whenUtc is checked when a catalogue loads, the built-in events included, and a trace sample is checked as the trace is read. The horizon is now - 169 h, so it moves with the clock. An event is accepted once its stamp is 169 hours old, so an event dated yesterday is rejected today and accepted after 6 days and 1 hour. There is no flag that disables it.

Replay an event dated 2 October 2026 (the capture was made on 3 October 2026):

gridsim replay-event example-recent --catalog results/recent-event.json --out results/replay-example-recent
$ gridsim replay-event example-recent --catalog results/recent-event.json --out results/replay-example-recent
REJECTED (forward inference): event 'example-recent' timestamp 2026-10-02T12:00:00.0000000Z is newer than the historical horizon 2026-09-26T07:16:48.3517197Z (data must lag real time by >=169 h). GridSim replays history only - it never processes recent or future data, so it cannot forward-infer.
[exit 2]

The message names the event, its timestamp and the horizon that applied. It goes to standard error, the exit code is 2, and no run directory is written. The horizon timestamp in the message differs on every run. The check covers the whole file, so one recent event in a catalogue stops every replay from that file, including a replay of an older event in the same file. scenario, fleet, evidence and h0-study load events the same way and reject the same way, with the same message and exit code.

Pitfalls

  • REJECTED (forward inference) and exit 2. An event in the catalogue is newer than 169 hours. Correct its whenUtc, or remove the event. You cannot replay a recent event. A catalogue that you edited this week with an event from this week is the usual cause.
  • Exit 3 with a printed report. The verdict is Marginal or Failed. The report is complete and the run directory is written, but the counterfactual verbs refuse the event until the baseline is Reproduced. A script must read the exit code, not look for a report.
  • An RMSE demotion looks like a regression. The same event moves from exit 0 to exit 3 when you add --trace. The headline errors have not changed. See Replaying against a recorded trace.
  • A placeholder event exits 1. replay-event refuses an event that is not sourced from a record, naming its weakest part. Source and re-tag the figures, or study the event with scenario, fleet, evidence or h0-study.
  • An unknown id exits 1, not 2. error: Event 'nope' not found. Available: ... lists the ids in the catalogue that was read. Check that --catalog points to the file you meant, because a catalogue file replaces the built-ins rather than extending them.
  • A missing trace exits 2. error: --trace file not found: <path> is printed instead of an RMSE line, so a mistyped path never silently drops the per-sample check. A path is relative to the current directory.
  • A flag meant for another verb exits 2. replay-event accepts only --catalog, --trace, --out and --dump-catalog; replay-event gb-2023-12-22 --device-ffr 1 prints error: replay-event does not use --device-ffr (it belongs to another verb, so it would be silently ignored). .... --forming and --asset-dynamics are refused the same way.
  • Default output goes under results/ in the current directory. Pass --out for any run you intend to keep.
  • The 2023 verdict is a result. Marginal on gb-2023-12-22 is a finding about the model, not a fault to repair by editing the event.

Limits

  • A trace shorter than the simulated window gives an RMSE over the part it covers only (with a WARNING line), so two RMSE figures over different coverage are not comparable.
  • The tolerances, the RMSE bar and the 5 s inertia cross-check window are fixed in the program and have no flags.
  • The model is a single-mass swing equation with three unfitted constants. It reproduces headline RoCoF and nadir, not the sample-by-sample shape of a long excursion (2019 RMSE 0.099 Hz).
  • Only the three built-in events ship with a gate result. The scoring of any other event depends on the sourcing of the figures you supply.
  • --inertia-model distributed is not honoured by replay-event. It prints a warning and runs the lumped scalar model.