Unbalanced three-phase distribution state estimation (DSSE)

Status (verified 1.95.091): Partly implemented and experimental: the per-phase network model, three-phase backward/forward sweep, node-voltage three-phase WLS (with an optional WLAV reweighting loop), branch-current DSSE, sequence-network fault study, transformer connection model, pseudo-measurements and a strict JSON feeder loader exist, reachable from the dist3ph CLI verb. The four-wire neutral model, Carson line construction, three-phase Y-bus, converter-loss and virtual-reference-bus devices, the sparse-l1 ExtendedWlav estimator and the embedded IEEE 13/34/123 feeders are not implemented. Implemented in: src/GridSim.Core/Distribution/MultiPhaseModel.cs (MultiPhaseModel, PhaseBus, PhaseBranch, PhaseLoad, PhaseImpedance, Phase), ThreePhaseSweep.cs (ThreePhaseSweep, IMultiPhaseSolver, MultiPhaseResult, ThreePhaseSweepOptions), ThreePhaseWlsEstimator.cs (ThreePhaseWlsEstimator, ThreePhaseVMag, ThreePhaseCurrent, ThreePhaseWlsResult), BranchCurrentDsse.cs (BranchCurrentDsse, BranchCurrentEstimate), SequenceFaultStudy.cs, SymmetricalComponents.cs, TransformerConnectionModel.cs, DistributionPseudoMeasurements.cs, MultiPhaseJsonLoader.cs (MultiPhaseFeeder, MultiPhaseMeasurementSet). Design-to-code name map:

Design name Implemented as
Phase.cs ([Flags] enum Phase, PhaseSet) Phase enum in MultiPhaseModel.cs; no PhaseSet; the sweep treats every bus and branch as three-phase
PhaseImpedance.cs with FromCarson, Kron reduction PhaseImpedance in MultiPhaseModel.cs (3x3 matrix, Diagonal, Invert); no Carson or Kron code, line codes are loaded as matrices
MultiPhaseYBus.cs, PhaseSource, four-wire neutral model not implemented; PhaseBus.IsSource and SourceV carry the source
ConverterLossModel.cs, VirtualReferenceBus.cs not implemented
MultiPhaseResult.cs, IMultiPhaseSolver.cs both in ThreePhaseSweep.cs
ThreePhaseMeasurement.cs (PhaseMeasurement, PhaseMeasurementKind) ThreePhaseVMag and ThreePhaseCurrent in ThreePhaseWlsEstimator.cs; file form is MultiPhaseMeasurementSet
ThreePhaseMeasurementModel.cs, IThreePhaseStep.cs not implemented as types; the model is inside ThreePhaseWlsEstimator.Estimate
ExtendedWlav.cs (sparse-l1 LP) not implemented; ThreePhaseWlsEstimator.Estimate(..., robust: true) runs an IRLS WLAV loop
DsseEstimationResult.cs ThreePhaseWlsResult and BranchCurrentEstimate (no shared type)
FaultAnalysis.cs additive SingleLineToGround, LineLine, LineLineGround not added; FaultAnalysis keeps FaultType.SingleLineToGround reported as not representable; the unbalanced faults are SequenceFaultStudy in Distribution/ (not Protection/)
PowerFlow/BackwardForwardSweep.cs extension ThreePhaseSweep is a separate class; PowerFlow/BackwardForwardSweep.cs is unchanged
data/distribution/ieee13.json, ieee34.json, ieee123.json not present; data/dist3ph/ holds the IEEE 4-node feeder cases only

This is a design record. The current behaviour is documented in the technical manual chapter 18. Real-time, distribution and dynamic estimation (section 18.5).

Implementation-ready design for the unbalanced, per-phase distribution state-estimation subsystem: the four-wire phase-impedance network model, a three-phase backward/forward-sweep power flow, two distribution estimation paths (node-voltage WLS and branch-current DSSE), an Extended-WLAV robust estimator, sequence-network fault support, and the pseudo-measurement layer that makes an under-metered feeder observable.

This is a design an implementer follows; it contains no C#. Equations are exact; data structures are named to fit the existing code. The whole subsystem is a separate model path that leaves the positive-sequence engine (GridModel, YBus, NewtonRaphsonPowerFlow, WlsStateEstimator) untouched.

Audience: an engineer extending src/GridSim.Core. Read UnderstandingRestrictions.md and RestrictionReview.Reviewed (src/GridSim.Core/Diagnostics/RestrictionReview.cs) first - the no-forward-inference rule governs every seam here.


1. Purpose and scope

Transmission state estimation (GridSim's WlsStateEstimator) assumes a balanced, transposed, positive-sequence network: one complex voltage per bus, one pi-model 2x2 stamp per branch. Distribution feeders break every one of those assumptions:

  • Unbalanced. Phase loads differ; single- and two-phase laterals exist; the three phase voltages are genuinely distinct, not one phasor times 1<0/-120/+120.
  • Untransposed. Overhead lines and cables carry real mutual coupling between phases (and to the neutral/earth). The series impedance is a full 3x3 (or 4x4) matrix, not a scalar.
  • High R/X. Newton-Raphson conditions badly; the sweep methods are standard.
  • Radically under-metered. A feeder may have telemetry only at the primary substation, plus sparse AMI. Observability comes from pseudo-measurements.
  • Increasingly inverter-dominated. DER changes injections and, in islanded operation, removes the transmission slack that anchors the reference.

This subsystem adds:

  1. A full per-phase 3x3 phase-impedance network model (self/mutual, untransposed, missing phases) with four-wire neutral-inclusive (LV) form.
  2. Sequence networks (zero / positive / negative) derived from the phase model, enabling Protection/FaultAnalysis.cs to represent single-line-to- ground (and line-line, line-line-ground) faults it currently declines.
  3. A three-phase backward/forward-sweep power flow extending PowerFlow/BackwardForwardSweep.cs.
  4. A three-phase node-voltage WLS estimator and a distinct branch-current DSSE estimator that cross-validate each other.
  5. A balanced virtual-bus reference for islanded / high-DER unbalanced grids.
  6. Converter-loss modelling for DER/inverter injections.
  7. An Extended-WLAV (sparse-l1) robust estimator.
  8. Pseudo-measurement generation (load allocation + AMI/profile priors).
  9. Validation to machine epsilon against an independent in-house reference, cross-checked to OpenDSS and pandapower-3ph on the IEEE 13/34/123 unbalanced test feeders.

Out of scope here: harmonics, electromagnetic transients, time-series/quasi- static simulation, and any recursive dynamic estimator (those are the gated Dynamics/->Estimation/ seam, not this).


2. Restriction posture: DSSE is a filter, not a predictor

Every estimator specified here is a static, measurement-only filter: given z = h(x) + e over a fixed network, resolve the present/past state x. None integrates a process model forward. The review gate (RestrictionReview) already permits these static estimators:

Static, measurement-only estimators (WLS, Huber, LAV, constrained, feasible, QR, linear-PMU, branch-current, EWLAV) are filters, not predictors - they need no entry and are unconditionally permitted.

So the two new estimation methods named in this design - branch-current and EWLAV - are already on the permitted list. No new RestrictionReview entry is required for anything in this document, because nothing here consumes a Dynamics/ process model. If a future revision fuses a load-dynamics process model into a recursive three-phase filter, that - and only that - trips invariant #5 and must be reviewed and logged first.

The rules that DO bind this subsystem:

  • Invariant #1 (the 169h floor). Every new dated input seam calls ForwardInferenceGuard.RejectFuture before touching data: MultiPhaseMeasurementSet.Load, and any AMI / smart-meter / load-profile ingester feeding the pseudo-measurement layer. A three-phase measurement set is a dated ingester exactly like MeasurementSet (Section 16.4).
  • Invariant #2 (no future-dated output). The estimators stamp their result at the measurement window time. There is no code path that emits a state dated later than its newest input.
  • Solving vs forward inference. The three-phase power flow (Section 10) is solving - a statement about the model. Seeded from guard-permitted GB data it is reconstruction; it never nowcasts the real feeder's unpublished present or future. Pseudo-measurements (Section 16) are historical/allocation priors, not forecasts: they derive from load-research profiles, nameplate allocation, or AMI reads that are themselves >=169h old or replayed. The generator never reads the wall clock (deterministic TakenUtc), mirroring SyntheticMeasurements.
  • Balanced virtual bus (Section 11) is a numerical reference device inside the model; it invents no observation of reality.

A dedicated ThreePhaseRestrictionInvariantTests fixture asserts the guard fires on a fresh three-phase set and on a fresh AMI pseudo-source, next to the machine-epsilon checks.


3. Design principles and non-regression of the positive-sequence path

  1. Separate model path. The unbalanced world lives in a new namespace GridSim.Core.Distribution under src/GridSim.Core/Distribution/. The positive-sequence types (GridModel, Bus, Branch, YBus, NewtonRaphsonPowerFlow, BackwardForwardSweep, WlsStateEstimator, MeasurementModel) are not modified except for two purely additive things: (a) the Protection/FaultAnalysis.cs gains a new SingleLineToGround entry point (the existing ThreePhase method is byte-for-byte unchanged), and (b) Generator/Branch gain optional, defaulted sequence/grounding fields that every existing case leaves at their defaults (Section 9.4). No existing test can change behaviour.

  2. Reuse the conventions, not the code. The three-phase types mirror the existing style - sealed record data, Complex from System.Numerics, internal implementation behind public seams, PowerFlowResult-shaped results, deterministic date-literal seeds - so a reader of the transmission code is immediately at home. Where the physics forces a different choice (rectangular state, 3x3 stamps) the divergence is called out.

  3. Bridges both ways, tested to machine epsilon.

  4. GridModel.ToBalancedThreePhase() lifts a positive-sequence case into a perfectly balanced MultiPhaseModel (phase impedance = diag with the positive-sequence value, zero mutuals). Running the three-phase BFS on it and collapsing back must reproduce the positive-sequence BackwardForward Sweep/Newton result to machine epsilon. This is the master non- regression and correctness gate (Section 18.3).
  5. MultiPhaseModel.ToPositiveSequence() projects an unbalanced model onto its positive-sequence single-line equivalent (average self minus average mutual -> z1), so all existing positive-sequence tooling (contingency, boundary, export) still runs on distribution cases at reduced fidelity.

  6. Fail loud, never silently degrade. Same doctrine as the rest of the engine: an unsupported connection, a singular grounding configuration, a feeder too meshed for the sweep, or a non-finite result is reported as a typed failure status, never as a NaN dressed up as converged.


4. File and namespace layout

All new code under src/GridSim.Core/Distribution/ in namespace GridSim.Core.Distribution, except the fault additions in GridSim.Core.Protection.

src/GridSim.Core/Distribution/
  Phase.cs                     [Flags] enum Phase; PhaseSet helpers; phase masks
  PhaseImpedance.cs            NxN complex matrix value type; Carson; Kron reduction
  SymmetricalComponents.cs     A / A^-1 transform; z_abc <-> z_012
  MultiPhaseModel.cs           MultiPhaseModel, PhaseBus, PhaseBranch, PhaseLoad,
                               PhaseSource, WindingConnection, LoadConnection enums
  ConverterLossModel.cs        quadratic converter-loss record + evaluation
  VirtualReferenceBus.cs       balanced virtual-bus reference device
  MultiPhaseYBus.cs            3n x 3n (or 4-wire) sparse admittance; sequence Ybus
  MultiPhaseResult.cs          MultiPhaseResult (per-phase Vm/Va, flows, losses, status)
  IMultiPhaseSolver.cs         solver seam (parallel to IPowerFlowSolver)
  ThreePhaseSweep.cs           three-phase BFS (extends the BackwardForwardSweep idea)
  ThreePhaseMeasurement.cs     PhaseMeasurement, PhaseMeasurementKind, PhaseMeasurementSet
  ThreePhaseMeasurementModel.cs  rectangular-state h(x) and Jacobian
  IThreePhaseStep.cs           estimation-step seam (parallel to IWlsStep)
  ThreePhaseWlsEstimator.cs    node-voltage 3-phase WLS + loop
  BranchCurrentDsse.cs         distinct branch-current formulation + estimator
  ExtendedWlav.cs              sparse-l1 (LP) robust estimator
  DistributionPseudoMeasurements.cs  load-allocation + AMI/profile priors
  DsseEstimationResult.cs      result type shared by the three estimators

src/GridSim.Core/Protection/
  FaultAnalysis.cs             + SingleLineToGround / LineLine / LineLineGround (additive)
  SequenceFaultStudy.cs        sequence-network Thevenin build (new file)

data/distribution/            embedded IEEE feeders (Section 18.1)
  ieee13.json  ieee34.json  ieee123.json

Public surface: MultiPhaseModel, PhaseBus/Branch/Load/Source, Phase, ThreePhaseSweep, ThreePhaseWlsEstimator, BranchCurrentDsse, ExtendedWlav, DsseEstimationResult, MultiPhaseResult, DistributionPseudoMeasurements, the fault entry points. Implementation (step backends, LP kernels, Carson helpers) stays internal with InternalsVisibleTo("GridSim.Tests") (already granted in the csproj).


5. Phasing and the primitive/phase-impedance model

5.1 Phase identity and masks

[Flags] enum Phase { None = 0, A = 1, B = 2, C = 4, N = 8 }

A PhaseBus, PhaseBranch, PhaseLoad and PhaseSource each carry a Phase Present mask. A single-phase lateral is A; a two-phase is A | C; a full three-phase is A | B | C; the four-wire LV form adds N. All per-phase arrays and matrices are indexed by the ordered present phases (a stable ascending order A,B,C,N). PhaseSet provides Count, IndexOf(Phase), and the ordered enumeration so a 2x2 submatrix on {A,C} is handled uniformly with a 3x3 on {A,B,C}.

Missing phases are first-class: a branch's series matrix is sized to Present.Count, and a bus's state carries only its present phases. A load or source on a phase the bus does not present is a validation Error.

5.2 The primitive impedance matrix (modified Carson)

For an overhead segment with conductors indexed by {a,b,c,n,...} the primitive series impedance (ohms per unit length, per Kersting's modified Carson's equations at line frequency f, earth resistivity rho) is:

Self  (conductor i):
  z_ii = (r_i + r_earth) + j * x_factor * ( ln(1/GMR_i) + earth_term )
Mutual (i != j):
  z_ij =         r_earth  + j * x_factor * ( ln(1/D_ij)  + earth_term )

with, at 50 Hz (SI, ohms/km) :
  r_earth   = pi^2 * f * 1e-4                      (earth return resistance)
  x_factor  = 4 * pi * f * 1e-4                    (= omega * mu0 / (2 pi))
  earth_term= 0.5 * ln( rho / f ) + C_earth        (Carson earth-return const)

GMR_i is the conductor geometric mean radius; D_ij the centre-to-centre distance from geometry. PhaseImpedance.FromCarson(conductors, geometry, f, rho) computes the primitive z_prim (an N x N complex matrix) and, from the potential-coefficient matrix P (same geometry, image charges), the primitive shunt y_prim = j * omega * C_prim with C_prim = 2*pi*eps0 * P^-1.

Because published feeders (IEEE 13/34/123, OpenDSS LineGeometry) most often provide the already-reduced phase matrices directly, the primary authoring path is to supply z_abc and y_abc per segment as data; FromCarson is the constructive path for cases given as geometry + conductor tables. Both must agree to machine epsilon on a shared fixture (Section 18.5).

5.3 Kron reduction of the neutral

The four-wire primitive partitions into phase block p and neutral block n:

        [ z_pp  z_pn ]
z_prim= [ z_np  z_nn ]

Kron reduction (grounded neutral folded to earth):
  z_abc = z_pp - z_pn * z_nn^-1 * z_np        (3x3 phase impedance)

PhaseImpedance.KronReduce(neutralPhases) performs the block solve (dense complex LU on the small z_nn). The 3-wire model uses z_abc; the 4-wire model keeps z_prim un-reduced (Section 6). A PhaseBranch records which form it is in (NeutralModel = Reduced | Explicit).

5.4 Per-unit conversion

Distribution data is in physical units (ohms, siemens, kV, kVA). The model carries a per-segment length and converts to per-unit on the segment's voltage base and the system BaseMva, exactly analogous to the transmission per-unit convention (technical ch. 2). Transformer segments define a voltage-base change; the per-unit z_abc is referred to the segment's own base. A MultiPhaseModel.Validate() pass checks base continuity across each transformer.


6. Four-wire neutral-inclusive admittance (LV-LSE) with neutral coupling

For LV feeders (and MV cases where neutral/earth current matters) the neutral is kept explicit rather than Kron-folded. This is the "LV low-voltage state-estimation" (LV-LSE) form: the state carries the neutral conductor voltage, and neutral-return / earthing currents are observable.

  • A four-wire PhaseBranch has Present = A|B|C|N, a 4x4 series z_prim, a 4x4 shunt y_prim, and NeutralModel = Explicit.
  • The neutral bus voltage is a genuine state at each four-wire node (it is NOT assumed zero); multi-grounded neutrals are modelled by a shunt earthing admittance y_g from the neutral node to the ideal ground (the reference for all phase voltages). PhaseBus.NeutralGroundingSiemens gives y_g (0 = ungrounded, infinite = solidly bonded to the reference).
  • Neutral coupling enters through the off-diagonal z_prim[a..c, n] / y_prim[..., n] terms exactly as for any other conductor; nothing special is needed in the sweep or the Y-bus once N is treated as a fourth phase index.

The 4-wire Y-bus is 4-present x 4-present per node. Grounding admittances stamp the neutral diagonal. Kron reduction (Section 5.3) is exactly the operation that maps a solved four-wire result onto the three-wire equivalent, so the two forms are cross-checked: solving the explicit four-wire model and Kron-reducing the voltages must match the reduced-model solve to machine epsilon on a common grounded case (Section 18.5).

The estimator treats the neutral phase identically to A/B/C: a four-wire node contributes 2 * Present.Count rectangular state components. Voltage/current measurements can address the neutral (Phase.N) - a neutral-current meter is a strong LV-LSE observation of unbalance.


7. The multi-phase network model

MultiPhaseModel (sealed class, parallels GridModel):
  double BaseMva
  double FrequencyHz          (default 50)
  IReadOnlyList<PhaseBus>     Buses
  IReadOnlyList<PhaseBranch>  Branches
  IReadOnlyList<PhaseLoad>    Loads
  IReadOnlyList<PhaseSource>  Sources         (slack / DER / grid-forming)
  VirtualReferenceBus?        VirtualReference (Section 11; null on grid-tied)
  string Name
  IReadOnlyList<GridDiagnostic> Validate()    (same diagnostic type as GridModel)
PhaseBus (sealed record):
  int Id
  Phase Present
  double BaseKv                    (line-to-line nominal)
  Complex NeutralGroundingSiemens  (per-unit; 4-wire only)
  double[] VmInitPu, VaInitDeg     (per present phase; flat-start default)

PhaseBranch (sealed record):
  int From, To
  Phase Present
  NeutralModelKind NeutralModel    (Reduced | Explicit)
  PhaseImpedance Zseries           (present x present, per-unit)
  PhaseImpedance Yshunt            (present x present, per-unit; split half/half)
  BranchKind Kind                  (Line | Cable | Transformer | Switch | Regulator)
  WindingConnection FromConn, ToConn   (transformer only; else Wye by default)
  double TapRatio                  (regulators/transformers; per phase optional)
  double[]? PhaseTapRatio          (independent per-phase regulator taps)
  string? Name
  bool InService

PhaseLoad (sealed record):
  int Bus
  LoadConnection Connection        (Wye | Delta)
  Phase Phases
  LoadModel Model                  (ConstantPower | ConstantCurrent | ConstantImpedance | ZIP)
  double[] Pkw, Qkvar              (per phase, or per phase-pair for Delta)
  ZipCoefficients? Zip

PhaseSource (sealed record):
  int Bus
  SourceRole Role                  (Slack | GridForming | GridFollowingPV | GridFollowingPQ)
  Phase Phases
  double[] Vsetpu, Vsetdeg         (per phase; Slack/GridForming)
  double[] Pkw, Qkvar              (GridFollowing)
  ConverterLossModel? Converter    (Section 12)
  Complex SequenceZ1, SequenceZ2, SequenceZ0   (machine/inverter sequence
                                                 impedances for fault studies)
  Complex NeutralGroundingZPu      (source neutral earthing; 0 = solidly grounded)

WindingConnection { Wye, WyeGrounded, Delta } and LoadConnection { Wye, Delta } capture the connection algebra that drives both the sweep transformer matrices (Section 10.4) and the zero-sequence network (Section 8.3).

Validate() reuses ValidationSeverity/GridDiagnostic and reports: a load or source on an absent phase (Error), no slack and no virtual reference (Error), a non-finite matrix entry (Error), a transformer base discontinuity (Error), an unsupported connection pair (Error), a delta load on a bus missing a required phase (Error), and an ungrounded four-wire island (Warning - it will float).


8. Multi-phase Y-bus and the sequence networks

8.1 Phase-domain Y-bus

MultiPhaseYBus.BuildSparse(model) produces a sparse per-phase admittance keyed by (busIndex, phase) compound indices, mirroring YBus.BuildSparse. Each in-service branch stamps its 2x2 block-of-blocks:

For a line/cable segment with series admittance Ys = Zseries^-1 (present x present)
and half shunt Bsh = 0.5 * Yshunt:
  Y[f,f] += Ys + Bsh
  Y[t,t] += Ys + Bsh
  Y[f,t] += -Ys
  Y[t,f] += -Ys

where each entry is itself a present x present complex matrix. For missing phases the submatrices are sized to the branch's present set and scattered into the matching phase slots of the two buses. Transformers stamp their connection- dependent nodal blocks (Section 10.4 gives the primitive per-connection admittance Yprim used identically here). Bus shunts and neutral-grounding admittances land on the diagonal. Determinism: stamps are visited in model order with a fixed accumulation order so each cell is bit-reproducible (same doctrine as YBus.BuildSparse).

8.2 Symmetrical-component transform

a = exp(j*2*pi/3)
      [ 1   1    1  ]              1     [ 1   1    1  ]
A =   [ 1   a^2  a  ]     A^-1 = ----- * [ 1   a    a^2]
      [ 1   a    a^2]              3     [ 1   a^2  a  ]

Sequence impedance of a 3x3 phase matrix:
  z_012 = A^-1 * z_abc * A

SymmetricalComponents provides A, Ainv, ToSequence(z_abc) and ToPhase(z_012). For a transposed line z_abc has equal diagonals and equal off-diagonals, so z_012 = diag(z0, z1, z2) exactly with

z0 = z_self + 2*z_mutual
z1 = z2 = z_self - z_mutual

For an untransposed line z_012 is full (inter-sequence coupling); the sequence networks are then coupled. The fault study (Section 9) uses the exact z_012 blocks; the common decoupled approximation (diagonal only) is available behind a flag for comparison to hand calculations, and the design records that the exact coupled form is the default so untransposed feeders are not silently approximated.

8.3 Sequence Y-bus / Z-bus

SequenceFaultStudy.Build(model) assembles three nodal networks:

  • Positive (1) and negative (2). For passive plant Y1 = Y2; they are the balanced single-phase network already produced by the positive-sequence path, reusable directly. Sources contribute 1/Z1 and 1/Z2 shunts (machine or inverter sequence impedance from PhaseSource).
  • Zero (0). Assembled from the zero-sequence line impedance z0 and, per transformer, the connection-dependent zero-sequence coupling:
  • WyeGrounded - WyeGrounded: passes zero-sequence through (series z0).
  • WyeGrounded - Delta: zero-sequence sees the grounded-wye winding to ground but is blocked to the delta side (shunt on the grounded side, open across).
  • Delta - Delta / Wye(ungrounded): blocks zero-sequence (open).
  • A grounded source neutral adds 3 * Zn in the zero-sequence path (3 * NeutralGroundingZPu).

The zero-sequence network topology is therefore genuinely different from the positive-sequence one - which is exactly why single-line-to-ground currents cannot be obtained from the positive-sequence model alone, and why the current FaultAnalysis reports SLG as not-representable.


9. Single-line-to-ground faults via sequence networks

This is the additive extension to Protection/FaultAnalysis.cs that lets the protection overlay operate on earth faults.

9.1 Thevenin sequence impedances at the fault bus

For fault bus k, solve one column of each sequence Z-bus (one complex linear solve per sequence, reusing the dense SolveComplex already in FaultAnalysis.cs):

Z1_kk = e_k^T * Y1^-1 * e_k
Z2_kk = e_k^T * Y2^-1 * e_k
Z0_kk = e_k^T * Y0^-1 * e_k

with prefault (positive-sequence) voltage E_k = V0_k at the fault bus taken from the prefault solved state (the same prefault-voltage source the existing ThreePhase uses).

9.2 Fault-type connection of the sequence networks

Single-line-to-ground (phase a), fault impedance Zf:
  I_a0 = I_a1 = I_a2 = E_k / (Z0_kk + Z1_kk + Z2_kk + 3*Zf)
  Phase currents:  I_abc = A * [I_a0; I_a1; I_a2]
  (=> I_b = I_c = 0 for a pure a-g fault, the physical signature)

Line-to-line (b-c), impedance Zf:
  I_a1 = -I_a2 = E_k / (Z1_kk + Z2_kk + Zf) ;  I_a0 = 0

Double line-to-ground (b-c-g):
  standard parallel combination of Z2 and (Z0 + 3*Zf) fed from Z1.

Faulted sequence voltages V_012(i) = V0_012(i) - Z_seq[:,k] * I_seq per network, then per-bus phase voltages V_abc = A * V_012; faulted phase branch currents follow from the phase-domain stamps (Section 8.1) at the faulted voltages, driving the protection elements exactly as ThreePhase does today.

9.3 Result and API

FaultAnalysis.SingleLineToGround(MultiPhaseModel model, MultiPhaseResult prefault,
    int faultBusId, Phase faultedPhase = Phase.A, double faultReactancePu = 0.0)
    -> MultiPhaseFaultResult
FaultAnalysis.LineLine(...)         FaultAnalysis.LineLineGround(...)

MultiPhaseFaultResult carries the faulted MultiPhaseResult, the per-phase fault current (pu and kA when BaseKv known), and the sequence currents for provenance. The existing balanced ThreePhase(GridModel, ...) overload is untouched; a new ThreePhase(MultiPhaseModel, ...) overload is the three-phase sibling (three-phase-to-ground = the balanced limit, a consistency check: sequence-network SLG with all three phases faulted must equal the direct phase-domain three-phase fault to machine epsilon).

9.4 Additive model fields

Generator and Branch in Model/Model.cs gain optional, defaulted fields so a positive-sequence case can still be fault-studied for SLG by supplying sequence data without a full phase model:

  • Generator: SequenceZ2Pu, SequenceZ0Pu, NeutralGroundingZPu (defaults: Z2 = Z1 synthesised, Z0 open, Zn = 0).
  • Branch: WindingConnection FromConn, ToConn (default WyeGrounded), SequenceZ0Pu (default: 3*Z1 overhead rule-of-thumb, provenance-noted).

Every existing case leaves these at defaults, so no positive-sequence test moves.


10. Three-phase backward/forward-sweep power flow

ThreePhaseSweep : IMultiPhaseSolver extends the algorithm in PowerFlow/BackwardForwardSweep.cs from scalars to present x present complex matrices/vectors. It is the reference truth for the estimators and the seed for warm starts.

10.1 State and structure

Voltages and currents become per-bus complex phase vectors V[bus] in C^{present}, I[bus] in C^{present}. Series impedances are the PhaseImpedance matrices. The spanning-tree / breakpoint machinery, PV-bus reactive correction, and weak-mesh compensation from the scalar sweep carry over unchanged in structure; only the per-edge algebra becomes matricial. The MaxCompensatedLoops gate and the "disconnected / too meshed -> non-radial report" fallbacks are preserved.

10.2 Backward sweep (leaves -> source)

For each bus in reverse tree order, accumulate the nodal injection current (load + shunt + DER) plus the accumulated child-branch currents, transformed across each child branch's connection matrix:

I_series[k] = sum over children c ( T_i(conn_k) * I_series[c] ) + I_node[bus]

I_node[bus] is the per-phase current the bus draws (Section 10.5). T_i is the branch current-transformation matrix (identity for a plain line; connection- dependent for transformers/regulators, Section 10.4).

10.3 Forward sweep (source -> leaves)

V[child] = T_v(conn_k) * V[parent] - Zseries_k * I_series[k]

T_v is the branch voltage-transformation matrix (identity for a plain line; the ideal-transformer ratio/connection for transformers). Convergence is on max over (bus,phase) |V - V_prev| < Tolerance, matching the scalar sweep's maxDelta contract, with the same NonFinite guard and status doctrine.

10.4 Transformer / regulator connection matrices

Each supported connection contributes a 6x6 primitive [Yprim] (equivalently the (T_v, T_i, Zseries) triple) per Kersting's generalized matrices [a],[b],[c],[d],[A],[B]:

V_abc(from) = a * V_abc(to) + b * I_abc(to)
I_abc(from) = c * V_abc(to) + d * I_abc(to)
V_abc(to)   = A * V_abc(from) - B * I_abc(to)

Connections supported at v1: WyeGrounded-WyeGrounded, Delta-WyeGrounded (the ubiquitous distribution step-down, with its 30-degree/1/sqrt3 shift), WyeGrounded-Delta, Delta-Delta, and the step/voltage regulator (per-phase tap on a wye or closed-delta). Each connection's [a..d,A,B] matrices are tabulated constants times the per-unit turns ratio; the design lists them explicitly in the implementation notes and each is unit-tested against a single-transformer hand calculation.

10.5 Load and source current models

Wye constant-power (phase p):   I_p = conj( S_p / V_p )
Wye constant-impedance:         I_p = V_p / Z_p          (Z_p from nameplate S,V)
Wye constant-current:           I_p = |I_p0| at fixed pf, angle tracks V_p
Delta constant-power (pair pq): I_pq = conj( S_pq / (V_p - V_q) ),
                                nodal current = I_pq - I_(previous pair into p)
ZIP: convex combination of the three above by (Zip.z, Zip.i, Zip.p) with z+i+p=1

DER GridFollowingPQ sources inject -I of the constant-power form at their setpoint (converter loss applied, Section 12); GridFollowingPV sources hold per-phase (or positive-sequence) voltage magnitude via the reactive correction already in the scalar sweep, generalized per phase.

10.6 Result

MultiPhaseResult mirrors PowerFlowResult: per-(bus,phase) Vm/VaDeg, per-phase net injections, per-branch per-phase flows and losses, total loss, and a MultiPhaseStatus { Converged, MaxIterations, NonFinite, NonRadial }. A ToPositiveSequence() collapses it to a PowerFlowResult for the existing UI / export plumbing (positive-sequence component of the solved phase voltages).


11. Balanced virtual-bus reference for islanded / high-DER grids

A grid-tied feeder inherits its angle/voltage reference from the transmission slack (the primary substation PhaseSource with Role = Slack). An islanded microgrid (grid-forming inverters, no transmission connection) has no such anchor, and its unbalance means there is no single "correct" reference phasor.

VirtualReferenceBus provides a balanced virtual bus: an internal, perfectly-balanced positive-sequence source E * [1, a^2, a] behind a small virtual series impedance Zv, attached to a nominated physical bus (usually the dominant grid-forming unit's terminal). It:

  1. Fixes the angle datum. The virtual bus's phase-a angle is 0 by definition, so the sweep and the estimator have a well-defined reference even when every physical source is grid-forming and imbalanced.
  2. Absorbs residual imbalance during the solve (it is the slack of the islanded network), while Zv keeps its influence local and physically interpretable rather than clamping the nearby physical bus to perfect balance.
  3. Grounds the sequence decomposition. Because it is balanced, V_012 at the virtual bus is pure positive-sequence, giving the fault study a clean reference and the estimator a stable positive-sequence datum.

Design points: - Zv is a design parameter (default: a few percent on the unit's base) chosen large enough not to distort the local unbalance yet small enough to anchor the solve; the sensitivity is documented and tested. - In the estimator, the virtual bus's three voltages are fixed reference states (removed from the free state, exactly as slack angles are removed in the transmission estimator), so it adds a datum, not free unknowns. - It is a model device, not an observation: it asserts nothing about the real grid and therefore raises no restriction concern. It appears in provenance as a synthetic reference so no consumer mistakes it for a metered bus.

Selection rule: if Sources contains a Slack, the virtual bus is off by default; if the model is islanded (no Slack), a VirtualReferenceBus is required or Validate() reports "no reference (Error)".


12. Converter-loss modelling

Inverter-interfaced DER (and any power-electronic converter) dissipates a current-dependent loss that a naive constant-power injection ignores, biasing both the power flow and the estimated DER output. Model it as the standard quadratic in converter current magnitude:

P_loss = a0 + a1 * |I_conv| + a2 * |I_conv|^2
ConverterLossModel (sealed record):
  double A0Kw     (no-load / switching loss)
  double A1       (conduction, linear, kW per pu-amp)
  double A2       (resistive, quadratic, kW per pu-amp^2)
  double Evaluate(double iConvMagPu)     -> P_loss (kW)

Placement: - Power flow. In the source current model (Section 10.5), the AC-side real injection is reduced by P_loss (the loss appears on the DC/prime-mover side); |I_conv| is the AC current the sweep already computes, so the correction is a fixed-point term evaluated each sweep - it converges with the outer iteration. - Estimation. When a measurement observes the DC-side or nameplate power and the state carries AC-side voltage/current, the loss enters h(x) as the same quadratic; its Jacobian contribution is dP_loss/d|I| = a1 + 2*a2*|I| chained through d|I|/dx. This keeps an estimated DER injection physically consistent with its metered AC current instead of over-crediting output by the loss.

The loss model is optional per source (null = ideal converter); coefficients are authored from datasheet efficiency curves and provenance-noted. A converter-loss consistency test checks that the power-flow AC/DC balance closes to machine epsilon for a chosen (a0,a1,a2).


13. The three-phase node-voltage WLS estimator

ThreePhaseWlsEstimator is the direct three-phase analogue of WlsStateEstimator, and its structure deliberately mirrors it (loop owns start point, damping, convergence, chi-square, bad-data removal; representation lives behind IThreePhaseStep). Two deliberate divergences from the transmission estimator, both standard DSSE practice:

13.1 Rectangular state

The state is rectangular voltage per present phase:

x = [ Vre(bus,phase), Vim(bus,phase) ]  over all buses and present phases,
    minus the reference bus/virtual-bus phases (fixed datum)

Rectangular coordinates are chosen because (a) current and power measurement Jacobians are lower-order and better-conditioned on stiff, high-R/X feeders, (b) there is no per-phase angle-wrap or reference-degeneracy pathology, and (c) the branch-current path (Section 14) shares the rectangular convention so the two estimators compare directly. The divergence from the transmission estimator's polar (Va, Vm) state is intentional and documented; the balanced-case bridge (Section 18.3) reconciles the two to machine epsilon.

The reference datum (slack PhaseSource phases, or the VirtualReferenceBus phases) is fixed and removed from the free state, exactly as slack angles are removed in the transmission MeasurementModel.

13.2 Measurement kinds and h(x)

PhaseMeasurementKind:
  VmPu        (per bus,phase)            h = sqrt(Vre^2 + Vim^2)
  VaRad       (per bus,phase; PMU)       h = atan2(Vim, Vre) - ref
  VreVim      (PMU rectangular pair)     h = Vre ; h = Vim        (linear)
  PInjKw      (per bus,phase)            h = Re( V_p * conj( sum_k Y_pk V_k ) )
  QInjKvar    (per bus,phase)            h = Im( V_p * conj( sum_k Y_pk V_k ) )
  PFlowKw     (per branch end,phase)     h = Re( V_p * conj( I_flow_p ) )
  QFlowKvar   (per branch end,phase)     h = Im( V_p * conj( I_flow_p ) )
  IMagPu      (per branch end,phase)     h = |I_flow_p|
  IReIm       (PMU branch current pair)  h = Re/Im( I_flow_p )    (linear)
  IneutralPu  (four-wire neutral current)                        (LV-LSE)

I_flow uses the phase-domain branch stamps from Section 8.1. Injection sums run over the bus's electrical neighbourhood only (the same O(nnz) sparse-injection discipline as MeasurementModel.ComputeInjectionsSparse), and there is a single Jacobian evaluation path writing into a dense or sparse sink, mirroring EvaluateJacobian<TSink> so the dense and sparse backends cannot drift.

13.3 Jacobians (rectangular)

With E_p = Vre_p + j Vim_p and nodal current Ii_p = sum_k Y_pk E_k (each Y_pk a scalar phase-to-phase admittance from the block matrix), the exact partials are the standard rectangular DSSE forms, e.g. for the linear/near-linear kinds:

VreVim:   dVre/dVre = 1, all else 0                        (constant, linear)
VmPu:     d|V|/dVre = Vre/|V| ,  d|V|/dVim = Vim/|V|
Pinj_p:   dP/dVre_p , dP/dVim_p , dP/dVre_k , dP/dVim_k
          from d/dx of Re( E_p * conj(sum_k Y_pk E_k) )    (bilinear -> linear-in-x partials)

Because P/Q injections and flows are bilinear in the rectangular state, the partials are affine in x; |V| and |I| add the only genuinely nonlinear rows. This is why rectangular DSSE converges in very few Gauss-Newton steps and why the gain is nearly constant - exploited in the branch-current path (Section 14) and noted as a conditioning advantage here.

13.4 Loop, damping, observability, bad data

Reused wholesale from the transmission estimator's doctrine: - Gauss-Newton on the normal equations G = H^T W H, G dx = H^T W (z - h), with W = diag(1/sigma^2). - Trust-region damping on ||dx|| (rectangular components share one cap; the angle/Vm split is not meaningful in rectangular coordinates, so a single per-component cap is used). - Observability by gain rank (dense) / unmeasured-island sweep (sparse), reusing the ObservabilityReport type and doctrine (Rank = -1 on the sparse backend). - Chi-square consistency (ChiSquare.Quantile, reused unchanged) and largest- normalised-residual bad-data removal with critical-measurement protection. - Zero-injection buses (no load, no source) are exact equality constraints via the same Hachtel/KKT mechanism as ConstrainedDenseWlsStep (Source == "virtual-zero-injection"), which is heavily used on feeders (every branchless junction is a zero-injection node).

DsseEstimationResult mirrors EstimationResult (status, converged, iterations, per-phase Vm/VaDeg, objective, dof, chi-square verdict, residual table, removals, observability), plus a ToMultiPhaseResult(model) projector analogous to EstimationResult.ToPowerFlowResult (pure evaluation, no solve - so no-forward-inference holds).


14. Branch-current DSSE (distinct estimation path)

A structurally different estimator that cross-validates the node-voltage WLS - the classic branch-current-based DSSE (Baran/Kelley), which is the distribution workhorse because its gain is nearly constant on radial feeders.

14.1 State

x = [ Ire(branch,phase), Iim(branch,phase) ]  over all branches and present phases

i.e. the complex series current of every branch per phase (rectangular). For a radial feeder with b branches and 3 phases the state is 6b; bus voltages are recovered from the branch currents by a forward sweep from the reference, not carried as state.

14.2 Measurement equations

  • Branch current (magnitude or PMU rectangular). Linear in the state - h = Ire / Iim or |I| directly. This is the natural, best-conditioned distribution measurement and makes H almost constant.
  • Branch power flow. S = V * conj(I); with V obtained from the current state by the forward sweep, P/Q flow rows are bilinear, evaluated at the swept voltages.
  • Injection. A bus injection is the (connection-resolved) sum of the incident branch currents times the bus voltage: S_inj = V_bus * conj( sum incident I ).
  • Voltage magnitude. |V_bus|, with V_bus from the forward sweep - the only rows coupling distant branches, and the reason a small number of voltage measurements is needed for the magnitude datum.

14.3 Why it is a distinct path, not a reformulation

The Jacobian topology is fundamentally different (branch-indexed, near-constant), the gain factorisation can be reused across iterations, and the two estimators have different numerical failure modes - so agreement between the node-voltage WLS and the branch-current DSSE on the same measurement set is a strong cross-check (Section 18.4), the same philosophy as GridSim's dense/sparse and Newton/BFS cross-validation. BranchCurrentDsse is a separate public estimator (not an IThreePhaseStep), returning the same DsseEstimationResult so callers and tests treat the three estimators uniformly.

14.4 Restriction note

Branch-current DSSE is explicitly on the permitted whitelist in the review gate (RestrictionReview): branch-current estimators are filters, not predictors. It is measurement-only, emits a present/past state, and needs no review entry.


15. Extended-WLAV robust estimator (sparse-l1)

ExtendedWlav implements the weighted least-absolute-value estimate as an exact linear program, "extended" to carry equality and inequality constraints - the robust sibling of the approximate IRLS-LAV already in the transmission estimator.

15.1 Formulation

WLAV minimises the weighted l1 norm of residuals:

min_x  sum_i  w_i * | z_i - h_i(x) |

Linearised at the operating point (H = Jacobian, r = z - h(x_bar), dx = x - x_bar), each Gauss-Newton step is the LP:

min   sum_i w_i (u_i + v_i)
s.t.  H dx - u + v = r
      u, v >= 0                          (u,v = pos/neg residual parts)
[extended]  C dx = d_c                   (zero-injection equalities)
            x_lo <= x_bar + dx <= x_hi   (state box, when Feasible-style guard on)

Solved by a sparse primal-dual interior-point method (or the equivalent sparse simplex on the dual), reusing the CSR/CSC + Gilbert-Peierls sparse LU already in GridSim.Core.Numerics for the KKT/normal-step factorisation. The outer Gauss-Newton loop re-linearises until ||dx|| meets tolerance.

15.2 Why WLAV, and why "extended"

  • Robustness by construction. The l1 estimate is insensitive to a bounded number of gross errors without an explicit detection-and-removal loop: a single bad measurement in a redundant set is fit with zero weight at the LP vertex. This is valuable on distribution data where pseudo-measurements and AMI reads carry heavy-tailed errors that break the Gaussian assumption behind WLS.
  • Extended = the same estimate honours hard zero-injection equalities (ubiquitous on feeders) and optional state boxes (voltage admissibility), reusing the constrained/feasible doctrine rather than the huge-weight trick.

15.3 Determinism and restriction

The LP uses a fixed pivot/ordering rule and a fixed starting point, so the vertex selected is deterministic and byte-reproducible (a determinism test pins it). On clean Gaussian data WLAV agrees with the node-voltage WLS to a documented tolerance (they minimise different norms, so not to machine epsilon, but close); on data with one injected gross error, WLAV's estimate is unmoved while WLS requires its removal loop - the discriminating test. EWLAV is on the permitted whitelist; it is measurement-only and needs no review entry.


16. Pseudo-measurement generation

Feeders are under-determined by real telemetry alone. DistributionPseudo Measurements makes a case observable by generating priors - the distribution analogue of SyntheticMeasurements + MeasuredInjectionPrior.

16.1 Sources of pseudo-measurements

  1. Nameplate / kVA allocation. Distribute a measured feeder-head load onto downstream buses in proportion to connected transformer kVA (or contract capacity), per phase. Sigma is large (typically 30-50% of value) - these are weak priors, not observations.
  2. Load-research / AMI profile priors. Where historical smart-meter or load-research class profiles exist, the expected per-phase demand at a bus and time-of-day is a pseudo-measurement with a tighter (profile-derived) sigma.
  3. Zero-injection equalities. Every branchless junction / pure connection node injects exactly zero on every present phase - authored as Source == "virtual-zero-injection" rows the constrained/EWLAV paths promote to hard equalities (Sections 13.4, 15).
  4. Voltage-schedule prior. A flat or regulator-scheduled voltage magnitude at unmetered buses at a loose sigma, the distribution version of the transmission pseudo-voltage-schedule prior.

16.2 Sigma model and provenance

Each pseudo-measurement carries a Source tag naming its composition (pseudo-alloc-kva, pseudo-ami-profile, virtual-zero-injection, pseudo-voltage-schedule), with sigmas combined root-sum-square, exactly the GDA sigma-model convention documented for the transmission estimator. This lets the bad-data / robust logic treat weak priors appropriately (never removing a zero-injection equality; down-weighting a 40%-sigma allocation before a 2%-sigma metered flow).

16.3 Determinism

Same discipline as SyntheticMeasurements: one seeded RNG (date-literal default seed), buses/branches walked in model order, Box-Muller Gaussians, NoiseScale = 0 draws nothing (exact-recovery fixture). The generator never reads the wall clock; TakenUtc is an explicit, safely-historical parameter.

16.4 Restriction: pseudo-measurements are historical priors, not forecasts

This is the load-bearing restriction point for the pseudo-measurement layer:

  • A pseudo-measurement encodes what a load typically was (allocation, historical profile), not what the feeder will do or is secretly doing now. It is a prior over the past/present state the estimator is reconstructing, never a forward projection of the real grid.
  • Any real AMI / profile input is a dated ingester and passes ForwardInferenceGuard.RejectFuture at load: profiles must be >=169h old or replayed. MultiPhaseMeasurementSet.Load horizon-checks its TakenUtc like MeasurementSet.Load does.
  • The generated set's timestamp is the reconstruction window's, so invariant #2 (no future-dated output) holds through the estimate.

17. Seams to extend (summary)

New seams, each a clean parallel to an existing one - no existing interface is widened:

New seam Parallels Purpose
IMultiPhaseSolver (Solve -> MultiPhaseResult) IPowerFlowSolver three-phase power flow
ThreePhaseSweep BackwardForwardSweep the v1 solver behind that seam
IThreePhaseStep (Begin/GateObservability/TrySolve/NormalizedResiduals) IWlsStep dense/sparse three-phase WLS backends
ThreePhaseEstimationMethod { Wls, BranchCurrent, Ewlav } EstimationMethod method selection; all three whitelisted
PhaseMeasurementKind MeasurementKind per-phase measurement vocabulary
MultiPhaseYBus / SequenceFaultStudy YBus phase and sequence admittances
DistributionPseudoMeasurements SyntheticMeasurements + MeasuredInjectionPrior observability priors

Method selection: rather than overloading the transmission EstimationMethod enum (which is bound to the positive-sequence WlsStateEstimator), the distribution estimators take a sibling ThreePhaseEstimationMethod. The names Wls, BranchCurrent, Ewlav map onto the permitted whitelist entries, and a comment in the enum cross-references RestrictionReview so the whitelist coverage is discoverable at the call site. Huber/Lav/Constrained/ Feasible are available on the node-voltage path by reusing the IRLS/KKT/box mechanisms behind IThreePhaseStep.

The RestrictionReview.AssertPermitted call is present at the head of every estimator (as it is for the transmission estimator); because none of these methods usesDynamicsModel, the gate passes them unconditionally, and RestrictionInvariantTests continues to assert the code table and the log agree.


18. Validation and test plan

The gate for merge: the full existing suite stays green (no positive-sequence regression) and the new suite below passes, under TreatWarningsAsErrors.

18.1 Reference feeders

Embed the IEEE 13-, 34-, and 123-bus unbalanced test feeders as data/distribution/ieee{13,34,123}.json (a faithful transcription of the IEEE PES / OpenDSS feeder data: line geometries or reduced phase matrices, spot and distributed loads, regulators, transformers, capacitors, phasing). Add them as EmbeddedResource with stable logical names (GridSim.Core.cases.dist.ieee13.json, ...), exactly like the MATPOWER case*.m resources. A DistributionCases factory (parallel to IeeeCases) materialises them into MultiPhaseModel.

18.2 Machine-epsilon vs an independent in-house reference

"Machine epsilon" is asserted against a second, structurally-different in-house solver, not against OpenDSS (whose reported precision is limited). The independent reference is a direct nodal-admittance (Y-bus) fixed-point / full 3n-dimension Newton three-phase power flow (a different algorithm from the BFS): its converged phase voltages must agree with ThreePhaseSweep to < 1e-9 pu on all three feeders. This is the same doctrine as the transmission Newton-vs-BFS and dense-vs-sparse cross-checks.

18.3 Non-regression / balanced-bridge (the master gate)

  • GridModel.ToBalancedThreePhase() on each MATPOWER case, solved by ThreePhaseSweep, collapsed via ToPositiveSequence(), must reproduce the positive-sequence BackwardForwardSweep (radial cases) and Newton result to < 1e-10 pu. This proves the three-phase machinery is correct AND that the positive-sequence path is untouched.
  • Every pre-existing test (power flow, transmission estimation, fault ThreePhase, protections) is asserted byte-identical - the additive model fields default to no-ops.

18.4 Estimator correctness and cross-agreement

  • Exact recovery. A full, exact (NoiseScale = 0) three-phase measurement set recovers the ThreePhaseSweep truth to < 1e-10 for the node-voltage WLS and the branch-current DSSE on all three feeders (mirrors WlsEstimatorTests.AssertRecoversTruth).
  • Cross-estimator. Node-voltage WLS, branch-current DSSE, and EWLAV agree on clean noisy data to a documented tolerance (WLS==BCDSSE to ~1e-8; EWLAV close, different norm).
  • Bad data. With one injected gross error, WLS's removal loop identifies and removes it; EWLAV's estimate is unmoved without removal. Both restore the truth within the clean-data band.
  • Observability. A feeder stripped to below observability reports Unobservable with the free directions named; adding the pseudo-measurement layer restores observability - a direct test of Section 16.

18.5 Model-layer checks

  • Carson vs supplied matrices. PhaseImpedance.FromCarson on a geometry with a published reduced matrix matches the supplied z_abc to machine epsilon.
  • Kron consistency. Four-wire explicit solve, Kron-reduced, equals the reduced three-wire solve on a common grounded case (Section 6).
  • Sequence identities. For a transposed line, z_012 = diag(z0,z1,z2) to machine epsilon; A * A^-1 = I.
  • Fault checks. SLG at a bus: I_a0 = I_a1 = I_a2 and I_b = I_c = 0 for a pure a-g fault (to machine epsilon); a symmetric three-phase-to-ground SLG-limit equals the direct phase-domain three-phase fault; magnitudes cross-checked to an OpenDSS FaultStudy to its reported precision.
  • Converter loss. AC/DC balance closes to machine epsilon for a chosen (a0,a1,a2); a zero-loss model reproduces the ideal-source solve exactly.

18.6 Cross-check to OpenDSS / pandapower-3ph

Under tools/crossval/ (parallel to the existing pandapower cross-validation), scripts export each feeder solve and estimate and compare against OpenDSS (Solve, Export Voltages) and pandapower three-phase (pandapower.pf. runpp_3ph, pandapower.estimation where applicable). Agreement is asserted to each tool's published precision (typically 1e-4..1e-6 pu), with the in-house machine-epsilon check (18.2) carrying the tight bound. Differences are documented, not silently tolerated.

18.7 Determinism

Byte-identical results across repeated runs and (CI) across platforms: the pseudo-measurement RNG is seeded, the sweep and estimator visit model order, the sparse orderings are deterministic, and the EWLAV LP uses a fixed pivot rule. A determinism fixture hashes the solved/estimated arrays and pins the hash.

18.8 Restriction invariants

ThreePhaseRestrictionInvariantTests: MultiPhaseMeasurementSet.Load rejects a TakenUtc newer than UtcNow - 169h; an AMI pseudo-source rejects a fresh stamp; the estimators emit a state stamped no later than their newest input; and RestrictionReview needs (and gains) no new dynamics-fused entry for any method here.


19. Build-gate and coding-standard conformance

The repo builds pedantically: TreatWarningsAsErrors=true, EnableNETAnalyzers, AnalysisMode=Recommended, Nullable=enable (root Directory.Build.props). The new code must land at zero warnings:

  • Nullable-clean: no ! dammit operators without justification; seams return non-null or typed-empty (Array.Empty<T>()), matching the existing style.
  • sealed on every concrete class not designed for extension (all of them); internal implementation with InternalsVisibleTo("GridSim.Tests").
  • No unused parameters/usings/locals; static where the analyser asks; culture- invariant parsing/formatting for the feeder JSON loader (CultureInfo. InvariantCulture, as MeasurementSet.TryResolveBranch already does).
  • Deterministic APIs: any Random is seeded from an explicit option, never the default clock-seeded ctor (an analyser/determinism concern both).
  • Complex/matrix value types (PhaseImpedance) implement value equality and guard against non-finite entries at construction, consistent with the model's finite-input validation doctrine.
  • XML doc comments on every public member (the codebase documents densely; the analyser set and the house style both expect it).

CI runs dotnet build -warnaserror and the full dotnet test; both must be green before the positive-sequence path is considered non-regressed.


20. Restriction invariants honoured (checklist)

Invariant (UnderstandingRestrictions.md) How this design honours it
#1 169h floor at every dated ingester MultiPhaseMeasurementSet.Load and every AMI/profile source call ForwardInferenceGuard.RejectFuture
#2 no future-dated output estimators stamp at the window time; ToMultiPhaseResult/ToPowerFlowResult are pure evaluation
#3 solver forward trajectories are model output the three-phase power flow is solving; seeded only from guard-permitted data; never presented as a feeder forecast
#4 real-time on replay/permitted-age only DSSE estimates present/past from permitted-age or replayed three-phase sets, never live feeder telemetry
#5 Dynamics->Estimation fusion is gated nothing here consumes a Dynamics/ process model; all methods are static filters; no new review entry needed (branch-current, EWLAV already whitelisted)

The pseudo-measurement layer is the subtlety: it is explicitly a historical/ allocation prior over the reconstructed state, not a forecast, and it is horizon-guarded like every other dated input. The balanced virtual bus is a model device that asserts nothing about reality.


21. Implementation phasing

A suggested build order that keeps the suite green at each step:

  1. Model + Y-bus (Sections 5-8.1): Phase, PhaseImpedance (+ Carson/Kron), MultiPhaseModel and records, MultiPhaseYBus, Validate, the balanced- bridge ToBalancedThreePhase/ToPositiveSequence. Gate: 18.3, 18.5.
  2. Three-phase power flow (Section 10): ThreePhaseSweep, MultiPhaseResult, the independent Newton reference. Gate: 18.2, 18.3.
  3. Sequence networks + faults (Sections 8.2-8.3, 9): SymmetricalComponents, SequenceFaultStudy, FaultAnalysis.SingleLineToGround and additive fields. Gate: 18.5 fault checks.
  4. Node-voltage WLS (Section 13): measurement model, IThreePhaseStep dense backend, loop, chi-square/bad-data reuse. Gate: 18.4 exact recovery.
  5. Pseudo-measurements (Section 16) + observability tests. Gate: 18.4 observability, 18.8.
  6. Branch-current DSSE (Section 14) and cross-agreement. Gate: 18.4 cross.
  7. EWLAV (Section 15) sparse-l1. Gate: 18.4 bad-data, 18.7 determinism.
  8. Converter loss + virtual bus + four-wire LV (Sections 6, 11, 12) as the islanded/DER-heavy hardening pass. Gate: 18.5 Kron/converter, islanded solves.
  9. Sparse backends + scaling (sparse IThreePhaseStep, sparse EWLAV) for large feeders. Gate: 18.7 determinism at scale.
  10. Cross-val scripts (Section 18.6) and the technical-manual chapter.

22. Open questions and future work

  • Time-series / quasi-static three-phase estimation over a day of AMI reads (state carried bus-to-bus as a warm start) - still a static filter per instant, but the chaining deserves its own restriction note (it must stay a sequence of present-state reconstructions, never a forecast).
  • Regulator/OLTC discrete-tap estimation (mixed-integer) - deferred; v1 treats taps as known inputs.
  • Meter placement / observability design tooling on the pseudo-measurement layer.
  • Harmonic / unbalanced-source extensions to the sequence model.
  • A GDA distribution feed (LV/MV network models + AMI in the data lake), analogous to the transmission GDA bridge, once such data is authored and horizon-guarded on the GDA side.

See also

  • State estimation - the positive-sequence estimator this parallels
  • Power flow - Newton/BFS engines and the pi-model stamps reused per phase
  • Protections and Protection assessment - the overlay the SLG fault feeds
  • Provenance and invariants - the horizon guard on dated inputs
  • UnderstandingRestrictions.md, RestrictionReview.Reviewed (src/GridSim.Core/Diagnostics/RestrictionReview.cs) - the governing rule and the DSE gate