25. IEC 60909 short-circuit duty study

This chapter specifies the IEC 60909-0 short-circuit duty study: the standardised currents that switchgear and protection must be rated for, as the code in src/GridSim.Core/Protection/ShortCircuit/Iec60909.cs computes them. The study answers "what is the highest (or lowest) current this bus can see", independent of the dispatch. It drives the fault from one equivalent voltage source c*Un/sqrt(3) at the fault bus, shorts every other source, leaves loads out, and reports the family of currents Ik'', ip, Ib, Ik, Ith and idc, with the factors kappa, mu, m and n that relate them. It is a different calculation from the operating-point fault study (FaultAnalysis, gridsim fault), which superposes a bolted fault on the solved prefault voltages and feeds the relay verdicts of ch. 17, Protection assessment. Relay elements and IDMT grading are in that chapter and in ch. 26, Overcurrent coordination; the protection stages of assets are in ch. 15, Protections. They are not repeated here.

The study has one entry module, Iec60909, and one command, gridsim iec60909. Its flags are listed once, in the CLI reference. The model fields it reads (Bus.BaseKv, Generator, Branch) are defined in ch. 2, Data model and per-unit conventions.

The study is deterministic: the same case, bus, objective and times give the same bits on every run. Every fault network, of any size, is factored by the same sparse LU, so a 9-bus case and gb-full run the same arithmetic (see Network size and islands).

Model

Equivalent source and the networks

The duty is a property of the network and its sources. Per unit on the system base GridModel.BaseMva, with the fault at bus k and nominal line-to-line voltage Un = Bus.BaseKv of that bus:

source at bus k:   c * Un / sqrt(3)          (c pu on the phase base)
positive network:  branch series impedances and taps (+ phase shifts)
                   + each synchronous generator as j*X to earth
                   loads: not stamped
                   line charging B/2 and bus shunts Gs/Bs: not stamped

FaultNetworkSystem.ForModel(model, shunts, seriesOnly: true) builds this network from the model's Y-bus after removing every branch B and every bus Gs/Bs; series impedance, tap ratio and phase shift are kept exactly. The operating-point study keeps the full network. One column of the bus-impedance matrix is solved, Y x = e_k, and the driving-point impedance is Zkk = x[k], the positive-sequence Thevenin impedance Z1.

Each in-service, non-converter, non-power-flow-only generator g on a bus of the model is a shunt to earth:

X_sys,g = FaultSourceReactancePu(0.20) * BaseMva / MBase_g          (pu on BaseMva)
FaultSourceReactancePu = X''d_eff + max(0, UnitTransformerXPu)      (pu on MBase)
X''d_eff = SubtransientXdPu if > 0, else the fallback 0.20
Y_g = 1 / (j * X_sys,g)

MBase <= 0 is read as BaseMva. The unit transformer reactance is in series with the machine because the network bus of a transmission-connected machine is the high-voltage side of its step-up transformer. A generator with PowerFlowOnly set (a slack balancer, a voltage-control unit) is no source. A converter-interfaced generator is open in the positive and negative networks and enters as a current source (below). Out-of-service units are not in GridModel.Generators and take no part.

The negative-sequence network is the same passive network with each machine's reactance replaced by X2_eff + max(0, UnitTransformerXPu), where X2_eff = NegativeSeqXPu if above zero, else X''d_eff (the round-rotor convention). With no X2 supplied, Z2 = Z1 exactly. Static plant has Z2 = Z1.

Voltage factor c

Iec60909.VoltageFactor(Un, objective) returns these values from IEC 60909-0 Table 1 (for low voltage, the row for a +6 % voltage tolerance; a c_max of 1.10 for low voltage is not offered):

Nominal voltage Maximum current (equipment duty) Minimum current (protection sensitivity)
Un <= 1 kV (low voltage) 1.05 0.95
Un > 1 kV 1.10 1.00

ShortCircuitObjective.Maximum and Minimum choose the column. The factor is taken at the fault bus's nominal voltage.

Initial symmetrical current Ik''

Ik''_pu = c / |Zk|                         Zk = R + jX (pu, system base)
Ik''_kA = Ik''_pu * BaseMva / (sqrt(3) * Un)
R/X     = R / X                            (0 when X = 0)

Iec60909.FromThevenin is this calculation on a supplied Zk. It throws ArgumentOutOfRangeException for Un <= 0, BaseMva <= 0 or |Zk| = 0.

Peak current, DC component and thermal current

kappa = 1.02 + 0.98 * exp(-3 * R/X)             PeakFactor
ip    = kappa * sqrt(2) * Ik''                  peak short-circuit current
idc   = sqrt(2) * Ik'' * exp(-2*pi*f*tb * R/X)  DC component at the breaker time tb
m     = (exp(4*f*Tk*ln(kappa-1)) - 1) / (2*f*Tk*ln(kappa-1))        ThermalDcFactor
n     = 1
Ith   = Ik'' * sqrt(m + n)                      thermal-equivalent current over Tk

kappa lies in (1.02, 2.0]: a purely reactive loop (R/X = 0) gives exactly 2, a resistive one tends to 1.02.

Meshed networks (Method B, the default). The study first decides whether the fault network is meshed (Iec60909.IsMeshed): its graph has the buses of the fault bus's island plus one earth node as nodes, and every in-service branch (each parallel circuit counted) plus one edge from each synchronous source to earth as edges. A connected graph with one edge fewer than nodes is a tree, the radial single-source case; any further edge (a ring, a parallel circuit, a second source) makes the network meshed. In a meshed network the peak takes IEC 60909-0 Method B's safety factor (Iec60909.PeakFactorMeshed):

kappa_b = max( kappa, min( 1.15 * kappa, cap ) )      cap = 1.8 when Un <= 1 kV, else 2.0
ip      = kappa_b * sqrt(2) * Ik''

The cap bounds what the safety factor adds; it never takes kappa_b below kappa. The factor is always applied in a meshed network (the standard's permission to omit it while every branch has R/X below 0.3 is not used). m keeps kappa(R/X) in both cases, because the DC heat is set by the network's own time constant; idc uses R/X directly. The duty records the choice in Duty.MeshedPeakFactor.

Method C (PeakFactorMethod.MethodC, verb --peak-method c). The equivalent-frequency method rebuilds the same fault network with every reactance (branch X, each machine's X''d, unit-transformer X) scaled by fc/f = 0.4 (Iec60909.MethodCFrequencyRatio), resistances, taps and phase shifts unchanged, and takes

R/X_C   = (R_c / X_c) * 0.4                 Z_c = R_c + j X_c, the driving point at fc
kappa   = 1.02 + 0.98 * exp(-3 * R/X_C)     no safety factor, no cap
idc     = sqrt(2) * Ik'' * exp(-2*pi*f*tb * R/X_dc)
R/X_dc  = (R_c / X_c) * r                   the network at fc/f = r, r set by f*tb
r       = 0.27 below 1, 0.15 below 2.5, 0.092 below 5, 0.055 below 10 cycles   (marked [VERIFY] in the source)

f*tb at or above 10 cycles is refused (ArgumentOutOfRangeException): the table ends there. For ll, slg and dlg the loop is the fault's own sequence connection (Z1 + Z2, Z1 + Z2 + Z0, Z1 + Z2 || Z0), every sequence network at the equivalent frequency, and an earth fault with no zero-sequence loop is refused. Method C moves only ip, kappa and idc; Ik'', Ib, Ik, Ith and m are Method B's. A single series path gives exactly the network's own R/X, so there Method C equals Method B without the 1.15. The duty carries PeakMethod, PeakRoverX and DcRoverX.

When |ln(kappa-1)| < 1e-9 (kappa = 2) the removable 0/0 of m is returned as its limit, 2; as kappa tends to 1, m tends to 0. f is GridModel.FrequencyHz in the verb (50 Hz by default) and FrequencyLimits.NominalHz (50.0) as the library default. n is fixed at 1 for every fault, near or far from a generator.

Breaking current

Ib is the symmetrical current the breaker interrupts at its minimum time delay tmin (the verb's --tb). The AC envelope of a machine's contribution decays during the fault. Two closed-form decay factors are provided, with break times 0.02, 0.05, 0.10, 0.25 s (the private table Iec60909.BreakTimes):

mu(r, tmin), r = Ik''_G / IrG, the machine's contribution over its rated current
  r <= 2 : mu = 1                                (far from generator: no decay)
  tmin = 0.02 s : mu = 0.84 + 0.26 * exp(-0.26 r)
  tmin = 0.05 s : mu = 0.71 + 0.51 * exp(-0.30 r)
  tmin = 0.10 s : mu = 0.62 + 0.72 * exp(-0.32 r)
  tmin >= 0.25 s: mu = 0.56 + 0.94 * exp(-0.38 r)
  between break times: linear interpolation of the two neighbouring values; below 0.02 s the
  0.02 s form, at or above 0.25 s the 0.25 s form; the result is capped at 1

q(m, tmin), here m = rated MW per pole pair of an asynchronous motor (m > 0, else ArgumentOutOfRangeException)
  tmin = 0.02 s : q = 1.03 + 0.12 ln(m)
  tmin = 0.05 s : q = 0.79 + 0.12 ln(m)
  tmin = 0.10 s : q = 0.57 + 0.12 ln(m)
  tmin >= 0.25 s: q = 0.26 + 0.10 ln(m)          interpolated and capped at 1 as for mu

BreakingFactorMu and MotorBreakingFactorQ are public pure functions. SynchronousBreakingCurrentKa(Ik'', IrG, tmin) returns mu * Ik'' for one machine that carries the whole fault; it throws for IrG <= 0. The model has no asynchronous-motor data, so q is a function only; no duty uses it.

Network breaking current (three-phase). ThreePhase folds the per-machine mu into Ib by the meshed-network (multiple-fed) formula of IEC 60909-0:2016 (subclause 9.1.7, breaking current in meshed networks, read from the 2016 contents list and marked [VERIFY]):

Ib = Ik'' - sum_g ( |V_g| / c ) * (1 - mu_g) * I_g                      (kA, summed over synchronous machines)
V_g  = c * Z_gk / Z_kk                  during-fault voltage at machine g's bus (pu)
I_g  = V_g / (j * X_sys,g)              the machine's partial current (pu), I_g[kA] = |I_g| * BaseMva/(sqrt(3)*Un)
r_g  = |I_g| / (MBase_g / BaseMva)      contribution over rated current, base-independent
mu_g = BreakingFactorMu(r_g, tb)

|V_g|/c is the machine's terminal voltage dip relative to the source (|dU''_G| / (c*Un/sqrt(3))), so a machine at the fault bus has weight 1 and a single machine at its own terminals gives exactly Ib = mu * Ik''. When every mu_g is 1 the deduction is exactly zero and Ib = Ik'' bit for bit (the duty record is returned unchanged). The result is checked: Ib outside (0, Ik''] or a non-finite deduction throws InvalidOperationException. Converter infeeds are added after this step with mu = 1. PartialThreePhase uses the same code, so its TotalBreakingIbKa equals ThreePhase's BreakingIbKa to the bit when its minTimeDelaySeconds equals ThreePhase's breakTimeSeconds.

Unbalanced faults report Ib = Ik'': no flux decay is taken into account for them (IEC 60909-0:2016 subclause 9.2, "Unbalanced short-circuits", read from the 2016 contents list and marked [VERIFY]). The steady-state current is Ik = Ik'' for every fault, and n is 1. Duty.SteadyBasis (SteadyStateBasis) says what that number is:

Basis When Meaning
FarFromGenerator every machine feeds at most twice its rated current Ik = Ik'' exactly
MeshedMultipleFed near a generator, several synchronous sources the standard's Ik = Ik''M (subclause 11.2.7); no motors are modelled, so it is Ik''
SingleFedUpperBound near the only synchronous source of the fault an upper bound: the standard's Ik = lambda * IrG needs the machine's x_dsat, which the model does not carry; Ith with n = 1 is an upper bound too
UnbalancedNoDecay ll, slg, dlg no decay for unbalanced faults, Ik = Ib = Ik''

Converter-interfaced plant

A generator is converter-interfaced when Generator.ConverterInterfaced is true, or when it is unset and Type is a converter type: wind, onshore, offshore, wind-onshore, wind-offshore, solar, pv, storage, battery, bess, interconnector, hvdc, tidal (ConverterPlant.IsConverterType, case-insensitive, _ read as -; pumped storage is synchronous). Such a unit has no internal EMF behind a reactance. It is left out of the source network and enters as a current source:

I_skPF,j = k_j * MBase_j / BaseMva                 (pu, system base)   k = EffectiveConverterFaultCurrentPu
uplift   = sum_j |Z_kj| * I_skPF,j                 Z_kj = transfer impedance, bus j to fault bus
Ik''     = (c + uplift) / |Z_kk|                   (pu)

k is Generator.ConverterFaultCurrentPu when set (zero is meaningful: the unit feeds nothing, as a line-commutated link), else Generator.DefaultConverterFaultCurrentPu, 1.2. The JSON v1 case folder sets the fields per generator as converterInterfaced, converterFaultCurrentPu, powerFlowOnly and unitTransformerXPu (JSON v2 nests the first two as converter.interfaced and converter.faultCurrentPu); the uk case gives converterFaultCurrentPu: 0.0 to Moyle, IFA and BritNed. Z_kj is row k of Zbus: the column already solved when every in-service branch has zero phase shift (Y is then symmetric), else a second solve on the transposed system. Each converter current is phased arg I_j = -arg Z_kj, so its share is in phase with the synchronous share and the arithmetic sum is exact. A controlled current has no DC offset and no AC decay:

converter share  pf = uplift / |Z_kk|                       (pu), reported in kA as Duty.ConverterIkppKa
Ik''   = Ik''_sync + pf
ip     = ip_sync + sqrt(2) * pf                              (no kappa)
Ib     = Ib_sync + pf          (mu = 1)
Ik     = Ik_sync + pf
Ith    = sqrt(m * Ik''_sync^2 + Ik''^2)                      (n = 1)

kappa, m, R/X and idc stay those of the synchronous part. For ll, slg and dlg the converters inject balanced positive-sequence current and are open in the negative sequence, so each sequence formula is evaluated once more with the source uplift in place of c, and that share is added by the same rules. A model with no synchronous source is refused with InvalidOperationException: the equivalent-source method needs one.

Unbalanced faults

Iec60909.FromSequenceImpedances(type, c, Un, Z1, Z2, Z0, BaseMva, ...) connects the sequence networks. With i1 = c / loopZ:

Fault (UnbalancedFaultType) Connection loopZ Reported Ik'' (pu)
SingleLineToGround Z1, Z2, Z0 in series Z1 + Z2 + Z0 \|3c / loopZ\|
LineToLine Z1, Z2 in series Z1 + Z2 \|sqrt(3) c / loopZ\|
DoubleLineToGround Z2 parallel Z0, in series with Z1 Z1 + Z2*Z0/(Z2+Z0) \|3 I0\|, I0 = -i1 * Z2/(Z2+Z0)

For DoubleLineToGround the reported current is the earth current, not the line-conductor currents. kappa, m and idc use R/X = Re(loopZ)/Im(loopZ); Duty.TheveninRPu and TheveninXPu carry the positive-sequence Z1. Ib and Ik equal Ik''; Ith = Ik'' sqrt(m + 1). The model entry points are LineToLine (positive and negative networks only), SingleLineToGround and DoubleLineToGround (all three). Z1 is PositiveSequenceThevenin, Z2 is NegativeSequenceThevenin, Z0 is ZeroSequenceThevenin.

Zero-sequence network

Iec60909.BuildZeroSequenceNetwork builds the zero-sequence admittance network from each in-service branch. A branch with no winding data (FromWinding or ToWinding null) is a line; one with both is a transformer.

Branch Zero-sequence element
Line series Z0 = R0 + jX0 if either is non-zero, else lineZeroSeqRatio * (R + jX) (default 3.0); nothing if that is zero
Transformer, WyeGrounded + WyeGrounded series Z0T + 3*FromNeutralXPu*j + 3*ToNeutralXPu*j between the buses
Transformer, WyeGrounded (from) + Delta (to) shunt 1/(Z0T + j*3*FromNeutralXPu) at the from bus, which gains an earth path
Transformer, Delta (from) + WyeGrounded (to) shunt 1/(Z0T + j*3*ToNeutralXPu) at the to bus, which gains an earth path
Any other pairing (Delta+Delta, any WyeUngrounded, ...) blocks the zero sequence

Z0T = R0 + jX0 of the branch when either is non-zero, else its positive-sequence R + jX. Generators add no zero-sequence path. ZeroSequenceThevenin walks the series edges breadth-first from the fault bus; if the component reaches no earth path the bus is ungrounded, Grounded is false and Z0 is infinity. SingleLineToGround and DoubleLineToGround then return an all-zero duty (every current 0, the R/X and factors of Z1 for reference). Otherwise Z0 is the driving point of Y_sub x = e_k on that grounded component only, so an isolated zero-sequence island elsewhere cannot make the solve singular. The operating-point earth-fault study uses the same network builder.

Partial currents and branch currents

PartialThreePhase decomposes the three-phase fault with the same single Zbus column: V_g = c*Z_gk/Z_kk and I_g = V_g/(j X_sys,g). Each MachinePartialCurrent carries IkppKa, IkppPu, RatedCurrentKa, Mu, BreakingIbKa (its own single-fed mu_g * |I_g|) and IsConverter. A converter's entry is I_skPF * |Z_kj|/|Z_kk| with mu = 1. TotalIkppPu is |c/Zkk| plus the converter partials; the machine entries are separate magnitudes and are not summed into it. For a lossless radial network the partials are in phase and the machine magnitudes sum to it; in a lossy network they exceed it (WSCC-9 bus 5: 1.4690796589338535 kA against Ik'' 1.4683989584292985 kA). TotalBreakingIbKa is the network formula above, not the sum of the single-fed values. Currents in kA are referred to the fault bus voltage: the base is BaseMva/(sqrt(3)*Un) of the fault bus.

BranchFaultCurrents(model, bus) returns, for each in-service branch, the from-end and to-end current magnitudes during a three-phase fault with the c_max source, whatever the objective. The bus voltages are V_i = c Z_ik/Z_kk plus the converter-driven voltages (one extra solve on the same factorisation); each end current uses the shared series-plus-tap stamp AdmittanceStamp.Branch(R, X, 0, TapRatio, PhaseShiftDeg) (charging zero, a TapRatio of 0 read as 1):

iFrom = Yff * Vf + Yft * Vt          iTo = Ytf * Vf + Ytt * Vt            (pu; kA = pu * BaseMva/(sqrt(3)*Un))

This is the current a protective relay on that branch measures; it is the input to grading a relay chain (ch. 26).

Impedance-correction factors

Three closed forms correct machine and transformer impedances so that the equivalent source reproduces the true contribution at rated conditions. All three are public pure functions.

K_G  = (Un / UrG) * c_max / (1 + x''d * sin(phi_rG))           GeneratorCorrectionKg
K_T  = 0.95 * c_max / (1 + 0.6 * x_T)                          TransformerCorrectionKt
K_S  = (UnQ/UrG)^2 * (UrTLV/UrTHV)^2 * c_max / (1 + |x''d - x_T| * sin(phi_rG))      PowerStationUnitCorrectionKs
K_SO = UnQ / (UrG*(1+p_G)) * (UrTLV/UrTHV) * (1 +/- p_T) * c_max / (1 + x''d*sin(phi_rG))   PowerStationUnitCorrectionKso
sin(phi_rG) = sqrt(1 - cos(phi_rG)^2)

K_G throws unless UrG > 0 and cos(phi_rG) is in [0, 1]; K_T throws for x_T < 0; K_S and K_SO throw unless every rated voltage is above zero and cos(phi_rG) is in [0, 1]. K_G equals c_max at matched voltage with no reactive loading; K_T equals 0.95*c_max at x_T = 0.

Iec60909.ApplyCorrectionFactors(model, ratedPowerFactor, unitTransformersHaveOltc = true) returns a corrected copy of the model (the input is unchanged) for a maximum-current study. The duty methods never apply the factors themselves; a study runs on the model it is given, and the verb applies them only under --corrections.

Element Condition Factor What is multiplied
Generator, directly connected in service, not converter, not power-flow-only, UnitTransformerXPu = 0 K_G X''d_eff and X2_eff
Power station unit same, UnitTransformerXPu > 0 K_S (OLTC) or K_SO (unitTransformersHaveOltc false; p_G = 0, main tap) X''d_eff, X2_eff and UnitTransformerXPu
Network transformer Branch.IsTransformer, in service, RateAMva > 0 K_T R, X, R0, X0

The model is per unit on nominal voltages, so every voltage ratio in the formulas is 1. c_max is the Table 1 maximum factor at the element's bus (the higher of a transformer's two buses). x_T = |X| * RateAMva / BaseMva, taking RateAMva as the transformer's rated power. A transformer with no RateAMva, and any element on a bus with no base voltage (BaseKv 0 or below, where no Table 1 row applies), is left uncorrected and listed in CorrectionReport.NotApplied. The rated power factor is the caller's input and must be in (0, 1], because the model carries none; it is never assumed.

Breaker rating check

CheckBreaker(duty, rating, systemVoltageKv) compares a Duty with a BreakerRating(RatedVoltageKv, MakingPeakKa, BreakingSymKa, ShortTimeWithstandKa, ShortTimeSeconds = 1.0). Margins are rating minus demand in kA, so a margin of zero or more passes:

voltage  : RatedVoltageKv >= systemVoltageKv
making   : MakingPeakKa   - ip
breaking : BreakingSymKa  - Ib
thermal  : ShortTimeWithstandKa * sqrt(min(1, ShortTimeSeconds / FaultDurationSeconds)) - Ith
           (the rating is used unscaled when either time is not above zero)
Adequate = all four pass

The thermal rule is equal energy, I_thr^2 * Tkr >= Ith^2 * Tk, for a fault at least as long as the rated duration (Tk >= Tkr). For a shorter fault the criterion is Ith <= I_thr (IEC 60865-1 clause 7): the rated short-time current is also an electromechanical ceiling, so the referral only ever scales the rating down, never up. Duty carries its own BreakTimeSeconds and FaultDurationSeconds, so the check needs no other input.

Network size and islands

FaultNetworkSystem factors Y once per study and reuses it for every right-hand side (a Zbus column, a row, the converter response). Every fault network, at every size, is factored by the real 2n-expansion sparse LU (RealExpandedComplexSolver); there is no bus-count switch. The dense complex LU survives only as a test oracle (FaultNetworkSystem.DenseReferenceScope, internal), which tests use to cross-check the sparse answers; no production path can select it. A singular network fails loud: the sparse factor reports the singular matrix and the study throws InvalidOperationException.

Before it builds the network the study keeps only the fault bus's island (Iec60909.FaultIsland): the buses connected to the fault bus through in-service branches, the branches between them and the generators on them, in the model's own order. A Zbus column of the fault bus is exactly zero outside its island, so dropping those buses changes no number, and a dead island elsewhere in the model (no source, so no path to earth) does not make the matrix singular. A connected model is used as it is. A fault bus whose own island has no synchronous source is refused by name.

Algorithm

ThreePhase(model, bus, objective, subtransientXdPu = 0.20, f0Hz, breakTimeSeconds = 0.10, faultDurationSeconds = 1.0):

1. index buses; Un = Bus.BaseKv of the fault bus (<= 0 -> InvalidOperationException; unknown bus -> ArgumentException)
2. for each generator in GridModel.Generators:
       PowerFlowOnly            -> skip
       converter-interfaced     -> record current source I_skPF
       else                     -> shunt Y_g = 1/(j X_sys,g)
   no synchronous machine       -> InvalidOperationException
3. factor Y (series-only network + shunts); solve Y x = e_k          -> Zkk
   converters present: Z_kj from row k (column k if Y symmetric, else a transposed solve)
4. c = VoltageFactor(Un, objective)
5. sync   = FromThevenin(c, Un, Re Zkk, Im Zkk, BaseMva, f0, tb, Tk)   -> Ik'', kappa, ip, idc, m, Ith, Ib = Ik = Ik''
6. sync   = WithNearGeneratorBreaking(sync)                           -> Ib from the multiple-fed formula
7. result = WithConverterInfeed(sync, uplift/|Zkk|)                   -> adds pf to Ik'', ip, Ib, Ik, Ith

The unbalanced entry points run steps 1 to 4, then FromSequenceImpedances with Z1 = Zkk, Z2 and Z0, then, when the bus is grounded, add the converter share by the rule above (an ungrounded bus returns the all-zero duty). ZeroSequenceThevenin is not solved for ThreePhase or LineToLine.

Parameters and defaults

Name Value Unit Meaning Source symbol
c maximum 1.10 (Un > 1 kV), 1.05 (Un <= 1 kV) - Voltage factor, equipment duty Iec60909.VoltageFactor
c minimum 1.00 (Un > 1 kV), 0.95 (Un <= 1 kV) - Voltage factor, protection sensitivity Iec60909.VoltageFactor
kappa constants 1.02, 0.98, 3 - 1.02 + 0.98*exp(-3 R/X) Iec60909.PeakFactor
m limit tolerance 1e-9 on \|ln(kappa-1)\| - Below it m returns 2 Iec60909.ThermalDcFactor
n 1 - Thermal AC factor Iec60909.Assemble
Break times 0.02, 0.05, 0.10, 0.25 s Tabulated tmin for mu and q Iec60909.BreakTimes
mu far-from-generator threshold Ik''_G/IrG <= 2 gives mu = 1 - No AC decay Iec60909.BreakingFactorMu
mu coefficients 0.84/0.26/0.26, 0.71/0.51/0.30, 0.62/0.72/0.32, 0.56/0.94/0.38 - a + b*exp(-d r) at 0.02, 0.05, 0.10, 0.25 s Iec60909.BreakingFactorMu
q coefficients 1.03/0.12, 0.79/0.12, 0.57/0.12, 0.26/0.10 - a + b*ln(m) at 0.02, 0.05, 0.10, 0.25 s Iec60909.MotorBreakingFactorQ
K_T constants 0.95, 0.6 - Fixed constants of the transformer factor Iec60909.TransformerCorrectionKt
Default X''d 0.20 pu on MBase Machine with no SubtransientXdPu Iec60909.DefaultSubtransientXdPu = FaultAnalysis.DefaultSubtransientXdPu
Default X2 X''d_eff pu on MBase Machine with no NegativeSeqXPu Generator.EffectiveNegativeSeqXPu
Default converter k 1.2 x rated Converter with no ConverterFaultCurrentPu Generator.DefaultConverterFaultCurrentPu
Line zero-sequence ratio 3.0 x Z1 Line with no R0/X0 lineZeroSeqRatio of SingleLineToGround, DoubleLineToGround, ZeroSequenceThevenin
Transformer Z0T R + jX pu Transformer with no R0/X0 Iec60909.BuildZeroSequenceNetwork
Neutral term 3 * FromNeutralXPu, 3 * ToNeutralXPu pu Added to the earthed path Branch.FromNeutralXPu, Branch.ToNeutralXPu
Breaker time tb 0.10 s Breaker minimum time delay (mu, idc) breakTimeSeconds; verb --tb
Fault duration Tk 1.0 s Duration for m and Ith faultDurationSeconds; verb --tk
Frequency f GridModel.FrequencyHz (the case's own: 50 Hz for GB cases, 60 Hz for case9) Hz idc, m f0Hz; FrequencyLimits.NominalHz (50.0) is the library default
Meshed safety factor 1.15, capped at 2.0 (1.8 at Un <= 1 kV), never below kappa - kappa_b in a meshed network Iec60909.MeshedPeakSafetyFactor, PeakFactorMeshed
Method C peak ratio fc/f 0.4 - Equivalent frequency for kappa Iec60909.MethodCFrequencyRatio
Method C DC ratios fc/f 0.27, 0.15, 0.092, 0.055 below f*tb = 1, 2.5, 5, 10 - Equivalent frequency for idc; [VERIFY] Iec60909.MethodCDcRatioBelow1 to MethodCDcRatioBelow10, MethodCDcTableEndFt
Peak method B - --peak-method b or c PeakFactorMethod.MethodB
Breaker short-time duration 1.0 s Duration of the withstand rating BreakerRating.ShortTimeSeconds
Singular residual 1e-9 relative Rejects a dense-oracle solve that misses Y x = b (tests only) FaultNetworkSystem.SingularResidualRel
Generator reactance basis X_sys = X * BaseMva / MBase pu Converts a machine reactance to the system base Iec60909.BuildPositiveNetwork

The iec60909 verb

gridsim iec60909 <case> (--bus <id> | --all-buses) [--type 3ph|ll|slg|dlg] [--objective max|min] [--tb 0.10] [--tk 1.0]
                 [--breaker kV,making_kA,breaking_kA,withstand_kA[,seconds[,asym_kA]]] [--branches [--top N]]
                 [--corrections --rated-pf <cos phi> [--no-unit-oltc]] [--peak-method b|c]

The verb maps --type to ThreePhase, LineToLine, SingleLineToGround or DoubleLineToGround, --objective to ShortCircuitObjective, --peak-method to PeakFactorMethod (default b), and passes GridModel.FrequencyHz, --tb and --tk. The flag semantics are in the CLI reference. The single-bus duty lines print at round-trip precision; branch currents print to three decimals, and the sweep table and correction ranges to four.

One bus. The output is a header line (case, bus, fault type, objective, frequency, tb, Tk), then:

Line Fields
Ik'' kA, pu, and the converter share in kA when above zero
ip kA, kappa, R/X; then meshed network: 1.15 x kappa(R/X), Method B when the meshed factor applies, or Method C: kappa(R/X_C), R/X_C <value> at fc = 0.4 f under --peak-method c
Ib and Ik kA each; then a note on the steady-state basis (none far from every generator; the multiple-fed rule; UPPER BOUND single-fed; unbalanced fault: IEC 60909-0 takes no decay)
Ith kA, m; and idc(tb) in kA
Zth Zkk = R + jX of the positive sequence, pu

With --breaker a verdict line (ADEQUATE or NOT ADEQUATE) follows, then the voltage status and the three margins (making, breaking, thermal), and the asymmetrical breaking margin when the sixth value is given. The rated voltage is compared with the highest system voltage Um (Iec60909.HighestSystemVoltageKv: the lowest IEC 60038 Um at or above the nominal voltage above 1 kV, the nominal plus 10 % at or below 1 kV), because IEC rates a device by Um. A double-line-to-earth duty reports the earth current 3 I0; its breaker check scales every current demand by Duty.DlgLineToEarthRatio, the largest line-conductor current over the earth current, when that is above 1. With --branches every in-service branch current in the fault bus's island follows, largest first (--top N prints the first N and a footer counts the rest; the result file holds every branch); they are always computed with c_max, so --objective min --branches prints Ik'' at c_min beside branch currents at c_max. With --corrections a summary of the factors applied (per factor: element count, minimum and maximum value to four decimals) precedes the duty.

All buses. --all-buses prints one row per bus with a base kV (bus, kV, Ik'', ip, Ib, Ith, plus a breaker verdict with --breaker, each bus checked at its own voltage), then the count studied and the bus with the largest Ik''. A bus that cannot be studied (no base kV, no source) is listed with the reason.

Result file. With --json, --csv or --out the summary carries case, bus, type, objective, frequency_hz, tb_s, tk_s, ikpp_ka, ikpp_pu, converter_ikpp_ka, ip_ka, kappa, r_over_x, ib_ka, ik_ka, ith_ka, thermal_m, idc_ka, thevenin_r_pu, thevenin_x_pu, kappa_meshed, ik_basis; peak_method and r_over_x_c under --peak-method c; earthing_data for slg and dlg; the breaker margins and breaker_adequate with --breaker; tables branch_currents, corrections and (for --all-buses) buses.

Exit codes.

Code Condition
0 The duty was computed and every requested check passed
1 Case load error; InvalidOperationException or ArgumentException from the study (no base kV, no synchronous source, singular network); with --all-buses, at least one bus could not be studied; --corrections rejected by the library
2 Usage error: no case argument; a flag with a missing or non-numeric value; no --bus and no --all-buses, or both; unknown bus; --type or --objective not in its list; --tb or --tk not above 0; --branches with a type other than 3ph or with --all-buses; --corrections without --rated-pf, --rated-pf or --no-unit-oltc without --corrections, --rated-pf outside (0, 1], or --corrections with --objective min; --breaker not 4 or 5 positive finite numbers
3 A breaker rating is inadequate (at any bus with --all-buses); an earth fault (slg, dlg) on a model that carries no transformer winding connection

Process tests cover the usage exit, the earth-fault exit 3 and the result file. The other rows were confirmed by running the Release binary (usage, unknown bus, an inadequate breaker, gb-full) or by reading Program.cs.

The last case prints the duty, then says on stderr that the earth-fault duty reflects missing data. A model with no winding connection has no earthed neutral, so the zero current is a data gap, not a network result. MATPOWER and JSON v1 carry no winding connections, so every earth fault on such a case exits 3. A JSON v2 case can carry them (N234, October 2026, phase P5 opened for fault sequence data): transformer windings, r0Pu / x0Pu, neutralXPu, and generator subtransientXdPu / negativeSeqXPu (ch. 28); a v2 case that gives windings is studied with its own earth paths and exits 0. The library entry points accept models built with FromWinding/ToWinding (and the bridge protocol carries them).

Invariants

Invariant Test
c follows Table 1 for both objectives and both voltage classes Iec60909Tests.Voltage_factor_follows_table_1
kappa equals its closed form; R/X = 0 gives 2; a resistive loop stays in (1.02, 1.03) Iec60909Tests.Peak_factor_matches_its_closed_form_and_bounds
A single 0.20 pu generator gives Zk = j0.20, Ik'' = 5.5 pu, kappa = 2, ip = kappa*sqrt(2)*Ik'' Iec60909Tests.Single_generator_bolted_fault_matches_the_hand_calculation
A series reactance 0.30 gives Zk = j0.50, Ik'' = 2.2 pu Iec60909Tests.A_series_reactance_reduces_the_current_by_the_series_impedance
idc follows the exact exponential; no decay at R/X = 0 Iec60909Tests.Dc_component_follows_the_exact_exponential_envelope
m equals its closed form, equals 2 at kappa = 2; Ith = Ik'' sqrt(m+1) Iec60909Tests.Thermal_factor_matches_its_closed_form_and_removable_limit
Far from the generator (Ik''_G/IrG <= 2) Ib == Ik == Ik'', exact equality Iec60909Tests.Far_from_generator_the_breaking_and_steady_currents_equal_the_initial
Near a generator Ib = Ik'' (1 - 0.4 (1 - mu)) for the 0.20 + 0.30 network; a single machine at its terminals gives mu * Ik''; a longer tb decays further; Ik = Ik'' Iec60909Tests.Near_generator_breaking_current_follows_the_multiple_fed_formula
Unbalanced faults keep Ib == Ik'' Iec60909Tests.Unbalanced_faults_keep_the_breaking_current_equal_to_the_initial
WSCC-9 Ik'' and Ib at buses 1, 4, 5, 7 are pinned to the bit (Assert.Equal on doubles) Iec60909Tests.Case9_breaking_currents_are_pinned
With Z1 = Z2 = Z0 the single-line and double-line-to-earth currents equal the three-phase c/\|Z1\|; line-to-line is sqrt(3)/2 of it Iec60909Tests.Sequence_faults_reduce_to_the_three_phase_for_symmetric_impedances, Line_to_line_from_the_model_is_root3_over_2_of_the_three_phase
Z0 = j0.60 gives Ik1'' = 3.3 pu Iec60909Tests.Single_line_to_ground_matches_the_hand_calculation
The unbalanced kappa uses the connection's loop R/X Iec60909Tests.Unbalanced_peak_factor_uses_the_sequence_loop_r_over_x
mu and q follow their closed forms at each tabulated time; mu = 1 at Ik''/IrG <= 2; interpolation is linear; both capped at 1 Iec60909Tests.Breaking_factor_mu_matches_its_closed_forms_at_the_tabulated_times, Breaking_factor_mu_is_one_far_from_generator, Breaking_factor_mu_interpolates_linearly_between_break_times, Motor_breaking_factor_q_matches_its_closed_forms, Single_machine_breaking_current_applies_mu_to_the_initial_current
One machine carries 100% of the fault; two identical machines split it evenly and their magnitudes sum to the total; TotalBreakingIbKa equals the hand multiple-fed formula and exceeds the single-fed sum Iec60909Tests.Partial_currents_put_the_whole_fault_on_a_single_machine, Partial_currents_split_evenly_between_identical_machines
PartialThreePhase.TotalBreakingIbKa equals ThreePhase.BreakingIbKa bit for bit at every WSCC-9 bus and at tmin 0.05, 0.10, 0.25 s; at 0.10 s it does not exceed Ik'' Iec60909PartialAgreementTests.Case9_partial_total_breaking_current_equals_ThreePhase, The_two_agree_at_every_break_time
A radial branch carries the whole fault; identical parallel feeders split it; the current feeds relay grading Iec60909Tests.Branch_fault_current_on_a_radial_feeder_is_the_whole_fault, Branch_fault_currents_split_between_parallel_feeders, Branch_fault_current_feeds_the_coordination_grading
A tap ratio of 0 gives the same branch currents as 1 ProtectionWs6Tests.Branch_fault_currents_handle_a_tap_ratio_of_zero_as_unity
A machine's own X''d and X2 replace the defaults (0.10 gives 11.0 pu, 0.40 gives 2.75 pu; X2 = 0.24 feeds line-to-line) Iec60909Tests.Per_machine_subtransient_reactance_overrides_the_synthesised_default, Per_machine_negative_sequence_reactance_feeds_the_line_to_line_fault
Delta + grounded-wye earths only the wye bus; 3*Xn adds to the path; a line and a through transformer sum; no earth means ungrounded Iec60909Tests.Zero_sequence_delta_wye_transformer_grounds_only_the_wye_side, Zero_sequence_neutral_grounding_adds_three_xn, Zero_sequence_series_path_sums_line_and_through_transformer, Zero_sequence_without_a_ground_reference_is_ungrounded
Model-wired earth faults match hand networks (Z1 = Z2 = j0.28, Z0 = j0.10 gives Ik1'' = 5.0 pu); an ungrounded bus gives zero Iec60909Tests.Single_line_to_ground_from_the_model_matches_the_hand_calculation, Double_line_to_ground_from_the_model_matches_the_sequence_form, Earth_faults_on_an_ungrounded_bus_are_zero
The operating-point earth-fault current times c equals the 60909 initial current on a no-load, no-charging network EarthFaultAndIec60909CompletionTests.With_no_load_or_charging_the_operating_point_slg_current_times_c_is_the_iec_60909_initial_current
The zero-sequence driving point is unchanged by the shared builder (j0.7 on the radial case) EarthFaultAndIec60909CompletionTests.The_zero_sequence_thevenin_is_unchanged_by_the_shared_builder
K_G, K_T, K_S, K_SO follow their closed forms and reductions Iec60909Tests.Generator_correction_kg_matches_its_closed_form, Transformer_correction_kt_matches_its_closed_form, EarthFaultAndIec60909CompletionTests.Ks_and_kso_follow_their_closed_forms
ApplyCorrectionFactors scales the right impedances, leaves the input untouched, lists an unrated transformer, rejects a power factor of 0 EarthFaultAndIec60909CompletionTests.Applying_the_corrections_scales_the_generator_and_transformer_impedances_and_leaves_the_input_untouched
The four breaker checks and their exact margins; the equal-energy thermal scaling Iec60909Tests.Breaker_adequacy_checks_each_rating_against_the_duty, Breaker_thermal_check_scales_by_equal_energy
Converter share: k * rated at the fault bus, transfer-scaled at a remote bus, no kappa on the share, mu = 1, zero k feeds nothing, converter-only model refused, power-flow-only unit is no source, unit transformer is in series ConverterFaultContributionTests (Iec_three_phase_adds_exactly_k_times_rated_for_a_converter_at_the_fault_bus, Iec_remote_converter_share_scales_by_transfer_over_driving_point_impedance, Iec_partial_currents_mark_the_converter_and_sum_to_the_total, Iec_branch_current_carries_the_converter_infeed_to_a_remote_fault, Iec_line_to_line_adds_the_sequence_formula_driven_by_the_converter_term, Iec_converter_only_model_is_refused_with_a_clear_reason, Zero_k_unit_feeds_no_fault_current_in_either_study, Power_flow_only_unit_is_no_fault_source, Unit_transformer_is_in_series_with_the_machine)
Converter classification and the explicit-flag override ConverterFaultContributionTests.Converter_types_are_classified, Explicit_flag_overrides_the_type_and_k_defaults
Line charging and bus shunts do not enter Z1, Z2 or Ik'' ProtectionWs6Tests.Iec60909_networks_neglect_line_charging_and_bus_shunts
A sourceless island fails loud; a dead island elsewhere changes no bit of a live fault, and the sparse engine solves it ProtectionWs6Tests.A_fault_on_a_sourceless_island_fails_loud_on_the_dense_path, A_fault_in_the_live_network_still_solves_when_a_dead_island_is_present, Doc4ProtectionIec60909Tests.D096_a_sourceless_island_elsewhere_changes_no_bit_and_the_sparse_path_now_solves
Every fault network is the sparse engine at every size, and the dense oracle does not leak out of its scope Doc16NumericsDeterminismTests.N233_every_fault_network_is_the_sparse_engine_at_every_size_and_the_oracle_does_not_leak
The sparse Zbus agrees with the dense oracle to 1e-9 of the column's largest entry on three columns and three rows of IEEE 118 and 300 FaultNetworkSystemTests.Sparse_zbus_columns_and_rows_match_dense, Sparse_triplet_network_matches_dense
Meshed kappa_b is 1.15 kappa, capped, never below kappa; the steady-state basis is reported Doc4ProtectionIec60909Tests.D098_meshed_kappa_is_one_point_one_five_times_kappa_capped, D097_the_steady_state_basis_says_exact_meshed_or_upper_bound
Method C moves only the peak and idc; on a single series path it gives the network's own ratio; beyond the DC table it is refused Cf3OpenCodeFindingsTests.N134_method_c_moves_the_peak_only, N134_on_a_single_series_path_method_c_gives_the_networks_own_ratio, Cf4HarmonicAfeAndMethodCTests.N134_rest_three_phase_method_c_gives_the_dc_component_from_its_own_ratio, N134_rest_method_c_beyond_the_dc_table_is_refused, N134_rest_unbalanced_method_c_moves_the_peak_and_dc_only
The factor-once dense LU equals the one-shot solve exactly, on a random 23x23 complex matrix ConverterFaultContributionTests.Factor_once_lu_is_bit_identical_to_the_one_shot_solve
Result-file ikpp_ka has the exact bits the console prints CliResultFilesProcessTests.Json_numbers_are_the_exact_bits_the_console_prints_in_round_trip_form
An earth fault without winding data exits 3 and says why; three-phase and line-to-line are unaffected; the result file records earthing_data = false CliS4CliAndLoaderProcessTests.N116_iec60909_earth_fault_without_winding_data_exits_3_and_says_why, N116_iec60909_faults_without_earth_path_are_unaffected, N116_iec60909_result_file_records_missing_earthing_data
No literal 50 Hz in the module: f0Hz is a parameter defaulting to FrequencyLimits.NominalHz, and the verb passes the model's frequency (no test runs a non-50 Hz model) Ws13CoreConstantsAntiDriftTests (no f0Hz = 50.0 in Iec60909.cs)

Most closed-form rows assert to 12 decimal places (Assert.Equal(expected, actual, 12)), not to the bit; the single-generator and partial-current rows assert to 10, the converter, island and live-network rows to 9 or 10, and the K_S/K_SO row to 12 and 15. The WSCC-9 pins, the far-from-generator row and the partial-versus-three-phase agreement tests are exact. The suite checks the formulas against hand-solved networks and against the textbook sequence-network connections. It holds no agreement test against a published IEC 60909 worked example, such as the examples of IEC TR 60909-4 (see Limits).

Worked example

Every number below comes from the captures in docs/_captures/iec60909/, except the bus-1 partial-current table, which is recomputed offline from the Zbus column (no verb prints partial currents; an independent recomputation agrees to about 1e-15). Timings do not appear; the values are deterministic. WSCC-9 (case9) is a 345 kV network on 100 MVA with three generators of 247.5, 192 and 128 MVA. IeeeCases.Case9 carries no machine reactance, so each machine takes the 0.20 pu default on its own MBase, which is 0.20 * 100 / 247.5 = 0.0808, 0.1042 and 0.1563 pu on the system base.

case9 carries its WSCC nominal frequency, 60 Hz, and is meshed (9 branches and 3 machine sources, 12 edges, over 9 buses and the earth node), so ip takes the Method B factor kappa_b = min(1.15 * kappa, 2.0): the kappa the ip line prints is kappa_b, and the line carries the meshed network note. The frequency enters m, Ith and idc. uk runs at 50 Hz and is meshed too, so its ip takes kappa_b (1.15 * 1.916 capped at 2.0) on the synchronous share.

Three-phase fault at bus 5

$ gridsim iec60909 case9 --bus 5
IEC 60909 - IEEE 9-bus (WSCC), bus 5, three-phase, Maximum (60 Hz, tb 0.1 s, Tk 1 s)
  Ik''  = 1.4683989584292985 kA  (8.774528526143639 pu)
  ip    = 4.143787818206106 kA  (kappa 1.995438943368623, R/X 0.10501342238071008, meshed network: 1.15 x kappa(R/X), Method B)
  Ib    = 1.4683989584292985 kA    Ik = 1.4683989584292985 kA
  Ith   = 1.4881526648788939 kA  (m 0.027086065637215752)    idc(tb) = 0.03963009392407432 kA
  Zth   = 0.013092788564404878 + j0.12467728665140516 pu
[exit 0]

(The full capture is three-phase-bus5.txt.) Recompute from the printed Zth:

|Zk|    = sqrt(0.013092788564404878^2 + 0.12467728665140516^2) = 0.125362861004162 pu
c       = 1.10                                  (Un = 345 kV, above 1 kV, maximum objective)
Ik''    = 1.10 / 0.125362861004162              = 8.77452852614364 pu      (printed 8.774528526143639)
Ibase   = 100 / (sqrt(3) * 345)                 = 0.167347904112935 kA
Ik''    = 8.77452852614364 * 0.167347904112935  = 1.4683989584293 kA       (printed 1.4683989584292985)
R/X     = 0.013092788564404878 / 0.12467728665140516 = 0.10501342238071    (printed 0.10501342238071008)
kappa   = 1.02 + 0.98 * exp(-3 * 0.10501342238071)   = 1.73516429858141
kappa_b = min(1.15 * 1.73516429858141, 2.0)          = 1.99543894336862    (printed 1.995438943368623)
ip      = 1.99543894336862 * sqrt(2) * 1.4683989584293 = 4.14378781820611 kA (printed 4.143787818206106)
m       = (exp(4 f Tk ln(kappa-1)) - 1) / (2 f Tk ln(kappa-1)) = 0.0270860656372157
                                                (series kappa, f = 60 Hz, Tk = 1 s; printed 0.027086065637215752)
Ith     = 1.4683989584293 * sqrt(1 + 0.0270860656372157) = 1.48815266487889 kA   (printed 1.4881526648788939)
idc(tb) = sqrt(2) * 1.4683989584293 * exp(-2*pi*60*0.1 * 0.10501342238071) = 0.0396300939240743 kA
                                                (printed 0.03963009392407432)

The hand figures agree with the printed ones to the last digit shown; the printed digits differ at the 15th to 16th significant figure because the hand figures are rounded. An independent complex solve of the nine-bus positive network (series impedances only, three machine shunts) agrees with the captured Zkk = 0.013092788564404878 + j0.12467728665140516 at bus 5 to 3e-17; the last digit depends on the elimination order.

Bus 5 is far from all three machines (each machine's Ik''_G/IrG is at most 2), so every mu is 1 and Ib = Ik = Ik''.

Near-generator breaking current at bus 1

$ gridsim iec60909 case9 --bus 1
IEC 60909 - IEEE 9-bus (WSCC), bus 1, three-phase, Maximum (60 Hz, tb 0.1 s, Tk 1 s)
  Ik''  = 2.934393338019216 kA  (17.534688310401165 pu)
  ip    = 8.299717711928068 kA  (kappa 2, R/X 0.019434794652556552, meshed network: 1.15 x kappa(R/X), Method B)
  Ib    = 2.3509284626333975 kA    Ik = 2.934393338019216 kA  (near a generator, fed from several sources: IEC 60909-0 Ik = Ik''M, the initial current without motors; no motors are modelled)
  Ith   = 3.1412149644062284 kA  (m 0.1459315044848038)    idc(tb) = 1.9945128315290945 kA
  Zth   = 0.0012189687934890236 + j0.06272095050557554 pu
[exit 0]

Ib is below Ik''. The multiple-fed formula, recomputed from the Zbus column of bus 1 at tb = 0.10 s:

Machine \|V_g\|/c I_g (kA) r_g = \|I_g\|/IrG mu_g (\|V_g\|/c)(1-mu_g) I_g (kA)
1 (bus 1, at the fault) 1 2.2780233447373277 5.5 0.743872301952596 0.58346487538581882
2 (bus 2) 0.20538641019773948 0.36295760455544029 1.1296252560875673 1 0
3 (bus 3) 0.25068149786064969 0.29533520379877126 1.3787482382335732 1 0

Machine 1 has r = c / x''d = 1.10 / 0.20 = 5.5 and mu = 0.62 + 0.72 * exp(-0.32 * 5.5) = 0.743872301952596. Machines 2 and 3 are far (r <= 2), so they take mu = 1. Then Ib = 2.934393338019216 - 0.58346487538581882 = 2.3509284626333975 kA, the printed value to the last digit.

Breaker check

$ gridsim iec60909 case9 --bus 5 --breaker 345,6,2,2
  ...
  breaker 345 kV / making 6 kA / breaking 2 kA / 2 kA for 1 s: NOT ADEQUATE
    voltage TOO LOW (system 345 kV, highest 362 kV)   making margin 1.856212181793894 kA   breaking margin 0.5316010415707015 kA   thermal margin 0.5118473351211061 kA
[exit 3]

The breaker is NOT ADEQUATE and the run exits 3, although all three current margins are positive: 6 - 4.143787818206106 = 1.856212181793894, 2 - 1.4683989584292985 = 0.5316010415707015 and 2 * sqrt(1/1) - 1.4881526648788939 = 0.5118473351211061. The voltage check fails: a 345 kV rating is below the highest system voltage Um of the 345 kV bus, 362 kV, so the line reads voltage TOO LOW and the breaker fails whatever its currents. At bus 1 the same rating also fails all three current checks (making margin -2.299717711928068 kA, breaking margin -0.3509284626333975 kA, thermal margin -1.1412149644062284 kA; breaker-inadequate.txt).

Rated for Um, the same currents pass: with 362 kV the voltage line reads voltage ok, the three margins are the ones above, and the breaker is ADEQUATE with exit 0 (breaker-adequate-um.txt):

$ gridsim iec60909 case9 --bus 5 --breaker 362,6,2,2
  ...
  breaker 362 kV / making 6 kA / breaking 2 kA / 2 kA for 1 s: ADEQUATE
    voltage ok (system 345 kV, highest 362 kV)   making margin 1.856212181793894 kA   breaking margin 0.5316010415707015 kA   thermal margin 0.5118473351211061 kA
[exit 0]

Converter infeed (the uk case)

$ gridsim iec60909 uk --bus 3
IEC 60909 - GB reduced (10-zone), bus 3, three-phase, Maximum (50 Hz, tb 0.1 s, Tk 1 s)
  Ik''  = 230.24585058250418 kA  (15.951900457632377 pu), of which converters 33.26107795539915 kA
  ip    = 604.195341604139 kA  (kappa 2, R/X 0.029872767022212653, meshed network: 1.15 x kappa(R/X), Method B)
  Ib    = 206.14092477227376 kA    Ik = 230.24585058250418 kA  (near a generator, fed from several sources: IEC 60909-0 Ik = Ik''M, the initial current without motors; no motors are modelled)
  Ith   = 239.6568418856552 kA  (m 0.11396670562621664)    idc(tb) = 108.98599257963483 kA
  Zth   = 0.002406695638187732 + j0.0805648715566982 pu
[exit 0]

The synchronous share is Ik''_sync = 230.24585058250418 - 33.26107795539915 = 196.984772627105 kA, which is 1.10/|Zk| = 13.647505380302 pu at 10000 / (sqrt(3) * 400) = 14.4337567297406 kA per pu. The peak adds the two shares without kappa on the converters, with kappa_b = min(1.15 * 1.91599449644715, 2.0) = 2 on the synchronous share:

ip  = kappa_b * sqrt(2) * 196.984772627105 + sqrt(2) * 33.26107795539915
    = 557.157074060465 + 47.0382675436743 = 604.195341604139 kA          (printed 604.195341604139)
Ith = sqrt(m * 196.984772627105^2 + 230.24585058250418^2) = 239.656841885655 kA   (printed 239.6568418856552)

Impedance corrections

$ gridsim iec60909 case9 --bus 5 --corrections --rated-pf 0.85
IEC 60909-0 impedance corrections (rated power factor 0.85): 3 applied
  K_G: 3 element(s), 0.9952 to 0.9952
IEC 60909 - IEEE 9-bus (WSCC), bus 5, three-phase, Maximum (60 Hz, tb 0.1 s, Tk 1 s)
  Ik''  = 1.4704922481380072 kA  (8.787037136393673 pu)
  ...
[exit 0]

Each machine takes K_G = 1.10 / (1 + 0.20 * sin(acos 0.85)) = 0.995154018321994, which multiplies X''d and X2. Ik'' at bus 5 moves from 1.4683989584292985 to 1.4704922481380072 kA. case9 has no branch flagged as a transformer, so only K_G applies.

Unbalanced and refused cases

gridsim iec60909 case9 --bus 5 --type ll --objective min gives Ik'' = 1.1560643644458017 kA, c = 1.00 and the R/X of Z1 + Z2 (here equal to that of Z1, so kappa is unchanged). An earth fault on case9 is refused:

$ gridsim iec60909 case9 --bus 5 --type slg
IEC 60909 - IEEE 9-bus (WSCC), bus 5, single-line-to-earth, Maximum (60 Hz, tb 0.1 s, Tk 1 s)
  Ik''  = 0 kA  (0 pu)
  ip    = 0 kA  (kappa 1.995438943368623, R/X 0.10501342238071008, meshed network: 1.15 x kappa(R/X), Method B)
  Ib    = 0 kA    Ik = 0 kA  (unbalanced fault: IEC 60909-0 takes no decay, Ik = Ib = Ik'')
  Ith   = 0 kA  (m 0.027086065637215752)    idc(tb) = 0 kA
  Zth   = 0.013092788564404878 + j0.12467728665140516 pu
iec60909: the model carries no transformer winding connections at all (MATPOWER and JSON v1 cannot hold them), so it has no earthed neutral and the earth-fault duty above reflects missing data. Exit 3.
[exit 3]

Other captures in the directory: all-buses.txt (the nine-bus sweep), branches.txt (the branch currents at bus 5), line-to-line-min-bus5.txt, unknown-bus.txt (exit 2), usage.txt (exit 2) and gb-full-bramford.txt (a fault on gb-full).

Source map

File Type Responsibility
src/GridSim.Core/Protection/ShortCircuit/Iec60909.cs Iec60909 (static) Voltage factor, PeakFactor, ThermalDcFactor, BreakingFactorMu, MotorBreakingFactorQ, FromThevenin, FromSequenceImpedances, ThreePhase, LineToLine, SingleLineToGround, DoubleLineToGround, PartialThreePhase, BranchFaultCurrents, the three sequence Thevenin functions, CheckBreaker, the four correction factors, ApplyCorrectionFactors
same Iec60909.Duty, BreakerRating, BreakerAdequacy, FaultContribution, MachinePartialCurrent, BranchFaultCurrent, CorrectionReport Result records
same ShortCircuitObjective, UnbalancedFaultType The objective and the unbalanced fault choice
same PositiveNetwork (private) The factored positive network: machines, converter infeeds, Zbus column, converter voltages
src/GridSim.Core/Protection/FaultNetworkSystem.cs FaultNetworkSystem Factor once on the sparse LU at every size (dense LU as a test oracle only), transposed solve, series-only network, singular checks
src/GridSim.Core/Model/Model.cs Generator, Branch, WindingConnection, ConverterPlant Machine reactances, converter fields, winding and neutral data, converter classification
src/GridSim.Core/PowerFlow/AdmittanceStamp.cs AdmittanceStamp The series-plus-tap branch stamp shared with BranchFaultCurrents
src/GridSim.Cli/Program.cs RunIec60909, RunIec60909Sweep The verb, its flag checks, output lines, result file and exit codes
tests/GridSim.Tests/Iec60909Tests.cs, Iec60909PartialAgreementTests.cs, ConverterFaultContributionTests.cs, EarthFaultAndIec60909CompletionTests.cs, ProtectionWs6Tests.cs, FaultNetworkSystemTests.cs Tests The invariants above

Limits

  • Method B takes one R/X, that of the driving-point impedance, for the whole network and adds the 1.15 safety factor when the network is meshed; it does not sum partial peaks source by source. The Method C DC ratios are marked [VERIFY] (no public source reproduces them).
  • The steady-state current is Ik = Ik'' and the thermal factor n is 1 for every fault, because lambda and n come from machine graphs that have no closed form here.
  • Ib for unbalanced faults equals Ik'', so a near-generator unbalanced fault is not decayed.
  • No asynchronous-motor contribution exists: the model carries no motor data and MotorBreakingFactorQ feeds no duty.
  • DoubleLineToGround reports the earth current |3 I0| only, not the line-conductor currents.
  • K_T covers two-winding network transformers only, K_S and K_SO are marked [VERIFY] in the source, and the generator rated power factor is the caller's input.
  • The correction factors are offered for the maximum-current case only, and whether the standard also corrects the zero-sequence impedances is marked [VERIFY].
  • IEC 60909-0 is not in docs/reference, so its clause numbers (9.1.7, 9.2, 8.1.2, 11.2.7, read from the 2016 contents list) and the K_S/K_SO equation forms are unchecked against the standard's text. IEC 60909-0:2026 Edition 3.0 exists; its numbering is unchecked.
  • There is no agreement test against a published IEC 60909 worked example; the formulas are pinned to closed forms, hand networks and the WSCC-9 case.
  • Of the case file formats the CLI reads, only a JSON v2 case can carry transformer winding connections, X''d or X2 (N234, above); every other file case has no earth paths for an earth fault and runs on the 0.20 pu default reactance.
  • Currents in kA are referred to the fault bus voltage, including the rated currents of machines at other voltage levels.