Status (verified 1.95.276): Partly implemented as a Core API with no CLI verb: an RDF/XML importer that takes one document or one per profile (EQ, TP, SSH, SV, DY, boundary), with a node-breaker topology processor, loads of every CGMES class, machines and injections with their reactive limits, voltage control and type, shunts, static var and series compensators, every concrete tap changer, and the SV tap and shunt positions by option; a bridge to GridModel with a slack rule and de-energised islands; a controlled solve for remote voltage control, SVCs and regulating shunts; and an exporter. The GridModel export, solved-state (SV voltage) import and export, measurement (Meas) mapping to MeasurementSet, operational limits, the md:FullModel header and the ForwardInferenceGuard gating of dated inputs are not implemented. Implemented in: src/GridSim.Core/IO/Cim/ (CimImporter.Parse and its .Topology, .Equipment, .Controls parts, CimNetwork, CimImportOptions; CimGridModelBridge.ToGridModel and Bridge; CimControlledPowerFlow; CimExporter.Export). The behaviour is specified in technical ch. 32, CIM/CGMES import and export. Design-to-code name map:

Design name Implemented as
namespace GridSim.Core.IO.Cgmes GridSim.Core.IO.Cim
CgmesImporter (ImportFiles, ImportWithDiagnostics) CimImporter.Parse(string rdfXml) or Parse(IEnumerable<string> documents); merged by mRID across the documents; diagnostics in CimNetwork.Notes
CgmesImportResult CimNetwork (no GridModel or MeasurementSet member)
CgmesExporter CimExporter.Export(CimNetwork), returns one RDF/XML string
CgmesNetworkBuilder, CgmesUnits, the GridModel build CimGridModelBridge.ToGridModel (ohm to per-unit through BaseVoltage)
CgmesProfile, CgmesProfileSchema, CgmesModelHeader, CgmesDataset not implemented; profiles are passed as separate documents and merged by mRID
CimRdfReader, CimTriple, CimObject.cs not implemented as files; a private CimObject class inside CimImporter over System.Xml.Linq (XDocument), not a streaming XmlReader
CgmesMapping, CgmesExportOptions not implemented
SV, SSH, Meas mapping (SvVoltage, SvPowerFlow, SvTapStep, Analog/Discrete) SSH values are read; SvTapStep and SvShuntCompensatorSections by CimImportOptions; SvVoltage, SvPowerFlow and Meas not implemented
ShuntCompensator, OperationalLimitSet, RegulatingControl shunts and RegulatingControl read; OperationalLimitSet not implemented

This is a design record. The current behaviour is documented in technical ch. 32, CIM/CGMES import and export.

This document specifies a CGMES / CIM subset importer and exporter that maps to and from GridModel (src/GridSim.Core/Model/Model.cs) and MeasurementSet (src/GridSim.Core/Estimation/MeasurementSet.cs). It is an implementation blueprint, not code: it fixes the CIM classes in scope, the RDF/XML parsing approach (no external dependencies), the exact field mapping and per-unit handling, the round-trip equivalence contract, the test plan, and how every dated input is routed through ForwardInferenceGuard so the no-forward-inference invariant holds by construction.


1. Purpose and scope

GridSim reads MATPOWER .m cases (IO/Matpower), a JSON case folder, and its own solve/estimate exports. CGMES is the lingua franca of European TSO/EMS toolchains (ENTSO-E's profiled subset of IEC 61970/61968 CIM). Supporting a CGMES subset lets GridSim:

  • ingest a published or replayed network snapshot (EQ + TP + SV + SSH) as a GridModel and estimate on it;
  • ingest CIM Meas analog values as a MeasurementSet;
  • export an estimated / solved GridModel state back out as CGMES SV (+ a light EQ/TP) for consumption by a standards-conformant tool or an independent validator.

In scope: a steady-state, balanced positive-sequence subset sufficient to reconstruct a GridModel and a MeasurementSet, and to write back the estimated bus voltages and branch flows. Out of scope (listed in section 17): three-phase / short-circuit sequence data, dynamics (DY) profile, diagram layout (DL/GL), CIM difference models, multi-authority boundary-set stitching, and the 61968 distribution-management packages.

This spec deliberately reuses GridSim's existing import idioms so the CGMES path reads like the MATPOWER path: a static entry class with a ...WithDiagnostics overload that returns a model plus human-readable notes (MatpowerParser.ParseWithDiagnostics, MatpowerParseResult), private DTO/intermediate types, and a post-build GridModel.Validate() gate that fails loud on structural faults.


2. Governing constraint: no forward inference

UnderstandingRestrictions.md draws one line: GridSim runs inference backward or on the present, never forward on the real grid. The estimator is a filter, not a predictor; every dated input must lag real time by at least ForwardInferenceGuard.HorizonHours (169 h = 7 days + 1 h). A CGMES importer is a dated ingestion seam and therefore sits squarely under invariant #1 ("no ingester accepts a timestamp newer than UtcNow - 169h").

CGMES timestamps live in three places, all of which this design routes through the guard before any model or measurement object is constructed:

  1. md:Model.scenarioTime in every profile's md:FullModel header - the instant the snapshot describes. This is the authoritative "as-of" stamp for an EQ/TP/SV/SSH set.
  2. md:Model.created - when the file was produced (secondary; checked when present).
  3. cim:MeasurementValue.timeStamp on each analog value in a Meas file - the per-sample telemetry stamp, mapped to (and no newer than) MeasurementSet.TakenUtc.

The guard is applied exactly the way MeasurementSet.Load applies it today (ForwardInferenceGuard.RejectFuture(taken, utcNow, "measurement set")): parse the stamp, call the guard, and let ForwardInferenceException propagate. There is no code path that reads a CGMES snapshot without first proving its scenarioTime is historical.

The exporter is the mirror obligation (invariant #2: "no public-data code path produces an output stamped later than its newest input"). It writes md:Model.scenarioTime equal to the source state's own as-of stamp (carried on the GridModel / estimate provenance), never DateTime.UtcNow, and asserts scenarioTime <= newestInputStamp before serialising. CGMES export is a pure rendering of an already-estimated present/past state; it introduces no new inference and no forward step.

Because the importer and exporter contain no solve and no dynamics fusion, they do not touch the Dynamics/ -> Estimation/ review gate (RestrictionReview, invariant #5). They are pure format translation on guard-checked data. This is stated explicitly so a reviewer does not have to re-derive it.


3. CGMES background and the profile subset in scope

A CGMES dataset is a set of RDF/XML files, one per profile, sharing object identity by mRID (a UUID carried as rdf:ID / rdf:about). The profiles this design consumes:

Profile Code What it carries GridSim use
Equipment (core) EQ Topology-independent equipment: lines, transformers, machines, loads, shunts, base voltages, terminals branch/gen/load/shunt structure and impedances
Topology TP TopologicalNodes and the terminal-to-node association (the bus model) the bus set (one Bus per TopologicalNode)
Steady-State Hypothesis SSH The operating point: load p/q, machine p/q, tap steps, shunt sections, controls injections and setpoints
State Variables SV The solved state: SvVoltage (v, angle), SvPowerFlow (p, q), SvTapStep, islands Vm/VaDeg, cross-check flows
Measurement Meas Analog/AnalogValue (+ Discrete) tied to a terminal or PSR the MeasurementSet

CGMES versions differ only in the CIM schema namespace and a few attribute spellings; this design targets CGMES 2.4.15 (CIM16) as the primary dialect and CGMES 3.0 (CIM100) as a recognised alternate, selected by the schema namespace URI found in the file (section 5). The differences are localised to the CgmesProfileSchema constants and never leak into the mapping logic.

The SSH profile is strongly recommended but optional: when absent, injections fall back to SV SvPowerFlow terminal flows aggregated per node (section 8.4), and the importer records a note. EQ + TP are mandatory to build a GridModel; SV is required to populate a solved state (else buses take flat/nominal Vm); Meas is required only for MeasurementSet import.


4. CIM classes and attributes in scope

All names are CIM16 (cim: = http://iec.ch/TC57/2013/CIM-schema-cim16#). Association targets are given by rdf:resource="#<mRID>". Attributes not listed are ignored on import (and not written on export) unless section 17 promotes them later.

4.1 Equipment (EQ) - core

Class Attributes / associations read Notes
IdentifiedObject .mRID (from rdf:ID/rdf:about), .name base of every object; name -> Name fields
BaseVoltage .nominalVoltage (kV) the per-unit voltage base; referenced by nodes and equipment
Terminal (ACDCTerminal) .ConductingEquipment, .ConnectivityNode, .sequenceNumber the incidence glue; end 1/2 by sequenceNumber
ConnectivityNode .ConnectivityNodeContainer node-breaker granularity; collapsed via TP to a TopologicalNode
ACLineSegment (Conductor) .r, .x, .bch, .gch (SI: ohm, S), .length pi-model line; .gch usually 0
PowerTransformer (container of ends) two-winding in scope; N-winding -> note + skip (section 17)
PowerTransformerEnd .r, .x, .g, .b (ohm/S), .ratedU (kV), .ratedS (MVA), .endNumber, .Terminal, .BaseVoltage per-end impedance; folded to a single pi branch
RatioTapChanger .stepVoltageIncrement, .neutralStep, .lowStep, .highStep, .neutralU, .TransformerEnd -> Branch.TapRatio (with SSH/SV step)
PhaseTapChangerLinear (and ...Asymmetrical) .stepPhaseShiftIncrement (or geometry), .TransformerEnd -> Branch.PhaseShiftDeg
SynchronousMachine (RotatingMachine, RegulatingCondEq) .ratedS (MVA), .minQ, .maxQ, .type, .RegulatingControl, .GeneratingUnit -> Generator
GeneratingUnit .minOperatingP, .maxOperatingP, .initialP -> Generator.Pmin/Pmax
RegulatingControl .mode, .targetValue, .Terminal, .enabled mode=voltage -> Generator.Vg, PV/Slack typing
EnergyConsumer (ConductingEquipment) (p/q from SSH) -> bus Pd/Qd (folded)
LinearShuntCompensator (ShuntCompensator) .bPerSection, .gPerSection (S), .nomU (kV), .maximumSections -> bus Gs/Bs (folded, with section count)
EnergySource / ExternalNetworkInjection .governorSCD (ignored); its terminal node -> slack candidate grid-boundary injection -> slack (section 8.5)
CurrentLimit / OperationalLimitSet / OperationalLimitType .value (A), .direction -> Branch.RateAMva via sqrt(3)*U*I

4.2 Topology (TP)

Class Attributes / associations Notes
TopologicalNode .mRID, .name, .BaseVoltage, .ConnectivityNodeContainer one Bus per node - the GridSim bus model
Terminal.TopologicalNode association maps each equipment terminal to its bus
ConnectivityNode.TopologicalNode association (node-breaker inputs) resolves CN-level terminals to a TN

4.3 Steady-State Hypothesis (SSH)

Class Attributes Maps to
EnergyConsumer .p, .q (MW, MVAr) bus Pd, Qd (summed per node)
RotatingMachine / SynchronousMachine .p, .q (MW, MVAr; CGMES sign: injection negative) Generator.Pg, Qg (sign-normalised)
TapChanger .step resolves RatioTapChanger to TapRatio; PhaseTapChanger to PhaseShiftDeg
ShuntCompensator .sections shunt susceptance = sections * bPerSection
RegulatingControl .targetValue, .enabled Generator.Vg (pu = targetValue/BaseKv), enabled -> typing
EquivalentInjection .p, .q boundary injection at a border node

4.4 State Variables (SV)

Class Attributes Maps to
SvVoltage .TopologicalNode, .v (kV), .angle (deg) bus Vm (= v/BaseKv), VaDeg
SvPowerFlow .Terminal, .p, .q (MW, MVAr) injection fallback + flow cross-check
SvTapStep .TapChanger, .position tap when SSH absent
SvShuntCompensatorSections .ShuntCompensator, .sections shunt when SSH absent
TopologicalIsland .AngleRefTopologicalNode, .TopologicalNodes slack reference bus (per island)
SvStatus .ConductingEquipment, .inService Branch.InService

4.5 Measurement (Meas)

Class Attributes / associations Maps to
Analog (Measurement) .measurementType, .unitSymbol, .unitMultiplier, .phases, .Terminal, .PowerSystemResource MeasurementKind + location
AnalogValue (MeasurementValue) .value, .Analog, .sensorAccuracy Measurement.Value, Sigma
MeasurementValue .timeStamp MeasurementSet.TakenUtc (guarded)
MeasurementValueSource .name (e.g. "SCADA", "PMU", "CALCULATED") Measurement.Source
Discrete / DiscreteValue .value (switch state) optional: Branch.InService (section 11.4)

5. RDF/XML parsing approach (no external dependencies)

CGMES files are RDF/XML but constrained to a flat, striped serialisation: a document is a sequence of top-level typed resource elements, each with literal-valued property children and rdf:resource reference children. GridSim does not need a general RDF/OWL reasoner - it needs a striped-RDF reader. That is implementable on System.Xml alone (already available in .NET; no NuGet, satisfying the "no external deps" rule and the zero-warning gate).

5.1 Reader

Use System.Xml.XmlReader over a FileStream (streaming, low-allocation, matches the "throttle disk I/O" house style) to produce a flat list of CimTriple(subject, predicate, object) where:

  • subject = the rdf:ID (prefix _ -> mRID) or rdf:about (#mRID or full URI) of the enclosing typed element;
  • predicate = the element-qualified name, either rdf:type (from the element name of the typed resource, e.g. cim:ACLineSegment) or a property QName (e.g. cim:ACLineSegment.r);
  • object = a literal (element text) for value properties, or a resource mRID (from the child element's rdf:resource) for associations.

Enumeration values arrive as rdf:resource="http://.../CIM-schema-cim16#RegulatingControlModeKind.voltage"; the reader keeps the fragment after # (RegulatingControlModeKind.voltage) as the object.

5.2 Graph

Fold the triples into CimObject records keyed by mRID:

CimObject:
    string   Mrid
    string   CimType                 // e.g. "ACLineSegment" (namespace stripped)
    IReadOnlyDictionary<string,string>  Literals     // predicate localName -> text
    IReadOnlyDictionary<string,string>  References    // predicate localName -> target mRID
    ILookup or multimap for repeated predicates (e.g. TopologicalIsland.TopologicalNodes)

predicate localName is the tail after the class-qualified dot: ACLineSegment.r -> r, Terminal.TopologicalNode -> TopologicalNode. Because CIM property names are unique within a class, storing by localName is safe and keeps the mapping code terse. Repeated associations (one-to-many, e.g. TopologicalIsland.TopologicalNodes) go into a separate multimap.

5.3 Dataset

CgmesDataset is the parsed multi-profile object set: it merges the CimObjects from every supplied file by mRID (an object may be defined in EQ and augmented in SSH/SV - CGMES carries the same mRID across profiles with different property subsets), and records which CgmesProfile each file declared (from md:Model.profile / the rdf:type mix). The header records (md:FullModel per file) are collected into CgmesModelHeader values carrying ScenarioTimeUtc, CreatedUtc, Version, Profile, ModelingAuthoritySet.

5.4 Robustness rules

  • Namespace-agnostic on the CIM prefix value: bind cim from the document's own xmlns:cim, and recognise CIM16 vs CIM100 by that URI. Fail loud (InvalidDataException) on an unrecognised CIM schema namespace rather than silently mis-parsing.
  • rdf:ID vs rdf:about: normalise both to a bare mRID (strip a leading _, #, or the urn:uuid: / full-URI prefix). Identity is by this normalised mRID everywhere.
  • Invariant culture for every numeric parse (CultureInfo.InvariantCulture, NumberStyles.Float), mirroring MatpowerParser.ParseNum.
  • Unknown classes and unknown properties are skipped and counted into the diagnostics notes ("skipped N objects of M unmapped classes"), never fatal - forward-compatible with richer files.

6. Namespace and file layout

New code lives in GridSim.Core.IO.Cgmes, mirroring GridSim.Core.IO.Matpower. All types are internal except the two entry classes and the public result/option records, matching the existing IO surface.

src/GridSim.Core/IO/Cgmes/
  CgmesProfile.cs         enum { Eq, Tp, Ssh, Sv, Meas, Unknown } + schema-namespace constants
  CimTriple.cs            readonly record struct (subject, predicate, object, IsResource)
  CimObject.cs            parsed resource (mRID, type, literals, refs, multimap)
  CgmesModelHeader.cs     md:FullModel header (ScenarioTimeUtc, CreatedUtc, Version, Profile, Mas)
  CimRdfReader.cs         XmlReader -> IEnumerable<CimTriple>; header extraction
  CgmesDataset.cs         merge triples across files by mRID; expose typed selectors
  CgmesUnits.cs           SI<->per-unit helpers (Zbase, shunt, tap, rating, angle)
  CgmesMapping.cs         static maps: measurementType/unitSymbol -> MeasurementKind; enum tables
  CgmesImporter.cs        static ImportFiles(...) / ImportWithDiagnostics(...) -> CgmesImportResult
  CgmesImportResult.cs    record (GridModel Model, MeasurementSet? Measurements, IReadOnlyList<string> Notes)
  CgmesExporter.cs        static Export(GridModel, EstimationResult|PowerFlowResult, options) -> files
  CgmesExportOptions.cs   record (profiles to write, mRID policy, scenario time source, author set)

Test project: tests/GridSim.Tests/Cgmes/ (section 15).

The CgmesImporter public surface, matching MatpowerParser's idiom:

CgmesImportResult ImportWithDiagnostics(
    IReadOnlyList<string> profilePaths,   // EQ/TP/SSH/SV/Meas files, any order
    DateTime? utcNow = null,               // for the guard; defaults to DateTime.UtcNow
    double frequencyHz = 50.0)

GridModel Import(IReadOnlyList<string> profilePaths, DateTime? utcNow = null)   // .Model of the above

utcNow is threaded exactly like MeasurementSet.Load(path, utcNow) so the guard is testable with a fixed clock (section 15.5).


7. Intermediate data structures

Between the CgmesDataset and the emitted GridModel sits one internal builder that resolves CIM's node-breaker/associative graph into GridSim's bus-branch arrays. Named to fit the codebase (...Builder, private nested DTOs like SolveImport):

  • CgmesNetworkBuilder - orchestrates the passes of section 8; owns the mRID->index maps.
  • NodeRecord - one TopologicalNode's accumulation: Mrid, Name, BaseKv, running Pd, Qd, Gs, Bs, SvVm, SvVaDeg, IsSlack, incident terminal mRIDs.
  • BranchRecord - one line or transformer reduced to a pi-model: FromNodeMrid, ToNodeMrid, RPu, XPu, BPu, TapRatio, PhaseShiftDeg, RateAMva, Name, IsTransformer, InService.
  • GenRecord - one SynchronousMachine: NodeMrid, Pg, Qg, Vg, Qmin, Qmax, Pmin, Pmax, MBase, Name, Type.

The builder maps TopologicalNode mRID -> a stable 1-based integer Bus.Id (CGMES has no integer bus numbers). The mRID<->id crosswalk is retained on CgmesImportResult (via a note and an optional out-map) so export can round-trip identity (section 13.2). Bus Id assignment is deterministic: nodes sorted by mRID ordinal, then numbered - so two imports of the same dataset produce byte-identical models (determinism, section 15.4).


8. Import pipeline (EQ + TP + SSH + SV -> GridModel)

Ordered passes over the merged CgmesDataset. Each pass is pure and side-effect-free except for accumulation into the builder.

8.0 Guard first

Extract every CgmesModelHeader.ScenarioTimeUtc (and CreatedUtc when present) and call ForwardInferenceGuard.AssertHistorical(stamps, utcNow, "cgmes snapshot") before pass 8.1. A future/recent stamp throws ForwardInferenceException and no model is built. The newest accepted scenarioTime becomes the dataset's as-of instant, carried onto the result for the export mirror (section 2) and stored as MeasurementSet.TakenUtc when Meas is imported.

8.1 Base voltages

Index BaseVoltage.mRID -> nominalVoltage (kV). This is the per-unit voltage base for every node and every SI impedance conversion downstream (section 9).

8.2 Nodes (buses)

One NodeRecord per TopologicalNode. BaseKv from TopologicalNode.BaseVoltage (fallback: the node's equipment BaseVoltage, else the container's). Build the Terminal.mRID -> TopologicalNode.mRID map from TP (resolving ConnectivityNode terminals via ConnectivityNode.TopologicalNode when the input is node-breaker).

8.3 Loads and shunts (folded onto the bus)

MATPOWER/GridSim fold demand and shunts onto the bus (Model.cs remarks). For each EnergyConsumer, find its terminal's node and add SSH .p/.q to that NodeRecord's Pd/Qd. For each LinearShuntCompensator, add sections * gPerSection (times nomU^2 scaling to the node base, section 9.4) to Gs and sections * bPerSection to Bs. sections comes from SSH ShuntCompensator.sections, else SV SvShuntCompensatorSections.sections, else 0 with a note.

8.4 Machines (generators)

One GenRecord per SynchronousMachine (and ExternalNetworkInjection/EnergySource treated as generators for typing). Pg/Qg from SSH with the sign convention normalised (CGMES RotatingMachine.p is load-positive at the terminal, i.e. generation is negative; GridSim Generator.Pg is generation-positive - negate on import, section 9.5). Vg from RegulatingControl.targetValue / BaseKv when mode = voltage and enabled. Qmin/Qmax from SynchronousMachine.minQ/.maxQ (else +/-Infinity, the GridSim "no limit" default). Pmin/Pmax from GeneratingUnit.minOperatingP/.maxOperatingP. MBase from ratedS (else BaseMva).

8.5 Bus typing (Slack / PV / PQ)

CIM has no explicit bus type; derive it (this is the one genuinely inferential step, and it is a model-structure inference, not a grid-state one, so it is unrestricted):

  1. Slack: the TopologicalIsland.AngleRefTopologicalNode (SV) is the reference bus for its island - BusType.Slack. If SV/island is absent, the node hosting an ExternalNetworkInjection / EnergySource is the slack; if several, the largest ratedS wins and the rest become PV (a note records the choice). Multiple islands -> multiple slacks, which GridModel.Validate treats as a benign multi-island warning.
  2. PV: a non-slack node with at least one SynchronousMachine whose RegulatingControl is voltage-mode and enabled -> BusType.Pv.
  3. PQ: everything else.

8.6 Branches (lines)

One BranchRecord per in-service ACLineSegment. Resolve its two terminals to FromNodeMrid/ToNodeMrid (terminal sequenceNumber 1 = From, 2 = To). Convert SI to per-unit against the line's BaseVoltage (section 9.2): RPu, XPu, BPu = bch * Zbase. RateAMva from the branch's CurrentLimit via sqrt(3) * BaseKv * I_amp / 1000 when present.

8.7 Branches (transformers)

One BranchRecord per two-winding PowerTransformer, IsTransformer = true. A CGMES transformer carries impedance on its PowerTransformerEnds (SI, referred to each end's ratedU). Reduce to a single pi branch on the network base (section 9.3):

  • Series impedance = sum of the two ends' r + jx, each referred to a common base voltage (choose the From end's ratedU), then per-unitised on BaseMva.
  • TapRatio from the RatioTapChanger: 1 + (step - neutralStep) * stepVoltageIncrement/100, with step from SSH TapChanger.step (else SV SvTapStep.position). Off-nominal turns ratio also folds the two ends' ratedU mismatch: ratedU_from / ratedU_to scaled to the node base.
  • PhaseShiftDeg from a PhaseTapChangerLinear: (step - neutralStep) * stepPhaseShiftIncrement.
  • RateAMva from the end ratedS or a CurrentLimit.

An N-winding (3+) transformer is not reduced in this phase: skip it, emit a diagnostic note, and (section 17) leave a seam for a star-point auxiliary bus. This matches the "fail loud / note, never silently corrupt" stance of MatpowerUnitNormalizer.

8.8 Solved state (SV)

For each SvVoltage, set the node's SvVm = v / BaseKv (per-unit) and SvVaDeg = angle. These populate Bus.Vm/Bus.VaDeg (initial/fixed voltages) and, when a solved PowerFlowResult is requested (an ImportOptions.WithSolvedState flag), a PowerFlowResult assembled through the same NewtonShell.AssembleResult path EstimationResult.ToPowerFlowResult uses - so SV import and estimate export share one assembly seam and cannot drift.

8.9 Emit and validate

Assemble the GridModel (sealed class - copy every property explicitly, as MatpowerUnitNormalizer.Normalize does), then run GridModel.Validate() and throw on any ValidationSeverity.Error (InvalidDataException naming every offender), exactly as MatpowerParser.ParseWithDiagnostics does. Warnings (multi-island, OLTC) become notes.


9. Unit and per-unit handling

GridSim is per-unit on BaseMva with impedances per-unit and power in MW/MVAr (docs/technical/02-data-model-and-per-unit.md, MatpowerUnitNormalizer). CGMES is SI: impedances in ohms, susceptance/conductance in siemens, voltage in kV, power in MW/MVAr, angle in degrees. Conversion is the textbook per-unit reduction, centralised in CgmesUnits.

9.1 Bases

BaseMva := dataset system base. CGMES has no single system base; adopt 100 MVA
           (GridSim default) unless every ratedS agrees on another value. Record the
           choice in a note; it is the invariant divisor for all power/impedance pu.
Zbase(kV) := kV^2 / BaseMva          (ohms)          // same formula as MatpowerUnitNormalizer
Ybase(kV) := 1 / Zbase(kV)           (siemens)

9.2 Lines

RPu = r_ohm / Zbase(BaseKv)
XPu = x_ohm / Zbase(BaseKv)
BPu = bch_siemens * Zbase(BaseKv)     // susceptance scales by *Zbase (=/Ybase), NOT /Zbase
GPu = gch_siemens * Zbase(BaseKv)

BaseKv is the line's BaseVoltage.nominalVoltage. (Note the MatpowerUnitNormalizer remark: charging susceptance converts by multiplying Zbase, not dividing - the design follows that.)

9.3 Transformers

Refer each end's SI r+jx to a common winding (the From end's ratedU) using the turns-ratio squared, sum, then per-unitise on BaseMva and the From node BaseKv. The off-nominal tap and the ratedU_from/ratedU_to ratio combine into Branch.TapRatio (dimensionless), so the pi-model matches MeasurementModel's transformer stamps (yff = (ys+bc)/tapA^2, yft = -ys/conj(tap)).

9.4 Shunts

LinearShuntCompensator susceptance is quoted at nomU. Convert to the node base: Bs_mvar_at_1pu = sections * bPerSection * nomU^2 (MVAr at 1.0 pu on the node), matching the Bus.Bs definition ("the MW/MVAr it would draw at 1.0 pu voltage", Model.cs). Likewise Gs.

9.5 Power and sign

Load EnergyConsumer.p/q are demand-positive -> add directly to Pd/Qd. Machine RotatingMachine.p/q follow the CIM terminal convention (flow into the equipment); GridSim Generator.Pg is generation-out-of-machine positive -> negate. This single sign flip is unit-tested against a case with a known dispatch (section 15.3).

9.6 Voltage and angle

SvVoltage.v (kV) -> Vm = v / BaseKv (pu). SvVoltage.angle is already degrees, matching Bus.VaDeg and MeasurementKind.VaDeg (the estimator holds angles in radians internally but the model/measurement surface is degrees - MeasurementModel converts on ingest). No re-referencing is needed: CGMES angles are already in the island's slack frame (TopologicalIsland.AngleRefTopologicalNode), which the importer makes the GridSim slack - so the angle datum is consistent by construction (contrast the Gridradar per-feed offset problem in docs/pmu-gridradar-design-note.md, which does not arise here).


10. GridModel <-> CGMES field mapping (authoritative table)

GridModel field CGMES source (import) CGMES target (export) Transform
GridModel.BaseMva adopted (100 or agreed ratedS) (not a CIM object; implicit) section 9.1
Bus.Id assigned from TopologicalNode.mRID (deterministic) mRID via crosswalk 1-based, mRID-sorted
Bus.Type inferred (section 8.5) island ref / regulating control derived
Bus.BaseKv TopologicalNode.BaseVoltage.nominalVoltage BaseVoltage.nominalVoltage kV, direct
Bus.Pd / Qd sum SSH EnergyConsumer.p/q at node one EnergyConsumer per node MW/MVAr
Bus.Gs / Bs LinearShuntCompensator (sections) LinearShuntCompensator section 9.4
Bus.Vm SvVoltage.v / BaseKv SvVoltage.v = Vm * BaseKv pu <-> kV
Bus.VaDeg SvVoltage.angle SvVoltage.angle degrees, direct
Bus.Name TopologicalNode.name .name text
Branch.From/To terminal sequenceNumber 1/2 -> node ids terminals to nodes id crosswalk
Branch.R/X ACLineSegment.r/x or transformer ends .r/.x (SI) / and * Zbase
Branch.B ACLineSegment.bch .bch * / Zbase
Branch.TapRatio RatioTapChanger + step RatioTapChanger + SvTapStep section 9.3
Branch.PhaseShiftDeg PhaseTapChangerLinear + step PhaseTapChanger degrees
Branch.RateAMva CurrentLimit / end ratedS OperationalLimit sqrt(3)*U*I
Branch.Name ACLineSegment.name / PowerTransformer.name .name text
Branch.IsTransformer class is PowerTransformer class choice boolean
Branch.InService SvStatus.inService (else true) SvStatus.inService boolean
Generator.Bus machine terminal -> node id terminal to node id crosswalk
Generator.Pg/Qg SSH machine p/q, negated p/q, negated back sign flip (9.5)
Generator.Vg RegulatingControl.targetValue/BaseKv RegulatingControl.targetValue pu <-> kV
Generator.Qmin/Qmax SynchronousMachine.minQ/maxQ .minQ/.maxQ MVAr
Generator.Pmin/Pmax GeneratingUnit.min/maxOperatingP .min/maxOperatingP MW
Generator.MBase RotatingMachine.ratedS .ratedS MVA
Generator.Name SynchronousMachine.name .name text
GridModel.Oltcs RatioTapChanger regulating -> Oltc RatioTapChanger.TapChangerControl optional (section 17)

Fields with no CGMES equivalent (Bus.X/Y layout, Generator.H inertia, DynamicsClass, Protections, Boundaries) are not written and default sensibly on import, exactly as SolveImport handles export-absent fields. Generator.H in particular is a DY-profile concern, out of scope here.


11. Measurement mapping (MeasurementSet <-> Meas profile)

11.1 Kind resolution

A CIM Analog carries measurementType + unitSymbol + unitMultiplier and is tied to a Terminal (branch-end quantity) or a PowerSystemResource (bus quantity). Resolve to MeasurementKind via CgmesMapping:

CIM measurementType unitSymbol Terminal? MeasurementKind Notes
Voltage / LineToLineVoltage / PhaseVoltage V on a node/PSR VmPu value/BaseKv -> pu
Angle / VoltageAngle deg node/PSR VaDeg already slack-frame
ThreePhaseActivePower / ActivePower W PSR (bus) PInjMw net injection
ThreePhaseReactivePower / ReactivePower VAr PSR (bus) QInjMvar net injection
ThreePhaseActivePower / ActivePower W Terminal (branch) PFlowMw end from terminal seq
ThreePhaseReactivePower / ReactivePower VAr Terminal (branch) QFlowMvar end from terminal seq
Current A Terminal (branch) IMagPu value/Ibase -> pu

unitMultiplier (M mega, k kilo) scales the raw value to MW/MVAr/kV before the per-unit or engineering-unit conversion the Measurement record expects (Measurement values are in engineering units: pu for voltage/current, MW/MVAr for power, degrees for angle - Measurement.cs).

11.2 Location resolution

  • Bus quantity (PInjMw, QInjMvar, VmPu, VaDeg): resolve the Analog's PowerSystemResource or its Terminal.TopologicalNode to a Bus.Id and set Measurement.Bus.
  • Branch quantity (PFlowMw, QFlowMvar, IMagPu): resolve the Analog.Terminal to its ConductingEquipment (the branch) and its two nodes -> Measurement.From, Measurement.To, and Measurement.End from the terminal sequenceNumber (1 -> BranchEnd.From, 2 -> BranchEnd.To). Parallel circuits are disambiguated with Measurement.Circuit set to the branch Name (or "#k" ordinal), exactly as MeasurementSet.TryResolveBranch expects.

11.3 Value, sigma, source, time

  • Measurement.Value = AnalogValue.value (scaled by unitMultiplier, per-unitised where the kind is pu).
  • Measurement.Sigma: CGMES rarely ships a per-sample sigma. Priority: Analog.sensorAccuracy if present (interpreted as a 1-sigma in the measurement's unit); else a kind-default sigma table in CgmesMapping (e.g. VmPu 0.005 pu, PFlowMw 1% of value floored at a small absolute, VaDeg per the PMU note). The chosen sigma policy is recorded in MeasurementSet.Note. Sigma must be finite and > 0 or MeasurementSet.Validate throws.
  • Measurement.Source = MeasurementValueSource.name lowercased ("scada", "pmu", "calculated"), matching the existing Measurement.Source convention (default "scada").
  • MeasurementValue.timeStamp: the newest timestamp across accepted values becomes MeasurementSet.TakenUtc. All timestamps are guard-checked (section 11.5); a set may not mix ages that straddle the horizon.

11.4 Discrete (optional)

A Discrete switch-status measurement can drive Branch.InService. In scope only as an importer-side note in this phase; wiring it to topology is deferred (section 17).

11.5 Guard on measurement timestamps

Before any Measurement is constructed, ForwardInferenceGuard.AssertHistorical is called over every MeasurementValue.timeStamp. This is the Meas-profile analogue of MeasurementSet.Load's single-stamp check, and it means the CGMES measurement path is a registered dated ingestion seam (to be pinned by RestrictionInvariantTests, section 16).


12. Import algorithm summary (pseudocode, not C#)

ImportWithDiagnostics(paths, utcNow, frequencyHz):
    files   = paths.map(CimRdfReader.ReadFile)          // streaming XmlReader -> triples + header
    dataset = CgmesDataset.Merge(files)                 // by mRID; classify profiles
    # --- GUARD FIRST (no-forward-inference) ---
    ForwardInferenceGuard.AssertHistorical(dataset.Headers.ScenarioTimes, utcNow, "cgmes snapshot")
    asOf = max(dataset.Headers.ScenarioTimes)

    require(dataset.HasProfile(Eq) and dataset.HasProfile(Tp))   // else InvalidDataException
    b = new CgmesNetworkBuilder(dataset, frequencyHz)
    b.IndexBaseVoltages()          # 8.1
    b.BuildNodes()                 # 8.2  -> Bus.Id crosswalk (mRID-sorted, deterministic)
    b.FoldLoadsAndShunts()         # 8.3
    b.BuildGenerators()            # 8.4
    b.InferBusTypes()              # 8.5
    b.BuildLines()                 # 8.6
    b.BuildTransformers()          # 8.7  (2-winding; note+skip N-winding)
    b.ApplySvState()               # 8.8  (optional)
    model = b.EmitModel()          # 8.9  -> GridModel.Validate(); throw on Error

    measurements = dataset.HasProfile(Meas)
                 ? ImportMeasurements(dataset, model, b.Crosswalk, utcNow, asOf)   # section 11
                 : null
    return CgmesImportResult(model, measurements, b.Notes)

13. Export pipeline (GridModel + estimated state -> CGMES)

13.1 What is written

A minimal, self-consistent CGMES set sufficient for an independent tool (or GridSim's own importer) to reconstruct the state:

  • EQ: BaseVoltage per distinct kV; TopologicalNode (also serves as the bus in a bus-branch export); Terminals; ACLineSegment / PowerTransformer (+ ends, tap changers); SynchronousMachine; EnergyConsumer; LinearShuntCompensator.
  • TP: TopologicalNodes and terminal associations (bus-branch: one TN per bus).
  • SSH: injections and setpoints (EnergyConsumer.p/q, machine p/q, tap step).
  • SV: SvVoltage (from the estimated Vm/VaDeg), SvPowerFlow per terminal (from the estimate's recomputed flows via EstimationResult.ToPowerFlowResult -> LineFlow), SvTapStep, TopologicalIsland with the slack as AngleRefTopologicalNode.
  • Meas (optional): the MeasurementSet back out as Analog/AnalogValue (inverse of section 11) - useful for a validator to check the estimator consumed what it claims.

13.2 Identity round-trip

When the source GridModel came from a CGMES import, the mRID<->id crosswalk on CgmesImportResult is reused so exported objects carry their original mRIDs - a true round-trip. When the source is a MATPOWER/JSON model with no mRIDs, deterministic UUIDv5-style mRIDs are minted from a fixed namespace + the bus id / branch endpoints (stable across runs, so export is reproducible - section 15.4). Minting uses only System.Security.Cryptography (in-box; no dependency).

13.3 Scenario time (the export mirror of the guard)

md:Model.scenarioTime is set from the source state's own as-of instant: CgmesExportOptions.ScenarioTimeUtc, which defaults to the imported dataset's asOf (section 8.0) or, for an estimate, the MeasurementSet.TakenUtc the estimate was computed from. The exporter asserts scenarioTime <= newestSourceInputStamp and never substitutes DateTime.UtcNow. A caller trying to stamp an export in the present/future fails loud (InvalidOperationException) - the code-level enforcement of invariant #2. md:Model.created may be UtcNow (it describes file creation, not the modelled instant) but is clearly separated from scenarioTime.

13.4 Serialisation

Write striped RDF/XML with System.Xml.XmlWriter (indented, invariant culture). Deterministic output ordering: objects sorted by (class, mRID); properties in a fixed schema order. This makes export byte-for-byte reproducible (the same doctrine as gridsim-solve-export/1: "byte-for-byte reproducible given a deterministic solve").


14. Round-trip equivalence contract

The central correctness property: import then export then import is a fixed point on the GridModel, and export then import then export is a fixed point on the CGMES bytes.

Define M = model, C = CGMES file set.

  1. import(C) = M0; export(M0, sv0) = C1; import(C1) = M1. Require M1 == M0 under the numeric equivalence of section 14.1 (structure exact, reals to machine epsilon).
  2. export(M0) = C1; import(C1) = M1; export(M1) = C2. Require C2 == C1 byte-for-byte (determinism + fixed ordering).

14.1 Numeric equivalence

  • Integer/enum/string fields (Bus.Id after crosswalk, Bus.Type, Branch.IsTransformer, names): exact.
  • Real fields (R, X, B, TapRatio, Pd, Vm, ...): equal to within a relative tolerance at the SI<->pu conversion's floating-point round-trip limit. Because pu conversion is a single multiply/divide by Zbase, the round trip x -> x/Zbase -> *Zbase recovers x to a few ULPs; the test tolerance is 1e-12 relative (the same machine-epsilon class as the solver validation gates), not an engineering tolerance.
  • Bus voltages carried through SV: Vm round-trips through v = Vm*BaseKv then Vm = v/BaseKv to a few ULPs.

15. Validation and test plan

Test project tests/GridSim.Tests/Cgmes/, xUnit, matching the existing suite conventions (ForwardInferenceGuardTests, MatpowerParserTests). All tests run under the zero-warning gate.

15.1 Fixtures

  • The CGMES conformity mini-cases (ENTSO-E's published "MicroGrid" / "MiniGrid" test configurations) as the primary real-format fixtures, checked into tests/.../Cgmes/fixtures/. These ship with a known SV solution - the independent reference (below).
  • A GridSim-authored round-trip fixture: export IeeeCases.Case9() / Case14() /Case118() to CGMES, then read back.

15.2 Machine-epsilon cross-checks against an independent reference

Two independent references, both giving machine-epsilon (not engineering) agreement:

  1. Against the CGMES SV file (the format's own published solution): import a MicroGrid configuration, and for every TopologicalNode assert the imported Bus.Vm/VaDeg equals the SvVoltage value to 1e-9 (SV is stored to full precision; the only arithmetic is the single v/BaseKv divide). This proves the parser and unit handling are exact, independent of any GridSim solve.
  2. Against GridSim's own power flow: import the network (EQ+TP+SSH), run SteadyStateSolver / Newton-Raphson on the reconstructed GridModel, and assert the solved Vm/VaDeg matches the CGMES SV solution to the solver's convergence tolerance. This proves the impedance/injection mapping is physically correct - the CGMES snapshot and GridSim's physics agree on the same state. (This is a solve on guard-checked historical data, permitted reconstruction, not forward inference.)

The MATPOWER path already cross-validates against published IEEE solutions; the CGMES path adds CGMES SV as a second independent oracle for the same networks where both formats exist.

15.3 Unit and sign tests

  • Zbase reduction: a line with known ohmic r/x/bch and a known BaseVoltage imports to the hand-computed per-unit values (exact to 1e-12).
  • Shunt: sections * bPerSection * nomU^2 -> Bus.Bs at 1.0 pu.
  • Transformer tap: step/neutralStep/stepVoltageIncrement -> TapRatio; phase shifter -> PhaseShiftDeg.
  • Machine sign flip: a case with a known dispatch (generation-positive Pg) imports with the correct sign; export negates it back.

15.4 Determinism

  • Import the same file set twice (and in shuffled file order, and with shuffled intra-file object order): assert the two GridModels are structurally identical and the Bus.Id assignment is byte-identical (mRID-sorted numbering).
  • Export the same model twice: assert byte-for-byte identical CGMES output (fixed ordering + minted-mRID stability).

15.5 No-forward-inference tests (the load-bearing suite)

  • A CGMES set whose md:Model.scenarioTime is UtcNow (or UtcNow - 1h, inside the 169 h horizon) throws ForwardInferenceException on import, with a fixed utcNow injected - and no GridModel is constructed (assert the exception precedes any partial build).
  • A set at exactly UtcNow - 169h is on the boundary; at UtcNow - 170h it imports cleanly.
  • A Meas file with a value timestamped inside the horizon throws before any Measurement is built.
  • Export refuses a scenarioTime newer than the source's newest input stamp (InvalidOperationException), and never emits DateTime.UtcNow as scenarioTime.
  • A RestrictionInvariantTests addition exercises CgmesImporter.Import and ImportMeasurements as dated seams, pinning them alongside the existing per-seam guard tests (the review log's "Note on invariant #1's marker" lists the seams; CGMES import joins them).

15.6 Round-trip tests

The two fixed-point properties of section 14, at 1e-12 relative for reals and exact for structure/bytes.

15.7 Robustness / negative tests

  • Unknown CIM schema namespace -> InvalidDataException (not a mis-parse).
  • Missing EQ or TP -> InvalidDataException.
  • N-winding transformer -> imported model omits it with a diagnostic note (asserted), never a corrupt branch.
  • A structurally invalid reconstructed model (dangling terminal, no slack) -> the GridModel.Validate() error path throws, naming offenders (mirrors MatpowerParser).

16. How the restriction invariants are honoured

Invariant (UnderstandingRestrictions.md) How this design satisfies it
#1 no ingester accepts a stamp newer than UtcNow - 169h ForwardInferenceGuard.AssertHistorical runs on every scenarioTime and every MeasurementValue.timeStamp before any model/measurement is built (sections 8.0, 11.5). CGMES import is registered as a dated seam in RestrictionInvariantTests.
#2 no output stamped later than its newest input The exporter sets md:Model.scenarioTime from the source's as-of instant and asserts <= newest input; it never uses UtcNow for scenarioTime (section 13.3).
#3 solver forward trajectories are model output only Not applicable - the importer/exporter run no solver forward step. The optional SV cross-check solve (test 15.2) is a reconstruction on historical data, seeded from and stamped at the guard-permitted scenarioTime.
#4 real-time features on permitted-age / replay data CGMES snapshots are historical by the guard; there is no live CGMES feed path.
#5 Dynamics -> Estimation fusion gated by review Not applicable - format translation fuses no dynamics process model; RestrictionReview.AssertPermitted is untouched. Stated explicitly (section 2) so no re-derivation is needed.

The importer is, like every other GridSim ingester, structurally incapable of nowcasting: it cannot construct a model from a snapshot it has not first proven is at least a week old.


17. Zero-warning build gate and coding-standard compliance

Directory.Build.props enforces TreatWarningsAsErrors=true, EnableNETAnalyzers=true, AnalysisMode=Recommended, Nullable=enable. The design is written to pass it with no suppressions:

  • No external dependencies: only System.Xml, System.Text, System.Globalization, System.Security.Cryptography (all in-box). No NuGet package is added, so no new analyser surface and no supply-chain review.
  • Nullable-clean: intermediate records use non-null defaults; optional CGMES data (MeasurementSet?, absent SSH) is modelled with explicit nullable reference types and handled, never null-forgiven without cause (the one ! idiom used in MeasurementSet.Save for a known directory is the pattern to follow if needed).
  • Culture-invariant every parse/format (CA1305), as MatpowerParser and SolveImport do.
  • XmlReader/XmlWriter configured with DtdProcessing = Prohibit and no external entity resolution (CA3075 / XXE safety) - a security-review-clean default.
  • Static entry classes, internal helpers, sealed records/DTOs - the exact surface shape of the existing IO code, so no new analyser categories are triggered.
  • Diagnostics are returned as IReadOnlyList<string> notes (the MatpowerParseResult pattern), not thrown for soft issues; only structural errors throw.

A green dotnet build with zero warnings is a merge precondition, asserted by the same CI gate that guards the rest of the tree.


18. Seams to extend and explicit out-of-scope

Left as clearly-marked extension points, each behind a note-and-skip today (never a silent approximation):

  • N-winding transformers: a star-point auxiliary Bus + N pi branches. The CgmesNetworkBuilder.BuildTransformers pass is the seam.
  • Full node-breaker topology processing: this phase collapses ConnectivityNodes via the TP association; a native breaker/switch model (with Discrete switch states driving Branch.InService) is a later phase.
  • Sequence / short-circuit data (r0/x0): for a future three-phase / unbalanced DSSE (Phase 4). The reader already carries the triples; only the mapping is deferred.
  • DY (dynamics) profile: Generator.H and machine models. Fusing DY into estimation would cross the Dynamics -> Estimation review gate (invariant #5) and must go through RestrictionReview first - out of scope for a format translator.
  • CIM difference models, boundary-set stitching, multi-authority merges, DL/GL diagram layout: recognised, unmapped, counted in notes.
  • Oltc export from RatioTapChanger.TapChangerControl: the import path can already build GridModel.Oltcs; the export inverse is a small follow-up.

End of specification. Implementation follows this document; deviations are recorded back into it and, where they touch a dated seam, cross-checked against UnderstandingRestrictions.md and RestrictionReview.Reviewed (src/GridSim.Core/Diagnostics/RestrictionReview.cs) before merge.