2. Data model and per-unit conventions

This chapter specifies the in-memory network model that every solver and study reads, and the per-unit system its numbers are expressed in. The whole model is defined in one file, src/GridSim.Core/Model/Model.cs: GridModel and its element records Bus, Generator, Branch, Oltc, Boundary, ZipLoad and GeneratorCost. The chapter gives every field with its unit, default, validation rule and the loaders that set it; the per-unit base system; the branch pi-model with tap and phase shift exactly as AdmittanceStamp implements it; the three Y-bus builders and how they stay bit-identical; the unit normalisation that rescues raw-unit distribution files; the immutability rules; and the invariants with the tests that pin them. The solvers that consume the model are specified in ch. 3, Power flow, the file formats that fill it in ch. 10, File and wire formats, and the JSON v2 case schema in ch. 28, The v2 JSON schema.

Model

Shape of the model

GridModel is a sealed class whose properties are init-only. Its elements are sealed records. By convention no code changes a built model (see "Immutability and the copy helpers"). There is no separate load type: demand is a property of the bus (the MATPOWER convention), and shunts are properties of the bus.

GridModel
  BaseMva                       system MVA base (required)
  Buses        : Bus[]          required; file order is the matrix order
  Generators   : Generator[]    required; the IN-SERVICE fleet (see "The generator fleet")
  AllGenerators / OutOfServiceGenerators     read-only views of the whole fleet
  Branches     : Branch[]       required; lines and transformers, file order
  Oltcs        : Oltc[]         default empty
  Boundaries   : Boundary[]     default empty
  FrequencyHz  : double         default 50.0
  Name         : string         default "grid"
  AssetDynamics: AssetDynamicsModel?   default null   (asset classes and bindings)
  Protections  : ProtectionModel?      default null   (placed protective devices)
  BusCount, SystemInertiaGvaS   computed

Result row i of every solver corresponds to Buses[i]; the solvers build an id-to-index map from Bus.Id, and results carry BusIds so an external id can always be recovered. Bus ids are arbitrary integers and need not be contiguous or sorted. They must be unique.

Which loader sets what

Five paths build a GridModel: the MATPOWER parser (src/GridSim.Core/IO/Matpower/MatpowerParser.cs), the JSON v1 loader (src/GridSim.Core/IO/Json/JsonGridLoader.cs), the JSON v2 loader (src/GridSim.Core/IO/Json/V2CaseLoader.cs, which maps a v2 case onto the v1 data carriers and builds through JsonGridLoader.Build, so a v2 case and its v1 equivalent give the same model bit for bit, as the invariants pin), the CIM bridge (src/GridSim.Core/IO/Cim/CimGridModelBridge.cs) and the GDA builder (src/GridSim.Gda/GdaModelBuilder.cs). A sixth, BridgeProtocol.BuildModel (src/GridSim.Core/IO/BridgeProtocol.cs), rebuilds a model from a bridge topology message or a solve export. It reads a subset of the fields, listed under each element table, and is the only loader that sets a branch InService false and the winding data. The tables below name the loader behaviour field by field. "v1" and "v2" share one builder, so a field set by "JSON" is set by both unless the entry says otherwise.

Bus

Bus(Id, Type, Pd, Qd, Gs, Bs, BaseKv, Vm, VaDeg, Name, X, Y, Zip, VminPu, VmaxPu).

Field Unit Default Validation (GridModel.Validate) Meaning
Id - required duplicate ids are an error, reported once per id External bus number.
Type BusType required no slack bus anywhere is an error; several are a warning Slack: Vm and Va fixed, absorbs the balance. Pv: P and Vm fixed, Q solved. Pq: P and Q fixed, V solved.
Pd, Qd MW, MVAr 0 must be finite Demand at 1.0 pu voltage.
Gs, Bs MW, MVAr at 1.0 pu 0 must be finite Fixed shunt, entered as the power it draws at 1.0 pu. Positive Gs draws MW; positive Bs injects MVAr (a capacitor bank).
BaseKv kV 0 none Nominal bus voltage. Never enters the solve; it converts per-unit voltage back to kV.
Vm pu 1.0 none Initial voltage magnitude. At a Slack or Pv bus that has a generator the generator's Vg takes precedence; FlatStart replaces the rest with 1.0.
VaDeg degrees 0 none Initial angle. Always honoured at a Slack bus.
Name - null none Asset identity carried through exports.
X, Y 0..1 0 none Layout coordinates for drawing. No solver reads them.
Zip ZipLoad? null JSON: all six coefficients present and finite, each triple sums to 1 within 1e-9 Voltage-dependent load; null is constant power.
VminPu, VmaxPu pu null each given limit finite and above 0; VminPu not above VmaxPu (equal is allowed) The bus's own voltage limits; null means the global operational band applies.

Loaders:

Field MATPOWER JSON v1 / v2 CIM GDA
Id mpc.bus column 1 id 1-based position in the CIM bus list; three-winding star points are numbered after the CIM nodes 0-based sequence in order of first use
Type column 2: 3 is Slack, 2 is Pv, anything else Pq; type 4 (isolated) is dropped with its elements; a type 2 bus with no in-service generator is demoted to Pq and a note says so type (pq; pv or gen; slack, ref or swing; any letter case; an unknown word or JSON null is refused); an in-service generator raises its bus to Pv, and a slack role makes its bus Slack; a pq role leaves the bus alone the first generator's bus is Slack, later generators on other buses are Pv, everything else Pq; a network with no generator makes bus 1 the slack Slack for each grid supply point infeed, Pq for the rest; an island left with no slack gets one at its highest-kV real bus (never a transformer star node)
Pd, Qd columns 3, 4 demand.json rows summed per bus: pMw, and qMvar or, when absent, pMw * tan(acos(powerFactor)) with powerFactor defaulting to 0.97 and clamped to [0.01, 1] summed P, Q of the CIM loads demand rows summed per bus
Gs, Bs columns 5, 6 gs, bs not set (0) not set (0)
BaseKv column 10 baseKv, required: a bus without it is refused naming up to twenty buses the CIM bus base voltage the voltage of the merged node
Vm, VaDeg columns 8, 9 vm, vaDeg 1.0, 0 1.0, 0
Name null name CIM name substation name
X, Y 0 x, y 0 set only by the optional geolocation step
Zip null zip null null
VminPu, VmaxPu columns 13, 12; a row of fewer than 13 columns leaves both null with no note; a longer row whose pair is non-finite, not above 0 or has VMIN above VMAX leaves both null and is counted in a parse note vminPu, vmaxPu (refused naming the bus when unusable) null null

BridgeProtocol.BuildModel reads Type, Pd, Qd, Gs, Bs, BaseKv, Vm, Name, X, Y and Zip; it does not read VaDeg or the voltage limits. A bus type name that does not parse silently becomes Pq; only winding names are refused.

Actual kV recovery. A solved result stores Vm in per-unit. The physical voltage at result index i is Result.Vm[i] * Buses[i].BaseKv. No other place applies a voltage base.

ZipLoad

ZipLoad(Ap, Bp, Cp, Aq, Bq, Cq) with defaults (0, 0, 1, 0, 0, 1):

P(V) = Pd * (Ap*V^2 + Bp*V + Cp)          V in pu
Q(V) = Qd * (Aq*V^2 + Bq*V + Cq)
dP/dV = Pd * (2*Ap*V + Bp)                 Jacobian contribution
dQ/dV = Qd * (2*Aq*V + Bq)

VariesWithVoltage is true when any of Ap, Bp, Aq, Bq is non-zero; a bus whose ZIP does not vary is treated as constant power, exactly as a bus with Zip null. ZipLoad.FromInverterFraction(f, nonInverter) blends a constant-power inverter share f (clamped to [0, 1]) with a base composition: f*(0,0,1) + (1-f)*nonInverter, so each triple still sums to 1 when nonInverter's does. The Newton engines apply the ZIP as a deviation from nominal in the mismatch and add its derivatives to the Jacobian diagonal. The drawn power at a solved voltage comes from one helper, LoadAtVoltage (src/GridSim.Core/PowerFlow/LoadAtVoltage.cs), shared by the reactive-limit check and slack reactive diagnostic (NewtonShell), the backward/forward sweep, the distributed-slack power flow, the physics audit and feasibility check (PhysicsLaws, PhysicsFeasibility) and power-flow tracing. JSON zip blocks, the bridge zip block and the JSON v2 zip member set it; MATPOWER, CIM and GDA do not, and the MATPOWER writer reports a ZIP bus as a loss because MATPOWER cannot hold one.

Generator

Generator(Bus, Pg, Qg, Vg, Qmin, Qmax, Pmin, Pmax, MBase, H, Name, Type, DynamicsClass, SubtransientXdPu, NegativeSeqXPu, ConverterInterfaced, ConverterFaultCurrentPu, PowerFlowOnly, UnitTransformerXPu, GridForming, InService, Cost, ReactiveCost).

Field Unit Default Validation Meaning
Bus - required the bus must exist (error), for in-service and out-of-service units alike The bus it sits on. Several generators on one bus are summed by the solvers.
Pg, Qg MW, MVAr Qg 0 finite (in-service units) Dispatched output. At Pv and Slack buses the solve determines the actual Q.
Vg pu 1.0 finite (in-service units) Voltage setpoint at Slack and Pv buses. When several generators share a bus the last one listed sets it (VoltageSetpoint.ForBus, src/GridSim.Core/PowerFlow/VoltageSetpoint.cs), matching MATPOWER.
Qmin, Qmax MVAr -Infinity, +Infinity none: infinity means unlimited and is exempt from the finite check Reactive capability; the per-bus sums feed the reactive-limit loop.
Pmin, Pmax MW 0, +Infinity none in Validate; the JSON loader refuses a non-finite pMinMw, a -Infinity pMaxMw, a +Infinity qMinMvar and a -Infinity qMaxMvar Real-power capability, read by the dispatch and optimal-power-flow studies. The load flow does not read it.
MBase MVA 100 none Machine base for H and the machine reactances.
H MW.s/MVA on MBase 0 none Inertia constant. System inertia is sum(H * MBase); GridModel.SystemInertiaGvaS divides by 1000.
Name, Type - null, "" JSON refuses a null type Identity and fuel or technology tag read by the fuel taxonomy.
DynamicsClass - null none Inline asset-dynamics class; wins over a binding rule.
SubtransientXdPu, NegativeSeqXPu pu on MBase 0 none X''d and X2 for short-circuit studies; at or below 0 selects the synthesised default (X''d) and the round-rotor rule (X2 = X''d).
ConverterInterfaced, ConverterFaultCurrentPu bool?, x rated null none Full-converter plant flag (null is inferred from Type by ConverterPlant.IsConverterType) and its fault-current multiple (null means 1.2, DefaultConverterFaultCurrentPu; 0 means no fault current).
PowerFlowOnly bool false none A balancing or voltage-control device, not physical plant.
UnitTransformerXPu pu on MBase 0 none Step-up transformer reactance added in series with the machine in fault studies.
GridForming bool false none Converter plant with grid-forming control.
InService bool true none False keeps the unit in the model but never solves it.
Cost, ReactiveCost GeneratorCost? null MATPOWER: see below The MATPOWER gencost rows. Cost is read by the costed dispatch (src/GridSim.Core/Analysis/DcOpfCosted.cs, dcopf --costs, and acopf --costs, whose DC passes call it); ReactiveCost is carried and written back by the MATPOWER writer, and no solver reads it.

GeneratorCost(Model, StartupCost, ShutdownCost, Coefficients) holds a MATPOWER cost row: Model 1 is piecewise linear (Coefficients are the points x1, y1, x2, y2, ... as (MW, currency per hour)); Model 2 is a polynomial (Coefficients are the NCOST coefficients, highest order first). PointCount is NCOST. The MATPOWER parser refuses a gencost matrix that has neither one row per generator nor two, a row shorter than MODEL STARTUP SHUTDOWN NCOST, a MODEL other than 1 or 2, an NCOST that is not a whole number of at least 1, a row too short for its NCOST, and any non-finite cost number. The row-count refusal names the counts; every other refusal names the row.

Loaders:

Field MATPOWER (mpc.gen) JSON (generation.json) CIM GDA
Bus column 1 bus the generator's node the matched bus
Pg column 2 outputMw, else capacityMva * capacityFactor, with the factor defaulting by type (Dispatcher.DefaultCapacityFactor); the case is then balanced by Dispatcher.Balance unless system.json sets "dispatch": false CIM P capacity times the fuel capacity factor (FuelMap.CapacityFactor); with GdaBuildOptions.EmbeddedGenAsNegativeLoad the output is subtracted from the bus Pd and no Generator is created
Qg column 3 qOutputMvar, default 0 0 0
Vg column 6 voltageSetpoint, default 1.0 1.0 1.0
Qmin, Qmax columns 5, 4 (absent columns give -Infinity, +Infinity) qMinMvar, qMaxMvar, defaulting to -capacityMva, +capacityMva; the strings "Infinity" and "-Infinity" are the only strings accepted -Infinity, +Infinity plus or minus 0.4 times capacity (GdaBuildDefaults.EmbeddedGenQRatio)
Pmin, Pmax columns 10, 9 (Pmax defaults to +Infinity on a short row) pMinMw default 0; pMaxMw default capacityMva 0, +Infinity 0, capacity
MBase column 7 when above 0, else baseMVA capacityMva 100 capacity
H 0 inertiaH 0 the fuel inertia constant (kind.H)
InService column 8 above 0; a status 0 unit is kept, marked out of service, unless its bus is dropped or undefined inService, default true true true
Cost, ReactiveCost mpc.gencost rows i and ng+i not read by the loader (a cost file is read separately by src/GridSim.Core/IO/Json/GeneratorCostFile.cs) null null
Type, DynamicsClass, machine and converter fields not read type (default ccgt), dynamicsClass, converterInterfaced, converterFaultCurrentPu, powerFlowOnly, unitTransformerXPu, gridForming; subtransientXdPu and negativeSeqXPu load from v2 (N234) and are absent from v1 not read fuel type

BridgeProtocol.BuildModel reads Pg, Qg, Vg, Qmin, Qmax, Pmin, Pmax, MBase, H, Name and Type.

The generator fleet. GridModel.Generators is the in-service fleet in the order given; every engine, analysis and report reads it, so an out-of-service unit is invisible to them. GridModel.AllGenerators is every unit in the order given, which is what the writers save, and GridModel.OutOfServiceGenerators is the units marked out of service. Setting Generators takes the whole fleet and holds the out-of-service units back from the in-service list. When every unit is in service the list given is returned by reference. An out-of-service unit does not raise its JSON bus to Pv and does not make it the slack; a JSON case whose only slack unit is out of service is refused with "No slack bus". A Pv bus with no in-service generator is solved as Pq.

Branch

Branch(From, To, R, X, B, TapRatio, PhaseShiftDeg, RateAMva, Name, IsTransformer, DynamicsClass, InService, LengthKm, Equipment, R0, X0, FromWinding, ToWinding, FromNeutralXPu, ToNeutralXPu, RateBMva, RateCMva). A branch is a line or a transformer in one pi-model.

Field Unit Default Validation Meaning
From, To - required both must be existing buses (error) Terminals. From is the tap side.
R, X pu on BaseMva required finite Series impedance.
B pu on BaseMva 0 finite TOTAL line-charging susceptance; the stamp puts half at each end.
TapRatio ratio 1.0 finite Off-nominal tap magnitude on the From side. A value at or below 0 is treated as 1.0 by every stamp.
PhaseShiftDeg degrees 0 finite Phase-shifting angle, combined with the tap into one complex tap.
RateAMva MVA 0 none Continuous thermal rating. 0 is unrated: loading is reported as 0 percent.
RateBMva, RateCMva MVA 0 none Short-term and emergency ratings. Read only by a contingency screen asked to judge post-fault loading against them (--post-fault-rating B or C); a branch with 0 uses rating A.
Name - null an Oltc and a BoundaryBranch find the branch by exact (ordinal) name Identity.
IsTransformer bool false none Classification flag. The electrical model is only TapRatio and PhaseShiftDeg.
InService bool true none False is an open branch (a recloser or switch): every Y-bus builder skips it and its LineFlow is a zero placeholder.
LengthKm, Equipment km, "ohl" or "cable" 0, null none Circuit length and conductor type for frequency-dependent (skin-effect) modelling in the harmonic engine.
R0, X0 pu on BaseMva 0 none Zero-sequence series impedance for fault studies; both 0 means not supplied (a line then uses the standard ratio times R + jX; a transformer uses R + jX).
FromWinding, ToWinding WindingConnection? null the bridge refuses an unknown name Transformer winding connection (Delta, WyeGrounded, WyeUngrounded) for the zero-sequence network; null on either side makes the branch a line in that network.
FromNeutralXPu, ToNeutralXPu pu 0 none Grounding reactance in the neutral; adds 3 * Xn to the zero-sequence path.
DynamicsClass - null none Inline passive-plant dynamics class.

Loaders:

Field MATPOWER (mpc.branch) JSON (transmission.json, transformer.json) CIM GDA
R, X, B columns 3, 4, 5 line: rPu / circuits, xPu / circuits, bPu * circuits; transformer: rPu, xPu, B = 0 line: ohm and siemens converted on the from bus base (a from bus with no base voltage takes the values as already per-unit); transformer: ohm on each end's rated voltage (a ratedU of 0 or less takes the value as per-unit), the two ends added, B = 0; a three-winding unit becomes a star point with one branch per winding circuit and transformer values converted to the model base; transformer B = 0
TapRatio column 9; 0 means a line (1.0) tapRatio (a line may carry one, so a converted case keeps its branch order) the tap changer, referred to the from side (each winding of a three-winding unit carries its own) 1.0
PhaseShiftDeg column 10 phaseShiftDeg the tap changer 0
RateAMva column 6 ratingMva * circuits (transformer: ratingMva) not set winter rating (line), nominal rating (transformer)
RateBMva, RateCMva columns 7, 8 ratingBMva, ratingCMva (times circuits on a line) not set not set
IsTransformer true when the ratio column is non-zero, even if it is 1 isTransformer; always true for a transformer.json row true true for a transformer
InService a status 0 branch is dropped, so the parsed branch is always in service no v1 key; v2 refuses "inService": false true true
LengthKm, Equipment, R0, X0 not read lengthKm, equipment, rPu0 / circuits, xPu0 / circuits (lines only) not set not set
windings, neutral reactances not read not read; v2 windings, neutralXPu, r0Pu and x0Pu on a transformer (N234) not set not set

BridgeProtocol.BuildModel reads every branch field except LengthKm, Equipment, DynamicsClass, RateBMva and RateCMva; it is the only loader that sets InService false and the winding fields.

Oltc

Oltc(Transformer, ControlsBus, TargetVpu, MinTap, MaxTap, StepPu, DeadbandPu) is an on-load tap changer on the branch named Transformer.

Field Unit Default Meaning
Transformer - required Branch.Name of the transformer it moves.
ControlsBus - required The regulated bus.
TargetVpu pu 1.0 Voltage target.
MinTap, MaxTap ratio 0.9, 1.1 Tap range.
StepPu ratio Oltc.DefaultStepPu = 0.0125 One tap step (1.25 percent).
DeadbandPu pu 0.01 No movement while |Vm - Target| <= Deadband.

Validate gives a warning, never an error, for an OLTC whose ControlsBus does not exist, whose Transformer names no branch, that controls the higher-BaseKv winding, or that controls a bus that is not an end of the transformer. The winding test is skipped only when the two end voltages are equal, both unknown included. If exactly one end has no BaseKv, the unknown end counts as the low-voltage side and the test can fire.

SteadyStateSolver (ch. 3, Power flow) applies these rules on each pass:

  • A record drives the first branch with its Transformer name that has ControlsBus at one end. When no same-named branch touches that bus, it falls back to the first branch of that name.
  • A record naming no branch, or whose ControlsBus is not in the result, is skipped. Those are the only two warned cases that stop regulation. A warned high-voltage-side OLTC, and one whose bus is not an end, still regulate.
  • A record whose controlled bus is generator-regulated as solved (a Pv or Slack bus that the reactive-limit loop has not pinned at a limit) holds its tap.
  • The step direction depends on the end. With the controlled bus on the To (untapped) end, lowering the tap raises its voltage. With the controlled bus on the From (tapped) end, raising the tap raises it. A bus on neither end uses the To rule.

JSON reads onloadtapchanger.json and the v2 oltcs array. The GDA builder creates one per transformer only when GdaBuildOptions.CreateOltcs is set, the two kV values differ and the published tap range is valid; a 0 %/0 % range or an invalid one gives none and is counted in the build notes. The bridge reads them, and MATPOWER and CIM carry none.

Boundary and BoundaryBranch

BoundaryBranch(Branch, Direction = 1) names one branch's contribution to a cut and the sign that counts as positive transfer. Boundary(Name, LimitMw, Branches) is the cut: the flow across it is the signed sum of the named branches' solved flows, compared against LimitMw by src/GridSim.Core/Analysis/BoundaryAnalysis.cs. Each branch name must name exactly one branch of the model, compared ordinally (Boundary.BranchNameProblems). A name that matches nothing, or that several branches share, is an error in GridModel.Validate, is refused by the JSON loader and the bridge model reader, and makes BoundaryAnalysis.Evaluate, LossAllocation.Allocate, PowerFlowTracing.BoundaryTransfers and the contingency screen throw InvalidDataException naming the boundary and the name. Out-of-service branches count as real names. In the reduced post-outage model of the contingency screen an outaged boundary branch is absent and carries no flow. JSON reads boundaries.json and the v2 boundaries array; the bridge reads boundaries and drops one with no branches; MATPOWER, CIM and GDA carry none.

Frequency, base MVA, name

GridModel.FrequencyHz defaults to GridSim.Core.Dynamics.FrequencyLimits.NominalHz (50 Hz), the same value the JSON defaults and the bridge reader take. MATPOWER files carry no frequency: the parser takes the caller's value, else MatpowerParser.AssumedFrequencyHz = 50.0 and writes a parse note saying the value is assumed; a frequency that is not positive and finite is refused. JSON takes system.frequencyHz (default 50.0 in v1; read from the system block in v2); the bridge takes frequencyHz and refuses a value that is not positive and finite; the GDA builder uses GdaBuildDefaults.SystemFrequencyHz = 50.0; the CIM bridge leaves the default.

BaseMva is required. MATPOWER takes mpc.baseMVA, defaulting to 100 when the scalar is absent; JSON takes system.baseMva, which becomes GridModel.DefaultBaseMva = 100 only when it is absent; a present value that is zero, negative or not finite is refused by Validate (below); the CIM bridge takes its baseMva argument (100); the GDA builder takes GdaBuildOptions.BaseMva (100); the bridge takes baseMva, reads an absent value as GridModel.DefaultBaseMva, and refuses a present value that is not finite and above 0. Name for MATPOWER is the caller's name, else the function mpc = <name>, else "matpower"; the file loader passes the file stem, so the stem wins over the function name, and a built-in case passes a display name such as "IEEE 14-bus". For JSON it is system.name or the folder name, for CIM the caller's argument, and for GDA the dataset and filter description. "grid" is only the GridModel.Name default.

Asset bindings and protections

GridModel.AssetDynamics is an AssetDynamicsModel(Library, Bindings): an AssetClassLibrary of authored asset classes and an AssetBindingSet of AssetBinding(MatchType, ClassName) rules. AssetBindingSet.Resolve(inlineClass, assetType) returns the inline DynamicsClass of the element when it has one; otherwise the first rule whose MatchType equals the element's Type (case-insensitive, exact rules first); otherwise the first prefix rule, a MatchType ending in * (wind* matches wind-onshore and wind-offshore); otherwise null, and the element stays passive. GridModel.Protections is a ProtectionModel(Library, Instances) of placed ProtectionInstance(Name, ClassName, MonitorBus, CapacityMw, TargetBranch) devices. Both are null for a case that ships no asset-classes.json or protections.json. The JSON loader builds them from asset-classes.json, asset-bindings.json and protections.json and fails loud on a binding to an unknown class, bindings with no classes, a class kind or provenance tag it does not know, and an instance whose class is not a protection class; after the model is built it checks every placed device against the network. The classes are specified in ch. 13, Asset dynamics and data grounding and ch. 15, Protections.

Per-unit conventions

  • One system base. All power is converted with GridModel.BaseMva alone. The specified injection at a bus is Pspec = (sum Pg - Pd) / BaseMva and Qspec = (sum Qg - Qd) / BaseMva (NewtonShell.BuildBusSpec, src/GridSim.Core/PowerFlow/NewtonShell.cs). Pspec and Qspec hold the nominal load; a ZIP load is applied as a deviation inside the iteration.
  • Voltage bases. Bus.BaseKv is the nominal line-to-line voltage of the bus. The solve never reads it. A branch's R, X and B are entered per-unit on BaseMva and on the voltage bases of its ends, so no impedance conversion happens inside the solvers. Converting an impedance given in ohms is a loader job and uses the base impedance of the bus voltage:
Zbase = BaseKv^2 / BaseMva            ohm   (BaseKv in kV, BaseMva in MVA)
r_pu  = r_ohm / Zbase,   x_pu = x_ohm / Zbase
b_pu  = b_siemens * Zbase             a susceptance converts the other way

The CIM bridge applies this to a line on the from-bus base and to each transformer winding on that winding's own rated voltage ratedU (the per-unit impedance is invariant across the ideal ratio, so the two windings' values add with no referral factor). The GDA builder converts percent data in three ways. A circuit impedance is pu = percent / 100 * (BaseMva / 100) and a circuit susceptance is pu = percent / 100 / (BaseMva / 100). A transformer impedance is pu = percent / 100 * (BaseMva / txBase), where txBase is the transformer rating (GdaBuildDefaults.TransformerRatingFallbackMva when the rating is 0 or less) if the dataset gives percent on rating, else 100. Ohm data is divided by the base impedance of RefZBase, which uses GdaBuildOptions.RefKv when it is set and otherwise the grid supply point group voltage. The MATPOWER unit normaliser (below) applies the formula above to raw distribution files. - Shunts are entered in engineering units (MW and MVAr at 1.0 pu) and divided by BaseMva at stamp time, the only place a bus field is converted inside the Y-bus builders. - Voltages are per-unit throughout; BaseKv converts back to kV for display. - Angles are degrees in Bus.VaDeg and PowerFlowResult.VaDeg and radians inside every solver loop. - Results return to engineering units at assembly: PInjMw = P_pu * BaseMva, and line flows likewise (NewtonShell.AssembleResult, NewtonShell.ComputeLineFlows). - Convergence tolerances are per-unit power mismatches; the default 1e-8 is 1 W on a 100 MVA base.

Transformer conventions

A transformer is one Branch. Its off-nominal ratio and phase shift form one complex tap on the from side:

a   = TapRatio                         (a <= 0 is replaced by 1.0)
phi = PhaseShiftDeg * pi / 180
tap = a * e^(j*phi)                    DetMath.FromPolar(a, phi)

The from terminal sees the pi-model through an ideal transformer of complex ratio tap : 1, as in MATPOWER; the to terminal connects to the pi-model directly. A tap of 1.0 with zero shift is a plain line. Oltc limits (MinTap, MaxTap) are tap ratios in the same convention. The phase shift acts only through the asymmetric mutual terms below. The magnetising branch is not modelled: no loader sets a shunt on a transformer branch, and B is 0 for every transformer a loader builds.

Y-bus construction

The branch stamp

The branch stamp has one source, AdmittanceStamp.Branch (src/GridSim.Core/PowerFlow/AdmittanceStamp.cs), which returns a BranchStamp(Yff, Ytt, Yft, Ytf). Every builder of the network matrix uses it: the dense YBus.Build, its cell-only twin YBus.BuildSparse, and the sparse power-flow Y SparseNewtonRaphsonPowerFlow.BuildY. So do the branch flows (NewtonShell.ComputeLineFlows), the estimator's flow measurement model, the fault studies, the physics audit and the harmonic Y(h), which at h = 1 agrees with the fundamental Y-bus to within 1e-9 per cell (FrequencyDependentYBusTests); that agreement is a tolerance, not a bit-identity claim.

ys  = 1 / (R + jX)                        series admittance
bc  = j * B / 2                           half the line charging, per end
a   = TapRatio  (<= 0 treated as 1.0)
tap = a * e^(j * PhaseShiftDeg * pi/180)  complex tap, on the FROM side

Yff = (ys + bc) / a^2                     from-end self term
Ytt =  ys + bc                            to-end self term
Yft = -ys / conj(tap)                     from-to mutual
Ytf = -ys / tap                           to-from mutual

These are the terms of the branch current equations

I_from =  (ys + bc)/a^2 * V_from  -  ys/conj(tap) * V_to
I_to   = -ys/tap        * V_from  + (ys + bc)     * V_to

Points to audit:

  • The ideal transformer sits on the from side. The from-end self term, including the from half of the line charging, is referred through the tap by 1/a^2; the to-end self term is unscaled.
  • The phase shift never appears in the self terms, because |tap|^2 = a^2. It rotates only the mutual terms, and asymmetrically (conj(tap) against tap), which is what makes a phase shifter move flow: Yft != Ytf whenever the shift is not a multiple of 180 degrees.
  • With no shift the stamp is symmetric: Yft = Ytf = -ys / a.
  • A branch with R = 0 and X = 0 has no finite series admittance; Validate refuses it (below), so no loaded model reaches the stamp with one.
  • DetMath.FromPolar is a * (cos phi + j sin phi) over the deterministic fdlibm DetMath.SinCos, not the platform's Complex.FromPolarCoordinates, so the tap has the same bits on every operating system.
  • The harmonic and long-line builders call AdmittanceStamp.FromAdmittance with an already computed series admittance and per-end shunt; the tap arithmetic is the same lines.

The bus matrix

For every in-service branch the builder adds the four stamp terms to Y[f,f], Y[t,t], Y[f,t] and Y[t,f], where f and t are the matrix indices of From and To (their positions in Buses). Branches are visited in model order. Then every bus with Gs != 0 or Bs != 0 adds (Gs + jBs) / BaseMva to its diagonal, in bus order. Cells start at +0.0 and accumulate by complex addition, so the result is a fixed sum in a fixed order:

Y[i,i] = sum over in-service branches with From = i of Yff
       + sum over in-service branches with To   = i of Ytt
       + (Gs_i + j*Bs_i) / BaseMva                                   added last
Y[i,k] = sum over in-service branches From = i, To = k of Yft
       + sum over in-service branches From = k, To = i of Ytf        (i != k)

with each sum taken in branch order. Parallel circuits between one pair of buses accumulate, so duplicated branches are summed admittances. With Y = G + jB, the shunt sign gives a drawn complex power |V|^2 * (Gs - jBs) at voltage V pu: positive Gs draws MW, positive Bs injects MVAr. Line charging is the only shunt on a branch.

Out-of-service branches and islands

An out-of-service branch (InService false) is skipped by every builder and contributes no admittance. A model with every branch in service builds the same matrix as a model with no such flag. NewtonShell.ComputeLineFlows emits a zero-flow LineFlow for the skipped branch, so LineFlows[i] stays aligned with Branches[i].

The Y-bus builders do not partition the network. A split network gives a block-diagonal Y, and a block with no reference bus is singular. Two rules keep that from reaching the solver. First, a model may carry several Slack buses, one reference per island, each held at its own setpoint (Validate warns, it does not refuse). Second, IslandPartition.Prepare (src/GridSim.Core/PowerFlow/IslandPartition.cs), applied by TopologyOps.Apply for the live simulator's recloser-opened branches, finds the connected components over in-service branches and, per island: keeps an island that has a slack; elects as slack the bus with the largest single |Pg| in an island that has generation (a bus counts as generating when its units' |Pg| sum is above 0) and no slack; and blacks out an island with no generation, removing its buses, branches and generators from the model and booking the lost demand (Pd) and lost generation (Pg) in the IslandReport. A model that is one connected component with a slack is returned unchanged (the same object). The pre-pass keeps the out-of-service generators of live buses (AllGenerators).

Dense and sparse builders, and how they stay identical

Builder Output Used by
YBus.Build (src/GridSim.Core/PowerFlow/YBus.cs) Complex[n,n] the dense Newton engine, the distributed-dynamics initialisation and the fault network system
YBus.BuildSparse SparseYBus: a dictionary of stamped cells (a cell that sums to exactly zero is kept) keyed (row, col) by bus index, no dense array the estimator's measurement model, the fault analysis and the subtransient initialisation of a large model
SparseNewtonRaphsonPowerFlow.BuildY (src/GridSim.Core/PowerFlow/SparseNewtonRaphsonPowerFlow.cs) ComplexCsr (src/GridSim.Core/Numerics/Sparse.cs): RowPtr, ColIdx, separate G and B arrays, a diagonal pointer per row the sparse Newton engine

All three read the same AdmittanceStamp.Branch, visit branches and then shunts in the same order, and begin every cell from +0.0. Three details make the sums bit-identical:

  1. Signed zeros. The dense array starts every cell at +0.0, so the first stamp is 0.0 + v, which turns a -0.0 component into +0.0. BuildSparse adds Complex.Zero to the first stamp of a cell for the same reason, and ComplexCsr.Builder.Build writes 0.0 + g, 0.0 + b for the first entry of a cell.
  2. Summation order. ComplexCsr.Builder.Build sorts each row by (column, insertion index), a unique key, so the entries of one cell keep their insertion order whatever the sort algorithm does. That order is the dense order (branches, then shunts). An unstable sort would sum the diagonal of a bus with many branches in a different order.
  3. Shunt division. The dense builder divides the complex number (Gs, Bs) by the real BaseMva; the sparse builder divides Gs and Bs separately. The dense division uses the Complex / double operator, which divides each component, so the values are equal; the dense-sparse parity tests pin that on the cases with shunts (case14, case30, case118).

ComplexCsr.Builder.Add skips a stamp whose real and imaginary parts are both exactly 0; a skipped stamp changes no sum. The CSR keeps a diagonal entry in every row, stored as zero when no stamp lands there.

Unit normalisation for distribution MATPOWER files

Four published radial feeders (case22, case33bw, case69, case85 in data/matpower/dist) declare baseMVA and per-bus baseKV but give branch impedance in ohms and bus demand in kW and kVAr. Read as per-unit and MW, a 3.715 MW feeder would be 3715 MW. MatpowerParser therefore passes every parse through MatpowerUnitNormalizer (src/GridSim.Core/IO/Matpower/MatpowerUnitNormalizer.cs) by default (MatpowerUnitHandling.NormaliseRawFeeders).

Detection. LooksRawUnits(model) is true only when all three tells agree; unit-ness is not recorded in the file, so the test errs towards leaving a file alone.

Tell Rule Constant
Distribution scale at least one BaseKv above 0, and no bus above DistributionKvCeiling = 35 kV DistributionKvCeiling
Load magnitude sum(abs(Pd)) / BaseMva at least LoadToBaseRatioTrigger = 30 LoadToBaseRatioTrigger
Ohmic impedance the median sqrt(R^2 + X^2) as given is at least OhmicImpedanceFloor = 0.05, and the median of that value divided by the from-bus Zbase is below ConvertedPuImpedanceCeiling = 1.0 OhmicImpedanceFloor, ConvertedPuImpedanceCeiling

A model with BaseMva at or below 0, no buses or no branches is never flagged. A 110 kV source bus vetoes the file, which is what keeps the already-per-unit cigre_mv case untouched.

Conversion. Normalize(model) returns the model unchanged when it does not look raw; otherwise it returns a copy (built through CopyWith) in which:

R, X     <- R, X / Zbase(from bus)         Zbase = BaseKv^2 / BaseMva
Pd, Qd, Gs, Bs <- value / 1000             kW, kVAr -> MW, MVAr

B and the generators are not changed: the known raw feeders carry no line charging, and their only generator is the slack, whose output the solve computes. A branch whose from bus has no BaseKv keeps its raw impedance.

Guards. MatpowerParser.ParseWithDiagnostics adds a parse note naming the conversion and sets MatpowerParseResult.RawUnitsConverted. It then checks that the converted model no longer looks raw and throws InvalidDataException if it does, because a caller that wraps Normalize again would otherwise convert a second time. MatpowerUnitHandling.AsWritten keeps the numbers as the file writes them and adds a note that the case looks raw and was not converted. An undefined MatpowerUnitHandling value throws ArgumentOutOfRangeException. A file that does not look raw is returned as the same result object, so every other bundled file parses exactly as written.

Immutability and the copy helpers

The element types are records. A "modified" element is a with copy; Normalize builds its buses with b with { Pd = ..., Qd = ... } and TopologyOps.Apply opens a branch with b with { InService = false }. Record equality compares fields, and compares the list-valued fields (Boundary.Branches, GeneratorCost.Coefficients) by reference. GridModel is a class with init-only properties and IReadOnlyList<T> collections, and no code changes a model after construction, so it is shared across parallel N-1 solves without a defensive copy. The language does not enforce this for the list contents: the loaders pass List<T> instances. A "modified" network is a new GridModel.

GridModel.CopyWith(buses, generators, branches, oltcs, boundaries, name, frequencyHz, assetDynamics) is the one copy method. Every argument left null is carried across unchanged, and every property it does not take (BaseMva, Protections) is carried too. Its generator rule:

  • With generators null, the whole fleet is carried, out-of-service units included, and the copy's Generators is the same in-service list.
  • With a generators list that holds no out-of-service unit (a redispatch builds it from Generators), this model's out-of-service units are appended after it; the copy's Generators is exactly the list given.
  • With a generators list that itself marks a unit out of service, that list is taken as the complete fleet.

Other helpers build on it: Dispatcher.Clone (src/GridSim.Core/Dispatch/Dispatcher.cs) passes through CopyWith; TopologyOps.Apply copies with an opened branch set; MatpowerUnitNormalizer.Normalize copies with replaced buses and branches. AssetEnvelope, which swaps the asset-dynamics bundle per sweep corner, copies through CopyWith too (assetDynamics, N314), so no copy is built by hand.

Validation

GridModel.Validate() returns a list of GridDiagnostic(Severity, Message) and never throws; ToString() renders error: ... or warning: ..., the format the CLI prints. Entry-point loaders throw InvalidDataException on any error (the MATPOWER parser and the JSON loader run it after building); the GDA merge pipeline collects the findings as notes.

Errors:

  1. A BaseMva or a FrequencyHz that is not a finite number above 0.
  2. Duplicate bus id, once per id.
  3. No slack bus.
  4. A branch From or To that is not a bus.
  5. A branch whose From equals its To (a self-loop), whatever its service state.
  6. A branch with R and X both 0 (either sign of zero), whatever its service state: its admittance 1 / (R + jX) is not finite. A real zero-impedance tie is modelled by merging its two buses or by a small reactance.
  7. An island (a set of buses joined by in-service branches) with no slack bus of its own, reported with its size and its lowest-id buses. Checked only when the model has a slack and no duplicate bus id.
  8. An in-service generator, or an out-of-service generator, on a bus that does not exist.
  9. A bus voltage limit that is not finite and above 0 pu, or a VminPu above its VmaxPu.
  10. A boundary branch name that matches no branch or more than one.
  11. A non-finite Pd, Qd, Gs or Bs per bus; R, X, B, TapRatio or PhaseShiftDeg per branch; Pg, Qg or Vg per in-service generator. A NaN or infinity here would feed the Y-bus and Jacobian and poison the solve, so it is caught as a model fault. Generator Qmin, Qmax, Pmin and Pmax are excluded because infinity means no limit.

Warnings: more than one slack bus (a multi-island system); an OLTC whose ControlsBus does not exist, whose Transformer names no branch, that controls the higher-BaseKv winding, or that controls a bus that is not an end of its transformer.

Parameters and defaults

Constants that fix the data-model defaults and thresholds:

Name Value Unit Meaning Source symbol
Default system base 100 MVA Used where the JSON system file gives no baseMva (absent), and where the bridge model block gives a value at or below 0; MATPOWER, CIM and GDA use their own literal 100.0 GridModel.DefaultBaseMva
Default frequency 50.0 Hz The GB nominal and the GridModel.FrequencyHz default (a literal 50.0 there); the JSON defaults and bridge reader take it from FrequencyLimits.NominalHz GridModel.FrequencyHz, FrequencyLimits.NominalHz
Assumed MATPOWER frequency 50.0 Hz Taken when the caller gives none; noted in the parse result MatpowerParser.AssumedFrequencyHz
Default OLTC step 0.0125 ratio One tap step Oltc.DefaultStepPu
Default OLTC range 0.9 to 1.1 ratio MinTap, MaxTap Oltc constructor defaults
Default OLTC deadband 0.01 pu No movement inside it Oltc.DeadbandPu
JSON load power factor 0.97 - Used when a demand row gives no qMvar JsonDefaults.LoadPowerFactor
JSON minimum power factor 0.01 - Lower clamp on a demand row's power factor JsonDefaults.MinPowerFactor
ZIP sum tolerance 1e-9 - How far a coefficient triple may sum from 1 JsonGridLoader.ZipSumTolerance
Converter fault current 1.2 x rated Default k of a converter-interfaced unit Generator.DefaultConverterFaultCurrentPu
Operational voltage band 0.94 to 1.06 pu Applies on a side a bus leaves null VoltageLimits.OperationalLowPu, OperationalHighPu
Distribution kV ceiling 35 kV Raw-feeder tell 1 MatpowerUnitNormalizer.DistributionKvCeiling
Load-to-base trigger 30 x BaseMva Raw-feeder tell 2 MatpowerUnitNormalizer.LoadToBaseRatioTrigger
Ohmic impedance floor 0.05 as given Raw-feeder tell 3 MatpowerUnitNormalizer.OhmicImpedanceFloor
Converted impedance ceiling 1.0 pu Raw-feeder tell 3 MatpowerUnitNormalizer.ConvertedPuImpedanceCeiling
Default tap 1.0 ratio Branch.TapRatio default; a MATPOWER ratio of 0 and any ratio at or below 0 at stamp time mean 1.0 Branch.TapRatio, AdmittanceStamp.FromAdmittance

The per-field defaults are in the element tables above.

The per-bus limits are used by the contingency verbs nminus1, nminus2 and n-1-1 by default, through VoltageLimits.OperationalLowFor and OperationalHighFor, which fall back to the operational band on a side the bus leaves null; --global-vlimits restores the single band. The API default, PowerFlowOptions.PerBusVoltageLimits, is false, and the CLI sets it unless --global-vlimits is given.

Invariants

Invariant Test
The branch stamp equals a separately written reference of the textbook pi-model with a from-side tap, bit for bit (the reference repeats the production formulas, so it guards drift, not the convention), for a plain line, a lossless reactance, an off-nominal tap, a phase shifter and a tap at or below 0 AdmittanceStampPinTests.Branch_stamp_matches_an_independent_textbook_derivation_bit_for_bit
YBus.BuildSparse cells equal YBus.Build cells bit for bit, and an absent cell is exactly zero in the dense matrix (case9, case30, case118, case300) YBusSparseEquivalencePinTests.BuildSparse_cells_are_bit_for_bit_the_dense_build
The CSR builder is byte-identical to a reference for shuffled and duplicate entries (a six-row case with at most three entries in a row, so the order above 16 entries is not exercised there), and the fundamental Y(h) build agrees with the dense Y-bus to within 1e-9 ComplexCsrBuilderPinTests.Build_is_byte_identical_to_a_reference_for_shuffled_and_duplicate_entries, Fundamental_Y_h_build_is_unchanged_by_the_sort_port
The dense and sparse Newton engines give the same bits on built-in, MATPOWER and JSON cases DenseSparseParityTests.Built_in_case_is_bit_identical_dense_vs_sparse, Matpower_file_is_bit_identical_dense_vs_sparse, Json_case_is_bit_identical_dense_vs_sparse
Rows above 16 entries sum in dense order: the largest bundled buses (17 incident branches in case1354pegase.m and case2869pegase.m) solve bit-identically on both engines DenseSparseParityTests.Matpower_file_is_bit_identical_dense_vs_sparse
An out-of-service branch is skipped by the sparse Y as by the dense one SparsePowerFlowTests.Matches_dense_when_a_branch_is_out_of_service
The island pre-pass is a no-op with every branch in service, elects a slack for a generating island, blacks out a dead island and books its lost load, and the adjusted model solves IslandPartitionTests.All_in_service_is_a_no_op, Islanding_a_generating_region_elects_a_slack, Islanding_a_dead_region_blacks_it_out_and_books_the_lost_load, The_adjusted_islanded_model_solves
CopyWith knows every settable GridModel property, so a new property cannot be silently dropped GridModelCopyTests.CopyWith_knows_every_settable_property
CopyWith() carries every property by reference, and replaces only what it is given GridModelCopyTests.CopyWith_with_no_arguments_carries_every_property_by_reference, CopyWith_replaces_only_what_it_is_given
A MATPOWER status 0 generator is kept and marked out of service; solving with it present is bit-identical to solving without it; an all-in-service fleet is returned by reference; CopyWith keeps the out-of-service units GeneratorInServiceTests.A_status_0_matpower_generator_is_kept_and_marked_out_of_service, Solving_a_model_with_out_of_service_units_is_bit_identical_to_solving_without_them, An_all_in_service_fleet_is_returned_by_reference, CopyWith_carries_out_of_service_units_and_keeps_the_in_service_list
A JSON unit marked out of service is kept, not solved and does not type its bus; a case whose only slack unit is out of service is refused GeneratorInServiceTests.A_json_unit_marked_out_of_service_is_kept_but_not_solved_and_does_not_type_its_bus, A_json_case_whose_only_slack_unit_is_out_of_service_is_refused
Derived models (scaled loads, warm-started copies, scenarios, laid-out copies, opened branches) keep the out-of-service units DerivedModelsKeepOutOfServiceUnitsTests
Duplicate bus ids, a missing slack, dangling branch or generator references and a non-finite branch reactance are errors; several slacks and infinite Q limits are not; case9 validates clean. The other non-finite checks and the OLTC "nonexistent bus" and "not an endpoint" warnings have no test GridModelValidateTests (Duplicate_bus_id_is_an_error, Missing_slack_is_an_error, Multiple_slacks_is_a_warning_not_an_error, Dangling_branch_endpoint_is_an_error, Generator_on_nonexistent_bus_is_an_error, Non_finite_branch_reactance_is_an_error, Infinite_generator_q_limits_are_not_flagged, Clean_case9_produces_no_diagnostics)
An out-of-service generator on a missing bus is an error GeneratorInServiceTests.Validate_refuses_an_out_of_service_unit_on_a_missing_bus
OLTC warnings: missing transformer, HV-side control, clean LV-side control GridModelValidateTests.Oltc_naming_a_nonexistent_transformer_warns, Oltc_on_the_hv_side_warns, Oltc_on_the_lv_side_is_clean
Per-bus limits are read from MATPOWER columns 12 and 13, a row too short to carry them leaves the global band silently, an unusable pair leaves it with a note, and Validate refuses unusable limits PerBusVoltageLimitTests.Matpower_bus_columns_12_and_13_are_read_as_vmax_and_vmin, A_short_or_unusable_limit_pair_leaves_the_bus_on_the_global_band_with_a_note, Validate_refuses_unusable_per_bus_limits
A ZIP block loads exactly, a missing or non-finite coefficient or a triple not summing to 1 is refused, and a decimal triple with binary rounding is accepted ZipLoadWiringTests.A_valid_zip_block_loads_onto_the_bus_exactly, A_zip_missing_a_coefficient_fails_loud_naming_the_bus_and_key, A_zip_real_triple_not_summing_to_one_fails_loud, A_decimal_triple_with_binary_rounding_is_accepted
Boundary branch names must resolve to exactly one branch in code, JSON, the bridge, Validate and the studies BoundaryNamesInCodeTests
A raw feeder parses to exactly the model the product paths built, every other bundled file parses as before, case33bw solves to the published Baran and Wu values, an undefined unit handling is refused, and a file that still looks raw after one conversion is refused N165MatpowerUnitDefaultTests
Export and import round trip, for one decorated case9 model, the ZIP load, a generator Pmin, branch R0 and X0, the windings, ToNeutralXPu, the OLTCs and one boundary; an opened branch stays out of service; and that model re-solves to the bit-identical state. VaDeg and the voltage limits are not carried (see Limits) SolveExportRoundTripTests.Every_carried_network_field_round_trips_exactly, An_opened_branch_stays_out_of_service_through_export_and_import, The_reimported_model_resolves_to_the_bit_identical_state
A bundled case loaded through its v2 projection gives the v1 model and solve bit for bit V2CaseLoaderTests.A_bundled_case_loaded_through_its_v2_projection_gives_the_v1_model_and_solve_bit_for_bit
The MATPOWER parser classifies a branch as line or transformer by its ratio, drops isolated buses and out-of-service branches, handles non-contiguous ids, and refuses a case with no reference bus MatpowerParserTests.Line_vs_transformer_by_ratio, Drops_isolated_buses_and_incident_elements, Skips_out_of_service_elements, Handles_noncontiguous_bus_ids, Throws_when_no_reference_bus

Worked example

The example builds by hand the Y-bus entries of one line and one transformer of case14 and compares them with the Y-bus triplets of a real run. The run writes a solve export, which holds the model as solved and the Y-bus as ybus triplets (I, J are zero-based matrix indices, G and B the real and imaginary parts, per-unit):

gridsim case14 --once --enableExport
$ gridsim case14 --once --enableExport
[export] dense-newton: converged=True iters=2 maxMis=1.32E-010  ->  results\exports\case14-solve.json
[exit 0]

The iteration count and mismatch are as captured; they and any timing differ by machine and run. The captures show the export path relative to the repository; the command prints the absolute path of the file. The model rows used below, from the export's model block (baseMva is 100):

$ python -c "import json;m=json.load(open('results/exports/case14-solve.json'))['model'];print(m['baseMva']);[print(json.dumps(b)) for b in m['branches'] if (b['from'],b['to']) in {(1,2),(4,7)}];print(json.dumps(m['buses'][8]))"
100
{"from": 1, "to": 2, "r": 0.01938, "x": 0.05917, "b": 0.0528, "tap": 1, "phaseShiftDeg": 0, "rateAMva": 0, "isTransformer": false, "inService": true, "r0": 0, "x0": 0, "fromNeutralXPu": 0, "toNeutralXPu": 0, "lengthKm": 0, "rateBMva": 0, "rateCMva": 0}
{"from": 4, "to": 7, "r": 0, "x": 0.20912, "b": 0, "tap": 0.978, "phaseShiftDeg": 0, "rateAMva": 0, "isTransformer": true, "inService": true, "r0": 0, "x0": 0, "fromNeutralXPu": 0, "toNeutralXPu": 0, "lengthKm": 0, "rateBMva": 0, "rateCMva": 0}
{"id": 9, "type": "Pq", "baseKv": 0, "pd": 29.5, "qd": 16.6, "gs": 0, "bs": 19, "vm": 1.056, "vaDeg": -14.94, "x": 0, "y": 0, "vminPu": 0.94, "vmaxPu": 1.06}
[exit 0]

case14 is the built-in IEEE case, so every baseKv is 0: the per-unit solve does not need it. The exported Y-bus cells for the buses involved (bus k is matrix index k - 1):

$ python -c "import json;[print(json.dumps(t)) for t in json.load(open('results/exports/case14-solve.json'))['solve']['ybus'] if (t['I'],t['J']) in {(0,0),(0,1),(3,3),(3,6),(6,3),(6,6),(8,8)}]"
{"I": 0, "J": 0, "G": 6.025029055768224, "B": -19.447070205514382}
{"I": 0, "J": 1, "G": -4.999131600798035, "B": 15.263086523179553}
{"I": 3, "J": 3, "G": 10.512989522036175, "B": -38.654171207607796}
{"I": 3, "J": 6, "G": 0, "B": 4.889512660317341}
{"I": 6, "J": 3, "G": 0, "B": 4.889512660317341}
{"I": 6, "J": 6, "G": 0, "B": -19.549005948264654}
{"I": 8, "J": 8, "G": 5.3260550394673585, "B": -24.092506375267877}
[exit 0]

The line, bus 1 to bus 2. R = 0.01938, X = 0.05917, B = 0.0528, tap 1.0, shift 0.

|z|^2 = 0.01938^2 + 0.05917^2 = 0.0038766733
ys    = 1/(0.01938 + j0.05917) = 4.999131600798035 - j15.263086523179553
bc    = j * 0.0528 / 2         = j0.0264
a = 1,  tap = 1

Yff = Ytt = ys + bc            = 4.999131600798035 - j15.236686523179552
Yft = Ytf = -ys                = -4.999131600798035 + j15.263086523179553

Y[1,2] is only this branch, so the exported cell is the stamp: G = -4.999131600798035, B = 15.263086523179553, equal to the last printed digit. Y[1,1] collects the from end of the two branches that leave bus 1 (1-2 and 1-5; bus 1 has no shunt). Branch 1-5 gives 1.025897454970189 - j4.210383682334831, so

Y[1,1] = (4.999131600798035 - j15.236686523179552) + (1.025897454970189 - j4.210383682334831)
       =  6.025029055768224 - j19.447070205514382

which is the exported I = 0, J = 0 cell.

The transformer, bus 4 to bus 7. R = 0, X = 0.20912, B = 0, TapRatio = 0.978, shift 0, so tap = 0.978 and a^2 = 0.956484.

ys  = 1/(j0.20912)             = -j4.781943381790359
bc  = 0
Yff = ys / a^2 = ys / 0.956484 = -j4.999501697665993     stamped on Y[4,4]
Ytt = ys                       = -j4.781943381790359     stamped on Y[7,7]
Yft = -ys / conj(tap)          = +j4.889512660317341     = ys * (-1/0.978), Y[4,7]
Ytf = -ys / tap                = +j4.889512660317341     Y[7,4]

The exported cells I = 3, J = 6 and I = 6, J = 3 hold G = 0, B = 4.889512660317341, equal to Yft and Ytf. The off-diagonal terms are scaled by 1/a and the from self term by 1/a^2: |Yft| = 4.78194 / 0.978, and Yff is larger than Ytt by the factor 1/0.956484. Bus 7 has no shunt and three branches, 4-7 (to end), 7-8 and 7-9 (from end, both untapped, no charging), which contribute -j4.781943381790359, -j5.676979846721544 and -j9.09008271975275; the sum, added in branch order, is -j19.549005948264654, the exported I = 6, J = 6 cell. Bus 4 collects five stamps in branch order:

2-4  Ytt   1.686033150614943  - j5.098838325872083
3-4  Ytt   1.9859757099255606 - j5.06241697759392
4-5  Yff   6.840980661495671  - j21.578553981691588
4-7  Yff   0                  - j4.999501697665993      (the tapped from end, 1/a^2)
4-9  Yff   0                  - j1.914860224784211      (tap 0.969, 1/a^2)
sum        10.512989522036175 - j38.654171207607796     = exported I = 3, J = 3

The shunt. Bus 9 has Bs = 19 MVAr, so 19 / 100 = j0.19 pu is added last to Y[9,9]. The branch stamps at bus 9 are the to end of 4-9 (-j1.7979790715236075), the to end of 7-9 (-j9.09008271975275) and the from ends of 9-10 (3.9020495524474277 - j10.365394127060915) and 9-14 (1.424005487019931 - j3.0290504569306034). Their sum plus the shunt is 5.3260550394673585 - j24.092506375267877, the exported I = 8, J = 8 cell. Without the shunt the imaginary part would be -24.282506375267877.

Every hand-computed cell equals the exported cell to the printed digits. AdmittanceStampPinTests and YBusSparseEquivalencePinTests assert the stamp and the sparse-dense equality in IEEE doubles, not to printed digits.

Unit normalisation of a raw feeder

case33bw stores its branch impedance in ohms and its demand in kW and kVAr. The parse converts it and says so:

$ gridsim data/matpower/dist/case33bw.m --once --enableExport
[export] bfs: converged=True iters=8 maxMis=6.82E-011  ->  results\exports\case33bw-solve.json
note: case33bw.m: nominal frequency not given (MATPOWER files carry none); assumed 50 Hz - pass the real value if this is, for example, a 60 Hz system (gridsim: --frequency-hz 60).
note: case33bw.m: the file has 2 indexed assignment(s) after the matrices (mpc.branch, mpc.bus); MATLAB statements are not run, so they are not applied (a raw-unit distribution feeder is converted by the unit normaliser instead).
note: case33bw.m: read mpc.gencost (1 row(s)); the costs are carried on the generators and used by dcopf / acopf when asked (--costs case); without it the OPF uses the fuel-type merit order.
note: case33bw.m: skipped 5 out-of-service branch(es).
note: case33bw.m: raw engineering units detected (branch impedance in ohms, demand in kW / kVAr, as in the published distribution feeders); converted to per-unit and MW: R and X divided by Zbase = baseKV^2 / baseMVA of the from bus, Pd, Qd, Gs and Bs divided by 1000.
[exit 0]

The raw rows, then the same rows in the model the solver received:

$ grep -nE '^\s(2\s1\s100|1\s2\s0.0922)' data/matpower/dist/case33bw.m
23: 2   1   100 60  0   0   1   1   0   12.66   1   1.1 0.9;
66: 1   2   0.0922  0.0470  0   0   0   0   0   0   1   -360    360;
[exit 0]
$ python -c "import json;m=json.load(open('results/exports/case33bw-solve.json'))['model'];print(m['baseMva']);print(json.dumps(m['buses'][1]));print(json.dumps(m['branches'][0]))"
10
{"id": 2, "type": "Pq", "baseKv": 12.66, "pd": 0.1, "qd": 0.06, "gs": 0, "bs": 0, "vm": 1, "vaDeg": 0, "x": 0, "y": 0, "vminPu": 0.9, "vmaxPu": 1.1}
{"from": 1, "to": 2, "r": 0.005752591161723931, "x": 0.002932448856844086, "b": 0, "tap": 1, "phaseShiftDeg": 0, "rateAMva": 0, "isTransformer": false, "inService": true, "r0": 0, "x0": 0, "fromNeutralXPu": 0, "toNeutralXPu": 0, "lengthKm": 0, "rateBMva": 0, "rateCMva": 0}
[exit 0]

With BaseMva = 10 and BaseKv = 12.66, Zbase = 12.66^2 / 10 = 16.02756 ohm, so R = 0.0922 / 16.02756 = 0.005752591161723931 pu and X = 0.0470 / 16.02756 = 0.002932448856844086 pu; the 100 kW, 60 kVAr load of bus 2 is 0.1 MW and 0.06 MVAr. The five skipped branches are the file's status 0 tie switches. The export solved this radial feeder with the backward/forward sweep (bfs).

Source map

File Type or function Responsibility
src/GridSim.Core/Model/Model.cs GridModel, Bus, Generator, Branch, Oltc, Boundary, BoundaryBranch, ZipLoad, GeneratorCost, WindingConnection, ConverterPlant, GridDiagnostic The model, Validate, CopyWith, the generator fleet split
src/GridSim.Core/PowerFlow/AdmittanceStamp.cs AdmittanceStamp.Branch, FromAdmittance, BranchStamp The single pi-model stamp with tap and phase shift
src/GridSim.Core/PowerFlow/YBus.cs YBus.Build, YBus.BuildSparse, SparseYBus Dense and cell-only Y-bus
src/GridSim.Core/PowerFlow/SparseNewtonRaphsonPowerFlow.cs BuildY Sparse (CSR) Y-bus for the sparse engine
src/GridSim.Core/Numerics/Sparse.cs ComplexCsr, ComplexCsr.Builder CSR storage and the order-preserving summation
src/GridSim.Core/PowerFlow/NewtonShell.cs BuildBusSpec, ComputeLineFlows, AssembleResult Per-unit injections, start point, flows back in MW
src/GridSim.Core/PowerFlow/VoltageSetpoint.cs VoltageSetpoint.ForBus The last-generator-wins setpoint rule
src/GridSim.Core/PowerFlow/LoadAtVoltage.cs LoadAtVoltage The one ZIP load rule
src/GridSim.Core/PowerFlow/IslandPartition.cs, TopologyOps.cs IslandPartition.Prepare, TopologyOps.Apply Island election and blackout, opened-branch application
src/GridSim.Core/IO/Matpower/MatpowerParser.cs MatpowerParser, MatpowerUnitHandling MATPOWER import, gencost, dcline, unit handling
src/GridSim.Core/IO/Matpower/MatpowerUnitNormalizer.cs LooksRawUnits, Normalize Raw ohm and kW feeder detection and conversion
src/GridSim.Core/IO/Matpower/MatpowerWriter.cs MatpowerWriter MATPOWER export and its loss notes
src/GridSim.Core/IO/Json/JsonGridLoader.cs, JsonDtos.cs JsonGridLoader.Build, DTOs JSON v1 import and the shared builder
src/GridSim.Core/IO/Json/V2CaseLoader.cs V2CaseLoader JSON v2 case import onto the v1 builder
src/GridSim.Core/IO/Json/JsonCaseWriter.cs JsonCaseWriter JSON v1 export and its loss notes
src/GridSim.Core/IO/Cim/CimGridModelBridge.cs ToGridModel CIM to model, ohm to per-unit
src/GridSim.Gda/GdaModelBuilder.cs GdaModelBuilder GDA dataset to model
src/GridSim.Core/IO/BridgeProtocol.cs BuildModel Bridge and solve-export model reader
src/GridSim.Core/Dispatch/Dispatcher.cs Clone, Balance Copy through CopyWith, dispatch of the in-service fleet
src/GridSim.Core/Assets/AssetBinding.cs, AssetDynamicsFleet.cs AssetBindingSet.Resolve, AssetDynamicsModel Asset class bindings
src/GridSim.Core/Assets/Protection/ProtectionModel.cs ProtectionModel, ProtectionInstance Placed protective devices
src/GridSim.Core/Analysis/VoltageLimits.cs OperationalLowFor, OperationalHighFor Per-bus limits with band fallback

Limits

  • A transformer has no magnetising shunt: Branch carries one B, and every loader sets it to 0 for a transformer.
  • JSON v1 and v2 cannot hold an out-of-service branch (the v2 loader refuses inService false on a line or transformer rather than dropping it). JSON v1 cannot hold transformer winding connections, neutral reactances, transformer zero-sequence data or generator subtransient and negative-sequence reactance; JSON v2 carries them into the model, as the bridge and solve-export reader do.
  • MATPOWER drops status 0 branches and isolated (type 4) buses at parse time, so a parsed case never holds an open branch; MATPOWER, CIM and GDA carry no windings, zero-sequence data or ZIP load, and MATPOWER and CIM carry no OLTC.
  • The bridge and solve-export reader does not read a bus VaDeg or its voltage limits, so a re-imported slack with a non-zero angle, or a case with per-bus limits, does not round trip those fields.
  • Generator.ReactiveCost is carried and written by the MATPOWER writer, and no solver reads it.
  • MatpowerParser keeps mpc.dcline in the parse result only; no solver models a DC line, so a case with DC lines solves differently from MATPOWER.
  • ProtectionCascade.WithBranches and GridInertiaTransforms.With build their copies by hand from the in-service generator list, so those copies do not hold the out-of-service units of the model they copy.
  • The island pre-pass is applied only by TopologyOps.Apply, which the live simulator calls for its opened branches.

See also