14. Cascade validation and blind prediction

This chapter specifies how GridSim tests whether its frequency models predict a recorded event or only reproduce it, and what the tests establish for the asset-dynamics cascade: embedded generation that trips on its own rate-of-change-of-frequency (RoCoF) protection, feeds the lost infeed back into the swing equation and deepens the fall. The protocol freezes every unmeasurable constant, feeds the model only recorded facts about the event, and compares the model nadir with the recorded nadir. The tests are tests/GridSim.Tests/BlindPredictionTests.cs (base swing model, two recorded GB events), tests/GridSim.Tests/Asset2019EventTests.cs (the cascade on 9 August 2019), tests/GridSim.Tests/AssetEnvelopeTests.cs (the sweep envelope) and tests/GridSim.Tests/AssetValidationTests.cs (the back-test gate). The swing model is specified in ch. 5, Frequency dynamics, the asset fleet and its data in ch. 13, Asset-dynamics data grounding, and the replay gate and evidence dossier in ch. 7, The evidence engine.

The outcome, stated once. The cascade mechanism is reproduced: with every catalogue loss except the embedded-generation trips fed in (the Hornsea and Little Barford losses, the later 100, 210 and 187 MW trips, and the recorded LFDD shed), a legacy embedded fleet trips on its own relay setting. The cascade depth is not predicted: the nadir is a function of the unmeasured embedded-trip volume and moves 2.7297 Hz across 500 to 4000 MW. The cascade cannot be blind-tested on GB data because 9 August 2019 is the only recorded GB embedded-generation cascade. Its standing is mechanism and envelope tool, tagged ProvenanceTag.UnvalidatedAtScale: use it for counterfactuals, sensitivity sweeps and screening, and treat a single cascade nadir as a scenario outcome. The base swing model is the part that is cross-checked on two recorded events: it matches 2019 as a replay (0.0410 Hz) and misses 2023 as a forward estimate (0.2955 Hz too deep). That result belongs to the base model, not to the asset framework.

Model

What is predicted and what is held out

Item Treatment
Nadir (Hz), initial RoCoF (Hz/s), nadir time (s) Predicted. Compared with the recorded outcome of the event (RecordedOutcome).
Droop, damping, responsive fraction, governor time constant Frozen. One DynamicsConfig for every event (table below). Never fitted to an event.
Pre-event inertia, demand, loss steps, recorded actions Recorded inputs, different per event. Facts, not knobs.
Procured response services (DC, DM, DR volumes and curves) Recorded input where the event declares them (GridEvent.ResponseServices).
Pre-event frequency Recorded input (GridEvent.PreEventFrequencyHz); the run starts in equilibrium there.
Recorded low-frequency demand disconnection (LFDD) Recorded action. Feeding it in makes the run a replay (see below).
Embedded-generation trip volume For the 2019 base model, the four Ofgem-derived embedded losses are fed as recorded steps (150, 390, 200 and 550 MW, 1290 MW in total). The volume that a relay cascade produces is unmeasured, and is swept in the cascade model.
Relay settings, inverter control loops Unmeasured. Class parameters tagged [VERIFY]; swept.

The single mapping from an event to a config is GridEvent.ApplyRecordedServices (src/GridSim.Core/Events/GridEvent.cs). It sets SystemResponseServices from ResponseServices, sets InitialFrequencyHz from PreEventFrequencyHz, and, when ResponseServicesComplete is true, sets ResponsiveFraction to 0 so the generic governor does not double-count a response the record already lists. The replay baseline, the scenario sweep, the fleet comparison, the evidence dossier and these tests all build their config through it.

Replay and forward estimate

A run is a replay when its inputs include an action that is itself a consequence of the frequency fall. 2019 feeds the recorded LFDD shed (+892 MW at 76 s) and the full recorded loss sequence, so the run confirms the integrator, not predictive power. A run is a forward estimate when no recorded action beyond the exogenous losses and the balancing-mechanism recovery is fed in and nothing is fitted to the nadir. 2023 is the forward estimate: its inputs are the two metered losses, the measured DC, DM and DR volumes, the measured pre-event frequency and the Balancing Mechanism (BM) recovery ramp derived from the acceptance record. Only a forward estimate counts as evidence about prediction. The 2023 inputs are measured, but they were chosen with the trace in view (the pre-event frequency is read off it and the BM ramp matches its recovery through 49.5 Hz), so it is a forward estimate in the protocol's sense, not a held-out one.

Equations as implemented

The base model is the single-mass swing equation of FrequencyDynamics.Simulate (src/GridSim.Core/Dynamics/FrequencyDynamics.cs), integrated by explicit Euler at StepSeconds (0.02 s):

E       = max(1, SystemInertia + DeviceRotationalInertia)             MW.s
D       = DampingPctPerHz / 100 * DemandMw                            MW/Hz
PResp   = ResponsiveFraction * DemandMw                               MW
pEvent  = sum of DeltaPMw over events with AtSeconds <= t + 1e-6 dt   MW
pGov   += (-(df/f0)/DroopPu * PResp - pGov) / GovernorTimeConstantS * dt
pSvc_s += (target_s(df) - pSvc_s) / max(dt, tau_s) * dt               for each recorded service s
pImb    = pEvent + pStanding + pGov + pTsgb + sum(pSvc_s) - D * df    df = f - f0
rocof   = f0 / (2 * E) * pImb
f      += rocof * dt

target_s(df) is SwingKernel.FastResponseTarget (src/GridSim.Core/Dynamics/SwingKernel.cs): zero for |df| <= DeadbandHz; with a = |df|, below the knee Mw * KneeFraction * (a - Deadband) / (Knee - Deadband), above it Mw * (KneeFraction + (1 - KneeFraction) * (a - Knee) / (Full - Knee)), capped at Mw and signed -sign(df). A knee at or below zero gives the line through zero -(Mw / Full) * df, clamped to +/- Mw.

When InitialFrequencyHz is set the run starts in equilibrium at that value:

df0       = fInit - f0
pGov(0)   = -(df0/f0)/DroopPu * PResp
pSvc_s(0) = target_s(df0)
pStanding = -(pGov(0) + sum(pSvc_s(0)) - D * df0)         so rocof(0) = 0 before the first loss

The initial RoCoF depends on inertia and the first losses only, and has no free parameter:

rocof0 = f0 * dP_early / (2 * E)        dP_early = sum of |DeltaPMw| over losses with AtSeconds <= 1.0

The cascade adds two terms to the imbalance sum, appended last (AssetFrequencyDynamics.Simulate, src/GridSim.Core/Dynamics/AssetFrequencyDynamics.cs): the fleet's net swing power and the cumulative lost dispatched generation of tripped units. A grid-following embedded unit trips when the delayed local RoCoF, scaled by the local uplift, exceeds the relay threshold for the confirmation time (GridFollowingInverter.Update, src/GridSim.Core/Assets/GridFollowingInverter.cs):

overRocof = |rocofMeas| * localRocofUpliftFactor > rocofTripHzPerS
n         = overRocof ? n + 1 : 0                         (ConfirmTimer: whole sub-steps counted)
rocofTrip = overRocof and DwellReached(n * dt, rocofTripConfirmS)

DwellReached is the protection layer's rule (ch. 15): the counted time reaches the confirm time, or is within 2^-49 of it relative, so a representation error in dt cannot add a step.

Once tripped the unit delivers 0 MW and reports its lost infeed _pgMw to the swing sum. The effective COI threshold is rocofTripHzPerS / localRocofUpliftFactor: 0.125 / 1.16 = 0.10776 Hz/s for the legacy class used in the 2019 test.

The envelope (AssetEnvelope.Sweep, src/GridSim.Core/Assets/AssetEnvelope.cs) runs the 2^k corners of k swept class parameters (k at most 12) and reports NadirMinHz, NadirMaxHz, NadirMedianHz (element n/2 of the sorted nadirs), the RoCoF range, a one-at-a-time tornado with the other parameters at their midpoint, and CascadeIsPossible = any corner trips and any corner does not.

Acceptance rules

Rule Value Where
2019 replay residual |model - recorded| < 0.10 Hz Base_model_reproduces_2019_when_fed_the_recorded_facts
2019 recorded nadir pinned 48.8 Hz to 1 decimal place same test
2023 forward residual recorded - model in [0.15, 0.45] Hz (positive means the model is too deep) Base_model_forward_estimates_2023_to_within_a_few_tenths_Hz
2023 recorded nadir pinned 49.275 Hz to 3 decimal places same test
Parameter-free initial RoCoF in [0.10, 0.20] Hz/s for both events Parameter_free_initial_rocof_is_physically_consistent_for_both_events
No second GB cascade 2019 has a loss containing "distributed generation"; 2023 has none The_cascade_has_no_second_gb_event_to_blind_predict
Cascade mechanism a legacy fleet of 1290 MW trips (TrippedCount > 0, TotalTrippedMw > 0) The_cascade_mechanism_emerges_from_first_principles
Envelope width nadir at 500 MW minus nadir at 2500 MW exceeds 1.0 Hz The_recorded_nadir_lies_WITHIN_the_embedded_trip_envelope_not_at_a_predicted_point
Envelope brackets the record 48.787 Hz (the recorded 76 s minimum, ch. 13) lies between the 2500 MW and 500 MW nadirs same test
Ride-through counterfactual a 10 Hz/s fleet at 1290 MW trips 0 units No_dg_fleet_means_no_cascade_and_a_shallower_fall
Sweep brackets trip and no trip CascadeIsPossible, NadirMinHz < NadirMaxHz, 2 samples for k = 1, tag UnvalidatedAtScale AssetEnvelopeTests.Sweeping_the_trip_threshold_brackets_cascade_and_no_cascade
Back-test gate |nadir err| <= 0.05 Hz and |RoCoF err| <= 0.05 Hz/s and |nadir time err| <= 2.0 s AssetValidation.Compare, ValidationTolerance.Default

The 2019 band is a replay check and the 2023 band is a documented miss: the test fails if the miss shrinks below 0.15 Hz or grows above 0.45 Hz, so a change to the base arrest model shows up in either direction.

AssetValidation.Compare (src/GridSim.Core/Assets/AssetValidation.cs) scores a simulated FrequencyResponse against a RecordedFrequencyTrace. The recorded RoCoF is the peak first-difference slope over the trace points; the recorded nadir time is the time of the minimum point. The RoCoF is compared on one basis: when the trace is coarser than the simulation step, the simulation is read on the trace's own window (ReplayValidator.MaxWindowedRocof). The gate is applied in two places. The credibility gate (ReplayValidator.Validate, used by gridsim replay-event) runs Compare whenever a recorded trace is attached, reports it as ReplayResult.BackTest, and caps a Reproduced verdict at Marginal when the back-test fails. AssetValidation.BlindPredict(frozen, shared, blindEvent, recorded) is the blind step of the protocol: it replays the blind event with the shared configuration and back-tests it, and throws InvalidOperationException, naming every difference, when the configuration changes any constant held in the FrozenParameterSet captured at the anchor (FrozenParameterSet.Differences), or when the blind event is the anchor event itself.

The replay gate used by gridsim replay-event (ReplayValidator, src/GridSim.Core/Replay/ReplayValidator.cs) applies a looser rule to the same events: Reproduced needs |RoCoF| relative error <= 0.15 and |nadir error| <= 0.15 Hz; Marginal needs both within twice that; otherwise Failed. A per-sample RMSE above 0.05 Hz, or a failed back-test (above), caps a Reproduced verdict at Marginal. Only a Reproduced baseline unlocks counterfactuals. See ch. 7 and the replay-event section of the CLI reference.

Event qualification

An event is a valid step-loss test only if its recorded RoCoF obeys step physics at the recorded inertia. The check is the closure ratio, the inertia implied by the recorded RoCoF over the recorded inertia, with the implied inertia E = f0 * dP / (2 * |rocof|) (InertiaEstimator.EstimateInertiaMwS, src/GridSim.Core/Dynamics/InertiaEstimator.cs).

Event Implied inertia / recorded inertia Qualifies
2019-08-09 223.7 / 215.0 GVA.s = 1.04 (replay capture); the GDA report's swing-equation estimate gives 267.8 / 215 = 1.25 yes
2023-12-22 193.6 / 161.0 GVA.s = 1.20 (replay capture; the recorded RoCoF is a 1 s window figure, inverted after scaling by the replay's instantaneous / windowed ratio 1.266) yes
2026-05-31 (992 MW) 19.32, from the GDA report of that event no

The 2026-05-31 report records a peak RoCoF of +0.007 Hz/s. Step physics at its recorded 183 GVA.s gives 50 * 992 / (2 * 183000) = 0.1355 Hz/s, so the recorded fall is 19 times slower than a step: a gradual imbalance. The event is excluded from step-loss prediction. No code computes a closure ratio or applies a qualification threshold: the qualification is a judgement from the ratio, and a ratio near 1 (1.04, 1.20) qualifies while 19.32 does not. The figure 19.32 is the report's own; the rounded inputs above give 19.4. The figures for this event come from the GDA analysis report, which is not part of this repository; the catalogue carries no entry for it.

Parameters and defaults

Frozen constants, the same for every event (DynamicsConfig, src/GridSim.Core/Dynamics/FrequencyDynamics.cs; BlindPredictionTests.SharedConfig changes only the duration):

Name Value Unit Meaning Source symbol
DroopPu 0.05 pu Governor droop. GB Grid Code figure, not fitted DynamicsConfig.DroopPu
DampingPctPerHz 1.0 % of demand per Hz Load self-damping. Literature value, unfitted DynamicsConfig.DampingPctPerHz
ResponsiveFraction 0.20 fraction of demand Governor-responsive capacity. Unfitted. Forced to 0 when an event's service list is complete DynamicsConfig.ResponsiveFraction
GovernorTimeConstantS 8.0 s Primary-response lag. Unfitted DynamicsConfig.GovernorTimeConstantS
StepSeconds 0.02 s Integration step DynamicsConfig.StepSeconds
DurationSeconds 150 s Window used by the blind tests BlindPredictionTests.SharedConfig
NominalHz 50.0 Hz f0 DynamicsConfig.NominalHz

Recorded inputs per event (EventCatalog.Builtin, src/GridSim.Core/Events/EventCatalog.cs):

Input 2019-08-09 2023-12-22
PreEventInertiaMwS 215,000 (NESO recorded outturn) 161,000 (NESO recorded outturn)
PreEventDemandMw 21,100 (WLS-estimated transmission-net demand) 22,400 (WLS-estimated transmission-net demand)
Losses nine steps, 2768 MW in total, including the embedded-generation trips (Ofgem 2.4.x) IFA -1000 MW at 0.5 s, Cottam -345 MW at 9.5 s (settlement-metered)
Recorded actions LFDD +892 MW at 76 s BM recovery ramp, twelve steps from 19 s to 129 s, +904 MW in total
ResponseServices none DCL 873 MW, DML 150 MW, DRL 203 MW (EAC auction 70), 1226 MW in total
ResponseServicesComplete false (ResponsiveFraction stays 0.20) true (ResponsiveFraction becomes 0)
PreEventFrequencyHz nominal 49.879
Recorded nadir 48.8 Hz 49.275 Hz
Recorded initial RoCoF -0.17 Hz/s (instantaneous basis) -0.102 Hz/s (1 s window, RocofMeasurementWindowS = 1.0)

The 2019 catalogue entry is also shipped as a measured catalogue, data/events/gb-2019-08-09-estimated.json, with a demand of 21,147.2 MW. The tests use the built-in entry.

Cascade fleet parameters used by Asset2019EventTests (AssetTestHelpers.GflClass, AssetParams in src/GridSim.Core/Assets/AssetClassLibrary.cs):

Parameter Value Unit Meaning
rocofTripHzPerS 0.125 (legacy), 10.0 (modern, rides through) Hz/s Loss-of-mains relay setting; 0.125 is the pre-ALoMCP setting
localRocofUpliftFactor 1.16 ratio Sub-cycle local RoCoF over the 1 s COI value
rocofTripConfirmS 0.0 in the tests s Trip on the first sample over threshold. The code fallback is 0.5
headroomUpFraction, headroomDownFraction 0.0 fraction The embedded unit contributes no frequency response
Fleet size 500, 1290, 2500, 4000 MW Unmeasured embedded-trip volume; swept. 1290 MW is the catalogue's embedded total (150 + 390 + 200 + 550)
Synchronous plant 20,000 MW dispatched, MBase 43,000 MVA, H 5.0 s E = 5.0 * 43,000 = 215,000 MW.s
Demand 21,100 MW Same as the catalogue entry

The cascade runs feed every catalogue loss whose description does not contain "distributed generation" (-737 MW at 0.5 s, -244 MW at 1.0 s, -100 MW at 40 s, -210 MW at 58 s, -187 MW at 90 s), plus the recorded LFDD action (+892 MW at 76 s). By the definition above that makes them replays. The shed lies after the cascade nadirs (13.5 to 13.7 s) and does not change them: without it the 1290 MW run still bottoms at 48.2291 Hz at 13.62 s.

Results

All numbers below were produced by the code the tests call: the base-model values by the baseline swing export of replay-event (baseline-frequency.json, a 120 s window for 2019 and 159 s for 2023), the cascade values by Asset2019EventTests.RunWithEmbeddedFleet at its 120 s window with the fleet sizes shown. Timings, durations and stamps in captured output differ by machine and run.

Base model, two recorded events

Event Run type Recorded nadir Model nadir Residual (recorded - model) Model nadir time Initial RoCoF (model)
2019-08-09 replay 48.800 Hz 48.8410 Hz -0.0410 Hz (model 0.0410 Hz too shallow) 76.00 s -0.1710 Hz/s
2023-12-22 forward estimate 49.275 Hz 48.9795 Hz +0.2955 Hz (model too deep) 49.00 s -0.1553 Hz/s (instantaneous peak; the replay gate scores the 1 s window figure, -0.123)

Parameter-free RoCoF, f0 * dP_early / (2 * E): 2019 50 * 1131 / (2 * 215000) = 0.1315 Hz/s; 2023 50 * 1000 / (2 * 161000) = 0.1553 Hz/s. Both lie inside the pinned band 0.10 to 0.20 Hz/s and next to the recorded figures (2019 -0.17 instantaneous and -0.151 on a 1 s window; 2023 -0.102 on a 1 s window). One-second averaging lowers the peak of a sharp step.

What the numbers show:

  • 2019 is a replay. The 0.0410 Hz agreement confirms the integrator at 215 GVA.s with the recorded losses, response services and shed. The first fall is arrested at 49.2339 Hz at 16.72 s; the model recovers to 49.3204 Hz at 40 s, falls with the later losses to 48.8569 Hz at 75 s and 48.8425 Hz at 75.9 s, and reaches its minimum, 48.8410 Hz, at 76.0 s, when the final embedded-generation loss and the +892 MW shed land together; the shed lifts it from there. The recorded minimum of 48.8 Hz at 75.9 s belongs to the same 76 s event.
  • 2023 is the forward number. The model under-arrests by 0.2955 Hz. The model minimum falls at 49.00 s against a recorded minimum at 20 s (13:10:11 against an onset of 13:09:51), and the recorded nadir lies outside the model's own declared-uncertainty corner envelope. The residual comes from the base arrest model (damping and the service time constants), because the 2023 event carries no embedded cascade.

The replay gate on the same events

Output of gridsim replay-event gb-2019-08-09 (docs/_captures/events/replay-event-gb-2019-08-09.txt):

$ gridsim replay-event gb-2019-08-09

=== Replay: GB 9 Aug 2019 disturbance (Hornsea + Little Barford) ===
  when (UTC):        2019-08-09T15:52:33.0000000Z   provenance: DerivedFromRecorded (event tagged Recorded; the weakest of its parts)
  pre-event inertia: 215.0 GVA.s   demand: 21.1 GW   total loss: 2768 MW
  inferred inertia from recorded RoCoF: 223.7 GVA.s (cross-check vs 215.0)

  RoCoF:  sim  -0.171   recorded  -0.170 Hz/s   (1 % error)
  Nadir:  sim   48.84   recorded   48.80 Hz   (0.04 Hz error)
  Nadir envelope (declared-uncertainty corners): [48.20, 49.17] Hz - recorded INSIDE (consistent within the model's own error bars)
  RMSE vs trace: n/a (no 1-sec NESO trace attached - data-gated)
  assessment: BELOW STATUTORY (49.5 Hz)

  VERDICT: REPRODUCED  - baseline reproduces the record; counterfactuals unlocked.
...
[exit 0]

Output of gridsim replay-event gb-2023-12-22 --trace data/neso/gb-2023-12-22-frequency.csv (docs/_captures/events/replay-event-gb-2023-12-22-trace.txt):

$ gridsim replay-event gb-2023-12-22 --trace data/neso/gb-2023-12-22-frequency.csv

=== Replay: GB 22 Dec 2023 excursion (IFA + Cottam, settlement-measured) ===
  when (UTC):        2023-12-22T13:09:51.0000000Z   provenance: DerivedFromRecorded (event tagged Recorded; the weakest of its parts)
  pre-event inertia: 161.0 GVA.s   demand: 22.4 GW   total loss: 1345 MW
  inferred inertia from recorded RoCoF: 193.6 GVA.s (cross-check vs 161.0)
    (recorded RoCoF is a 1 s windowed figure; inverted after scaling by the replay's instantaneous / windowed ratio 1.266)

  RoCoF:  sim  -0.123   recorded  -0.102 Hz/s   (20 % error)
  Nadir:  sim   48.98   recorded   49.27 Hz   (0.30 Hz error)
  Nadir envelope (declared-uncertainty corners): [48.65, 49.20] Hz - recorded OUTSIDE (a constant the corners don't cover - e.g. the inertia basis - is off)
  RMSE vs trace: 0.281 Hz over 7926 sample(s)
  back-test vs trace (gate 0.05 Hz / 0.05 Hz/s / 2.0 s): FAIL  nadir 0.295 Hz, RoCoF sim -0.123 vs rec -0.102 Hz/s, nadir time sim 49.0 s vs rec 20.5 s (28.5 s)
  assessment: BELOW STATUTORY (49.5 Hz)

  VERDICT: MARGINAL  - NOT reproduced; do not run counterfactuals until the baseline matches (check [VERIFY] figures / tolerances).
...
[exit 3]

With the 2019 trace attached (gridsim replay-event gb-2019-08-09 --trace data/neso/gb-2019-08-09-frequency.csv, docs/_captures/events/replay-event-gb-2019-08-09-trace.txt) the per-sample RMSE is 0.099 Hz, the back-test fails on the nadir (0.054 Hz against the 0.05 Hz gate), and the verdict drops to MARGINAL (exit 3), because the headline metrics match and the trace shape does not. The nadir match of 0.04 Hz is a match of one number, not of the trajectory. The 2023 verdict is MARGINAL because both metrics miss the Reproduced tolerance: the RoCoF error is 20 % (limit 15 %) and the nadir error 0.2955 Hz (limit 0.15 Hz). Both lie inside twice the tolerance, the nadir by 0.0045 Hz.

Cascade on 9 August 2019

The non-embedded losses and the recorded shed (listed above) are fed at 215 GVA.s into a model whose embedded fleet is a legacy class (0.125 Hz/s, uplift 1.16). The COI RoCoF reaches 50 * 737 / (2 * 215000) = 0.0857 Hz/s after the Hornsea step and 50 * 981 / (2 * 215000) = 0.1141 Hz/s after the Little Barford step at 1.0 s, which exceeds the effective threshold 0.10776 Hz/s, so the fleet trips at that point on its own protection.

Embedded fleet Nadir Nadir time Peak RoCoF Units tripped
none tripped (modern class, 10 Hz/s, 1290 MW) 49.2350 Hz 13.40 s -0.1128 Hz/s 0
legacy, 500 MW 48.8452 Hz 13.54 s -0.1709 Hz/s 1 (500.0 MW)
legacy, 1290 MW 48.2291 Hz 13.62 s -0.2628 Hz/s 1 (1290.0 MW)
legacy, 2500 MW 47.2854 Hz 13.68 s -0.4035 Hz/s 1 (2500.0 MW)
legacy, 4000 MW 46.1155 Hz 13.70 s -0.5779 Hz/s 1 (4000.0 MW)

The nadir spans 48.8452 - 46.1155 = 2.7297 Hz across the fleet sizes. The recorded 48.787 Hz (the minimum at 76 s, 15:53:49Z, ch. 13; the catalogue rounds it to 48.8 Hz) lies inside the 500 to 2500 MW band [47.2854, 48.8452], and a fleet of 574.621 MW gives a first-dip nadir of exactly 48.7870 Hz (bisection on fleet size). The two numbers are at different times: the cascade nadirs are the first dip at about 13.6 s, while 48.787 Hz is the 76 s minimum. The fleet size is selected by the recorded number (see the outcome above). The no-cascade run bottoms at 49.2350 Hz, 0.448 Hz above the recorded nadir, which is the depth the embedded trips add.

Why the cascade cannot be blind-tested on GB data

A blind test needs a second event in which embedded generation tripped on RoCoF. The GB record has none.

  1. 9 August 2019 is the only major GB embedded-generation RoCoF cascade. The catalogue records its trips as losses (150 MW vector-shift trip at 0.1 s, Ofgem 2.4.2; 390 MW at 3 s, the midpoint of the reported 350 to 430 MW; 200 MW at 65 s; 550 MW at 76 s; Ofgem 2.4.6, 2.4.11, 2.4.13).
  2. The Accelerated Loss-of-Mains Change Programme (ALoMCP) raised embedded relays from 0.125 Hz/s to 1.0 Hz/s (FrequencyLimits.RocofLimitModernHzPerS, src/GridSim.Core/Dynamics/FrequencyLimits.cs) with a 500 ms definite-time delay, to remove the mechanism.
  3. Every later recorded GB event carries no embedded trips. The_cascade_has_no_second_gb_event_to_blind_predict pins it for 2023.

The real-fleet deliverable is the sweep envelope (AssetEnvelope.Sweep), whose AssetEnvelopeResult carries ProvenanceTag.UnvalidatedAtScale by default. Only new measured evidence changes this: per-feeder embedded trip telemetry for a real event, or a future recorded GB cascade.

Invariants

Invariant Test
One config for all events: per-event differences enter only through ApplyRecordedServices BlindPredictionTests.Replay; ResponseServiceTests.ApplyRecordedServices_maps_and_completeness_zeroes_the_governor
2019 replay residual below 0.10 Hz; recorded nadir 48.8 BlindPredictionTests.Base_model_reproduces_2019_when_fed_the_recorded_facts
2023 forward residual in 0.15 to 0.45 Hz, model too deep; recorded nadir 49.275 BlindPredictionTests.Base_model_forward_estimates_2023_to_within_a_few_tenths_Hz
Parameter-free initial RoCoF in 0.10 to 0.20 Hz/s for both events BlindPredictionTests.Parameter_free_initial_rocof_is_physically_consistent_for_both_events
2019 carries embedded-generation losses, 2023 carries none BlindPredictionTests.The_cascade_has_no_second_gb_event_to_blind_predict
The cascade emerges from the relay setting with no scripted embedded steps Asset2019EventTests.The_cascade_mechanism_emerges_from_first_principles
The nadir band is wider than 1.0 Hz and brackets 48.787 Hz Asset2019EventTests.The_recorded_nadir_lies_WITHIN_the_embedded_trip_envelope_not_at_a_predicted_point
A ride-through fleet produces no trips Asset2019EventTests.No_dg_fleet_means_no_cascade_and_a_shallower_fall; InverterTripCascadeTests.A_fleet_below_its_limit_does_not_trip
A lower relay threshold trips and deepens the nadir InverterTripCascadeTests.A_low_rocof_threshold_trips_and_deepens_the_nadir
Local RoCoF uplift trips a relay the COI value would not InverterTripCascadeTests.Local_rocof_uplift_makes_a_relay_trip_that_the_coi_value_would_not
The sweep brackets trip and no trip, is tagged UnvalidatedAtScale, ranks the trip threshold first AssetEnvelopeTests.Sweeping_the_trip_threshold_brackets_cascade_and_no_cascade
A ride-through-only range reports no cascade AssetEnvelopeTests.A_ride_through_only_range_reports_no_cascade
An empty or unmatched fleet reproduces the baseline bit for bit AssetDynamicsReductionTests.Flag_off_is_bit_identical_to_the_lumped_baseline, Enabled_but_nothing_bound_reduces_to_baseline, Enabled_with_only_unmatched_assets_reduces_to_baseline
The back-test gate passes a matching trace and fails one shifted by 0.3 Hz AssetValidationTests.A_matching_simulation_passes_the_gate, A_perturbed_recording_fails_the_gate
Initial RoCoF reproduces the recorded 2019 figure: -0.151 Hz/s at 267.8 GVA.s, -0.188 Hz/s at 215 GVA.s AssetValidationTests.Recorded_2019_08_09_initial_rocof_is_reproduced_at_the_reported_inertia
The replay gate reproduces a self-consistent event, fails a corrupted one, marks a slightly off one Marginal and strips any device ReplayValidatorTests

Worked example

Question: does the legacy embedded fleet trip in the 2019 replay, and how much does the answer depend on its size?

  1. Take the 2019 catalogue entry: E = 215,000 MW.s, demand 21,100 MW, ApplyRecordedServices leaves ResponsiveFraction at 0.20 because the entry declares no services.
  2. Remove the embedded-generation losses and keep the rest (Hornsea -737 MW at 0.5 s, Little Barford -244 MW at 1.0 s, the later GT trips and the +892 MW shed at 76 s).
  3. Bind a legacy class (rocofTripHzPerS 0.125, uplift 1.16, no headroom) to a 1290 MW unit with H = 0, so the system inertia stays 215,000 MW.s.
  4. At 1.0 s the COI RoCoF is 50 * (737 + 244) / (2 * 215000) = 0.1141 Hz/s. The relay sees 0.1141 * 1.16 = 0.1324 Hz/s against 0.125, and trips.
  5. The lost 1290 MW enters the swing sum. The peak RoCoF becomes -0.2628 Hz/s (50 * (981 + 1290) / 430000 = 0.2641 before damping and governor response) and the nadir is 48.2291 Hz at 13.62 s.
  6. Repeat at 500, 2500 and 4000 MW: 48.8452, 47.2854 and 46.1155 Hz. The same trip, the same loss sequence, a 2.7297 Hz spread. The recorded 48.787 Hz selects 574.621 MW.
  7. Replace the class by a modern one (10 Hz/s). No unit trips and the nadir is 49.2350 Hz.

Steps 4 and 7 show the mechanism; steps 5 and 6 show how the depth depends on the fleet size.

Source map

File Type Responsibility
tests/GridSim.Tests/BlindPredictionTests.cs tests Base-model cross-event protocol: shared config, 2019 replay, 2023 forward estimate, parameter-free RoCoF, no second cascade
tests/GridSim.Tests/Asset2019EventTests.cs tests Cascade mechanism, nadir envelope and ride-through counterfactual on 2019
tests/GridSim.Tests/AssetEnvelopeTests.cs tests Sweep envelope, tornado ranking, UnvalidatedAtScale tag
tests/GridSim.Tests/AssetValidationTests.cs tests Back-test gate and 2019 RoCoF anchor
tests/GridSim.Tests/InverterTripCascadeTests.cs tests Relay trip, nadir deepening, local RoCoF uplift
tests/GridSim.Tests/AssetDynamicsReductionTests.cs tests Empty-fleet reduction to the baseline
src/GridSim.Core/Events/EventCatalog.cs EventCatalog The built-in recorded events and their provenance tags
src/GridSim.Core/Events/GridEvent.cs GridEvent, ResponseService, RecordedOutcome Recorded inputs and outcome; ApplyRecordedServices
src/GridSim.Core/Dynamics/FrequencyDynamics.cs DynamicsConfig, FrequencyDynamics Frozen constants and the swing integrator
src/GridSim.Core/Dynamics/SwingKernel.cs SwingKernel Governor and service delivery curves
src/GridSim.Core/Dynamics/AssetFrequencyDynamics.cs AssetFrequencyDynamics, AssetFrequencyResult Swing solve with the asset fleet and the trip deficit
src/GridSim.Core/Assets/GridFollowingInverter.cs GridFollowingInverter Relay trip rule with local RoCoF uplift
src/GridSim.Core/Assets/AssetEnvelope.cs AssetEnvelope, AssetEnvelopeResult Corner sweep, tornado, CascadeIsPossible, provenance tag
src/GridSim.Core/Assets/AssetValidation.cs AssetValidation, ValidationTolerance, FrozenParameterSet Back-test gate against a recorded trace; the enforced freeze and blind prediction
src/GridSim.Core/Replay/ReplayValidator.cs ReplayValidator, ReplayTolerance Replay verdict and corner envelope used by gridsim replay-event
src/GridSim.Core/Dynamics/InertiaEstimator.cs InertiaEstimator Inertia implied by a recorded RoCoF (closure ratio)

Limits

  • The freeze is enforced only on the blind step: AssetValidation.BlindPredict refuses a configuration that changed a frozen constant, but nothing stops a caller from fitting constants and freezing the result as a new anchor, and no CLI verb runs a blind prediction.
  • The 0.05 Hz, 0.05 Hz/s and 2.0 s back-test runs in the credibility gate only when a recorded trace is attached to the event; it can only demote a Reproduced verdict, never promote one.
  • The 2023 forward estimate misses the recorded nadir by 0.2955 Hz and the nadir time by 29 s, and ends MARGINAL in the replay gate; the base arrest model (damping and service time constants) is not fitted to a recorded trip.
  • The embedded-trip volume and every inverter control and relay parameter are unmeasured; the cascade result is a band, UnvalidatedAtScale.
  • The vector-shift trip is a frequency-offset proxy and not a phase-jump detector.
  • The cascade runs on the single-bus lumped model; per-node validation against the four-node PMU data awaits the distributed model carrying the asset fleet.
  • The 2026-05-31 closure figures come from a GDA report outside this repository and cannot be reproduced from it.